OUTDOOR UNIT SPECIFICATION

MULTI V 5 HIGH EFFICIENCY_220V


ARUM072BTE5 / ARUM096BTE5 / ARUM121BTE5 / ARUM144BTE5 / ARUM168BTE5

RT 6.0 8.0 10.0 12.0 14.0


Combination Unit ARUM072BTE5 ARUM096BTE5 ARUM121BTE5 ARUM144BTE5 ARUM168BTE5
Model Name
Independent Unit ARUM072BTE5 ARUM096BTE5 ARUM121BTE5 ARUM144BTE5 ARUM168BTE5
Btu/h 72,000 96,000 120,000 144,000 168,000
Cooling
kW 21.1 28.1 35.2 42.2 49.2
Norminal
Btu/h 81,000 108,000 135,000 162,000 189,000
Heating
kW 23.7 31.7 39.6 47.5 55.4
Capacity
Btu/h 69,000 92,000 114,000 138,000 160,000
Cooling
kW 20.2 27.0 33.4 40.4 46.9
Rated
Btu/h 77,000 103,000 129,000 154,000 180,000
Heating
kW 22.6 30.2 37.8 45.1 52.8
Cooling kW 4.28 5.33 7.72 9.30 12.23
Norminal
Heating kW 5.39 6.74 9.20 10.54 13.98
Input
Cooling (Nonducted / Ducted) kW 5.15 / 5.31 6.39 / 6.82 8.7 / 9.12 11.04 / 11.41 13.68 / 14.41
Rated
Heating (Nonducted / Ducted) kW 6.49 / 5.89 8.25 / 6.97 10.93 / 9.523 12.82 / 11.75 16.49 / 14.78
Norminal Cooling 16.82 18.01 15.54 15.48 13.74
EER
Rated Cooling (Nonducted / Ducted) 13.4 / 13 14.40 / 13.5 13.1 / 12.5 12.5 / 12.1 11.7 / 11.1
IEER Rated Cooling (Nonducted / Ducted) 28.4 / 23.6 33 / 25.1 29.6 / 24.6 28.6 / 23 25.4 / 21.9
Norminal Heating 4.40 4.70 4.30 4.50 3.96
COP
Rated Heating (Nonducted / Ducted) 3.83 / 3.48 4.33 / 3.66 3.97 / 3.46 3.84 / 3.52 3.57 / 3.2
Power Factor Rated - 0.93 0.93 0.93 0.93 0.93
Casing Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray
Heat Exchanger Ocean Black Fin Ocean Black Fin Ocean Black Fin Ocean Black Fin Ocean Black Fin
Compressor Motor Output × Number W × No. 4,200 × 1 5,300 × 1 5,300 × 1 4,200 × 1 + 4,200 × 1 4,200 × 1 + 4,200 × 1
Type Propeller fan Propeller fan Propeller fan Propeller fan Propeller fan
Motor Output × Number W 1,200 × 1 900 × 2 900 × 2 900 × 2 900 × 2
Fan m /min
3
240 × 1 320 × 1 320 × 1 320 × 1 320 × 1
Air Flow Rate (High)
ft3/min 8,476 × 1 1,1301 × 1 1,1301 × 1 1,1301 × 1 1,1301 × 1
Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER DC INVERTER
Liquid Pipe mm (inch) 9.52(3/8) 9.52(3/8) 12.7(1/2) 12.7(1/2) 15.88(5/8)
Pipe Connections For Low Pressure Gas Pipe mm (inch) 19.05(3/4) 22.2(7/8) 28.58(1-1/8) 28.58(1-1/8) 28.58(1-1/8)
Heat Pump
High Pressure Gas Pipe mm (inch) 15.88(5/8) 19.05(3/4) 19.05(3/4) 22.2(7/8) 22.2(7/8)
Pipe Connections For Liquid Pipe mm (inch) 9.52(3/8) 9.52(3/8) 12.7(1/2) 12.7(1/2) 15.88(5/8)
Heat Pump Gas Pipe mm (inch) 19.05(3/4) 22.2(7/8) 28.58(1-1/8) 28.58(1-1/8) 28.58(1-1/8)
(930 × 1,690 × 760) (1,240 × 1,690 × (1,240 × 1,690 × (1,240 × 1,690 × (1,240 × 1,690 ×
mm ×1 760) × 1 760) × 1 760) × 1 760) × 1
Dimensions (W × H × D)
(36-5/8 × 66-17/32 × (48-13/16 × 66-17/32 (48-13/16 × 66-17/32 (48-13/16 × 66-17/32 (48-13/16 × 66-17/32
inch 29-29/32) × 1 × 29-29/32) × 1 × 29-29/32) × 1 × 29-29/32) × 1 × 29-29/32) × 1
kg 195 × 1 230 × 1 230 × 1 290 × 1 290 × 1
Net Weight
lbs 430 × 1 507 × 1 507 × 1 639 × 1 639 × 1
Sound Pressure Level Cooling dB(A) 58.0 58.0 59.0 60.0 61.0
Sound Power Level Cooling dB(A) 77.0 78.0 79.0 83.0 85.0
Communication Cable No.× mm2 (VCTF-SB) 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5
Refrigerant name R410A R410A R410A R410A R410A
Precharged Amount in kg 13.0 16.0 20.0 24.0 29.0
factory lbs 28.7 35.3 44.1 52.9 63.9
Refrigerant GWP 2087.5 2087.5 2087.5 2087.5 2087.5
TCO2eq 27.1 33.4 41.8 50.1 60.5
Electronic Expansion Electronic Expansion Electronic Expansion Electronic Expansion Electronic Expansion
Control Valve Valve Valve Valve Valve
220, 3, 60 220, 3, 60 220, 3, 60 220, 3, 60 220, 3, 60
Power Supply Ø , V, Hz
220-240, 3, 50 220-240, 3, 50 220-240, 3, 50 220-240, 3, 50 220-240, 3, 50
Number of maximum connectable indoor units5) 13 16 20 24 29

Note :
1. Nominal capacity applied with non-ducted indoor units, and is rated 0 m. above sea level with 7.5 m. of refrigerant line per indoor unit and a 0 m. level difference between outdoor and indoor units.
All capacities are net with a Combination Ratio between 95–105%. Nominal cooling capacity rating obtained with air entering the indoor unit at 80°F (27°C) dry bulb (DB) and 67°F (19°C) wet bulb
(WB) and outdoor ambient conditions of 95°F (35°C) dry bulb (DB) and 75°F (24°C) wet bulb (WB). Nominal heating capacity rating obtained with air entering the indoor unit at 70°F (21°C) dry bulb
(DB) and 59°F (15°C) wet bulb (WB) and outdoor ambient conditions of 47°F (8°C) dry bulb (DB) and 43°F (6°C) wet bulb (WB).
2. Rated capacity is certified under AHRI Standard 1230. For AHRI ratings, refer to the AHRI website http://www.ahridirectory.org.
3. The System Combination Ratio must be between 50–130%.
4. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
5. Communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded or unshielded, and must comply with applicable local and national codes.
If shielded, ensure the communication cable is properly grounded to chassis at the master ODU only. Do not ground the ODU-IDU (or HRU) communication cable at any other point.
6. Power wiring is field provided, solid or stranded, and must comply with the applicable local and national codes..
7. LG requires that LATS software be used on all projects to ensure correct line sizing. Designer must verify the shop drawing design against the as built design using LATS.
Contractor must also use LG manufactured Y-Branch and Header Kits only.

058
DIGITALAIR.MX
OUTDOOR UNIT
ARUM192BTE5 / ARUM216BTE5 / ARUM241BTE5 / ARUM264BTE5 / ARUM288BTE5

RT 16.0 18.0 20.0 22.0 24.0


Combination Unit ARUM192BTE5 ARUM216BTE5 ARUM241BTE5ARUM264BTE5 ARUM288BTE5
Model Name ARUM168BTE5 ARUM192BTE5
Independent Unit ARUM192BTE5 ARUM216BTE5 ARUM241BTE5 ARUM096BTE5 ARUM096BTE5
Btu/h 192,000 216,000 240,000 264,000 288,000
Cooling
kW 56.3 63.3 70.3 77.4 84.4
Norminal
Btu/h 216,000 243,000 243,000 297,000 324,000
Heating
kW 63.3 71.2 71.2 87.0 95.0
Capacity
Btu/h 184,000 206,000 222,000 252,000 276,000
Cooling
kW 53.9 60.4 65.1 73.9 80.9
Rated
Btu/h 206,000 230,000 230,000 283,000 309,000
Heating
kW 60.4 67.4 67.4 82.9 90.6
Cooling kW 13.61 15.37 16.80 17.56 18.94
Norminal
Heating kW 15.46 17.75 17.75 20.72 22.20
Input
Cooling (Nonducted / Ducted) kW 14.84 / 16.73 18.39 / 19.25 22 / 21.35 20.06 / 21.23 21.23 / 23.55
Rated
Heating (Nonducted / Ducted) kW 18.3 / 16.1 21.07 / 19.1 21.07 / 20.12 24.74 / 21.75 26.55 / 23.07
Norminal Cooling 14.11 14.05 14.29 15.03 15.21
EER
Rated Cooling (Nonducted / Ducted) 12.4 / 11 11.2 / 10.7 10.13 / 10.4 12.56 / 11.87 13 / 11.72
IEER Rated Cooling (Nonducted / Ducted) 25.9 / 23 24.8 / 22.4 23.5 / 22.7 22 / 21.5 22 / 21
Norminal Heating 4.09 4.01 4.01 4.20 4.28
COP
Rated Heating (Nonducted / Ducted) 3.75 / 3.3 3.53 / 3.2 3.35 / 3.2 3.81 / 3.35 3.93 / 3.41
Power Factor Rated - 0.93 0.93 0.93 0.93 0.93
Casing Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray
Heat Exchanger Ocean Black Fin Ocean Black Fin Ocean Black Fin Ocean Black Fin Ocean Black Fin
(5,300 × 1)
Compressor Motor Output × Number W × No. 5,300 × 2 5,300 × 2 5,300 × 2 5,300 × 3
+ (4,200 × 2)
Type Propeller fan Propeller fan Propeller fan Propeller fan Propeller fan
Motor Output × Number W 900 × 2 900 × 2 900 × 2 900 × 2 900 × 4
Fan m3/min 320 × 1 320 × 1 320 × 1 320 × 1 320 × 2
Air Flow Rate (High)
ft /min
3
1,1301 × 1 1,1301 × 1 1,1301 × 1 11,301 × 2 11,301 × 2
Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER DC INVERTER
Liquid Pipe mm (inch) 15.88(5/8) 15.88(5/8) 15.88(5/8) 19.05(3/4) 19.05(3/4)
Pipe Connections For Low Pressure Gas Pipe
Heat Pump mm (inch) 28.58(1-1/8) 28.58(1-1/8) 34.9(1-3/8) 34.9(1-3/8) 34.9(1-3/8)
High Pressure Gas Pipe mm (inch) 28.58(1-1/8) 28.58(1-1/8) 28.58(1-1/8) 28.58(1-1/8) 28.58(1-1/8)
Pipe Connections For Liquid Pipe mm (inch) 15.88(5/8) 15.88(5/8) 15.88(5/8) 19.05(3/4) 19.05(3/4)
Heat Pump Gas Pipe mm (inch) 28.58(1-1/8) 28.58(1-1/8) 34.9(1-3/8) 34.9(1-3/8) 34.9(1-3/8)
(1,240 × 1,690 × (1,240 × 1,690 × (1,240 × 1,690 × (1,240 ×1,690 × (1,240 ×1,690 ×
mm
760) × 1 760) × 1 760) × 1 760) × 2 760) × 2
Dimensions (W × H × D)
(48-13/16 × 66-17/32 (48-13/16 × 66-17/32 (48-13/16 × 66-17/32 (48-13/16 × 66-17/32 (48-13/16 × 66-17/32
inch
× 29-29/32) × 1 × 29-29/32) × 1 × 29-29/32) × 1 × 29-29/32) × 2 × 29-29/32) × 2
kg 299 × 1 302 × 1 302 × 1 (230 × 1) + (290 × 1) (230 × 1) + (299 × 1)
Net Weight
lbs 659 × 1 666 × 1 666 × 1 (507 × 1) + (639 × 1) (507 × 1) + (659 × 1)
Sound Pressure Level Cooling dB(A) 62.0 64.0 65.0 63.0 63.0
Sound Power Level Cooling dB(A) 87.0 88.0 88.0 86.0 87.0
Communication Cable No.× mm2 (VCTF-SB) 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5
Refrigerant name R410A R410A R410A R410A R410A
Precharged Amount in kg 32.0 35.0 39.0 45.00 48.00
factory lbs 70.5 77.2 86.0 99.2 105.8
Refrigerant GWP 2087.5 2087.5 2087.5 2087.5 2087.5
TCO2eq 66.8 73.1 81.4 93.9 100.2
Electronic Expansion Electronic Expansion Electronic Expansion Electronic Expansion Electronic Expansion
Control
Valve Valve Valve Valve Valve
220, 3, 60 220, 3, 60 220, 3, 60 220, 3, 60 220, 3, 60
Power Supply Ø , V, Hz
220-240, 3, 50 220-240, 3, 50 220-240, 3, 50 220-240, 3, 50 220-240, 3, 50
Number of maximum connectable indoor units5) 32 35 39 42 45

Note :
1. Nominal capacity applied with non-ducted indoor units, and is rated 0 m. above sea level with 7.5 m. of refrigerant line per indoor unit and a 0 m. level difference between outdoor and indoor units.
All capacities are net with a Combination Ratio between 95–105%. Nominal cooling capacity rating obtained with air entering the indoor unit at 80°F (27°C) dry bulb (DB) and 67°F (19°C) wet bulb
(WB) and outdoor ambient conditions of 95°F (35°C) dry bulb (DB) and 75°F (24°C) wet bulb (WB). Nominal heating capacity rating obtained with air entering the indoor unit at 70°F (21°C) dry bulb
(DB) and 59°F (15°C) wet bulb (WB) and outdoor ambient conditions of 47°F (8°C) dry bulb (DB) and 43°F (6°C) wet bulb (WB).
2. Rated capacity is certified under AHRI Standard 1230. For AHRI ratings, refer to the AHRI website http://www.ahridirectory.org.
3. The System Combination Ratio must be between 50–130%.
4. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
5. Communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded or unshielded, and must comply with applicable local and national codes.
If shielded, ensure the communication cable is properly grounded to chassis at the master ODU only. Do not ground the ODU-IDU (or HRU) communication cable at any other point.
6. Power wiring is field provided, solid or stranded, and must comply with the applicable local and national codes..
7. LG requires that LATS software be used on all projects to ensure correct line sizing. Designer must verify the shop drawing design against the as built design using LATS.
Contractor must also use LG manufactured Y-Branch and Header Kits only.

059

DIGITALAIR.MX
OUTDOOR UNIT SPECIFICATION

MULTI V 5 HIGH EFFICIENCY_220V


ARUM312BTE5 / ARUM336BTE5 / ARUM360BTE5 / ARUM384BTE5 / ARUM408BTE5

RT 26.0 28.0 30.0 32.0 34.0


Combination Unit ARUM312BTE5 ARUM336BTE5 ARUM360BTE5 ARUM384BTE5 ARUM408BTE5
Model Name ARUM216BTE5 ARUM216BTE5 ARUM216BTE5 ARUM216BTE5 ARUM216BTE5
Independent Unit ARUM096BTE5 ARUM121BTE5 ARUM144BTE5 ARUM168BTE5 ARUM192BTE5
Btu/h 312,000 336,000 360,000 384,000 408,000
Cooling
kW 91.4 98.5 105.5 112.5 119.6
Norminal
Btu/h 351,000 378,000 405,000 432,000 459,000
Heating
kW 102.9 110.8 118.7 126.6 134.5
Capacity
Btu/h 298,000 320,000 344,000 366,000 390,000
Cooling
kW 87.3 93.8 100.8 107.3 114.3
Rated
Btu/h 333,000 359,000 384,000 410,000 436,000
Heating
kW 97.6 105.2 112.5 120.2 127.8
Cooling kW 20.70 23.09 24.67 27.60 28.98
Norminal
Heating kW 24.49 26.95 28.29 31.73 33.21
Input
Cooling (Nonducted / Ducted) kW 24.78 / 26.07 27.1 / 28.37 29.43 / 30.66 32.07 / 33.66 33.23 / 35.98
Rated
Heating (Nonducted / Ducted) kW 29.32 / 26.07 32 / 28.62 33.89 / 30.85 37.56 / 33.88 39.37 / 35.2
Norminal Cooling 15.07 14.55 14.59 13.91 14.08
EER
Rated Cooling (Nonducted / Ducted) 12.02 / 11.43 11.81 / 11.28 11.69 / 11.22 11.41 / 10.87 11.74 / 10.84
IEER Rated Cooling (Nonducted / Ducted) 22 / 21 20.5 / 20.5 20 / 19.5 19 / 19.3 18.8 / 19
Norminal Heating 4.20 4.11 4.20 3.99 4.05
COP
Rated Heating (Nonducted / Ducted) 3.74 / 3.33 3.68 / 3.29 3.65 / 3.32 3.55 / 3.2 3.63 / 3.25
Power Factor Rated - 0.93 0.93 0.93 0.93 0.93
Casing Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray
Heat Exchanger Ocean Black Fin Ocean Black Fin Ocean Black Fin Ocean Black Fin Ocean Black Fin
(5,300 × 2) (5,300 × 2)
Compressor Motor Output × Number W × No. 5,300 × 3 5,300 × 3 5,300 × 4
+ (4,200 × 2) + (4,200 × 2)
Type Propeller fan Propeller fan Propeller fan Propeller fan Propeller fan
Motor Output × Number W 900 × 4 900 × 4 900 × 4 900 × 4 900 × 4
Fan m3/min 320 × 2 320 × 2 320 × 2 320 × 2 320 × 2
Air Flow Rate (High)
ft /min
3
11,301 × 2 11,301 × 2 11,301 × 2 11,301 × 2 11,301 × 2
Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER DC INVERTER
Liquid Pipe mm (inch) 19.05(3/4) 19.05(3/4) 19.05(3/4) 19.05(3/4) 19.05(3/4)
Pipe Connections For Low Pressure Gas Pipe
Heat Pump mm (inch) 34.9(1-3/8) 34.9(1-3/8) 41.3(1-5/8) 41.3(1-5/8) 41.3(1-5/8)
High Pressure Gas Pipe mm (inch) 28.58(1-1/8) 28.58(1-1/8) 34.9(1-3/8) 34.9(1-3/8) 34.9(1-3/8)
Pipe Connections For Liquid Pipe mm (inch) 19.05(3/4) 19.05(3/4) 19.05(3/4) 19.05(3/4) 19.05(3/4)
Heat Pump Gas Pipe mm (inch) 34.9(1-3/8) 34.9(1-3/8) 41.3(1-5/8) 41.3(1-5/8) 41.3(1-5/8)
(1,240 ×1,690 × (1,240 ×1,690 × (1,240 ×1,690 × (1,240 ×1,690 × (1,240 ×1,690 ×
mm
760) × 2 760) × 2 760) × 2 760) × 2 760) × 2
Dimensions (W × H × D)
(48-13/16 × 66-17/32 (48-13/16 × 66-17/32 (48-13/16 × 66-17/32 (48-13/16 × 66-17/32 (48-13/16 × 66-17/32
inch
× 29-29/32) × 2 × 29-29/32) × 2 × 29-29/32) × 2 × 29-29/32) × 2 × 29-29/32) × 2
kg (230 × 1) + (302 × 1) (230 × 1) + (302 × 1) (290 × 1) + (302 × 1) (290 × 1) + (302 × 1) (299 × 1) + (302 × 1)
Net Weight
lbs (507 × 1) + (666 × 1) (507 × 1) + (666 × 1) (639 × 1) + (666 × 1) (639 × 1) + (666 × 1) (659 × 1) + (666 × 1)
Sound Pressure Level Cooling dB(A) 65.0 65.0 66.0 66.0 66.0
Sound Power Level Cooling dB(A) 88.0 88.0 89.0 89.0 90.0
Communication Cable No.× mm2 (VCTF-SB) 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5
Refrigerant name R410A R410A R410A R410A R410A
Precharged Amount in kg 51.00 55.00 59.00 64.00 67.00
factory lbs 112.4 121.3 130.1 141.1 147.7
Refrigerant GWP 2087.5 2087.5 2087.5 2087.5 2087.5
TCO2eq 106.5 114.8 123.2 133.6 139.9
Electronic Expansion Electronic Expansion Electronic Expansion Electronic Expansion Electronic Expansion
Control
Valve Valve Valve Valve Valve
220, 3, 60 220, 3, 60 220, 3, 60 220, 3, 60 220, 3, 60
Power Supply Ø , V, Hz
220-240, 3, 50 220-240, 3, 50 220-240, 3, 50 220-240, 3, 50 220-240, 3, 50
Number of maximum connectable indoor units5) 52 55 58 61 64

Note :
1. Nominal capacity applied with non-ducted indoor units, and is rated 0 m. above sea level with 7.5 m. of refrigerant line per indoor unit and a 0 m. level difference between outdoor and indoor units.
All capacities are net with a Combination Ratio between 95–105%. Nominal cooling capacity rating obtained with air entering the indoor unit at 80°F (27°C) dry bulb (DB) and 67°F (19°C) wet bulb
(WB) and outdoor ambient conditions of 95°F (35°C) dry bulb (DB) and 75°F (24°C) wet bulb (WB). Nominal heating capacity rating obtained with air entering the indoor unit at 70°F (21°C) dry bulb
(DB) and 59°F (15°C) wet bulb (WB) and outdoor ambient conditions of 47°F (8°C) dry bulb (DB) and 43°F (6°C) wet bulb (WB).
2. Rated capacity is certified under AHRI Standard 1230. For AHRI ratings, refer to the AHRI website http://www.ahridirectory.org.
3. The System Combination Ratio must be between 50–130%.
4. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
5. Communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded or unshielded, and must comply with applicable local and national codes.
If shielded, ensure the communication cable is properly grounded to chassis at the master ODU only. Do not ground the ODU-IDU (or HRU) communication cable at any other point.
6. Power wiring is field provided, solid or stranded, and must comply with the applicable local and national codes..
7. LG requires that LATS software be used on all projects to ensure correct line sizing. Designer must verify the shop drawing design against the as built design using LATS.
Contractor must also use LG manufactured Y-Branch and Header Kits only.

060
DIGITALAIR.MX
OUTDOOR UNIT
ARUM432BTE5 / ARUM456BTE5 / ARUM480BTE5 / ARUM504BTE5

RT 36.0 38.0 40.0 42.0


Combination Unit ARUM432BTE5 ARUM456BTE5 ARUM480BTE5 ARUM504BTE5
Model Name ARUM192BTE5 ARUM216BTE5 ARUM216BTE5 ARUM216BTE5
Independent Unit ARUM121BTE5 ARUM121BTE5 ARUM144BTE5 ARUM168BTE5
ARUM121BTE5 ARUM121BTE5 ARUM121BTE5 ARUM121BTE5
Btu/h 432,000 456,000 480,000 504,000
Cooling
kW 126.6 133.6 140.7 147.7
Norminal
Btu/h 486,000 513,000 540,000 567,000
Heating
kW 142.4 150.4 158.3 166.2
Capacity
Btu/h 412,000 434,000 458,000 480,000
Cooling
kW 120.8 127.2 134.2 140.7
Rated
Btu/h 464,000 488,000 513,000 539,000
Heating
kW 136.0 143.0 150.4 158.0
Cooling kW 29.05 30.81 32.39 35.32
Norminal
Heating kW 33.86 36.15 37.49 40.93
Input
Cooling (Nonducted / Ducted) kW 32.24 / 34.97 35.8 / 37.49 38.14 / 37.78 40.77 / 42.78
Rated
Heating (Nonducted / Ducted) kW 40.16 / 35.15 42.93 / 38.15 44.82 / 40.37 48.49 / 43.4
Norminal Cooling 14.87 14.80 14.82 14.27
EER
Rated Cooling (Nonducted / Ducted) 12.78 / 11.78 12.12 / 11.58 12.01 / 11.51 11.77 / 11.22
IEER Rated Cooling (Nonducted / Ducted) 19.8 / 20 19.2 / 18.5 19 / 18 18.6 / 17.5
Norminal Heating 4.21 4.16 4.22 4.06
COP
Rated Heating (Nonducted / Ducted) 3.87 / 3.36 3.75 / 3.33 3.72 / 3.36 3.64 / 3.26
Power Factor Rated - 0.93 0.93 0.93 0.93
Casing Color Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray Warm Gray / Dawn Gray
Heat Exchanger Ocean Black Fin Ocean Black Fin Ocean Black Fin Ocean Black Fin
Compressor Motor Output × Number W × No. 5,300 × 4 5,300 × 4 (5,300 × 3) + (4,200 × 2) (5,300 × 3) + (4,200 × 2)
Type Propeller fan Propeller fan Propeller fan Propeller fan
Motor Output × Number W 900 × 6 900 × 6 900 × 6 900 × 6
Fan m3/min 320 × 3 320 × 3 320 × 3 320 × 3
Air Flow Rate (High)
ft3/min 11,301 × 3 11,301 × 3 11,301 × 3 11,301 × 3
Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER
Liquid Pipe mm (inch) 19.05(3/4) 19.05(3/4) 19.05(3/4) 19.05(3/4)
Pipe Connections For Low Pressure Gas Pipe mm (inch) 41.3(1-5/8) 41.3(1-5/8) 41.3(1-5/8) 41.3(1-5/8)
Heat Pump
High Pressure Gas Pipe mm (inch) 34.9(1-3/8) 34.9(1-3/8) 34.9(1-3/8) 34.9(1-3/8)
Pipe Connections For Liquid Pipe mm (inch) 19.05(3/4) 19.05(3/4) 19.05(3/4) 19.05(3/4)
Heat Pump Gas Pipe mm (inch) 41.3(1-5/8) 41.3(1-5/8) 41.3(1-5/8) 41.3(1-5/8)
mm (1,240 ×1,690 × 760) × 3 (1,240 ×1,690 × 760) × 3 (1,240 ×1,690 × 760) × 3 (1,240 ×1,690 × 760) × 3
Dimensions (W × H × D) (48-13/16 × 66-17/32 × 29- (48-13/16 × 66-17/32 × 29- (48-13/16 × 66-17/32 × 29- (48-13/16 × 66-17/32 × 29-
inch
29/32) × 3 29/32) × 3 29/32) × 3 29/32) × 3
(230 × 1) + (290 × 1) (230 × 1) + (290 × 1)
kg (230 × 2) + (299 × 1) (230 × 2) + (302 × 1)
+ (302 × 1) + (302 × 1)
Net Weight
(507 × 1) + (639 × 1) (507 × 1) + (639 × 1)
lbs (507 × 2) + (659 × 1) (507 × 2) + (666 × 1)
+ (666 × 1) + (666 × 1)
Sound Pressure Level Cooling dB(A) 66.0 66.0 67.0 67.0
Sound Power Level Cooling dB(A) 89.0 89.0 89.0 90.0
Communication Cable No.× mm2 (VCTF-SB) 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5
Refrigerant name R410A R410A R410A R410A
Precharged Amount in kg 72.00 75.00 79.00 84.00
factory lbs 158.7 165.3 174.2 185.2
Refrigerant
GWP 2087.5 2087.5 2087.5 2087.5
TCO2eq 150.3 156.6 164.9 175.4
Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
220, 3, 60 220, 3, 60 220, 3, 60 220, 3, 60
Power Supply Ø , V, Hz
220-240, 3, 50 220-240, 3, 50 220-240, 3, 50 220-240, 3, 50
Number of maximum connectable indoor units5) 64 64 64 64
Note :
1. Nominal capacity applied with non-ducted indoor units, and is rated 0 m. above sea level with 7.5 m. of refrigerant line per indoor unit and a 0 m. level difference between outdoor and indoor units.
All capacities are net with a Combination Ratio between 95–105%. Nominal cooling capacity rating obtained with air entering the indoor unit at 80°F (27°C) dry bulb (DB) and 67°F (19°C) wet bulb
(WB) and outdoor ambient conditions of 95°F (35°C) dry bulb (DB) and 75°F (24°C) wet bulb (WB). Nominal heating capacity rating obtained with air entering the indoor unit at 70°F (21°C) dry bulb
(DB) and 59°F (15°C) wet bulb (WB) and outdoor ambient conditions of 47°F (8°C) dry bulb (DB) and 43°F (6°C) wet bulb (WB).
2. Rated capacity is certified under AHRI Standard 1230. For AHRI ratings, refer to the AHRI website http://www.ahridirectory.org.
3. The System Combination Ratio must be between 50–130%.
4. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
5. Communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded or unshielded, and must comply with applicable local and national codes.
If shielded, ensure the communication cable is properly grounded to chassis at the master ODU only. Do not ground the ODU-IDU (or HRU) communication cable at any other point.
6. Power wiring is field provided, solid or stranded, and must comply with the applicable local and national codes..
7. LG requires that LATS software be used on all projects to ensure correct line sizing. Designer must verify the shop drawing design against the as built design using LATS.
Contractor must also use LG manufactured Y-Branch and Header Kits only.

061