Sentinel Power: 5-6 kVA 6.5-10 kVA
Sentinel Power: 5-6 kVA 6.5-10 kVA
Sentinel Power: 5-6 kVA 6.5-10 kVA
Power
6
VFI
TYPE
ONLINE Tower
USB Supercaps
plug UPS
Energy Service
share 1st start
HIGHLIGHTS Sentinel Power is the ideal solution for and stabilised in terms of voltage, form and
powering sensitive, mission critical systems frequency. Input and output filters provide
• High UPS reliability such as safety devices (electro-medical significant further immunity from mains
devices), ensuring maximum power disturbances and lightning strikes.
reliability. In terms of technology, performance
• Operating mode The series includes 5-6 kVA single/single- (selectable Eco and Smart Active Modes) and
selection phase and 6.5-8-10 kVA single/single-phase diagnostics (LCD custom display, RS232 and
and three/single-phase models with on-line USB interfaces with Powershield3 software
• High quality output double conversion technology (VFI): the included, ESD input, interface slot for
load is powered continuously by the inverter optional boards), Sentinel Power is one of
voltage which supplies a sinusoidal voltage, filtered the best UPS available on the market.
• Simplified installation
• High battery reliability
Simplified installation
• UPS can be installed on a single-phase or
three-phase distribution network
• Output terminal board + 2 IEC sockets for
powering local consumers (computers,
modems, etc.)
• Simplified positioning (built-in castors).
615
Dimensions
(mm) MULTICOM 352
BB
MULTICOM 372
MULTICOM 384
5
78
MULTI I/O
28
2
DETAILS
SPW 5000 - SPW 6000
SPT 6500 - SPT 8000 - SPT 10000
EMERGENCY SWITCH
DEVICE (ESD)
IEC SOCKETS
USB PORT
MAINTENANCE BYPASS
INPUT SWITCH (SWMB)
(SWIN)
OUTPUT SWITCH
BATTERY FUSE PORT (SWOUT)
(SWBT)
MODELS SPW 5000 SPW 6000 SPT 6500 SPT 8000 SPT 10000
POWER 5000 VA/4000 W 6000 VA/4800 W 6500 VA/5200 W 8000 VA/6400 W 10000 VA/8000 W
INPUT
Nominal voltage 220-230-240 Vac single-phase 220-230-240 Vac single-phase or 380-400-415 Vac three-phase + N
Voltage tolerance 230 Vac ± 20% 230 Vac ± 20% / 400 Vac ± 20%
Minimum voltage without
170 Vac @ 100% load / 140 Vac @ 50% load
battery intervention
Nominal frequency 50/60 Hz ±5 Hz
BYPASS
Voltage tolerance 180 - 264 Vac (selectable in Eco Mode or Smart Active Mode)
Frequency tolerance Selected frequency ±5%
Overload Times 125% for 4 seconds, 150% for 0.5 seconds
OUTPUT
Nominal voltage 220 - 230 - 240 Vac selectable
Voltage distortion < 3% with linear load / < 6% with non-linear load
Frequency 50/60 Hz selectable or with automatic selection
DATSPTB1Y18CREN The information in this document is subject to change without notice. Riello UPS assumes no responsibility for any errors that may appear in this document.
Static variation ± 1.5%
Dynamic variation ≤ 5% in 20 ms
Waveform Sinusoidal
Crest factor ≥3:1
BATTERIES
Type VRLA AGM maintenance-free lead based
Recharge time 6-8 hours
OTHER FEATURES
Net weight (kg) 91 92 105 106
Gross weight (kg) 99 100 110 111
Dimensions (WxDxH) (mm) 282 x 785 x 615
Packaged dimensions
863 x 388 x (650+15)
(WxDxH) (mm)
Smart Active efficiency up to 98%
Protections Overcurrent - short-circuit - overvoltage - undervoltage - temperature - excessive low battery
Communications USB / RS232 + slot for communications interface
Input plugs Terminal board
Output sockets Terminal board + 2 IEC 320 C13
Standards EN 62040-1 EMC EN 62040-2 Directives 2014/35/EU - 2014/30/EU EN 62040-3
Operating temperature 0 °C / +40 °C
Relative humidity < 95% non-condensing
Colour Dark grey RAL 7016
Noise level at 1 m (ECO Mode) < 45 dBA
Moving the UPS castors