Datmptf2y15eren Mps Brochure
Datmptf2y15eren Mps Brochure
Datmptf2y15eren Mps Brochure
MPS
VFI
TYPE
ONLINE Tower 4
SmartGrid Flywheel
ready compatible
Supercaps Service
UPS 1st start
Flexibility
Master MPS is suitable for a wide range of
applications including IT and the most
demanding industrial environments. The UPS
is suitable for power capacitive loads such as
blade servers, from 0,9 leading to 0,8 lagging. Detail of connection area
With a broad range of accessories and
options, complex configurations and system
architectures can be achieved to guarantee network adapters, potential free contacts, Options
maximum power availability and the option to etc. • UPS Group Synchroniser (UGS)
add new UPS without interruption to existing • REPO Remote Emergency Power Off for Allows two or more non-parallel UPS
installation. switching off the UPS via a remote devices to remain synchronised even
emergency button during mains power failure.
Battery care system: maximum • Input for the connection of the auxiliary The UGS also enables a Riello UPS to be
battery care contact of an external manual bypass synchronised with another power source
Normally the batteries are kept charged by • Input for synchronisation from an external that is independent and of a different
the rectifier; when mains power fails, the source power rating.
UPS uses this energy source to power the • Graphic display panel for remote
consumers. Proper battery care is therefore connection. • Parallel Systems Joiner (PSJ)
critical to ensuring correct UPS operation Allows two groups of UPS to be connected
under emergency conditions. The Riello UPS Maximum reliability and in parallel whilst operating, in the event of
battery care system consists of a series of availability maintenance (with no interruption to the
functions designed to optimise battery • Distributed or centralised parallel output), using a power coupling switch.
management and achieve the best configuration of up to 8 units per Should one of the UPS in one of the
performance and operating life possible. redundant (N+1) or power parallel system. parallel groups fail, it is automatically
Master MPS is also compatible with different Parallel configurations using models with excluded.
battery technologies: vented open lead acid, different power ratings are also possible. The PSJ connects the remaining UPS, to
VRLA AGM, Gel, NiCd, Flywheels, Supercaps • Hot System Expansion (HSE): allows the the other parallel group via an external
and Lithium. addition of a further UPS into an existing bypass, in order to continue to guarantee
system, without the need to switch off the load redundancy.
Specific solutions existing UPS or transfer them to bypass
The UPS can be adapted to meet the most mode. This guarantees maximum load
specific requirements. Contact our TEC team protection, even during maintenance and
to discuss specific solutions and options not system expansion.
listed in this catalogue. • Maximum levels of availability, even in the
event of an interruption to the parallel bus
Advanced communications cable: the system is “FAULT TOLERANT”. It
• Compatible with TeleNetGuard for remote is not affected by connection cable faults
monitoring. and continues powering the load without
• Advanced multi-platform communications disruption, signalling an alarm condition.
for all operating systems and network • Efficiency Control System (ECS): a system
environments: PowerShield3 monitoring to optimise the operating efficiency of
and shutdown software included for parallel systems, according to the power
Windows operating systems 8, 7, Hyper-V, required by the load. N +1 redundancy is
2012, 2008, and previous versions, Mac guaranteed, with every UPS working in
OS X, Linux, VMWare ESXi, Citrix XenServer parallel at the best load level possible to
and other Unix operating systems. achieve higher overall efficiency.
• Double RS232 serial
• 3 slots for the installation of optional
communications accessories such as
DIMENSIONS
1400
1900
1900
1900
1400
1400
1400
0 0 0 0 0 0
555 74 800 74 825 74 800 80 1070 74 1070 80
Solution to ensure redundancy up to the distribution of the Solution to ensure redundancy of the power supply even during
power supply to the loads and improved STS operation. maintenance. + High availability and redundancy
+ Downstream fault discrimination
Battery
Battery
Battery
Battery
Battery
Battery
Battery
UGS
Sinchroniser PSJ
Static Transfer
SWITCH SWITCH
Load 3
Load 1 Load 2 Load 1 Load 2
Static Transfer
SWITCH
Load 4
DETAILS
RS232-REPO SWBYP
CONNECTORS FAN FUSES
DRY CONTACTS
SWMB
COMMUNICATIONS
INTERFACE SLOT
SWOUT
PARALLEL
INTERFACE
UGS
INTERFACE
MULTI I/O
MODEM
INTERFACE
DIGITAL I/O
AND GENERATOR
INTERFACE
BATTERY BOX
Dimensions
1900
1400
1400
(mm) BB BB
BB
86 86
55 0 0 0 0 0
5 74 74 80
Dimensions Dimensions
1900
1900
1900
1400
1400
1900
1900
(mm) (mm)
TC TC TC
E E E
64 64 0 0 0 0
0 0 0 0 74 74 00 64 64 80 80
27 80 40 85 40 10 0 0
0 0 0
MODELS TBX 10 T - TBX 80 T TBX 100 T - TBX 160 T TBX 200 T - TBX 250 T
UPS MODELS MPT 10-80 MPT 100-160 MPT 200
Dimensions
1900
1900
1400
(mm)
64 0 0 80
0 74 64
0 80 0 80
0
MODELS MPM 10 BAT MPM 15 BAT MPM 20 BAT MPM 30 MPM 40 MPM 60 MPM 80 MPM 100
INPUT
Nominal voltage 380 - 400 - 415 Vac three-phase
Voltage tolerance 400 V + 20% /- 25%
Frequency 45 - 65 Hz
Soft start 0 - 100% in 120’’ (selectable)
Permitted frequency tolerance ± 2% (selectable from ± 1% to ± 5% from front panel)
Standard equipment provided Back Feed protection; separable bypass line
BYPASS
Nominal voltage 220 - 230 - 240 Vac single-phase + N
Nominal frequency 50 or 60 Hz (selectable)
OUTPUT
Nominal power (kVA) 10 15 20 30 40 60 80 100
Active power (kW) 9 13,5 18 27 36 54 72 90
Number of phases 1
Nominal voltage 220 - 230 - 240 Vac single-phase + N (selectable)
Static stability ± 1%
Dynamic stability ± 5% in 10 ms
Voltage distortion < 1% with linear load / < 3% with non-linear load
Crest factor 3:1 lpeack/lrms
Frequency stability on battery 0,05%
Frequency 50 or 60 Hz (selectable)
Overload 110% for 60’; 125% for 10’; 150% for 1’
BATTERIES
Type VRLA AGM / GEL; NiCd; Supercaps; Li-ion; Flywheels
Residual ripple voltage < 1%
Temperature compensation -0,5 Vx°C
Typical charge current 0,2 x C10
INFO FOR INSTALLATION
Weight without batteries (kg) 200 220 230 270 302 440 500 580
800 x 800 x
Dimensions (WxDxH) (mm) 555 x 740 x 1400 800 x 740 x 1400
1900
Remote signals dry contacts
Remote controls ESD and bypass
Communications Double RS232 + dry contacts + 2 slots for communications interface
Operating temperature 0 °C/ +40 °C
Relative humidity <95% non-condensing
Colour Dark grey RAL 7016
Noise level at 1 m (ECO Mode) 60 dBA 62 dBA
IP rating IP20
Smart Active efficiency up to 98%
Directives LV 2006/95/EC - 2004/108/EC; Safety IEC EN 62040-1;
Standards
EMC IEC EN 62040-2; Performance IEC EN 62040-3
Classification in accordance
(Voltage Frequency Independent) VFI - SS - 111
with IEC 62040-3
Moving the UPS transpallet
BAT
Also available with internal batteries
MODELS MPT 10 BAT MPT 15 BAT MPT 20 BAT MPT 30 MPT 40 MPT 60 MPT 80
INPUT
Nominal voltage 380 - 400 - 415 Vac three-phase
Voltage tolerance 400 V + 20% /- 25%
Frequency 45 - 65 Hz
Soft start 0 - 100% in 120’’ (selectable)
Permitted frequency tolerance ± 2% (selectable from ± 1% to ± 5% from front panel)
Standard equipment provided Back Feed protection; separable bypass line
BYPASS
Nominal voltage 380 - 400 - 415 Vac three-phase + N
Nominal frequency 50 or 60 Hz (selectable)
OUTPUT
Nominal power (kVA) 10 15 20 30 40 60 80
Active power (kW) 9 13,5 18 27 36 54 72
Number of phases 3+N
Nominal voltage 380 - 400 - 415 Vac three-phase + N (selectable)
Static stability ± 1%
Dynamic stability ± 5% in 10 ms
Voltage distortion < 1% with linear load / < 3% with non-linear load
Crest factor 3:1 lpeack/lrms
Frequency stability on battery 0,05%
Frequency 50 or 60 Hz (selectable)
Overload 110% for 60’; 125% for 10’; 150% for 1’
BATTERIES
Type VRLA AGM / GEL; NiCd; Supercaps; Li-ion; Flywheels
Residual ripple voltage < 1%
Temperature compensation -0,5 V/°C
Typical charge current 0,2 x C10
INFO FOR INSTALLATION
Weight without batteries (kg) 228 241 256 315 335 460 540
Dimensions (WxDxH) (mm) 555 x 740 x 1400 800 x 740 x 1400
Remote signals dry contacts
Remote controls ESD and bypass
Communications Double RS232 + dry contacts + 2 slots for communications interface
Operating temperature 0 °C / +40 °C
Relative humidity <95% non-condensing
Colour Dark grey RAL 7016
Noise level at 1 m (ECO Mode) 60 dBA 62 dBA
IP rating IP20
Smart Active efficiency up to 98%
Directives LV 2006/95/EC - 2004/108/EC; Safety IEC EN 62040-1;
Standards
EMC IEC EN 62040-2; Performance IEC EN 62040-3
Classification in accordance
(Voltage Frequency Independent) VFI - SS - 111
with IEC 62040-3
Moving the UPS transpallet
BAT
Also available with internal batteries
MODELS MPT 100 MPT 120 MPT 160 MPT 200
INPUT
Nominal voltage 380 - 400 - 415 Vac three-phase
Voltage tolerance 400 V + 20% /- 25%
Frequency 45 - 65 Hz
Soft start 0 - 100% in 120’’ (selectable)
Permitted frequency tolerance ± 2% (selectable from ± 1% to ± 5% from front panel)
Standard equipment provided Back Feed protection; separable bypass line
BYPASS
Nominal voltage 380 - 400 - 415 Vac three-phase + N
Nominal frequency 50 or 60 Hz (selectable)
OUTPUT
Nominal power (kVA) 100 120 160 200
Active power (kW) 90 108 144 180
Number of phases 3+N
Nominal voltage 380 - 400 - 415 Vac three-phase + N (selectable)
Static stability ± 1%
Dynamic stability ± 5% in 10 ms
Voltage distortion < 1% with linear load / < 3% with non-linear load
Crest factor 3:1 lpeack/lrms
Frequency stability on battery 0,05%
Frequency 50 or 60 Hz (selectable)
Overload 110% for 60’; 125% for 10’; 150% for 1’
BATTERIES
Type VRLA AGM / GEL; NiCd; Supercaps; Li-ion; Flywheels
Residual ripple voltage < 1%
Temperature compensation -0,5 V/°C
Typical charge current 0,2 x C10
INFO FOR INSTALLATION
Weight (kg) 600 610 690 790
Dimensions (WxDxH) (mm) 800 x 800 x 1900
Remote signals dry contacts
Remote controls ESD and bypass
Communications Double RS232 + dry contacts + 2 slots for communications interface
Operating temperature 0 °C / +40 °C
Relative humidity <95% non-condensing
Colour Dark grey RAL 7016
Noise level at 1 m (ECO Mode) 65 dBA 68 dBA
IP rating IP20
Smart Active efficiency up to 98%
Directives LV 2006/95/EC - 2004/108/EC; Safety IEC EN 62040-1;
Standards
EMC IEC EN 62040-2; Performance IEC EN 62040-3
Classification in accordance
(Voltage Frequency Independent) VFI - SS - 111
with IEC 62040-3
Moving the UPS transpallet
RPS S.p.A.
The information in this document is subject to change without notice. Riello UPS assumes no responsibility for any errors that may appear in this document.
Neufahrner Str. 12b Fax +34 93 71 46 562 Sales office Guangzhou
85375 Neufahrn/Grüneck Address Unit 1507 East Building,
Tel +49 8165 / 9458-0 ROMANIA Dongshan Square, No. 65,
Fax +49 8165 / 9458-26 Xianlie Zhong Road, Yuexiu District
S.C. Banattika S.r.l. 510095, Guangzhou
FRANCE (Riello UPS Romania) Tel +86 20 28848001
Str. Varsovia Nr. 4 Fax +86 20 28848002
RIELLO ONDULEURS S.a.r.l. 307160 Dumbravita
2/4 Rue du Bois Chaland, Timis County - Romania Sales office Jinan
ZAC du Bois Chaland Tel +40 256 214 681 Room 3508, Building2
91090 Lisses Fax +40 256 214 682 Inzone Center, No.22799
Tel +33 1 60 875454 Jingshi Road, Jinan
Fax +33 1 60 875450 AUSTRALIA Tel +86 531 87969877
Fax+86 531 87960977
Agence Rhone Alpes - Sud RIELLO UPS AUSTRALIA Pty. Ltd.
147 Avenue M. Mérieux, Unit 22/80 Box Road Sales office Xi’an
Parc de Sacuny, Park Avenir 1 Taren Point NSW 2229 A2604, Oak Constellation ,
69530 Brignais Tel +61 2 9531 1999 No. 3, Ke Ji 5th Road,
Tel +33 4 72 177108 Fax +61 2 9531 1988 High-Tech Zone, Xi’an
Fax +33 4 78 351422 Tel +86 29 89526941
Unit 17/810-818 Princes Hwy Fax+86 29 89526943
Springvale VIC 3171
Tel +61 3 9574 6922 Sales office Chengdu
Fax +61 3 9574 6933 Room 1703, Level 17,
Raffles City Tower 2,
PO Box 2251 No. 3 Section 4,
Yokine South WA 6060 South Renmin Road, Chengdu
Tel +61 1300 138,709 Tel +86 28 6511 2870/71
Fax+86 28 6511 8199
PRE-SALES SUPPORT INDIA
(TEC)
tec@riello-ups.com RIELLO PCI India Pvt. Ltd.
Prime Tower: 287-288
Udyog Vihar, Phase II
AFTER-SALES SUPPORT 122015 Gurgaon (HR)
(UPService) Tel.: +91-124-6656999
service@riello-ups.com Fax: +91-124-4871698
DATMPTF2Y15EREN