ARUM192168096BTE5
ARUM192168096BTE5
ARUM192168096BTE5
Note :
1. Nominal capacity applied with non-ducted indoor units, and is rated 0 m. above sea level with 7.5 m. of refrigerant line per indoor unit and a 0 m. level difference between outdoor and indoor units.
All capacities are net with a Combination Ratio between 95–105%. Nominal cooling capacity rating obtained with air entering the indoor unit at 80°F (27°C) dry bulb (DB) and 67°F (19°C) wet bulb
(WB) and outdoor ambient conditions of 95°F (35°C) dry bulb (DB) and 75°F (24°C) wet bulb (WB). Nominal heating capacity rating obtained with air entering the indoor unit at 70°F (21°C) dry bulb
(DB) and 59°F (15°C) wet bulb (WB) and outdoor ambient conditions of 47°F (8°C) dry bulb (DB) and 43°F (6°C) wet bulb (WB).
2. Rated capacity is certified under AHRI Standard 1230. For AHRI ratings, refer to the AHRI website http://www.ahridirectory.org.
3. The System Combination Ratio must be between 50–130%.
4. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
5. Communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded or unshielded, and must comply with applicable local and national codes.
If shielded, ensure the communication cable is properly grounded to chassis at the master ODU only. Do not ground the ODU-IDU (or HRU) communication cable at any other point.
6. Power wiring is field provided, solid or stranded, and must comply with the applicable local and national codes..
7. LG requires that LATS software be used on all projects to ensure correct line sizing. Designer must verify the shop drawing design against the as built design using LATS.
Contractor must also use LG manufactured Y-Branch and Header Kits only.
058
DIGITALAIR.MX
OUTDOOR UNIT
ARUM192BTE5 / ARUM216BTE5 / ARUM241BTE5 / ARUM264BTE5 / ARUM288BTE5
Note :
1. Nominal capacity applied with non-ducted indoor units, and is rated 0 m. above sea level with 7.5 m. of refrigerant line per indoor unit and a 0 m. level difference between outdoor and indoor units.
All capacities are net with a Combination Ratio between 95–105%. Nominal cooling capacity rating obtained with air entering the indoor unit at 80°F (27°C) dry bulb (DB) and 67°F (19°C) wet bulb
(WB) and outdoor ambient conditions of 95°F (35°C) dry bulb (DB) and 75°F (24°C) wet bulb (WB). Nominal heating capacity rating obtained with air entering the indoor unit at 70°F (21°C) dry bulb
(DB) and 59°F (15°C) wet bulb (WB) and outdoor ambient conditions of 47°F (8°C) dry bulb (DB) and 43°F (6°C) wet bulb (WB).
2. Rated capacity is certified under AHRI Standard 1230. For AHRI ratings, refer to the AHRI website http://www.ahridirectory.org.
3. The System Combination Ratio must be between 50–130%.
4. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
5. Communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded or unshielded, and must comply with applicable local and national codes.
If shielded, ensure the communication cable is properly grounded to chassis at the master ODU only. Do not ground the ODU-IDU (or HRU) communication cable at any other point.
6. Power wiring is field provided, solid or stranded, and must comply with the applicable local and national codes..
7. LG requires that LATS software be used on all projects to ensure correct line sizing. Designer must verify the shop drawing design against the as built design using LATS.
Contractor must also use LG manufactured Y-Branch and Header Kits only.
059
DIGITALAIR.MX
OUTDOOR UNIT SPECIFICATION
Note :
1. Nominal capacity applied with non-ducted indoor units, and is rated 0 m. above sea level with 7.5 m. of refrigerant line per indoor unit and a 0 m. level difference between outdoor and indoor units.
All capacities are net with a Combination Ratio between 95–105%. Nominal cooling capacity rating obtained with air entering the indoor unit at 80°F (27°C) dry bulb (DB) and 67°F (19°C) wet bulb
(WB) and outdoor ambient conditions of 95°F (35°C) dry bulb (DB) and 75°F (24°C) wet bulb (WB). Nominal heating capacity rating obtained with air entering the indoor unit at 70°F (21°C) dry bulb
(DB) and 59°F (15°C) wet bulb (WB) and outdoor ambient conditions of 47°F (8°C) dry bulb (DB) and 43°F (6°C) wet bulb (WB).
2. Rated capacity is certified under AHRI Standard 1230. For AHRI ratings, refer to the AHRI website http://www.ahridirectory.org.
3. The System Combination Ratio must be between 50–130%.
4. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
5. Communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded or unshielded, and must comply with applicable local and national codes.
If shielded, ensure the communication cable is properly grounded to chassis at the master ODU only. Do not ground the ODU-IDU (or HRU) communication cable at any other point.
6. Power wiring is field provided, solid or stranded, and must comply with the applicable local and national codes..
7. LG requires that LATS software be used on all projects to ensure correct line sizing. Designer must verify the shop drawing design against the as built design using LATS.
Contractor must also use LG manufactured Y-Branch and Header Kits only.