Multi V Arub Series
Multi V Arub Series
Multi V Arub Series
website http://www.lgservice.com
LG
ITALIANO
System
Heat Recovery Outdoor Unit R410A
ESPAÑOL
INSTALLATION MANUAL
MODELS: ARUB Series
FRANÇAIS
DEUTSCH
PORTUGUESE
IMPORTANT
• Please read this installation manual completely before
installing the product.
• Installation work must be performed in accordance with
the national wiring standards by authorized personnel
only.
• Please retain this installation manual for future reference
after reading it thoroughly.
ARUB Series Outdoor Unit Installation Manual
TABLE OF CONTENTS
Safety Precautions................................3
Installation ...........................................21
Electrical Wiring..................................43
HR unit PCB.........................................53
Test Run...............................................70
2 Outdoor Unit
Safety Precautions
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must
ENGLISH
be followed.
■ Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is
classified by the following indications.
■ Installation
Have all electric work done by a licensed Ask the dealer or an authorized technician to
electrician according to "Electric Facility install the air conditioner.
Engineering Standard" and "Interior Wire
Regulations" and the instructions given in
this manual and always use a special circuit.
• If the power source capacity is inadequate or • Improper installation by the user may result in
electric work is performed improperly, electric water leakage, electric shock, or fire.
shock or fire may result.
Always ground the product. Always intstall a dedicated circuit and breaker.
• There is risk of fire or electric shock. • Improper wiring or installation may cause fire or
electric shock.
Installation Manual 3
Safety Precautions
For re-installation of the installed product, Do not install, remove, or re-install the unit
always contact a dealer or an Authorized by yourself (customer).
Service Center.
• There is risk of fire, electric shock, explosion, or • There is risk of fire, electric shock, explosion, or
injury. injury.
Do not store or use flammable gas or Use the correctly rated breaker or fuse.
combustibles near the air conditioner.
• There is risk of fire or failure of product. • There is risk of fire or electric shock.
Gasolin
Prepare for strong wind or earthquake and Do not install the product on a defective
install the unit at the specified place. installation stand.
• Improper installation may cause the unit to top- • It may cause injury, accident, or damage to the
ple and result in injury. product.
When installing and moving the air condition- Do not reconstruct to change the settings of
er to another site, do not charge it with a the protection devices.
different refrigerant from the refrigerant
specified on the unit.
• If a different refrigerant or air is mixed with the • If the pressure switch, thermal switch, or other
original refrigerant, the refrigerant cycle may protection device is shorted and operated
malfunction and the unit may be damaged. forcibly, or parts other than those specified by
LGE are used, fire or explosion may result.
R410A R22
R407C
4 Outdoor Unit
Safety Precautions
Ventilate before operating air conditioner Securely install the cover of control box and
when gas leaked out. the panel.
• It may cause explosion, fire, and burn. • If the cover and panel are not installed securely,
ENGLISH
dust or water may enter the outdoor unit and fire
or electric shock may result.
If the air conditioner is installed in a small room, measures must be taken to prevent the
refrigerant concentration from exceeding the safety limit when the refrigerant leaks.
• Consult the dealer regarding the appropriate measures to prevent the safety limit from being exceed-
ed. Should the refrigerant leak and cause the safety limit to be exceeded, harzards due to lack of oxy-
gen in the room could result.
Don't use the existing manifold gage for R22 Don't mix and use the R22 pipe and the
refrigerant. installation appliances that were used until
now
• Use the manifold gage for high pressure (R410A) • Mixing the oil of R22 and R410A may cause
as possible as for stable refrigerant filling. failure of the unit due to hydrolysis.
Installation Manual 5
Safety Precautions
■ Operation
Do not damage or use an unspecified power Use a dedicated outlet for this appliance.
cord.
• There is risk of fire, electric shock, explosion, or • There is risk of fire or electrical shock.
injury.
Be cautious that water could not enter the Do not touch the power switch with wet
product. hands.
• There is risk of fire, electric shock, or product • There is risk of fire, electric shock, explosion, or
damage. injury.
Take care so that children should not ran- When the product is soaked (flooded or
domly operate the wire remote control for submerged), contact an Authorized Service
play. Center.
• Frequent conversion to cold or heat mode may • There is risk of fire or electric shock.
cause failure of the unit.
Be cautious not to touch the sharp edges Take care to ensure that nobody could step
when installing. on or fall onto the outdoor unit.
• It may cause injury. • This could result in personal injury and product
damage.
6 Outdoor Unit
Safety Precautions
Do not open the inlet grill of the product during operation. (Do not touch the electrostatic filter,
if the unit is so equipped.)
• There is risk of physical injury, electric shock, or product failure.
ENGLISH
■ Installation
Always check for gas (refrigerant) leakage Do not install the product where the noise or
after installation or repair of product. hot air from the outdoor unit could damage
the neighborhoods.
• Low refrigerant levels may cause failure of • It may cause a problem for your neighbors.
product.
Keep level even when installing the product. Do not install the unit where combustible gas
may leak.
• To avoid vibration or water leakage. • If the gas leaks and accumulates around the
unit, an explosion may result.
90˚ Gasolin
Use power cables of sufficient current Do not use the product for special purposes,
carrying capacity and rating. such as preserving foods, works of art, etc. It
is a consumer air conditioner, not a precision
refrigeration system.
• Cables that are too small may leak, generate • There is risk of damage or loss of property.
heat, and cause a fire.
Installation Manual 7
Safety Precautions
Keep the unit away from children. The heat When installting the unit in a hospital, com-
exchanger is very sharp. munication station, or similar place, provide
sufficient protection against noise.
• It can cause the injury, such as cutting the finger. • The inverter equipment, private power generator,
Also the damaged fin may result in degradation high-frequency medical equipment, or radio com-
of capacity. munication equipment may cause the air condition-
er to operate erroneously, or fail to operate. On the
other hand, the air conditioner may affect such
equipment by creating noise that disturbs medical
treatment or image broadcasting.
Do not install the product where it is exposed to sea wind (salt spray) directly.
• It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins,
could cause product malfunction or inefficient operation.
■ Operation
Do not use the air conditioner in special Do not block the inlet or outlet.
environments.
• Oil, steam, sulfuric smoke, etc. can significantly • It may cause failure of appliance or accident.
reduce the performance of the air conditioner or
damage its parts.
8 Outdoor Unit
Safety Precautions
Make the connections securely so that the Be sure the installation area does not deteri-
outside force of the cable may not be applied orate with age.
to the terminals.
ENGLISH
• Inadequate connection and fastening may gen- • If the base collapses, the air conditioner could
erate heat and cause a fire. fall with it, causing property damage, product
failure, and personal injury.
Install and insulate the drain hose to ensure that water is drained away properly based on the
installation manual.
• A bad connection may cause water leakage.
Safely dispose of the packing materials. Turn on the power at least 6 hours before
starting operation.(In case of outdoor
temperature below 10°C)
• Packing materials, such as nails and other metal or • Starting operation immediately after turning on
wooden parts, may cause stabs or other injuries. the main power switch can result in severe
• Tear apart and throw away plastic packaging bags damage to internal parts. Keep the power switch
so that children may not play with them. If children turned on during the operational season.
play with a plastic bag which was not torn apart,
they face the risk of suffocation.
Installation Manual 9
Safety Precautions
Do not touch any of the refrigerant piping Do not operate the air conditioner with the
during and after operation. panels or guards removed.
• It can cause a burn or frostbite. • Rotating, hot, or high-voltage parts can cause
injuries.
Do not directly turn off the main power Auto-addressing should be done in condition of
switch after stopping operation. connecting the power of all indoor and outdoor
units. Auto-addressing should also be done in
case of changing the Indoor unit PCB.
• Wait at least 5 minutes before turning off the
main power switch. Otherwise it may result in
water leakage or other problems.
Use a firm stool or ladder when cleaning or Do not insert hands or other objects through
maintaining the air conditioner. the air inlet or outlet while the air conditioner
is plugged in.
• Be careful and avoid personal injury. • There are sharp and moving parts that could
cause personal injury.
Avoid a place where rain may enter since the Install the HR unit at a place in which it
HR unit is for indoor Is not affected by operation mode changing noise.
• There is risk of property damage, failure of product, • Installation within cell such as meeting room
or electric shock. etc, may disturb business due to noise.
10 Outdoor Unit
Installation Process
Installation Process
Determination of division work Indicate clearly who is to be responsible for switch settings
ENGLISH
Make relationship between outdoor, indoor, remote controller, and option connections clear.
Preparation of contract drawings (Prepare control circuit diagram)
All tight test In the final check for 24hours at 3.80 MPa(38.7 kgf/cm2) there must be no drop in pressure.
Vacuum drying The vacuum pump used must have a capacity of reaching at least 5 Torr, more than 1 hour.
Additional charge of refrigerant Recharge correctly as calculated in this manual and record the amount of added refrigerant
Automatic addressing of indoor unit and valves Refer to automatic addressing flowchart
Preheat the crank case with the electrical heater for more than 6 hours.
(In case of the outdoor temperature below 10°C)
Fit facing panels Make sure there are no gaps left between the facing materials used on the ceiling
Test run adjustment Run each indoor unit in turn to make sure the pipe work has been fitted correctly
Transfer to customer with explanation Explain the proper use of the system as clearly as possible to your customer and make
sure all relevant documentations are in order.
• The above list indicates the order in which the individual work operations are normally carried out but this order may be
varied where local conditions warrants such change.
• The wall thickness of the piping should comply with the relevant local and national regulations for the designed pres-
sure 3.8MPa.
• Since R410A is a mixed refrigerant, the required additional refrigerant must be charged in its liquid state.(If the refriger-
ant is charged in its gaseous state, its composition changes and the system will not work properly.)
Installation Manual 11
Installation Process
2) In case, to install the outdoor unit on the seaside, set up a windbreak not to be exposed to the sea wind.
1. If you can’t meet above guide line in the seaside installation, please contact LG Electronics for the additional anticorrosion treatment.
2. Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on the heat exchanger by using water
12 Outdoor Unit
Outdoor Units Information
ENGLISH
CAUTION: A ratio of the connectable Indoor Units with the Outdoor: Within 50 ~ 130%
A ratio of the running Indoor Units with the Outdoor: Within 10 ~ 100%
(A combinated operation over 100% causes to reduce the total capacity.)
Installation Manual 13
Select the Best Location
14 Outdoor Unit
Installation Space
481
7
100 more
(Serviceing space)
ENGLISH
300more 300more
345
(NOTICE 2)
1 (Servicing space) (Servicing space)
2
3
100 more
(Serviceing space)
450
Inspection door(NOTICE 1)
(servicing space) 300more 450more
(NOTICE 2)
450 (Servicing space) (Servicing space)
124
128 4 5
218
182
60
61 419 (137)
30
(174) 453 (174)
6
Description
No. Part Name
PRHR040/030 PRHR020
1 Low pressure Gas pipe connection port Ø28.58 Brazing connection Ø22.2 Brazing connection
2 High pressure Gas pipe connection port Ø22.2 Brazing connection Ø19.05 Brazing connection
3 Liquid pipe connection port Ø12.7 Brazing connection Ø9.52 Brazing connection
4 Indoor unit Gas pipe connection port Ø15.88 Brazing connection Ø15.88 Brazing connection
5 Indoor unit Liquid pipe connection port Ø9.52 Brazing connection Ø9.52 Brazing connection
6 Control box
7 Hanger metal M10 of M8 M10 of M8
NOTICE :
1. Be sure to install the inspection door at the control box side.
2. If reducers are used, servicing space must be increased equal to reducer's dimension.
Installation Manual 15
Installation Space
Installation Space
Individual Installation
■ Basic space required
A space of at least 250 mm is necessary at the back for inlet air. Taking servicing, etc. from the rear into
account, a space of about 900 mm should be provided, the same as at the front.
C
Control Box
Front Side
E Rear inlet (open in principle) B
Control Box
Front Side Front Side
B B
■ When inlet air enters from right and left sides of unit
A 900 mm or more
(Control box is of a open/close type)
B 250 mm or more
Rear Side
C 150 mm from the wall A B
h B
C C
CAUTION
H
Front Side
Wall height(H) must not exceed height of A
Add (h) to , .
Rear Side Rear Side
B B
C C C C
A 250 mm or more
(350mm or more at the coastal area)
B 150 mm from the wall
A
h
Rear Side
A
CAUTION
B B
H
Wall height(H) must not exceed height of
the product. If the wall height is higher Front Side
than the whole height of product by (h), < Side view > < Top view >
Add (h) to , .
B B B B
16 Outdoor Unit
Installation Space
■ When unit is surrounded by walls
A 900 mm or more (Control box is of a open/close type)
B 250 mm or more
ENGLISH
Rear Side B Rear Side B
B B B B
Rear Side B
B B
Front Side A
A A
A
B B B
C C C
D 1000 mm or more
E Air outlet guide (Procured at the site)
F 250 mm or more 587.6
D
F
E
372.5
390
723.5
125
Installation Manual 17
Installation Space
Front Side
Rear Side
Rear Side
Rear Side Rear Side Rear Side Rear Side
Front Side
Front Side
Front Side
Rear Side
Rear Side
Rear Side
Front Side Front Side Front Side Front Side
Rear Side
Front Side
Front Side
Rear Side
Front Side
Front Side
Front Side
Front Side
Rear Side
Rear Side
Rear Side
Front Side
Rear Side
Rear Side
Front Side
Front Side
Rear Side
Rear Side
Rear Side
Front Side
Rear Side
Rear Side
18 Outdoor Unit
Installation Space
Cautions in winter especially for seasonal wind
• Sufficient measures are required at a snow area or severe cold area in winter so that product can be operated
well.
• Get ready for seasonal wind or snow in winter even in other area.
ENGLISH
• Install a suction and discharge duct not to let in snow or rain.
• Install the outdoor unit not to come in contact with snow directly. If snow piles up and freezes on the air suction
hole, the system may malfunction. If it is installed at snowy area, attach the hood to the system.
• Install the outdoor unit at the higher installation console by 50cm than the average snowfall (annual average
snowfall) if it is installed at the area with much snowfall.
• Where snow accumulated on the upper part of the outdoor unit by more than 10cm, always remove snow for
operation.
1. The height of H frame must be more than 2 times the snowfall and its width shall not exceed the width of the
product. (If width of the frame is wider than that of the product, snow may accumulate)
2. Don't install the suction hole and discharge hole of the outdoor unit facing to the seasonal wind.
CAUTION
• Always apply main power of the outdoor unit during use of product
(cooling season/heating season).
• Always apply power before 6 hours to heat the crank case heater where performing test run after instal-
lation of product or where operating the product after cutting the main power of the outdoor unit (for
example, power failure). It may result in burning out of the compressor if not preheating the crank case
with the electrical heater for more than 6 hours.(In case of the outdoor temperature below 10°C)
CAUTION
Do not install the product where it is exposed to sea wind (salt spray) directly.
• It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins,
could cause product malfunction or inefficient operation.
Installation Manual 19
Lifting Method
Lifting method
• When carrying the unit suspended, pass the ropes under the unit and use the two suspension points each at
the front and rear.
• Always lift the unit with ropes attached at four points so that impact is not applied to the unit.
• Attach the ropes to the unit at an angle of 40° or less.
Sub line
A 40° or less
WARNING
CAUTION
Be very careful while carrying the product.
• Do not have only one person carry product if it is more than 20 kg.
• PP bands are used to pack some products. Do not use them as a mean for transportation because they
are dangerous.
• Do not touch heat exchanger fins with your bare hands. Otherwise you may get a cut in your hands.
• Tear plastic packaging bag and scrap it so that children cannot play with it. Otherwise plastic packaging
bag may suffocate children to death.
• When carrying in outdoor unit, be sure to support it at four points. Carrying in and lifting with 3-point
support may make outdoor unit unstable, resulting in a fall of it.
20 Outdoor Unit
Installation
Installation
Location of anchor bolt
ENGLISH
■ Individual installation
10 10 10
700
700
700
900 900 383 900 900 383 900 383 900
10 10 10 10 10
900 383 900 383 900 383 900 383 900 383 900
Installation Manual 21
Installation
A Ensure that the corner part can be securely mounted. Otherwise, the support for
installation may be bent.
B Obtain and use the M10 anchor bolt.
C The corner was not properly mounted.
D Outdoor unit (Insert the cushion pad between outdoor unit and base support to ensure that
anti-vibration may be done in a wide area)
G E Pipe and wiring space (in case of piping and wiring on the floor surface)
F H-Beam support
G Concrete base support
WARNING
• Be sure to install unit in a place strong enough to withstand its weight.
Any lack of strength may cause unit to fall down, resulting in a personal injury.
• Have installation work in order to protect against a strong wind and earthquake. Any installation
deficiency may cause unit to fall down, resulting in a personal injury.
• Especially take care for support strength of the floor surface, water drain processing (processing of
water flown out from the outdoor unit during operation) and paths of the pipe and wiring when mak-
ing a base support.
• Don't use a tube or pipe for water drain in the base pan and perform water drain processing by
using the drain path. Water drain may be done due to freezing of a tube or pipe.
Rear view Side view
Water
Drain
Path
22 Outdoor Unit
Installation
Preparation of Piping
Main cause of gas leakage is defect in flaring work. Carry out correct flaring work in the following procedure.
ENGLISH
1) Cut the pipes and the cable.
■ Use the accessory piping kit or the pipes purchased Copper
locally. tube 90° Slanted Uneven Rough
■ Measure the distance between the indoor and the
outdoor unit.
■ Cut the pipes a little longer than measured distance.
■ Cut the cable 1.5m longer than the pipe length.
Pipe
2) Burrs removal Reamer
■ Completely remove all burrs from the cut cross section
of pipe/tube.
■ Put the end of the copper tube/pipe to downward direc- Point down
tion as you remove burrs in order to avoid to let burrs
drop in the tubing.
3) Flaring work
■ Carry out flaring work using flaring tool as shown below.
Handle
Indoor unit Pipe "A" Bar Bar
[kW(Btu/h] Gas Liquid Gas Liquid "A" Yoke
<5.6(19,100) 1/2" 1/4" 1.6~1.8 1.1~1.3 Cone
<16.0(54,600) 5/8" 3/8" 1.6~1.8 1.5~1.7
<22.4(76,400) 3/4" 3/8" 1.9~2.1 1.5~1.7
Copper pipe
Firmly hold copper tube in a bar(or die) as indicated
dimension in the table above. Clamp handle
Red arrow mark
4) Check
■ Compare the flared work with figure below.
■ If flare is noted to be defective, cut off the flared section
and do flaring work again. Smooth all round
Inside is shining without scratches.
= Improper flaring =
Installation Manual 23
Installation
Ø9.52mm 34~42 45
° ±2
A
Ø12.7mm 55~66
Ø15.88mm 63~82 R=0.4~0.8
Ø19.05mm 99~121
CAUTION
• Always use a charge hose for service port connection.
• After tightening the cap, check that no refrigerant leaks are
present. Union
• When loosening a flare nut, always use two wrenches in
combination, When connecting the piping, always use a spanner
and torque wrench in combination to tighten the flare nut.
• When connecting a flare nut, coat the flare(inner and outer faces)
with oil for R410A(PVE) and hand tighten the nut 3 to 4 turns as
the initial tightening.
Tightening torque
Shutoff Tightening torque N-m(Turn clockwise to close)
valve size Shaft(valve body) Cap(Valve lid) Service port Flare nut Gas line piping attached to unit
Ø6.4 14-17
5.4-6.6 Hexagonal 13.5-16.5
Ø9.5 33-39
wrench 4mm
Ø12.7 8.1-9.9 18-22 50-60 -
Hexagonal 11.5-13.9
Ø15.9 13.5-16.5 23-27 62-75
wrench 6mm
Ø22.2 Hexagonal
27-33 36-44 - 22-28
Ø25.4 wrench 10mm
24 Outdoor Unit
Installation
HEAT INSULATION
1. Use the heat insulation material for the refrigerant piping which has an excellent heat-resistance (over
120°C).
ENGLISH
Fastening band
(accessory)
2. Precautions in high humidity circumstance:
This air conditioner has been tested according to the
"ISO Conditions with Mist" and confirmed that there is
not any default. However, if it is operated for a long
time in high humid atmosphere (dew point tempera- Refrigerant piping
ture: more than 23°C), water drops are liable to fall. In
Indoor unit
this case, add heat insulation material according to
Thermal insulator
the following procedure: (accessory)
• Heat insulation material to be prepared... EPDM
(Ethylene Propylene Diene Methylene)-over 120°C
the heat-resistance temperature.
• Add the insulation over 10mm thickness at high humidity environment.
Installation Manual 25
Refrigerant piping installation
WARNING
After completing work, securely tighten both service ports and caps so that gas does not leak.
Pipe joint (auxiliary parts): Securely perform brazing with a nitrogen blow into the service valve port.
(Releasing pressure : 0.02 MPa or less)
Flare nut: Loose or tighten flare nut by using the wrench with both ends. Coat the flare connection part with
oil for the compressor.
Service port: Make the refrigerant pipe vacuum and charge it using the service port. Always reattach caps
after completing work (tightening torque of service cap: 14Nm (140kg-cm) or more).
Liquid pipe
Low Pressure Gas pipe
High Pressure Gas pipe
Elbow joint
Ball Valve
Flare Valve (Liquid pipe)
(High Pressure Gas pipe)
Ball Valve
(Low Pressure Gas pipe)
26 Outdoor Unit
Refrigerant piping installation
3
When connecting the pipes from the front of
Knock out
the outdoor unit, Remove part (or part
and part ). Transmission Line Hole
ENGLISH
Power Cable Hole
When connecting the pipes from the side of the
Pipe Hole
outdoor unit, remove part (the whole "Knock
out" part).
(Front) (Side)
WARNING
After installing the pipe, clog the pipe excavation inlet of the front panel and the side panel
(Wire may be damaged due to entering of rats, animals, etc).
Installation Manual 27
Refrigerant piping installation
Model Low Pressure Gas Pipe Liquid Pipe High Pressure Gas Pipe
Ø 9.52
Ø34.9 Ø22.2
Ø28.58 Ø19.05
Ø31.8 Ø12.7 Ø28.58
Ø12.7 Ø19.05
Ø19.05 Ø15.88
Ø28.58 Ø22.2 Ø12.7 Ø22.2 Ø22.2
Ø28.58 Ø15.88
ARCNB20
Ø15.88
OD34.9 Ø19.05 Ø15.88
OD28.58 Ø22.2 OD12.7 OD22.2
3 outdoor units
Model Low Pressure Gas Pipe Liquid Pipe High Pressure Gas Pipe
Ø15.88
OD34.9 Ø19.05 Ø15.88
OD28.58 Ø22.2 OD12.7 OD22.2
Ø15.88
Ø41.3
Ø34.9
Ø34.9
Ø38.1 Ø19.05 Ø28.58
Ø19.05 Ø31.8
Ø19.05
Ø28.58 Ø12.7
Ø28.58 Ø12.7 Ø22.2
Ø22.2
Ø34.9
ARCNB30 Ø22.2 Ø28.58
Ø19.05
OD28.58 OD12.7 Ø15.88
OD22.2
Ø22.2
Ø9.52 Ø19.05
28 Outdoor Unit
Refrigerant piping installation
Installation Procedure
1. Using an insert-hole-in- anchor, hang the hanging bolt.
ENGLISH
2. Install a hexagon nut and a flat washer (locally-procured)to the hanging bolt as shown
in the figure in the bottom, and fit the main unit to hang on the hanger metal. Six-sided Nut
(M10 or M8)
3. After checking with a level that the unit is level, tighten the hexagon nut.
* The tilt of the unit should be within ±5° in front/back and left/right. Hanger metal
4. This unit should be installed suspended from ceiling and side A should always be Flat washer
facing up. (M10)
5. Insulate not used pipes completely as shown in the figure.
Hanging bolt
(M10 or M8)
Insulation
Gas pipe
CAUTION:
Whenever connecting the indoor units with the HR unit, install the indoor units in numerical order from No.1.
Ex) In case of installing 3 indoor units : No. 1, 2, 3 (O), No. 1, 2, 4 (X), No.1, 3, 4 (X), No.2, 3, 4 (X).
Installation Manual 29
Refrigerant piping installation
Type of HR Unit
Select an HR unit according to the number of the indoor units to be installed. HR units are classified into 3 types
by the number of connectable indoor units.
Ex) Installation of 6 indoor units
Consists of HR unit for 4 rooms and HR unit for 2 rooms.
2 3 3 4
1 1
2 1 2
WARNING
• 1 port of HR unit allows up to 14.1kW based on cooling capacity of the indoor unit (up to 14.1kW
(48kBtu/hr) for max installation).
• The maximum total capacity of the indoor units connected to one PRHR040 HR unit is 47kW
(160kBtu/hr). In case of installation of four indoor units of 14.1kW (48kBtu/hr), use two PRHR020's
rather than one PRHR040.
Remove caps on
the brazing part. Gas pipe Ø15.88
Liquid pipe Ø9.52
Brazing Type
30 Outdoor Unit
Refrigerant piping installation
[ Reducers for indoor unit and HR unit ]
Gas pipe
Models
ENGLISH
Liquid pipe
High pressure Low pressure
Indoor unit
reducer OD9.52 Ø6.35
OD15.88 Ø12.7
HR unit
reducer
OD15.88 Ø12.7
OD19.05 Ø15.88
Installation Manual 31
Refrigerant piping installation
Caution
1. Use the following materials for refrigerant piping.
• Material: Seamless phosphorous deoxidized copper pipe
• Wall thickness : Comply with the relevant local and national regulations for the designed pressure
3.8MPa. We recommend the following table as the minimum wall thickness.
Outer diameter
6.35 9.52 12.7 15.88 19.05 22.2 25.4 28.58 31.8 34.9 38.1 41.3
[mm]
Minimum
0.8 0.8 0.8 0.99 0.99 0.99 0.99 0.99 1.1 1.21 1.35 1.43
thickness [mm]
2. Commercially available piping often contains dust and other materials. Always blow it clean with a
dry inert gas.
3. Use care to prevent dust, water or other contaminants from entering the piping during installation.
4. Reduce the number of bending portions as much as possible, and make bending radius as big as
possible.
5. Always use the branch piping set shown below, which are sold separately.
Y branch
ARBLB01620 ARBLB03320
ARBLB07120 ARBLB14520
6. If the diameters of the branch piping of the designated refrigerant piping differs, use a pipe cutter to cut
the connecting section and then use an adapter for connecting different diameters to connect the piping.
7. Always observe the restrictions on the refrigerant piping (such as rated length, difference in height, and
piping diameter).
Failure to do so can result in equipment failure or a decline in heating/cooling performance.
8. The system will stop due to an abnormality like excessive or insufficient refrigerant. At such a time, always
properly charge the unit. When servicing, always check the notes concerning both the pipe length and the
amount of additional refrigerant.
9. Never perform a pump down. This will not only damage the compressor but also deteriorate the
performance.
10. Never use refrigerant to perform an air purge. Always evacuate using a vacuum pump.
11. Always insulate the piping properly. Insufficient insulation will result in a decline in heating/cooling perfor-
mance, drip of condensate and other such problems.
12. When connecting the refrigerant piping, make sure the service valves of the outdoor unit is completely
closed (the factory setting) and do not operate it until the refrigerant piping for the outdoor and indoor
units has been connected, a refrigerant leakage test has been performed and the evacuation process
has been completed.
13. Always use a non-oxidizing brazing material for brazing the parts and do not use flux. If not, oxidized film
can cause clogging or damage to the compressors and flux can harm the copper piping or refrigerant oil.
14. Diameter of the refrigerant pipe from the HR unit to the indoor unit is determined by capacity of the
indoor unit. The pipe port is installed to suit a large capacity of the indoor unit for the connection flare of
the HR unit. It is sufficient to cut, connect and install the subsidiary flare to suit the pipe of the indoor unit
connected.
15. Take care so that there is no thermal damage on the service valves of the outdoor unit.
(Especially packing part of service port.) Wrap the service valve with a wet towel when brazing it.
32 Outdoor Unit
Refrigerant piping installation
WARNING
When installing and moving the air conditioner to another site, be sure to make recharge refrigerant
after perfect evacuation.
ENGLISH
- If a different refrigerant or air is mixed with the original refrigerant, the refrigerant cycle may malfunction and
the unit may be damaged.
- After selecting diameter of the refrigerant pipe to suit total capacity of the indoor unit connected after
branching, use an appropriate branch pipe set according to the pipe diameter of the indoor unit and the
installation pipe drawing.
Unit: mm
1,280
1,280
Installation Manual 33
Refrigerant piping installation
F3
F2
E2
E F1
E1
A
B1
D1
a
D2
b B
C1 C1
c
*
B2
H D3
"a" C3 D
d C3 C4
h C2 g i j k
"b"
C2 D7 D9
D4 D10
e D8
D6
D5
■ Case1 ("a")
: Maximum height is 15 m if you install with Y branch.
■ Case2 ("b")
: Height is zero(0) m in HR unit serial connector.
WARNING
* : Serial connection of HR units : Capacity sum of indoor units ≤ 160kBtu/hr
• Refer to the HR unit PCB part for the valve group control setting.
• It is recommended that difference in pipe lengths between an HR unit and indoor units, for example
difference in length of a, b, c, and d, be minimized. The larger difference in pipe lengths, the more different
performance between indoor units.
• Piping length from outdoor branch to outdoor unit ≤ 10m, equivalent length : max 13m (for 16HP or more)
34 Outdoor Unit
Refrigerant piping installation
➲ Refrigerant pipe diameter between branches and HR units (B,C,D)
Downward indoor unit total capacity Liquid pipe Gas pipe [mm(inch)]
[kW(Btu/h)] [mm(inch)] Low pressure High pressure
< 5.6 (19,100) Ø6.35(1/4) Ø12.7(1/2) Ø9.52(3/8)
ENGLISH
< 16.0 (54,600) Ø9.52(3/8) Ø15.88(5/8) Ø12.7(1/2)
< 22.4 (76,400) Ø9.52(3/8) Ø19.05(3/4) Ø15.88(5/8)
< 33 (112,600) Ø9.52(3/8) Ø22.2(7/8) Ø19.05(3/4)
< 47 (160,400) Ø12.7(1/2) Ø28.58(1 1/8) Ø22.2(7/8)
< 71 (242,300) Ø15.88(5/8) Ø28.58(1 1/8) Ø28.58(1 1/8)
< 104 (354,900) Ø19.05(3/4) Ø34.9(1 3/8) Ø28.58(1 1/8)
104 (354,900) ≤ Ø19.05(3/4) Ø41.3(1 5/8) Ø28.58(1 1/8)
15m
HR1 HR1 HR2
1 2 3 4 1 2 3 4 5 6 7 8
48k 48k 48k 48k 12k 24k 24k 12k 48k 48k 48k 12k
• Capacity sum of indoor units is over 160kBtu/hr. • Distance between neighboring HR unit is over 10m,
and Capacity sum of indoor units is over 160kBtu/hr.
Pattern Pattern
A A
HR1 HR2
HR1 HR2
1 2 3 4
1 2 3 4 5 6 7 8
36k 36k 36k 36k
12k 24k 24k 12k 48k 48k 48k 12k
Installation Manual 35
Refrigerant piping installation
◆ Outdoor Unit Connection
➲ Refrigerant pipe diameter before 1st branch (A,E,F)
Upward outdoor unit total capacity Liquid pipe Gas pipe [mm(inch)]
[HP] [mm(inch)] Low pressure High pressure
8 Ø9.52(3/8) Ø19.05(3/4) Ø15.88(5/8)
10 Ø9.52(3/8) Ø22.2(7/8) Ø19.05(3/4)
12 Ø12.7(1/2) Ø28.58(1 1/8) Ø19.05(3/4)
14, 16 Ø12.7(1/2) Ø28.58(1 1/8) Ø22.2(7/8)
18, 20 Ø15.88(5/8) Ø28.58(1 1/8) Ø22.2(7/8)
22, 24 Ø15.88(5/8) Ø34.9(1 3/8) Ø28.58(1 1/8)
26~34 Ø19.05(3/4) Ø34.9(1 3/8) Ø28.58(1 1/8)
36 Ø19.05(3/4) Ø41.3(1 5/8) Ø28.58(1 1/8)
38, 40 Ø19.05(3/4) Ø41.3(1 5/8) Ø34.9(1 3/8)
WARNING
Do not choose the main pipe diameter, namely A, by downward indoor unit total capacity but its outdoor unit model name.
Do not let the connection pipe from branch to branch exceed the main pipe diameter chosen by outdoor unit model name.
EX) Where connecting the indoor units to the 22 HP (61.5 kW) outdoor unit to 130% of its system capacity (79.9 kW) and
branching one HR unit of four 7k indoor units (8.4kW) at the 1st branch.
Main pipe diameter(22 HP outdoor unit): Ø15.88(Liquid pipe), Ø34.9(Low pressure gas pipe), Ø28.58(High pressure gas pipe)
Pipe diameter between 1st and 2nd branch (71.5kW indoor units): Ø19.05(Liquid pipe), Ø34.9(Low pressure gas pipe) and
Ø28.58(High pressure gas pipe) in conformity with downward
indoor units.
Since the main pipe diameter of 22HP outdoor unit is Ø15.88(Liquid pipe), Ø34.9(Low pressure gas pipe) , Ø28.58(High pressure gas
pipe), it should be used as the diameter of the main pipe and the connection pipe between 1st and 2nd indoor branches.
WARNING
When the equivalent length between the outdoor unit and a indoor unit is 90 m or more, the size of main
pipes (only liquid pipe) must be increased one grade.
Liquid pipe
8, 10HP..........................................Ø9.52 → Ø12.7 18, 20, 22, 24HP............................Ø15.88 → Ø19.05
12, 14, 16HP..................................Ø12.7 → Ø15.88 26, 28, 30, 32, 34, 36, 38, 40HP....Ø19.05 → Ø22.2
36 Outdoor Unit
Refrigerant piping installation
◆ The Amount of Refrigerant
The calculation of the additional charge should take account of the length of pipe.
A Product charge(1unit)=8kg
ENGLISH
Ex) ARUB1208T1
B Additional charge (kg) Outdoor unit
HR unit (1EA)
Indoor unit
= Total liquid pipe (m): Ø22.2mm x 0.354(kg/m)
WARNING
Regulation for refrigerant leakage
: the amount of refrigerant leakage should satisfy the following equation for human safety.
❐ If the above equation can not be satisfied, then follow the following steps.
- Selection of air conditioning system: select one of the next
1. Installation of effective opening part
2. Reconfirmation of outdoor unit capacity and piping length
3. Reduction of the amount of refrigerant
4. Installation of 2 or more security device (alarm for gas leakage)
- Change indoor unit type
: installation position should be over 2m from the floor (wall mounted type → cassette type)
- Adoption of ventilation system
: choose ordinary ventilation system or building ventilation system
- Limitation in piping work
: Prepare for earthquake and thermal stress
WARNING Refer to model information since the CF value of correction factor differs depending
on model.
Installation Manual 37
Refrigerant piping installation
• Ensure that the branch pipes are attached horizontally or vertically (see the diagram below.)
Horizontal Facing Facing
plane downwards upwards
A
Viewed from point A
in direction of arrow
Within ± 3° Within ± 3°
Tape
(field supply)
38 Outdoor Unit
Refrigerant piping installation
Models Low Pressure Gas Pipe Liquid pipe High Pressure Gas Pipe
ENGLISH
Ø19.05 Ø15.88
Ø12.7 Ø9.52
Ø12.7
Ø15.88 Ø12.7 Ø9.52 Ø6.35 Ø12.7
Ø15.88
ARBLB01620 Ø9.52
~ under 22.4kW
(76kBtu/h) Ø12.7 Ø9.52 Ø6.35 Ø12.7 Ø9.52
Ø15.88
Ø22.2 Ø19.05
Ø15.88 Ø12.7
Ø19.05 Ø22.2 Ø9.52 Ø6.35 Ø15.88 Ø19.05
Ø9.52 Ø12.7
ARBLB03320
~ under 33.0kW
(112kBtu/h) Ø15.88 Ø12.7 Ø6.35
Ø12.7 Ø9.52
Ø9.52
Ø22.2
Ø28.58 Ø28.58
Ø22.2 Ø19.05
Ø12.7 Ø19.05
Ø15.88 Ø9.52 Ø28.58 Ø28.58
Ø19.05
Ø12.7 Ø19.05
Ø25.4
ARBLB07120 Ø22.2
Ø6.35
Ø28.58
~ under 71.0kW Ø15.88 Ø22.2
Ø12.7 Ø9.52 Ø19.05
(242kBtu/h)
Ø34.9 Ø31.8 OD28.58 OD22.2 Ø15.88
Installation Manual 39
Refrigerant piping installation
Note:
If the ambient temperature differs between the time when pressure is applied and when the pressure drop is checked, apply
the following correction factor
There is a pressure change of approximately 0.1 kg/cm2 (0.01 MPa) for each 1°C of temperature difference.
Correction= (Temp. at the time of pressurization – Temp. at the time of check) X 0.1
For example: Temperature at the time of pressurization (3.8 MPa) is 27 °C
24 hour later: 3.73 MPa, 20°C
In this case the pressure drop of 0.07 is because of temperature drop
And hence there is no leakage in pipe occurred.
CAUTION
To prevent the nitrogen from entering the refrigeration system in the liquid state, the top of the cylinder must be at higher
position than the bottom when you pressurize the system.
Usually the cylinder is used in a vertical standing position.
(2) Vacuum
Vacuum of the pipe and the indoor units should be made from the port of the outdoor unit's service valve
with the service valve closed. Vacuum should be made from the high pressure gas pipe and the liquid pipe
simultaneously with a vacuum pump including a vacuum gage. (The low pressure gas pipe becomes vacu-
um via the HR unit.) After the degree of vacuum gets to 5 Torr, keep vacuum for more than an hour.
* Never perform air purging by using refrigerant.
• Vacuum drying : Use a vacuum pump that can evacuate to -
100.7kPa (5 Torr, -755mmHg).
1. Evacuate the system from the liquid pipes and the high pres-
sure gas pipes with a vacuum pump for over 2 hours and
bring the system to -100.7kPa. After maintaining system
under that condition for over 1 hour, confirm the vacuum
gauge rises. If it rises, the system may contain moisture or
leak.
2. Following should be executed if there is a possibility of mois-
ture remaining inside the pipe.
(Rainwater may enter the pipe during work in the rainy sea-
son or over a long period of time)
After evacuating the system for 2 hours, give pressure to the
system to 0.05MPa(vacuum break) with nitrogen gas and
then evacuate it again with the vacuum pump for 1 hour to
-100.7kPa(vacuum drying). If the system cannot be evacuat- High pressure gas pipe Liquid pipe
ed to -100.7kPa within 2 hours, repeat the steps of vacuum
break and its drying. Finally, check if the vacuum gauge rise Low pressure gas pipe
or not, after maintaining the system in vacuum for 1 hour.
40 Outdoor Unit
Refrigerant piping installation
(3) Refrigerant Charged Method
After vacuum completion, primarily charge the calculated amount of additional refrigerant through the high
pressure gas pipe and the liquid pipe. If the refrigerant is not charged any more, secondarily charge the
remaining refrigerant through the low pressure gas pipe and the liquid pipe.
ENGLISH
Vacuum and Primary charging Secondary charging
High pressure gas pipe Liquid pipe High pressure gas pipe Liquid pipe
Note : Always add an appropriate amount of refrigerant. (For the refrigerant additional charge)
Too much or too little refrigerant will cause trouble.
WARNING
• If the primary charging through the high pressure gas pipe and the liquid pipe is not performed after vacuum, wet
air may go into the outdoor unit. If air is mixed with the refrigerant, the refrigerant cycle may malfunction and the
unit may be damaged.
• Charging of refrigerant while the compressor is working is prohibited. Otherwise, liquid may go into the compres-
sor. It may cause faults of the compressor.
• Use a gravimeter accurate to 0.1kg.
• Pipe to be vacuum: liquid pipe, high pressure gas pipe (low pressure gas pipe is vacuumed via the HR unit).
• If other refrigerants are mixed in the original refrigerant, a refrigerant cycle may cause malfunction or damage.
• Add accurate refrigerant quantity via calculation.
Too much or too little refrigerant may cause problems
• Repeated on and off of the indoor units without charging refrigerant may cause faults of LEV.
• Since R410A is a mixed refrigerant, the required additional refrigerant must be charged in its liquid state. If the
refrigerant is charged in its gaseous state, its composition changes and the system will not work properly.
• When installing and moving the air conditioner to another site, recharge after perfect evacuation.
- If a different refrigerant or air is mixed with the original refrigerant, the refrigerant cycle may malfunction
and the unit may be damaged.
Installation Manual 41
Refrigerant piping installation
B A C
Heat
Adhesive + Heat - resistant polyethylene foam +
insulation
material Adhesive tape
Indoor Vinyl tape
Outer
Floor exposed Water-proof hemp cloth + Bronze asphalt
covering
A Heat insulation material Outdoor Water-proof hemp cloth + Zinc plate + Oily paint
B Pipe Note:
C Outer covering When using polyethylene cover as covering material, asphalt roof-
(Wind the connection part and cutting part of ing shall not be required.
heat insulation material with a finishing tape.)
• Do not insulate gas or low pressure pipe and liquid or high • Be sure to fully insulate connecting portion.
pressure pipe together.
B A
A Liquid pipe
A F B Gas pipe
Bad example
C Power lines
C D Finishing tape
E Insulating material
D F Transmission lines
E A These parts are not insulated.
C
E Power lines Transmission lines
E
B A
E
F
D
Good example G
A Liquid pipe
B Low pressure gas pipe Separation
C Power lines
D Finishing tape
E Insulating material
F High pressure gas pipe
G Transmission lines
Penetrations
Inner wall (concealed) Outer wall Outer wall (exposed) Sleeve
D Heat insulating material
C E
A A B B Lagging
B
Caulking material
Band
I Waterproofing layer
Sleeve with edge
Penetrating portion on fire
Lagging material
Floor (fireproofing) Roof pipe shaft limit and boundary wall
Mortar or other incombustible caulking
D I Incombustible heat insulation material
G J
F
D When filling a gap with mortar, cover the
B
penetration part with steel plate so that
H the insulation material will not be caved in.
G A For this part, use incombustible materials
B for both insulation and covering.(Vinyl
1m 1m
covering should not be used.)
42 Outdoor Unit
Electrical Wiring
Electrical Wiring
Areas of Caution
ENGLISH
1. Follow ordinance of your governmental organization for technical standard related to electrical equipment,
wiring regulations and guidance of each electric power company.
WARNING
Be sure to have authorized electric engineers do electric work using special circuits in accordance
with regulations and this installation manual. If power supply circuit has a lack of capacity or electric
work deficiency, it may cause an electric shock or fire.
2. Install the outdoor unit transmission line away from the power source wiring so that it may not affected by
electric noise from the power source. (Do not run it through the same conduit.)
3. Be sure to provide designated grounding work to outdoor unit.
CAUTION
Be sure to put outdoor unit to earth. Do not connect earth line to any gas pipe, water pipe, lightening
rod or telephone earth line. If earth is incomplete, it may cause an electric shock.
4. Give some allowance to wiring for electrical part box of Indoor, HR unit and outdoor units, because the box is
sometimes removed at the time of service work.
5. Never connect the main power source to terminal block of transmission line. If connected, electrical parts will
be burnt out.
6. Use 2-core shield cable for transmission line.(O mark in the figure below) If transmission lines of different sys-
tems are wired with the same multiplecore cable, the resultant poor transmitting and receiving will cause erro-
neous operations. ( mark in the figure below)
7. Only the transmission line specified should be connected to the terminal block for outdoor unit transmission.
Installation Manual 43
Electrical Wiring
Indoor Indoor
Indoor Indoor unit unit
unit unit HR
unit
HR
unit Remote Remote
Remote Remote control control
control control
CAUTION
• Use the 2-core shield cables for transmission lines. Never use them together with power cables.
• Never use multi-core cable
• As this unit is equipped with an inverter, to install a phase leading capacitor not only will deteriorate
power factor improvement effect, but also may cause capacitor abnormal heating. Therefore, never
install a phase leading capacitor.
• Keep power imbalance within 2% of the supply rating. Large imbalance will shorten the life of the
smoothing capacitor.
44 Outdoor Unit
Electrical Wiring
ENGLISH
- Connect transmission line between main and sub
outdoor unit through the terminal block.
- Connect transmission lines between outdoor unit
and indoor/HR units through the terminal block.
- When the central control system is connected to the
outdoor unit, a dedicated PCB must be connected
between them.
- When connecting transmission line between out-
door unit and indoor/HR units with shielded wire,
connect the shield ground to the earth screw.
Front Panel
WARNING
The temperature sensor for outdoor air should not be exposed to direct sunlight.
- Provide an appropriate cover to intercept direct sunlight.
Capacitor
Heatsink
(Inverter Comp
Driver)
Transformer Transformer
Control board for inverter fan Connect the ground line of Ground Terminal
distribution panel here. for Transmission
Line Shield
Installation Manual 45
Electrical Wiring
Note:
1. The figures are based on assumed length of parallel cabling up to 100m. For length in excess of 100m
the figures will have to be recalculated in direct proportion to the additional length of line involved.
2. If the power supply waveform continues to exhibit some distortion the recommended spacing in the
table should be increased.
• If the lines are laid inside conduits then the following point must also be taken into account when grouping
various lines together for introduction into the conduits
• Power lines(including power supply to air conditioner) and signal lines must not be laid inside the same
conduit
• In the same way, when grouping the power lines and signal lines should not be bunched together.
CAUTION
■ If apparatus is not properly earthed then there is always a risk of electric shocks, the earthing of the
apparatus must be carried out by a qualified person.
■ Use a power wire pipe for the power wiring.
46 Outdoor Unit
Electrical Wiring
◆ Wiring of Main Power Supply and Equipment Capacity
Outdoor unit (3Ø, 380 ~415V, 50Hz ) Indoor unit (1Ø, 220V, 50Hz)
1. Use a separate power supply for the outdoor unit and indoor unit.
2. Bear in mind ambient conditions (ambient temperature,direct sunlight, rain water,etc.) when proceeding with the wiring and connections.
ENGLISH
3. The wire size is the minimum value for metal conduit wiring. The power cord size should be 1 rank thicker taking into account the line volt-
age drops. Make sure the power-supply voltage does not drop more than 10%.
4. Specific wiring requirements should adhere to the wiring regulations of the region.
5. Power supply cords of parts of appliances for outdoor use should not be lighter than polychloroprene sheathed flexible cord.
6. Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.
WARNING
• Follow ordinance of your governmental organization for technical standard related to electrical equipment, wiring reg-
ulations and guidance of each electric power company.
• Be sure to use specified wires for connections so that no external force is imparted to terminal connections. If connec-
tions are not fixed firmly, it may cause heating or fire.
• Be sure to use the appropriate type of overcurrent protection switch. Note that generated overcurrent may include
some amount of direct current.
CAUTION
• Some installation site may require attachment of an earth leakage breaker. If no earth leakage breaker is installed, it may
cause an electric shock.
• Do not use anything other than breaker and fuse with correct capacity. Using fuse and wire or copper wire with too large
capacity may cause a malfunction of unit or fire.
Installation Manual 47
Electrical Wiring
48 Outdoor Unit
Electrical Wiring
◆ Precautions when laying power wiring
Use round pressure terminals for connections to the power terminal block.
Power wire
ENGLISH
Round pressure terminal
• For wiring, use the designated power wire and connect firmly, then secure to prevent outside pressure
being exerted on the terminal block.
• Use an appropriate screwdriver for tightening the terinal screws. A screwdriver with a small head will
strip the head and make proper tighterning impossible.
• Over-tightening the terminal screws may break them.
CAUTION
When the 400 volt power supply is applied to “N” phase by mistake, replace inverter PCB and transformer in
control box.
Installation Manual 49
Electrical Wiring
◆ Example Connection of Transmission Cable
1 Outdoor Unit
Single phase
power supply
HR unit
WARNING
• Indoor unit ground lines are required for preventing electrical shock accident in current leakage,
transmission disorder by noise effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the
power supply.
CAUTION
• You can install as below figure.
• The transmission cable of HR unit can be installed between indoor unit and indoor unit.
HR unit 3 4 3 4 3 4
The GND terminal is a '–' terminal for the central controller, not ground line
50 Outdoor Unit
Electrical Wiring
◆ Example Connection of Transmission Cable
2 Outdoor Units
ENGLISH
3 phase 4 wires power line(R, S, T)
In series between the units. Main
Transmission line (3 line): wired remote control
Sub
Single phase of power supply line
Transmission line (2 shield line):
Power supply switch
(switch fuse) between outdoor unit and outdoor unit
Transmission line (2 shield line):
3 phase 4 wires between indoor unit and outdoor unit
power supply
Single phase
power supply
HR unit
HR unit
Single phase
power supply
HR unit
HR unit
WARNING
• Indoor unit ground lines are required for preventing electrical shock accident in current leakage,
transmission disorder by noise effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the
power supply.
• All wiring, components and materials to be procured on the site must comply with the applicable local and
national codes.
Between indoor and main outdoor unit Between main outdoor and sub outdoor unit
Indoor Outdoor Central Indoor Outdoor Central
unit unit controller Main unit unit controller Main
outdoor unit outdoor
unit
Sub
HR unit
outdoor unit
The GND terminal is a '–' terminal for the central controller, not ground line
Installation Manual 51
Electrical Wiring
◆ Example Connection of Transmission Cable
3 Outdoor Units
Main
■ When the power source is connected
In series between the units. 3 phase 4 wires power line(R, S, T)
Sub1
Transmission line (3 line): wired remote control
Sub2 Single phase of power supply line
Transmission line (2 shield line):
Power supply switch between outdoor unit and outdoor unit
(switch fuse)
Transmission line (2 shield line):
3 phase 4 wires between indoor unit and outdoor unit
power supply
Single phase
power supply
HR unit HR unit
Main
■ When the power source is supplied to
Each outdoor unit individually.
Sub1
Sub2
Single phase
power supply
HR unit HR unit
WARNING
• Indoor unit ground lines are required for preventing electrical shock accident in current leakage,
transmission disorder by noise effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the
power supply.
• All wiring, components and materials to be procured on the site must comply with the applicable local
and national codes.
Between indoor and main outdoor unit Between main outdoor and sub outdoor unit
Indoor Outdoor Central Indoor Outdoor Central
unit unit controller Main unit unit controller Main
outdoor unit outdoor
unit
Outdoor Outdoor
HR unit
unit Sub 1 unit Sub 2
outdoor outdoor
unit unit
The GND terminal is a '–' terminal for the central controller, not ground line
52 Outdoor Unit
HR Unit PCB
HR Unit PCB
#4 valve housing
ENGLISH
#1 valve housing
7-SEG
SW05M
(Switch for
addressing
HR unit)
SW01M
SW02M SW01M/SW03M/SW04M
(Dip switch for setup of (Switch for manual valve
the function of HR unit) SW03M SW04M
addressing)
Manual
Auto
Installation Manual 53
HR Unit PCB
2) Selection of the model of the HR unit
2 3 3 4
1 1
2 1 2
Initial
Setting
1 room
Connected
2 rooms
Connected
3 rooms
Connected
4 rooms
Connected
❈ Each model is shipped with the switches No.2 and No.3 pre-adjusted as above in the factory.
WARNING
• If you want to use a PRHR030 for 2 rooms HR unit after closing the 3rd pipes, set the dip switch for 2 rooms HR unit.
• If you want to use a PRHR040 for 3 rooms HR unit after closing the 4th pipes, set the dip switch for 3 rooms HR unit.
• If you want to use a PRHR040 for 2 rooms HR unit after closing the 3rd and 4th pipes, set the dip switch for 2 rooms HR unit.
• The unused port must be closed with a copper cap, not with a plastic cap.
54 Outdoor Unit
HR Unit PCB
2. SW05M (Rotary S/W for addressing HR unit)
Must be set to '0' when installing only one HR unit.
When installing multiple HR units, address the HR units with sequentially increasing numbers starting from '0'.
ENGLISH
Ex) Installation of 3 HR units
3 4 3 4 3 4
3 4 3 4 3 4
1 2 1 2 1 2
3. SW01M/SW03M/SW04M (Dip S/W and tact S/W for manual valve addressing)
- Used in manual addressing of the valve in the HR unit
- Set the address of the valve of the HR unit to the central control address of the connected indoor unit.
- SW01M: selection of the valve to address
SW03M: increase in the digit of 10 of valve address
SW04M: increase in the last digit of valve address
- Prerequisite for manual valve addressing : central control address of each indoor unit must be preset differ-
ently at its wired remote control.
Installation Manual 55
HR Unit PCB
SW02M
AUTO ADDRESS
2) Auto pipe detection
• Turn No.1 of SW02M of HR unit PCB off.
• Confirm that the setting of No.2, 3 of SW02M corresponds with the number of indoor units.
• Reset the power of HR unit PCB
• Turn off the No.5 DIP S/W of main unit PCB when outdoor temperature is below 15°C
• Turn on the No.5 DIP S/W of main unit PCB when outdoor temperature is over 15°C
• Reset the power of outdoor unit.
• Wait 3 minuts.
• Press SW01M of the outdoor unit main PCB for 5 Seconds.
• The number of connected HR unit is displayed.
Ex) In case of installing four HR units : 04
• Operated after 88 is displayed on 7-SEG of the outdoor unit main PCB.
• Pipe detection proceed.
• 5~30 minutes are required depending on the number of the indoor units and outdoor temperature.
• The number of the indoor units installed is displayed on 7-SEG of the outdoor unit main PCB for about 1
minute
(For a HR unit, the number of the indoor units connected to each HR unit is displayed.
• '200' is displayed in case of auto pipe detection error, and auto detection is completed after '88' is disap-
peared.
❈ Auto pipe detection function : the function that sets connection relationship automatically between the indoor
unit and HR unit.
56 Outdoor Unit
HR Unit PCB
WARNING
1. Execute auto addressing and auto pipe detection again whenever the indoor PCB and HR unit PCB
ENGLISH
is replaced.
• Operation error occurs unless power is applied to the indoor and HR units.
2. Error No.200 occurs if the number of connected indoor units and that of scanned indoor units are
different.
3. When auto pipe detection fails, complete it with manual pipe detection (see Manual pipe detection).
4. When auto pipe detection addressing is completed normally, manual pipe detection is not
required.
5. If you want to do auto pipe detection again after auto pipe detection fails, do after reset of outdoor
unit by all means.
WARNING
• In case that central controller is not installed, remain the address data after installer sets central
control address as he wants
• In case that central controller is installed, there would be central control address in wired remote
control of indoor unit.
• In this case, set the HR unit manual pipe address according to central control address of indoor unit.
• Pipe which is not connected with indoor unit should be set different address with pipe Connected
with indoor unit.
(If addresses are piled up, corresponding valve is not working.
• If you want to change the setting of manual pipe, you should do it on HR unit PCB.
• If an error occurred, it means that manual pipe setting is not completed.
Installation Manual 57
HR Unit PCB
58 Outdoor Unit
HR Unit PCB
ENGLISH
Confirmation of indoor unit address setting
Outdoor unit is operated for 5~30 minues.
Is the pipe
setting condition NO
Confirm that the setting of No.2, 3 of satisfied during the operation of
SW02M corresponds with the number of indoor unit?
indoor units. Display error on outdoor unit PCB
Display error on HR unit PCB
YES
Reset the power of HR unit PCB
Outdoor unit PCB : HR ➠ HR unit
number ➠ Valve number
HR unit : '200'
Confirm the No.5 DIP S/W of SW03M of
outdoor PCB The number of indoor units detected is
Outdoor temperature is over 15°C : ON displayed for 30 seconds on the outdoor
Check the HR unit and indoor unit
Outdoor temperature is below 15°C : OFF unit PCB after outdoor unit stopped
Press SW01M of the outdoor unit main Check the installation of pipe of
Completion of auto pipe detection outdoor, indoor, HR unit
PCB for 5 seconds
Installation Manual 59
HR Unit PCB
Turn No.1 of SW02M of HR unit PCB on. The number of the indoor units installed is
displayed.
Ex)HR ➠ The number of the indoor
Turn No.6 of SW03M of outdoor unit PCB Completion of manual pipe detection
on.
60 Outdoor Unit
HR Unit PCB
ENGLISH
• Prerequisite for manual valve addressing: central control address of each indoor unit must be preset differ-
ently at its wired remote control
1 • Operation: None
7-SEG SW01M SW03M SW04M
• Display: None
Installation Manual 61
HR Unit PCB
62 Outdoor Unit
Main unit and Sub unit PCB
ENGLISH
Main Unit PCB
7 Segments
(Shows setting status)
LED
(Shows setting status)
SW03M
(DIP switch)
Installation Manual 63
Main unit and Sub unit PCB
1) LED2, LED1
00 : 8HP unit 01 : 10HP unit 10 : 12HP unit 11 : 14HP unit
2) LED6, LED5
00 : - 01 : sub1 10 : sub2 11 : sub3
3) LED8, LED7
00 : normal 11 : data display
CAUTION
Product may not properly operate if the relevant DIP switch is not properly setup.
LED2
LED1
64 Outdoor Unit
Main unit and Sub unit PCB
■ Setting the DIP switch (SW03M)
• Set the dip switch with the power turned off. If you change the setting when the power is on, the
changed setting is not applied immediately. The changed setting is applied at the moment that the
ENGLISH
power is on.
• Instant indoor unit checking, data display mode, and forced oil collecting operation are used when the
units are running. If you don't have to use those functions after using them, restore the dip switch set-
ting.
1. Settings of main outdoor unit
4) Instant indoor unit checking: Cooling mode With dip switch setting as left
side, push address(red) button
1 2 3 4 5 6 7 8 data 3 times in 3 sec.
ON With data button, select the
indoor unit that you want to turn
OFF address
on/off. Push address button for
3 sec, and the indoor unit will
be turned on/off.
5) Instant indoor unit checking: Heating mode After using, restore the dip
switch setting.
1 2 3 4 5 6 7 8 data
ON
OFF address
Installation Manual 65
Main unit and Sub unit PCB
66 Outdoor Unit
Main unit and Sub unit PCB
ENGLISH
1 2 3 4 5 6 7 8 At the 1st sub unit, set dip switch
ON as the left side.
OFF
Installation Manual 67
Main unit and Sub unit PCB
GND D
Vcc C
68 Outdoor Unit
Main unit and Sub unit PCB
ENGLISH
2. The current group and the indoor unit numbers are indicated on the "88" of the wired remote control.
RESET
Hour Min
WARNING
• Valve address and central control address of its corresponding indoor unit should be set identical in manual
addressing.
EX)
Valve (04) Indoor unit (04)
Valve (03) Indoor unit (03)
HR unit
Valve (02) Indoor unit (02)
Valve (01) Indoor unit (01)
Installation Manual 69
Test Run
Test Run
Checks Before Test Run
1 Check to see whether there is any refrigerant leakage, and slack of power or transmission cable.
2 Confirm that 500 V megger shows 2.0 MΩ or more between power supply terminal block and ground.
Do not operate in the case of 2.0 MΩ or less.
NOTE: Never carry out megaohm check over terminal control board. Otherwise the control board
would be broken.
Immediately after mounting the unit or after leaving it turned off for an extended length of time,
the resistance of the insulation between the power supply terminal board and the ground may
decrease to approx. 2 MΩ as a result of refrigerant accumulating in the internal compressor.
If the insulation resistance is less than 2 MΩ, turning on the main power supply and energizing
the crankcase heater for more than 6 hours will cause the refrigerant to evaporate, increasing
the insulation resistance.
3 Check if Liquid pipe, High Pressure Gas, Low Pressure Gas are fully opened
NOTE: Be sure to tighten caps.
CAUTION
when cutting main power of the Multi V
• Always apply main power of the outdoor unit during use of product
• Always apply power before 6 hours to heat the crank case heater where performing test run after
installation of product. It may result in burning out of the compressor if not preheating the crank
case with the electrical heater for more than 6 hours.(In case of the outdoor temperature below 10°C)
70 Outdoor Unit
Test Run
ENGLISH
Component Phenomenon Cause Check method and Trouble shooting
Not operating Motor insulation broken Check resistance between terminals and
Compressor chassis
Stop during running Motor insulation failure Check resistance between terminals and
chassis
Outdoor High pressure error Motor failure, Check the outdoor fan operation after being
fan at cooling Bad ventilation around turned the outdoor units off for some time.
outdoor heat exchanger Remove obstacles around the outdoor units
Heating failure, fre- Bad connector contact Check connector
quent defrosting
No operating sound Coil failure Check resistance between terminals
at applying power
Outdoor
EEV Heating failure, EEV clogged Service necessary
Frozen outdoor heat
exchanger part
Low pressure error EEV clogged Service necessary
or discharge temper-
ature error
When system fault occurs, the error code is displayed at indoor unit display or remote control display, the trou-
ble shooting guide is in the service manual
Test Run
The test operation starts automatically by operating the DIP switch and buttons in the main unit as follows.
(1) Before turning on the system, turn on the Dip switch No7,8, turn on the No.1 Dip switch for cooling test and No.1,2 on for the
heating test operation . After that, turn on the system. And you must wait for 1 minute.
(2) If you turn on the No.7 and 8 DIP switch and press the black button for 2.5 seconds, you will see a character that looks like ‘St’ in
the 7segment. When you turn both No. 7 and 8 off at this time, the test operation will start.
(3) Indoor units are automatically setting as strong wind mode, set temperature to 30°C for heating and 18°C for air conditioning
(4) When the compressor is normally operated with the operating logic, the target frequency will be 30Hz and when operated for
more than 7 minutes after step (3), the unit will proceed to the next step.
(5) Turn on one constant speed compressor, maintain the target frequency of the compressor to 40Hz and maintain this condition
for 10.
(6) Turn off the constant speed compressor that is on and at the same time turn on the other compressor.
(7) Maintain the compressor that has been turned on newly in step (6) minutes (for series).
(8) Maintain all compressors on for 10 minutes until the rotational switching operation of turning on each compressor at a time is
completed.
(9) Proceed to the next stage when step (8) is completed.
(10) Turn off the constant speed compressor, wait 3 minutes and raise the target frequency of the compressor to 95Hz. This opera-
tion keeps about 7min.
(11) Start the oil return operations.
(12) When the oil return operation is completed, set the compressor frequency to 0 and maintain all indoor devices off.
(13) When step (12) is completed, it means that the test operation is completed. Turn off the No. 1, 2 of DIP switch in the main unit
and must reset the system.
(14) If there is any error during the operation, the error code will be shown in 7segment and the test operation will automatically end.
(The error does not include poor operation of the constant speed compressor and communication error from the indoor
device.)
Installation Manual 71
Test Run
Self-Diagnosis Function
Error Indicator
• This function indicates types of failure in self-diagnosis and occurrence of failure for air condition.
• Error mark is displayed on display window of indoor units and wired remote controller, and 7-segment LED of
outdoor unit control board as shown in the table.
• If more than two troubles occur simultaneously, lower number of error code is first displayed.
• After error occurrence, if error is released, error LED is also released simultaneously.
72 Outdoor Unit
Test Run
ENGLISH
4 2 Low pressure sensor of main outdoor Low pressure sensor of main outdoor unit is open or short
unit
Outdoor unit related error
4 3 High pressure sensor of main outdoor High pressure sensor of main outdoor unit is open or short
unit
4 4 Air temperature sensor of main out- Air temperature sensor of main outdoor unit is open or short
door unit
4 5 Temperature sensor of front-side heat Temperature sensor of front-side heat exchanger is open or
exchanger short
4 6 Suction temperature sensor of main Suction temperature sensor of main outdoor unit is open or
outdoor unit short
Discharge temperature sensor of the Discharge temperature sensor of the constant speed com-
4 7
constant speed compressor of main pressor of main outdoor unit is open or short
outdoor unit
4 8 Temperature sensor of rear-side heat Temperature sensor of rear-side heat exchanger is open or
exchanger short
Excessive capacity of indoor units Excessive connection of indoor units compared to capacity of
Transmission related error
5 1
outdoor unit
Transmission error : inverter PCB ➡ Failing to receive inverter signal at main PCB
5 2
main PCB
Transmission error : indoor unit ➡ Failing to receive indoor unit signal at main PCB of outdoor
5 3
main PCB of outdoor unit unit
Reverse connection of R, S, T power Reverse connection or omitting connection of R, S, T power
5 4
of main outdoor unit of main outdoor unit
Transmission error : main PCB ➡ Failing to receive main PCB signal at inverter PCB
5 7
inverter PCB
Outdoor unit
related error
Installation Manual 73
Test Run
1 0 0 speed compressor 1 of sub1 outdoor ture of constant speed compressor 1 of sub1 outdoor unit
unit
Discharge temperature of constant System is off by excessive increase of discharge tempera-
1 0 1 speed compressor 2 of sub1 outdoor ture of constant speed compressor 2 of sub1 outdoor unit
unit
Discharge temperature of constant System is off by excessive increase of discharge tempera-
1 0 2 speed compressor 1 of sub2 outdoor ture of constant speed compressor 1 of sub2 outdoor unit
unit
Discharge temperature of constant System is off by excessive increase of discharge tempera-
1 0 3 speed compressor 2 of sub2 outdoor ture of constant speed compressor 2 of sub2 outdoor unit
unit
Transmission error : sub1 outdoor unit Failing to receive sub1 signal at main PCB of main outdoor
1 0 4
➡ main outdoor unit unit
Transmission error : fan PCB ➡ main Failing to receive fan signal at main PCB
Transmission related error
1 0 5
PCB
1 0 6 Over-current of fan motor (IPM fault) Over-current of fan motor (IPM fault)
1 0 7 Low voltage of fan motor driver Low voltage of fan motor driver
1 0 8 Transmission error : main PCB ➡ fan Failing to receive main signal at fan PCB
PCB
1 0 9 High pressure switch of sub1 outdoor High pressure switch of sub1 outdoor unit is operated by high
unit pressure rising
1 1 0 Reverse connection of R, S, T power Reverse connection or omitting connection of R, S, T power
of sub1 outdoor unit of sub1 outdoor unit
1 1 1 Transmission error : main outdoor unit Failing to receive main signal at main PCB of sub1 outdoor
➡ sub1 outdoor unit unit
Liquid pipe temperature sensor of Liquid pipe temperature sensor of main outdoor unit is open
1 1 3
main outdoor unit or short
Subcooling inlet temperature sensor of Subcooling inlet temperature sensor of main outdoor unit is
1 1 4
main outdoor unit open or short
Subcooling outlet temperature sensor Subcooling outlet temperature sensor of main outdoor unit is
1 1 5
of main outdoor unit open or short
High pressure sensor of sub1 outdoor High pressure sensor of sub1 outdoor unit is open or short
Outdoor unit related error
1 1 6
unit
Low pressure sensor of sub1 outdoor Low pressure sensor of sub1 outdoor unit is open or short
1 1 7
unit
Air temperature sensor of sub1 out- Air temperature sensor of sub1 outdoor unit is open or short
1 1 8
door unit
Suction temperature sensor of sub1 Suction temperature sensor of sub1 outdoor unit is open or
1 2 0
outdoor unit short
Discharge temperature sensor of the Discharge temperature sensor of the constant speed com-
1 2 1 constant speed compressor 1 of sub1 pressor 1 of sub1 outdoor unit is open or short
outdoor unit
Discharge temperature sensor of the Discharge temperature sensor of the constant speed com-
1 2 2 constant speed compressor 2 of sub1 pressor 2 of sub1 outdoor unit is open or short
outdoor unit
Temperature sensor of front-side heat Temperature sensor of front-side heat exchanger of sub1
1 2 3
exchanger of sub1 outdoor unit unit is open or short
74 Outdoor Unit
Test Run
ENGLISH
1 2 5 sub1 outdoor unit or short
Subcooling inlet temperature sensor of Subcooling inlet temperature sensor of sub1 outdoor unit is
1 2 6 sub1 outdoor unit open or short
Subcooling outlet temperature sensor Subcooling outlet temperature sensor of sub1 outdoor unit is
1 2 7 of sub1 outdoor unit open or short
High pressure sensor of sub2 outdoor High pressure sensor of sub2 outdoor unit is open or short
1 2 8 unit
Low pressure sensor of sub2 outdoor Low pressure sensor of sub2 outdoor unit is open or short
1 2 9 unit
Air temperature sensor of sub2 Air temperature sensor of sub2 outdoor unit is open or short
1 3 0 outdoor unit
Suction temperature sensor of sub2 Suction temperature sensor of sub2 outdoor unit is open or
1 3 2 outdoor unit short
Discharge temperature sensor of the Discharge temperature sensor of the constant speed com-
1 3 3 constant speed compressor 1 of sub2 pressor 1 of sub2 outdoor unit is open or short
outdoor unit
Discharge temperature sensor of the Discharge temperature sensor of the constant speed com-
Outdoor unit related error
1 3 4 constant speed compressor 2 of sub2 pressor 2 of sub2 outdoor unit is open or short
outdoor unit
Temperature sensor of front-side heat Temperature sensor of front-side heat exchanger of sub2 unit
1 3 5 exchanger of sub2 outdoor unit is open or short
Temperature sensor of rear-side heat Temperature sensor of rear-side heat exchanger of sub2 unit
1 3 6 exchanger of sub2 outdoor unit is open or short
Liquid pipe temperature sensor of Liquid pipe temperature sensor of sub2 outdoor unit is open
1 3 7
sub2 outdoor unit or short
Subcooling inlet temperature sensor of Subcooling inlet temperature sensor of sub2 outdoor unit is
1 3 8
sub2 outdoor unit open or short
Subcooling outlet temperature sensor Subcooling outlet temperature sensor of sub2 outdoor unit is
1 3 9
of sub2 outdoor unit open or short
High pressure sensor of sub2 outdoor High pressure sensor of sub2 outdoor unit is open or short
1 4 0
unit
Reverse connection of R, S, T power Reverse connection or omitting connection of R, S, T power
1 4 1
of sub2 outdoor unit of sub2 outdoor unit
Transmission error : main outdoor unit Failing to receive main signal at main PCB of sub2 outdoor
1 4 2
➡ sub1 outdoor unit unit
High pressure of sub1 outdoor unit System is off by excessive increase of high pressure of sub1
1 4 3 outdoor unit
Low pressure of sub1 outdoor unit System is off by excessive decrease of low pressure of
1 4 4 sub1 outdoor unit
High pressure of sub2 outdoor unit System is off by excessive increase of high pressure of
1 4 5 sub2 outdoor unit
Low pressure of sub2 outdoor unit System is off by excessive decrease of low pressure of
1 4 6 sub2 outdoor unit
Low/high voltage of sub1 outdoor Input voltage of sub1 outdoor unit is more than 487V or
1 4 7 unit less than 270V
Installation Manual 75
Test Run
Failure of Main constant speed com- Comp locking, Check Valve leakage, comp dielectric break-
1 7 3
pressor operation down
Failure of Sub1 constant speed com- Comp locking, Check Valve leakage, comp dielectric break-
1 7 4
pressor1 operation down
Failure of Sub1 constant speed com- Comp locking, Check Valve leakage, comp dielectric break-
1 7 5
pressor2 operation down
Failure of Sub2 constant speed com- Comp locking, Check Valve leakage, comp dielectric break-
1 7 6
pressor1 operation down
Failure of Sub2 constant speed com- Comp locking, Check Valve leakage, comp dielectric break-
1 7 7
pressor2 operation down
Failure of Sub3 constant speed com- Comp locking, Check Valve leakage, comp dielectric break-
1 7 8
pressor1 operation down
Failure of Sub3 constant speed com- Comp locking, Check Valve leakage, comp dielectric break-
1 7 9
pressor2 operation down
2 0 0 Automatic addressing of valves Failure of automatic addressing of valves
2 0 1 Liquid pipe sensor of HR unit 1 Liquid pipe sensor of HR unit 1 is open or short
2 0 2 Inlet sensor of subcooler of HR unit 1 Inlet sensor of subcooler of HR unit 1 is open or short
2 0 3 Outlet sensor of subcooler of HR unit 1 Outlet sensor of subcooler of HR unit 1 is open or short
Transmission error : HR unit 1 → Failing to receive HR unit 1 signal at outdoor unit
2 0 4
outdoor unit
2 0 5 Liquid pipe sensor of HR unit 2 Liquid pipe sensor of HR unit 2 is open or short
2 0 6 Inlet sensor of subcooler of HR unit 2 Inlet sensor of subcooler of HR unit 2 is open or short
2 0 7 Outlet sensor of subcooler of HR unit 2 Outlet sensor of subcooler of HR unit 2 is open or short
Transmission error : HR unit 2 → Failing to receive HR unit 2 signal at outdoor unit
2 0 8
outdoor unit
2 0 9 Liquid pipe sensor of HR unit 3 Liquid pipe sensor of HR unit 3 is open or short
2 1 0 Inlet sensor of subcooler of HR unit 3 Inlet sensor of subcooler of HR unit 3 is open or short
HR unit related error
2 1 1 Outlet sensor of subcooler of HR unit 3 Outlet sensor of subcooler of HR unit 3 is open or short
Transmission error : HR unit 3 → Failing to receive HR unit 3 signal at outdoor unit
2 1 2
outdoor unit
2 1 3 Liquid pipe sensor of HR unit 4 Liquid pipe sensor of HR unit 4 is open or short
2 1 4 Inlet sensor of subcooler of HR unit 4 Inlet sensor of subcooler of HR unit 4 is open or short
2 1 5 Outlet sensor of subcooler of HR unit 4 Outlet sensor of subcooler of HR unit 4 is open or short
Transmission error : HR unit 4 → out- Failing to receive HR unit 4 signal at outdoor unit
2 1 6
door unit
2 1 7 Liquid pipe sensor of HR unit 5 Liquid pipe sensor of HR unit 5 is open or short
2 1 8 Inlet sensor of subcooler of HR unit 5 Inlet sensor of subcooler of HR unit 5 is open or short
2 1 9 Outlet sensor of subcooler of HR unit 5 Outlet sensor of subcooler of HR unit 5 is open or short
Transmission error: HR unit 5 → out- Failling to receive HR unit 5 signal at outdoor unit
2 2 0
door unit
2 2 1 Liquid pipe sensor of HR unit 6 Liquid pipe sensor of HR unit 6 is open or short
2 2 2 Inlet sensor of subcooler of HR unit 6 Inlet sensor of subcooler of HR unit 6 is open or short
2 2 3 Outlet sensor of subcooler of HR unit 6 Outlet sensor of subcooler of HR unit 6 is open or short
Transmission error: HR unit 6 → out- Failling to receive HR unit 6 signal at outdoor unit
2 2 4
door unit
2 2 5 Liquid pipe sensor of HR unit 7 Liquid pipe sensor of HR unit 7 is open or short
76 Outdoor Unit
Test Run
2 2 7 Outlet sensor of subcooler of HR unit 7 Outlet sensor of subcooler of HR unit 7 is open or short
Transmission error: HR unit 7 → out- Failling to receive HR unit 7 signal at outdoor unit
ENGLISH
2 2 8
error
door unit
2 2 9 Liquid pipe sensor of HR unit 8 Liquid pipe sensor of HR unit 8 is open or short
2 3 0 Inlet sensor of subcooler of HR unit 8 Inlet sensor of subcooler of HR unit 8 is open or short
2 3 1 Outlet sensor of subcooler of HR unit 8 Outlet sensor of subcooler of HR unit 8 is open or short
■ Please refer to trouble shooting guide in service manual for each error title
CAUTION
In case that the control box is opened and before checking electrical parts, it should be checked that
the LED 01Y turned off (wait 3 minutes after main power OFF), otherwise, it may cause electrical
shock.
Installation Manual 77
Test Run
Position of the LED01Y in inverter board
78 Outdoor Unit
Caution For Refrigerant Leak
ENGLISH
The following standards may be applicable if local regulations are not available.
Introduction
Though the R410A refrigerant is harmless and incombustible itself , the room to equip the air conditioner should be large to
such an extent that the refrigerant gas will not exceed the limiting concentration even if the refrigerant gas leaks in the room.
■ Limiting concentration
Limiting concentration is the limit of Freon gas concentration where immediate measures can be taken with-
out hurting human body when refrigerant leaks in the air. The limiting concentration shall be described in the
unit of kg/m3 (Freon gas weight per unit air volume) for facilitating calculation.
Limiting concentration: 0.30kg/m3(R410A) (ISO5149, EN378-1)
Outdoor unit
Flow of
(No.1 system) refrigerant
Installation Manual 79
Caution For Refrigerant Leak
(3) With partition and without opening which serve as passage of air to adjoining room
Outdoor unit
Indoor unit
Smallest
room
Indoor unit
Pay a special attention to the place, such as a basement, etc. where refrigerant can stay, since refrigerant is
heavier than air.
80 Outdoor Unit
P/No.: 3828A24002F Printed in Korea
After reading this manual, keep it in a place easily accessible to the user for future reference.