Inventor Service Manual
Inventor Service Manual
Inventor Service Manual
RCONDI
TIONING
SYSTEMS
Model
s:
U-
MATCH I
NVERTER
Ser
viceManual
Ser
viceManual
Ⅰ
ChapterⅠ Introduction to Products
. Kinds of Products
1.
Universal Duct type Floor ceiling Cassette
outdoor unit type type
VDI VKI VCI
URS-09 9K 9K -
URS-12 12K 12K -
URS-18 18K 18K 18K
URS-24 Single 24K 24K 24K
URS-30 phase 30K 30K 30K
URS-36 36K 36K 36K
URS-45 45K 45K 45K
URS-50 50K 50K 50K
URT-36 36K 36K 36K
URT-45 Three 45K 45K 45K
URT-50 phase 50K 50K 50K
URT-60 60K - -
Power supply mode:Single phase 1PH 220-240V ~ 50Hz
Three phase 3PH 380-415V ~ 50Hz
3. Features of Products
Combining the comfort of central air conditioner and easy installation, high flexibility and suchlike
advanges of high-grade small-sized split household air conditioner, INVENTOR duct type air-conditioner
unit features high efficiency, long-distance air supply, high- quality room air, reliable performance, simple
operation, etc. It can be widely used in small supermarket, chain stores, living rooms, hotel, restaurant,
offices, meeting room and villa.
a) Flexible Installation: The user can determine the air supply/return mode, condensate outflow
direction and air vent type according to the needs of installation.
b) High Efficiency and Energy Saving: High-quality compressor is installed. The evaporator
employs hydrophilic aluminum foil and inner threaded copper tube so as to ensure high
efficiency of heat exchange and increased energy-efficiency ratio of the unit.
c) Long-distance Air Supply: For extra residual pressure design, the air can be blown to a long
distance after centralized handling within the indoor unit.
d) High- quality Room Air: The air duct of the unit may be connected to multiple air vents so
that the air-conditioning temperature and humidity within the room will be evenly distributed.
To improve the room air quality, the unit is equipped with highly efficient and healthy filter in
which nanometer photocatalyst or catechin is used as the filtering medium.
e) Reliable Performance: The unit with full functions has powerful self-diagnosis function. (See
the Microcomputer Control System for detailed information).
f) Simple Operation: Simple controller and flexible remote controller enable control of unit as
your desire.
g) Control of Fresh Air: 11 kinds of different fresh air flow volume can be set to adjust it
accurately and reduce power consumption.
h) Lock of Temperature Range: The user can lock the temperature range as desired. This is
suitable for public space.
i) Weekly Timer: It has the function of centralized control and can set startup and stop of the unit
at 4 periods of time of each day in a week.
◇Control Functions:
Memory Function (Upon reset after power failure, the unit will run under its original status without
any change in mode and parameters).
Remote Control (The unit is provided with different controllers for your option. The wired controller
can receive the command from a distance up to 10 meters).
Timer Function (The unit may be set to TIMER On / Off separately or in cycle).
2
Diagnosis and Alarm Function (Upon any failure during operation, the unit will display the failure
code and give out alarm).
Energy Saving Function (The unit can automatically perform cost-effective control under
energy-saving mode).
Auto Function (When the unit is under cooling mode, the indoor fan can automatically adjust its
speed according to the actual needs of the system).
Anti Cold-air Function (Under heating mode, indoor fan will operate till indoor heat exchanger is
Control Function to Sub-rooms (The startup and stop of the unit can be controlled through control of
Residual Heat Blowing Function (Under heating mode, the indoor fan will stop after compressor has
◇ Protection Functions:
High / Low Pressure Protection (If the suction pressure of the compressor is too low and the
exhaust pressure is two high, the compressor will be stopped and the failure code will be displayed).
Overload Protection: (The compressor with self-heat protection will be stopped if its temperature
exceeds the permissible value, and will be started as long as the temperature resumes to normal.
Over-current Protection (When the compressor current exceeds the normal value, the compressor
will be stopped and the failure code will be displayed).
Exhaust High Temperature Protection (When the exhaust temperature of the compressor exceeds
the permissible value, the compressor will be stopped and the failure code will be displayed).
Reverse Phase (Phase Loss) Protection (If the power is inconsistent of phase sequence or phase
loss, the unit will not be started and the failure code will be displayed).
Antifreezing Protection (When the surface temperature of indoor heat exchanger is too low, the
compressor will be stopped and the failure code will be displayed).
High Temperature Protection (When the surface temperature of indoor heat exchanger is too high,
the compressor will be stopped and the failure code will be displayed).
Sensor Fault Alarm (When the sensor is in short circuit or open circuit, the failure code will be
displayed).
◇ Display Function:
CLOCK Display (To display and set the real time).
Timer ON/ OFF Display (To display and set the time for auto start or stop).
3
CANCEL TIMER Display (To display the timer cancellation).
FAN SPEED Display (The fan speed is displayed in HIGH, MEDIUM or LOW).
RUN MODE Display (Cooling, Dehumidify, Heating, Fan)
TEST Display (Display when under test mode).
ENERGY SAVING Display (Display when running under energy saving mode)
TEMPERATURE Display (Display the room temperature and preset temperature)
Failure code Display
Up to groups
DIP swicth
Location
Power supply
Max.
Switch power supply
Fig.1-1
Note: Please specified whether need this control function or not before purchase.
4
4 Specifications and Technical Parameters
,URS-12,
4.2.1 URS-09, ,URS-18,
,URS-24
5
wall thickness)
4.2.2 ,URS-45,
URS-36, ,URS-50
URS-36 URS-45 URS-50
Model
VDI-36 VDI-45 VDI-50
Items Cooling Heating Cooling Heating Cooling Heating
Capacity Capacity 10000 12000 12000 14000 14000 15500
Power Power 3700 3800 5000 4500 6000 5100
Current Current 17.0 17.0 22.9 20.8 27.4 23.3
Power supply 220-240V~ 50Hz
Compressor Hermetic scroll inverter compressor
3
Air flow volume m /h 2000 2000 2400
Indoor dB(A) 50 50 50
Noise
Outdoor dB(A) 62 63 63
Refrigerant R410A
Charge volume kg 4.0 4.0 4.0
Connecting Liquid mm ф12 ф12 ф12
pipe Gas mm ф19 ф19 ф19
W mm 1335 1335 1335
D mm 834 834 834
Indoor unit
H mm 290 290 290
Weight kg 57 57 57
W mm 1110 1110 1110
Outdoor D mm 450 450 450
unit H mm 1385 1385 1385
Weight kg 128 128 128
Drainage pipe mm
(inside diameter x wall ф20×1.5 ф20×1.5 ф20×1.5
thickness)
,URT-45,
4.2.3 URT-36, ,URT-50,
,URT-60
URT-36 URT-45 URT-50 URT-60
Model
VDI-36 VDI-45 VDI-50I VDI-60
Items Cooling Heating Cooling Heating Cooling Heating Cooling Heating
Capacity W 10000 12000 12000 14000 14000 15500 16000 18000
Power W 3600 4000 5100 4900 6300 5500 6700 5200
Current A 6.5 7.2 8.3 8.2 10.3 9.0 13.0 8.9
Power supply 380-415 ~ 50Hz
6
Compressor Hermetic scroll inverter compressor
3
Air flow volume m /h 2000 2000 2400 2800
Indoor Noise 50 50 50 53
Noise
Outdoor 62 63 63 64
Refrigerant R410A
Charge volume kg 4.0 4.0 4.0 4.3
Connecting Liquid mm ф12 ф12 ф12 ф12
pipe Gas mm ф19 ф19 ф19 ф22
W mm 1335 1335 1335 1335
D mm 834 834 834 882
Indoor unit
H mm 290 290 290 330
Weight kg 57 57 57 66
W mm 1110 1110 1110 1110
Outdoor D mm 450 450 450 450
unit H mm 1385 1385 1385 1385
Weight kg 128 128 128 138
Drainage pipe mm
(inside diameter x ф20×1.5 ф20×1.5 ф20×1.5 ф32×1.4
wall thickness)
,URS-12,
4.2.4 URS-09, ,URS-18,
,URS-24
URS-09 URS-12 URS-18 URS-24
Model
VKI-09 VKI-12 VKI-18 VKI-26
Items Cooling Heating Cooling Heating Cooling Heating Cooling Heating
Capacity Capacity 2600 2900 3500 3900 5000 5500 7000 8000
Power Power 900 1100 1200 1300 2000 2400 2500 2600
Current Current 6.5 7.0 7.5 8.5 11.5 13.5 17.5 18.7
Power supply 220-240V~ 50Hz
Compressor Hermetic scroll inverter compressor
3
Air flow volume m /h 550 600 700 1100
Indoor dB(A) 45 46 54 50
Noise
Outdoor dB(A) 55 56 56 59
Refrigerant R410A
Charge volume kg 1.0 1.2 1.5 1.8
Connecting Liquid mm ф6 ф6 ф6 ф9.52
pipe Gas mm ф9.52 ф12 ф12 ф16
W mm 836 836 836 1300
Indoor unit
D mm 695 695 695 600
7
H mm 238 238 238 188
Weight kg 27 27 27 32
W mm 878 878 878 994
Outdoor D mm 360 360 360 428
unit H mm 610 610 610 750
Weight kg 32 40 40 56
Drainage pipe mm
(inside diameter x ф20×1.5 ф20×1.5 ф30×1.4 ф20×1.5
wall thickness)
4.2.5 ,URS-45,
URS-36, ,URS-50
URS-36 URS-45 URS-50
Model
VKI-36 VKI-45 VKI-50
Items Cooling Heating Cooling Heating Cooling Heating
Capacity Capacity 10000 12000 12000 14000 14000 15500
Power Power 3700 3800 5000 4500 6000 5100
Current Current 17.0 17.0 22.9 20.8 27.4 23.3
Power supply 220-240V~ 50Hz
Compressor Hermetic scroll inverter compressor
3
Air flow volume m /h 1400 1400 1800
Indoor dB(A) 53 53 53
Noise
Outdoor dB(A) 62 63 63
Refrigerant
Charge volume kg 4.0 4.0 4.0
Connecting Liquid mm ф12 ф12 ф12
pipe Gas mm ф19 ф19 ф19
W mm 1590 1590 1590
D mm 695 695 695
Indoor unit
H mm 228 228 228
Weight kg 42 42 42
W mm 1110 1110 1110
Outdoor D mm 450 450 450
unit H mm 1385 1385 1385
Weight kg 128 128 128
Drainage pipe mm
(inside diameter x wall ф20×1.5 ф20×1.5 ф20×1.5
thickness)
,URT-45,
4.2.6 URT-36, ,URT-50
8
URT-36 URT-45 URT-50
Model
VKI-36 VKI-45 VKI-50
Items Cooling Heating Cooling Heating Cooling Heating
Capacity W 10000 12000 12000 14000 14000 15500
Power W 3600 4000 5100 4900 6300 5500
Current A 6.8 8.2 8.3 8.2 10.3 9.0
Power supply 380-415V~ 50Hz
Compressor Hermetic scroll inverter compressor
3
Air flow volume m /h 1400 1400 2400
Indoor dB(A) 53 53 53
Noise
Outdoor dB(A) 62 63 63
Refrigerant R410A
Charge volume kg 4.0 4.0 4.0
Connecting Liquid mm ф12 ф12 ф12
pipe Gas mm ф19 ф19 ф19
W mm 1590 1590 1590
D mm 692 692 692
Indoor unit
H mm 238 238 238
Weight kg 42 42 42
W mm 1110 1110 1110
Outdoor D mm 450 450 450
unit H mm 1385 1385 1385
Weight kg 128 128 128
Drainage pipe mm
(inside diameter x ф20×1.5 ф20×1.5 ф20×1.5
wall thickness)
,URS- 24
4.2.7 URS-18,
URS-09 URS-12 URS-18 URS-24
Model
VCI-09I VCI-12 VCI-18 VCI-24
Items Cooling Heating Cooling Heating Cooling Heating Cooling Heating
Capacity W 5000 5800 7000 8000
Power W 2000 2400 2500 2600
Current A 11.5 13.5 17.5 18.7
Power supply 220-240V~ 50Hz
Compressor Hermetic scroll inverter compressor
3
Air flow volume m /h 680 1180
Indoor Noise 47 47
Noise
Outdoor 56 59
Refrigerant
Charge volume kg 1.5 1.8
9
Connecting Liquid mm ф6 ф9.52
pipe Gas mm ф12 ф16
W mm 660 840
D mm 660 840
Indoor unit
H mm 230 240
Weight kg 20 30
W mm 878 994
Outdoor D mm 360 428
unit H mm 610 750
Weight kg 40 56
Drainage pipe
(inside diameter x ф30×1.4 ф20×1.5
wall thickness)
4.2.8 ,URS-45,
URS-36, ,URS-50
URS-36 URS-45 URS-50
Model
VCI-36 VCI-45 VCI-50
Items Cooling Heating Cooling Heating Cooling Heating
Capacity W 10000 12000 12000 14000 14000 15500
Power W 3700 3800 5000 4500 6000 5100
Current A 25.1 26.2 33.3 30.6 28.8 35.5
Power supply 220-240V~ 50Hz
Compressor Hermetic scroll inverter compressor
3
Air flow volume m /h 1600 1650 1700
Indoor dB(A) 53 53 53
Noise
Outdoor dB(A) 62 63 63
Refrigerant R410A
Charge volume kg 4.0 4.0 4.0
Connecting Liquid mm ф12 ф12 ф12
pipe Gas mm ф19 ф19 ф19
W mm 840 840 840
D mm 840 840 840
Indoor unit
H mm 320 320 320
Weight kg 38 38 38
W mm 1110 1110 1110
Outdoor D mm 450 450 450
unit H mm 1385 1385 1385
Weight kg 128 128 128
Drainage pipe mm
ф20×1.5 ф20×1.5 ф20×1.5
(inside diameter x
10
wall thickness)
,URT-45,
4.2.9 URT-36, ,URT-50
URT-36 URT-45 URT-50
Model
VCI-36 VCI-50 VCI-50
Items Cooling Heating Cooling Heating Cooling Heating
Capacity Capacity 10000 12000 12000 14000 14000 15500
Power Power 3600 4000 5100 4900 6300 5500
Current Current 8.5 9.5 11.6 11.0 13.8 12.5
Power supply 380-415V~ 50Hz
Compressor Hermetic scroll inverter compressor
3
Air flow volume m /h Air flow volume 1650 1700
Indoor Noise 53 53 53
Noise
Outdoor 62 63 63
Refrigerant R410A
Charge volume kg 4.0 4.0 4.0
Connecting Liquid mm ф12 ф12 ф12
pipe Gas mm ф19 ф19 ф19
W mm 840 840 840
D mm 840 840 840
Indoor unit
H mm 320 320 320
Weight kg 38 38 38
W mm 1110 1110 1110
Outdoor D mm 450 450 450
unit H mm 1385 1385 1385
Weight kg 128 128 128
Drainage pipe mm
(inside diameter x ф20×1.5 ф20×1.5 ф20×1.5
wall thickness)
Note:
1.The cooling capacity was tested under nominal condition corresponding to the unit external standard residual pressure. The parameters are
subject to that on nameplate.
2.The noise was measured in semi-anechoic room. In actual operation, it may be higher due to change of environment.
11
5. Characteristics Curve
5.1 Relationship between Air-Conditioner Low Pressure and Temperature (Fig. 3-1)
Heating running: Indoor condition, dry bulb of 21℃, wet bulb of 15.5℃.
7 7
Low低压压力(绝对值)(bar)
低压压力(绝对值)(bar)
6
5 5
4
4
3
Low 3
2
15 20 25 30 35 2
50 60 70 80(%) 0 5 10 15 20
干球温度(℃)/湿度(%)
Dry bulb temp. (℃)/Humidity (%) 干球温度(℃)/湿度(%)
Dry bulb temp. (℃)/Humidity (%)
Outdoor Dry Bulb Temp. (℃) Outdoor Dry Bulb Temp. (℃)
12
5.3 Relationship between Cooling Capacity / Refrigerant Charge and Connection Pipe Length
(Fig. 3-3)
30
20
indoor and outdoor units (m)
90%
92%
室内外机高度差(m)
0
Height difference between
-10
-20
-30
10 20 30 40
连接管长度(m)
Connection pipe length (m) Connection pipe length (m)
(a) Change of cooling capacity with that of connection pipe length (b) Change of refrigerant charge volume with that of connection pipe length
1800
1600
1400
AIR FLOW(m3/h)
1200
1000
800
600
400
0 20 40 60 80 100 120
EXTERNAL STAIC
PRESSURE(Pa)
13
VDI-45
VDI-50
3000
2800
2600
2400
2200
AIR FLOW(m3/h)
2000
1800
1600
1400
1200
1000
800
600
400
Fig. 3-4
14
6. Main Parts
15
7. Outline and Installation Dimension
7.1 Outline and Dimension of Indoor Unit (Fig.5.1)
Duct type indoor unit
(b) VDI-18
16
Air return Air supply
H
J
I
Gas pipe Liquid pipe Drainage pipe Electric box
A
B
F
C
D
E
G
Unit:mm
Drainage pipe (out
Items Liquid Gas
A B C D E F G H I J diameter×wall
Models pipe pipe
thickness)
VDI-24 1063 505 820 1159 1247 504 1088 160 211 268 ф9.52 ф16 ф20×1.5
VDI-36 1011 748 820 1115 1226 744 1047 160 231 290 ф12 ф19 ф20×1.5
ф12 ф19
VDI-45 1011 748 820 1115 1226 744 1047 160 231 290 ф20×1.5
VDI-50 1011 748 820 1115 1226 744 1047 160 231 290 ф12 ф19 ф20×1.5
(c)Other models
17
Floor ceiling type unit
Model A B C D E
VKI-09
VKI-12 836 238 745 695 260
VKI-18
VKI-24 1300 188 1202 600 260
VKI-36
VKI-45 1500 238 1491 695 260
VKI-45
18
(Fig.5-2)
7.2 Outline and Dimension of Outdoor Unit( )
E
D
A
Unit:mm
URT-36
URS-09 URS-36
Unit URT-45
URS-12 URS-24 URS-45
Model URT-50
URS-18 URS-50
URT-60
A 760 950 950
B 320 412 412
C 530 700 1250
D 540 572 572
E 286 378 378
Fig. 5-2 Outline and Dimesion of Outdoor Unit
19
8. Refrigeration System Principles
Refrigeration Cycle: The low-temperature and low-pressure refrigerant vapour in the evaporator is
compressed into high-temperature and high-pressure gas by the compressor, and then the gas enters
into condenser.The gas becomes high-temperature and high-pressure liquid through heat exchange with
outdoor air, and then the liquid passes through the capillary for cooling and decompression by throttling
and enters into evaporator.After that, the gas-liquid refrigerant in the envopator is completely evaporated
to cool the indoor air.The vapour out of the evaporator is re-compressed by the compressor. So is the
above procedure recycled that the cooled air in the duct is contiuously sent to air-conditioning area with
Heating Cycle: It is reverse to cooling cycle。In this case, 4-way valve will reverse and flow direction of
refrigerant changes, i.e the vapour out of the compressor enters into heat exchanger for condensation.
The refrigerant after condensation passes through the capillary for throttling.After that it evaporates in
the outdoor heat exchanger, at last it will be sucked and compressed by compressor. So is the above
procedure recycled that the hot air in the duct is contiuously sent to air-conditioning area with the help of
fan motor.
Connection pipe
(with insulating tube)
Gas-liquid separator
Comp-
ressor
Flare joint
Main Capillary
Connection pipe
(with insulating tube) 3-way Valve (liquidvalve)
20
Flow direction during cooling
Connection pipe
(with insulating tube)
Gas-liquid separator
Comp-
Flare joint ressor
Main Capillary
Auxiliary Capillary
Filter
Fig. 6-1
21
Chapter II Control Functions
1. Control Mode
The 4-in-1 DC Inverter Unit consists of outdoor mainboard, indoor mainboard and manual
controller, which are lined via communication wires. In this way, one outdoor unit can be used with
different indoor units of the equal capacity (duct type unit, floor ceiling unit, cassette type unit and
ceiling type unit), and the cooling and heating share one electronic expansion valve.
The outdoor compressor is DC inverter compressor, in which the advanced sine wave control
mode is used, featuring in low vibration, low noise and high efficiency. The single-phase unit also
uses the PFC control, with PFC value up to 0.99 or higher, so the interference to the electric grid
is very low.
The outdoor unit also applies the advanced PI algorithm, able to automatically and quickly adjust
the working frequency of the compressor according to the change of indoor loads. This can not
only meet the user’s requirements for comfort but also save unnecessary electric energies.
This unit can be controlled via LCD controller easily or controlled from remote controller. It can
also be controlled from centralized controller, or put under remote monitor by PC computer.
Besides, it can also be configured with weekly timer wired controller which can automatically
switch on or off the unit at predefined time for each day in a week. This is suitable to family, office,
factory and man-free places.
2 Introduction Control Functions
2.1 Basic Control Functions
2.1.1 Cooling Mode
After setting to cooling mode, the indoor fan will run at preset speed after 3 seconds and the
outdoor unit will start to calculate the system load demand. If the load is “0”, the other loads
except the indoor fan and indoor drainage pump will not be put into operation. If the load is over
“0”, the electronic expansion valve will be firstly opened and then the outdoor fan is started. After
30 seconds, the compressor is started.
Under cooling mode the range of temperature setting is 16℃~30℃ and the initial value is 26℃.
2.1.2 DRY Mode
The DRY mode is basically same as the cooling mode. The difference is that: ①The speed of
indoor fan is fixed at low speed; and ②The maximum value of capacity output is 90%.
Under DRY mode, the range of temperature setting is 16℃~30℃ and the initial value is 24℃.
2.1.3 Heating Mode
After setting to heating mode, the outdoor unit will start to calculate the system load demand. If
the load is “0”, all the other loads will not be put into operation. If the load is over “0”, the electronic
expansion valve will be firstly opened and then the outdoor fan is started. After 30 seconds, the
compressor is started, the 4-way valve is energized and the indoor fan runs under anti cold air
mode.
Under DRY mode, the range of temperature setting is 16℃~30℃ and the initial value is 20℃.
2.1.4 Fan Mode
When the indoor unit is set to fan mode, all the loads of the outdoor unit will be stopped and the
indoor fan will run at preset speed. Under this mode, the fault is detected but will not be treated.
The temperature is not adjustable, displayed at 26℃.
2.1.5 Auto Mode
Under this mode, the run mode will vary with the ambient temperature according to the following
conditions:
When Tamb.>26℃, the unit will run under cooling mode and the preset temperature is 26℃;
When 20℃≤Tamb.≤26℃, the unit will run under DRY mode and the preset temperature is 24℃;
When Tamb.<20℃, the unit will run under heating mode and the preset temperature is 20℃. When
Tamb. ≥24℃, the unit will exit the heating mode. For cooling-only unit, when Tamb.<20℃, the unit
will run under fan mode and the preset temperature is 20℃. When Tamb.≥24℃, the unit will exit the
fan mode.
Once the mode is activated, the unit will run 30 seconds the shortest before it switch the run
status under auto mode according to the ambient temperature.
2.2 Special Control Functions
2.2.1 Energy-saving Function
Set a upper and lower limit of temperature by using manual controller, so that the temperature of
air conditioner is set to an energy-saving range, thus to save the power consumption of the air
conditioner. For example, the temperature under cooling mode is defaulted 16~30℃, but the user
may customize it to 26~30℃ by using manual controller. In this range, the lowest setting is 26℃
other 16℃.
2.2.2 Memory Function
Upon re-energization after power shutdown or failure, the air conditioner can memorize the last
work mode, temperature setting, fan speed and other parameters, so that it is not necessary to
repeat setting of those parameters. The user may also inactivate this function by using manual
controller.
2.2.3 Timer Function
For easy control of the air conditioner, the user may set the air conditioner to timer on or timer off
by using the manual controller. The timer is available with two modes for user’s option, i.e.
countdown and 7-day time section.
2.2.4 Sleep Function
If the user requires air conditioner during sleep, this function may automatically increase or
decrease the preset temperature, so as to meet the users’ needs for comfort and also save the
energy. If used with timer function, the energy saving effect will be better.
2.2.5 Alarm Function
When the air conditioner is abnormal, it can automatically display the fault or protection type,
while triggering the sound and lighting alarm.
2.2.6 Week Timer Centralized Control Function
The user may select centralized controller to control 16 units simultaneously for their start/stop,
timer on/off each day and key shield. The function is powerful, particularly suitable to
long-distance air conditioner system with many units.
2.2.7 Remote Monitor Function
By selecting the remote monitor function, the user may monitor the working parameters and
control the run mode of the air conditioner from a family PC. This is suitable to centralized control
of air conditioners in hotel, restaurants and factory. Up to 254 sets of units may be monitored
simultaneously.
2.2.8 Fresh Air Function (Duct Type Unit)
This function is suitable to duct type unit and helpful to introduce outdoor fresh air and enhance
the user’s comfort during use of the air conditioner. It is a truly air conditioning system.
2.2.9 Drainage Function (Duct Type Unit)
This function is suitable to duct type unit and helpful to extend the applications of the air
conditioner. By this function, the installation of air conditioner will no longer be restricted.
2.2.10 Air Valve Control Function (Duct Type Unit)
This function is suitable to duct type unit. By this function, the unit may be connected to 8 air valve
controllers. The fan speed is controlled by controlling the number of air valves that will be opened
or closed, thus to meet the needs of each room for air flow.
2.3 Protection Function
2.3.1 High Pressure Protection
When high pressure protection is detected, the unit will shut down all the loads (except the 4-way
valve of heating) and shield all the keys and remote signals except the On/Off, in which case the
run indicator will blink (or display fault code E1) and the buzzer will alarm. The fault cannot be
restored automatically. You shall need to press ON/Off to stop the unit, then turn off the indicator
(or clear E1 display) before pressing ON/OFF. The unit will be restarted if the high pressure
protection disappears. Otherwise, the run indicator will blink (or display fault code E1) and the
buzzer will alarm.
2.3.2 Low Pressure Protection
No matter the unit is under ON or standby status, it will be deemed low-pressure protection as
long as it is detected that the low-pressure switch is cut off, in which case the indicator will blink
(or display E3), all the loads will be stopped (except the 4-way valve of heating). If the fault is
eliminated, the compressor will be restarted after 3 minutes. If three low-pressure faults of
compressor are detected successively in 30 minutes from the first detection to the occurrence of
fault, the indicator will blink (or display E3) and the buzzer will alarm. The unit cannot be restored
automatically. You shall need to press ON/Off to stop the unit, then turn off the indicator before
pressing ON/OFF. The unit will be restarted if the high pressure protection disappears. Otherwise,
the run indicator will blink (or display fault code E3) and the buzzer will alarm.
2.3.3 Exhaust Overtemperature Protection
After the compressor is started, if it is detected that the compressor overload switch is cut off, it
will be deemed compressor overload protection. In this case, the indicator will blink (or display
E5), all the loads will be stopped (except the 4-way valve of heating). If the fault is eliminated, the
compressor will be restarted after 3 minutes. If three compressor overload protections are
detected successively in 30 minutes from the first detection to the occurrence of fault, the
compressor cannot be resumed automatically and the buzzer will alarm. You shall need to press
ON/Off to stop the unit and clear the sound alarm before pressing ON/OFF again. The unit will be
restarted if the high pressure protection disappears. Otherwise, the run indicator will blink (or
display fault code E5) and the buzzer will alarm.
2.3.4 Overload Protection
The temperature of outdoor heat exchanger will be detected during cooling and the temperature
of indoor heat exchanger will be detected during heating. When the temperature of heat
exchanger exceeds the normal working temperature permissible to the unit, it may be reduced by
adjusting the compressor frequency or stopping the unit.
2.3.5 Sensor Fault Protection
The unit will perform real-time detection of the indoor room sensor, evaporator sensor, outdoor
ambient sensor, compressor exhaust sensor and condenser sensor are normally connected. If
the controller detects that any sensor is connected abnormal (in open circuit or short circuit), it will
send out fault signal and the fault code will be displayed on indoor panel or lamp panel. Except
that the unit will not be stopped upon the fault of room ambient sensor, the fault of other sensors
will result in stop of the unit.
2.3.6 Anti-freeze Protection
If the temperature of indoor heat exchanger is too low under cooling mode, frost might occur and
thus affect the cooling effect. This unit is provided with antifreeze protection, so that the frost may
be automatically eliminated to ensure the unit is under the best performance.
3. Wired Controller, Remote Controlled and Week Timer Centralized Controller
9 10
11
1
12
2
13
3
14
4
5
15
6
16
7
8
17
Fig. 1
Fig. 2
2) Fan control (Fig. 3) (Shown in the figure is relevant
area of display. Same as below).
Fig. 3
3) Temperature adjustment (Fig. 4)
Press the temperature adjustment key.
▲:For increasing temperature setting;
Fig. 5
5) Run Mode Setting (Fig. 6)
With each press of this key, the run mode will
change in the following sequence:
→ COOL→DRY→FAN→HEAT→AUTO
Fig. 7
7) Setting of Fresh Air Valve (Fig. 8)
Under stop status, you may hold down FAN SPEED
key for 5 seconds to call out the fresh air setting.
In this case, the FRESH AIR will blink on LCD, and the
exiting fresh air mode will be displayed in temperature
setting area. The user may press “▲” or “▼” to adjust
the fresh air mode. The number definition is as follows:
00――Always under closed statue
01――The fresh air valve will open for 6 minutes if the
unit is started 60 minutes continuously.
02――The fresh air valve will open for 12 minutes if the
unit is started 60 minutes continuously.
03――The fresh air valve will open for 18 minutes if the
unit is started 60 minutes continuously.
04――The fresh air valve will open for 24 minutes if the
unit is started 60 minutes continuously. Fig. 8
05――The fresh air valve will open for 30 minutes if the
unit is started 60 minutes continuously.
06――The fresh air valve will open for 36 minutes if the
unit is started 60 minutes continuously.
07――The fresh air valve will open for 42 minutes if the
unit is started 60 minutes continuously.
08――The fresh air valve will open for 48 minutes if the
unit is started 60 minutes continuously.
09――The fresh air valve will open for 52 minutes if the
unit is started 60 minutes continuously.
10―Fully open
Press ON/OFF to confirm after adjusting the fresh air
mode, so that the system will store this number. After
that, the unit will run per this fresh air mode. The
factory default value is “0” and the fresh air valve is
closed. If starting the unit in this case, there will be no
display of FRESH AIR on LCD.
If the user has set the fresh air mode (1-10), the
FRESH AIR will always appear on LCD as long as the
unit is running, regardless of the system run mode.
The data of fresh air setting will not be cleared upon
re-energization after de-energization.
Fig. 11
Fig.15
3.2 User Guideline for Remote Controller
Names and Functions of Remote Controller Keys
Precautions:
This remote controller is a general-purpose remote controller, which can be used in
various types (functions) air conditioner. The keys not applicable to this air conditioner
are not explained here.
Ensure there is no obstacle between the remote controller and the signal receiving
window of the air conditioner.
The distance able to receive the signal of the remote controller can be as far as 8
meters.
Never drop or throw at will the remote controller.
Never let any liquid enter the remote controller. Avoid direct sunshine over the remote
controller. Do not place the remote controller in an extremely hot place.
Swing Swing
Auto Auto
o o
22 C 22 C
o Auto
22 C o
22 C
Model ON/OFF
Model ON/OFF
Fig.20
This WEEKLY TIMER adopts 485 mode to communicate with manual control of every duct type
unit, and it can control up to 16 units. Adopting 2-core twisted-pair wire, the longest
communication distance of this TIMER is 1200m. After connected to power, the WEEKLY TIMER
can display all connected units (sequence of unit is determined by code switch of manual control
of every duct type unit). On and off of every duct type unit can be done through the Timer On / Off
of this WEEKLY TIMER, and the button shield operation of manual control can be done through
shield setting on WEEKLY TIMER. Mode selection and temperature adjustment and other
operations are done through the manual control at every unit.
1. Press ▲ or ▼ to select the unit that needed to be control. It is available to control several
units by Group Control (1~16), or control single unit by Single Control.
1. When selected a certain or several units by Single Control or Group Control, Timer setting
and On/off setting can be set. Timer setting can set 4 on/off times in a day in one week; and
on/off setting can be done by pressing on/off button.
2. Connection between WEEKLY TIMER and manual control is shown as following:
Note: Fig.21
1. For upper unit checks 16 lower units consecutively, there will be no more than 16 seconds delay when
setting works till unit responds.
2 Please let us know your requirement before your placing the order, for this WEEKLY TIMER will only be
prepared when customer orders (communication joint with WEEKLY TIMER on manual control had been
prepared).
Chapter III Installation and Test (HV)
(1) DC Overvoltage: If it is detected that the DV voltage is higher than 420V upon energization,
this fault will be alarmed. It is non-restorable if this protection occurs six times successively in
1 hour. In this case, you must de-energize, discharge completely and re-energize before you
can eliminate this fault.
(2) DC Undervoltage: If it is detected that the DV voltage is lower than 200V upon energization,
this fault will be alarmed. It is non-restorable if this protection occurs six times successively in
1 hour. In this case, you must de-energize, discharge completely and re-energize before you
can eliminate this fault.
(3) Inverter Module Resetting: Initialize the inverter program. This fault is alarmed upon
energization after each de-energization or upon resetting of inverter chip caused by some
interference. 5s will be displayed after occurrence of this fault. Note: It is normal that this
alarm will occur upon energization after de-energization.
(4) Inverter IPM Abnormal: This fault is alarmed when it is detected that IMP module or PFC
module is abnormal. It is non-restorable if this protection occurs six times successively in 1
hour. In this case, you must de-energize, discharge completely and re-energize before you
can eliminate this fault.
(5) Radiator Fin Overheat Protection: This fault is alarmed when it is detected in 1s successively
that the radiator fin temperature is higher than 105℃. It is non-restorable if this protection
occurs six times successively in 1 hour. In this case, you must de-energize, discharge
completely and re-energize before you can eliminate this fault.
(6) Compressor Overcurrent Protection: This fault is alarmed when it is detected in 1ms
successively that the transient current of compressor is higher than 18A. It is non-restorable if
this protection occurs six times successively in 1 hour. In this case, you must de-energize,
discharge completely and re-energize before you can eliminate this fault.
(7) Compressor in Loss of Synchronization: This fault is alarmed when it is detected in 2s
successively that the negative potential of the compressor in run period is lower than 20V. It is
non-restorable if this protection occurs six times successively in 1 hour. In this case, you must
de-energize, discharge completely and re-energize before you can eliminate this fault.
(8) Compressor Over-frequency Protection: This fault is alarmed when it is detected in 2s
successively that the working frequency of compressor is higher than 200HZ or the difference
between working frequency and preset frequency is over 40Hz. It is non-restorable if this
protection occurs six times successively in 1 hour. In this case, you must de-energize,
discharge completely and re-energize before you can eliminate this fault.
(9) Communication Fault between Inverter and Main Controller: This fault is alarmed when it is
detected in 60s successively that it cannot communicate with the main controller normally.
This fault can be restored automatically.
(10) Current Detection Circuit Fault: This fault is alarmed when it is detected that the average bias
voltage is higher than 12.5% of 1.65V. It is non-restorable if this protection occurs six times
successively in 1 hour. In this case, you must de-energize, discharge completely and
re-energize before you can eliminate this fault.
Eliminate the
fault and make
records.
The screws fixing the IPM module or PFC module is not properly tightened.
Interference.
Manual
controller
displays E5
(overcurrent
protection)
Mainboard indicators
Monitor display (LED1~LED5)
Yes
No Check if the
If the fault is eliminated? compressor is
normal.
Yes
Make records
correctly and report.
Tripping
If the switch
capacity meets
the requirement
Make records
correctly and report.
E5
主板指示灯 indicators
Mainboard
Monitor监控显示
display (LED1~LED5)
(LED1~LED5)
If如果散热器脏堵,
the radiator is dirty or
If the radiator is dirty blocked, the radiation
散热器是否脏堵? 会使散热器散热效
or blocked? effect will become poor.
果变差
If the IPM
IPM模块和 If如果IPM模块或PFC
the IPM or PFC
module and module is not correctly
模块不打紧,会使
PFC
PFC模块是 module tightened, it may cause
are correctly 模块温度过高,甚
overheating of module or
否打紧?
tightened?
至烧毁模块
even burn.
If如果散热硅胶涂覆
the silicate gel is
If the silicate gel on IPM coated too thick, it will
IPM模块好PFC模块
module or PFC module 太厚,也会影响散
meets the also affect the radiation
热效果,甚至烧毁
硅胶是否满足要求? effect or even burn the
requirements? 模块
module.
请检查感温包是否失
Please check if the
temperature
效,或者重新安装模块 sensor
fails, or reinstall the
并打紧
module and tighten it.
Make records
如实记录并反馈
correctly and report.
Mainboard indicators
Monitor display (LED1~LED5)
No
Possible problem:
1. The temperature of PFC module is too high. Please check if the
PFC module is correctly tightened.
2. Input AC overcurrent protection. Please check if the voltage of
electric grid is too low.
3. The system is abnormal. Please check if the compressor or
system pressure is normal.
Mainboard indicators
Monitor display (LED1~LED5)
Yes
If the compressor is
started to run?
Yes No
1. Use monitor software to judge if the bus voltage De-energize for 1 minute and then check according
is normal? The normal voltage is 380V±10V. If to the following steps:
not, it is the fault of PFC board or its wiring fault. 1. Measure if the IPM module is damaged.
2. If the DC bus voltage is normal, de-energize for 1 Method: Remove the UVW wiring of the
minute and then check according to the following compressor and use multimeter to measure
steps: the resistance U-N, V-N, W-N, P-U, P-V and
1) Check if the screw fixing IPM module is P-W on inverter. It is normal if the resistance is
properly tightened. If not, it might result in over 1MΩ; otherwise the module is damaged
module overtemperature or IPM protection. and it is needed to replace the inverter.
2) If the screw fixing IPM module is properly 2. If the test in Step 1 shows that the IPM module
tightened, please check if +15V voltage of pin is normal, check the inverter and test the
CN11 on power board is stable. If lower than resistor RS1 ~ RS6 for any damage, e.g.
13.5, it can be determined that the power broken pin or burnt mark. If any, replace the
board has fault. Please replace the power inverter.
board. 3. If the tests in both Step 1 and Step 2 show that
3) If the above problems have been eliminated, it is normal, please check if +15V voltage of pin
check if the outdoor unit is well ventilated. If CN11 on power board is normal (The inverter
the outdoor temp. is too high under cooling can work normally only when this voltage is
mode, it may cause IPM protection due to higher than 13.5V). If not, replace the power
poor radiation of IPM module. board; otherwise, replace the diverter. Finish
4) Check if the radiator is dirty or blocked. If dirty the check and connect the wire properly.
or blocked, it may cause protection due to Re-energize the unit to start it again.
poor radiation of the module.
No Check if the
If the fault is eliminated? compressor is
normal.
Yes
Make records
correctly and
report.
Tripping
If the switch No
capacity meets
the
requirements?
Yes
Install electric
Tripping switch according to
No Tripping occurs No the capacity
occurs upon after start of required in the
energization? compressor? instruction manual.
Yes Yes
The leakage
Check the PFC board. Cut off current is too high.
the power. Cut off the power Please check for
for 1 minute or drop the bus moisture or
replace the filter.
voltage to 36V or lower. Then, Yes No
remove the wiring on PFC PFC is on?
board and use multimeter to
measure the P-N, P-L1_2,
P-L2_1, L1_2-N or L2_1-N on
PFC board for short circuit. Check the PFC board. Cut off
the power. Cut off the power
for 1 minute or drop the bus
voltage to 36V or lower. Then,
remove the wiring on PFC
Yes No board and use multimeter to
Short circuit? measure the P-N, P-U, P-V,
P-W, U-N, V-N or W-N on PFC
board for short circuit.
Yes
AC contactor is
Replace PFC Check if the
damaged. Replace
inductance wiring is wrong.
with the same
contactor.
Make records
correctly and
report.
Generally, it is normal that the inductance will send out continuous and slight “ZHI ZHI” sound.
The abnormal noise of inductance refers to continuous “DU DU”, “PI PA” or “BI BI” sound easy to
hear by human ears. The possible reasons causing PFC inductance noise include:
● PFC fault
Abnormal
Noise of PFC
PFC电感异响
Inductance
Abnormal
压缩机开
noise upon
异响? of
start
compressor?
Yes
是
断电1分钟或
De-energize for 1
minute or drop the bus
母线电压降至
voltage to 36V or
36V以下后,
lower. Then, check
PFC 检查PFC板
board
If是否受潮、
wet, dirty or No
否
受污或器件
short
短路?
circuited?
是
Yes
Dry,烘干、清理污
clear off the dirt or
eliminate the short
物或清除短路
circuit. Reinstall and
start点,重新安装
to test.
并开机调试
No
否 Check the working
检查压缩机运
正常工作?
Work normally? status of
行状况
compressor.
是
Yes
Make records
如实记录并反馈
correctly and report.
E5
主板指示灯indicators
Mainboard
Monitor display
监控显示 (LED1~LED6)
(LED1~LED5)
请检查感温包是否
Please check if the
temperature
失效,或者重新安 sensor
fails, or reinstall the
装模块并打紧
module and tighten
it.
Make records
如实记录并反馈
correctly and
report
Manual
手操器显示E5
controller
Displays E5
(过流保护)
(Overcurrent
Protection)
主板指示灯indicators
Mainboard
Monitor监控显示
display (LED1~LED6)
(LED1~LED5)
DC Bus
直直直直直直 ON, ON, ON,
Overvoltage 亮亮亮亮闪亮
ON, BLINK,
直直直
Protection ON
是
Yes
是
Yes No
否
Does it1个小时内
occur repeatedly Does it occur upon
within 1 hour? 压缩机降频时出现?
reduction of compressor
出现多次? frequency?
Yes
是 No
否 Yes
是 No
否
Make records
如实记录并反馈
correctly and report.
Manual
手操器显示E5
controller
(过流保护)
Displays E5 E5
(Overcurrent
Protection)
主板指示灯 indicators
Mainboard
Monitor display
监控显示 (LED1~LED6)
(LED1~LED5)
DC
直直直直直 Bus ON, BLINK,
Undervoltage 亮闪闪亮闪亮
BLINK, ON,
直直直直
Protection BLINK, ON
是
Yes
Does it occur during
压缩机运行过程中 of
operation
compressor?
出现?
是
Yes No
否
Does it occur
1个小时内
repeatedly within 1 Does it occur upon
压缩机启动时出现?
start of compressor?
hour?出现多次?
是
Yes No
否 是
Yes No
否
PFC board is abnormal. Caused by interference. The input voltage is at the PFC board is abnormal.
PFC板异常。 输入电压处于低电压临界
lower limit. Please check if
PFC板异常。
1. Please check of the
1. Please check of the resistor R6, 干扰引起,请检查走线或
Please check the wire route
1、请检查PFC板上电压采样电路
R3 and R9 on voltage sampling or确定干扰源,并加强抗干
determine the source of 点,请检查电源线线径是
the wire diameter conforms 1、请检查PFC板上电压
resistor R6, R3 and R9 on
to requirements, or if the
否符合要求,或者线长是 voltage sampling circuit of
采样电路中的电阻R6、
中的电阻R6、R3、R9是否异常;
circuit of PFC board is abnormal. interference
扰措施
and take wire is too long thus
measures to prevent PFC board is abnormal.
2. Please check if the wiring on PFC
2、请检查PFC板与驱动板接线是 否太长以至于分压严重。
resulting into severe R3、R9是否异常;
2. Or replace the PFC
board and inverter is loose, broken interference. diversion of the voltage
否松脱或断路或接触不良;
or in poor contact.
2、或者更换PFC板。
board.
3、或者更换PFC板。
3. Or replace the PFC board.
Make records
如实记录并反馈
correctly and report
URT-60
ZB WZ863 Fig7
ZB Z814B Fig8
ZB WZ814A Fig9
主板指示灯
Mainboard indicators 驱动板指示灯
Inverter Board Indicators
(LED1~LED6)
(LED1~LED6) (LED1~LED3)
(LED1~LED3)
监控显示
Monitor display
断电1分钟或母线电
Cut off the power for 1 minute or 干扰引起的误判断,请
Wrong judgment caused by
drop the bus voltage to 36V or
压降至36V以下再上
lower. Then re-energize and
No
否 interference. Please check if
检查周围是否有干扰源
there is source of interference
start the unit to run for a period
of电,开机运行一段时
time. Check if the fault
或者电器盒内走线是否
nearby or if the wiring inside the
间后故障复现?
reoccurs? 规范 box is correct.
electric
是
Yes
If the compressor is
压缩机是否启动
started to run?
并运行?
是
Yes No
否
一、检查接线L1,L2,L3,N是否接对。
1. Check if the wiring on L1, L2, L4 and N is correct.
De-energize for 1 minute and then check according
二、用万用表检测输入电源质量,观察两
2. Use multimeter to test the quality of input power and check
to the following steps:
if there is significant fluctuation between two power cables.
两电源线之间是否有较大波动。 1. Measure if the IPM module is damaged.
3. If the above are normal, de-energize for 1 minute and then
二、若上述都正常,则断电1分钟后按如下
check according to the following steps: 断电1分钟后按如下步骤检查:
Method: Remove the UVW wiring of the
步骤检查:
1) Check if all the wires in inverter board are securely 1、测量IPM模块是否损坏,方法是:卸下
compressor and use multimeter to measure
fixed.
1、检查驱动板中的接线是否全部接牢固; 压缩机UVW三相接线和PN接线,用万用表
the resistance U-N, V-N, W-N, P-U, P-V and
2) Check if the screw fixing IPM module is properly
2、检查固定IPM模块的螺钉是否打紧,如
tightened. If not, it might result in module 电阻档分别测量驱动板的U-N、V-N、W-
P-W on inverter. It is normal if the resistance
未打紧,会引起模块温度过高或者IPM保
overtemperature or IPM protection. N、P-U、P-V、P-W间阻抗值,若在1MΩ
is over 1M Ω ; otherwise the module is
护; 3) Check if the silicate gel on the bottom of IPM module 以上则正常,否则模块坏,需更换驱动
damaged and it is needed to replace the
is evenly coated.
3、检查IPM模块底下的硅胶是否涂均匀;
4) Take special care to check if the pin seat of inverter
板; inverter.
4、特别检查驱动板U14模块针座是否接好
U14 module is correctly connected. 2、检查驱动板中的接线是否全部接牢固;
2. Check if all the wires in inverter board are
5、检查散热器是否脏堵,如果脏堵会引起
5) Check if the radiator is dirty or blocked. If dirty or 3、特别检查驱动板U14模块针座是否接好
securely fixed.
blocked, it may cause protection due to poor
模块散热不良而保护。 请更换驱动板;
3. Take special care to check if the pin seat of
radiation of the module.
6、如上述问题都已排除,则检查室外机通
6) If the above problems have been eliminated, check if
inverter U14 module is correctly connected.
风是否良好,在制冷时,室外温度太高会
the outdoor unit is well ventilated. If the outdoor NIf not, replace the inverter.
使IPM模块散热不良引起保护。
temp. is too high under cooling mode, it may cause
IPM protection due to poor radiation of IPM module.
If the fault is 否
No Check if the
检查压缩机是
故障排除?
eliminated? compressor is
否正常
normal.
是
Yes
Make records
如实记录并反馈
correctly and report
跳闸
Tripping
If the switch No
所接开关是否满足要
capacity meets the 否
求?
requirements?
是
Yes
Install electric
Tripping occurs 请按说明书
switch
Tripping occurs No
否 压缩机开启后才跳 No
否 要求安装电
upon上电就跳闸?
energization? after
闸?
start of according to
compressor? 是 气开关
instruction
manual.
是
Yes 是
Yes
Make records
如实记录并反馈
correctly and report
Manual
手操器显示E5
controller
displays E5
主板指示灯
Mainboard indicators 驱动板指示灯
Inverter Board Indicators
(LED1~LED6)
(LED1~LED6) (LED1~LED3)
(LED1~LED3)
监控显示
Monitor display
DC Bus Overvoltage ON, ON, ON,
直流母线电压过高保护 亮亮亮亮闪亮
ON,BLINK, ON,
Protection or DC Bus BLINK, BLINK,
或 or ON,或 BLINK, 闪闪灭
Undervoltage Protection BLINK, ON, ON
直流母线电压过低保护 亮闪闪亮闪亮
BLINK, ON
否
No
Yes
是 Fault occurs upon No
否
一上电就显示故障
energization. If压缩机开机后
it is displayed after
start才显示
of compressor.
是
Yes If the filter is If the filter is 是
Yes
滤波是否有损坏 滤波是否有损坏
damaged.
damaged.
否
No 否
No
是
Yes If the bridge rectifier If the AC contactor is 是
Yes
is 整流桥是否损坏
damaged 交流接触器是否卡死
clogged.
No
否 否
No
是
Yes 是
Yes
If the cement resistor If the capacitor fails.
水泥电阻是否短路 电容是否失效
is short circuited.
否
No 否
No
Yes
是 If驱动和模块是否接对
the inverter and No
否
module are correctly
wired. 线
Make records
如实记录并反馈
correctly and report
Fig. 3.4.3.3 Troubleshooting Process for DC Bus Overvoltage Protection and DC Bus
Undervoltage Protection
3.4.3.4 Radiator Overheating Protection
Manual
手操器显示E5
controller
displays E5
主板指示灯
Mainboard indicators 驱动板指示灯
Inverter Board Indicators
(LED1~LED6)
(LED1~LED6) (LED1~LED3)
(LED1~LED3)
监控显示
Monitor display
Yes
是
否
No
Make records
如实记录并反馈
correctly and report
Manual
手操器显示E5
controller
displays E5
主板指示灯
Mainboard indicators 驱动板指示灯
Inverter Board Indicators
(LED1~LED6)
(LED1~LED6) (LED1~LED3)
(LED1~LED3)
监控显示
Monitor display
Sensor
传感器连接保 BLINK, ON, ON, ON,
Connection 闪亮亮闪闪亮
ON. BLINK, 亮亮闪
护
Protection BLINK
BLINK, ON
否
No
否
No
If the compressor 是
Yes
压缩机绕组是否短
winding is short
circuited, or open circuit
路,对地断路
to the ground.
否
No
If IPM module is
Yes
是
IPM模块是否损坏
damaged.
No
否
更改相关部
Change relevant
更换驱动板
Replace the inverter.
件
components.
Make records
如实记录并反馈
correctly and report
Silkscreen Interface
AC-L Power Live Wire
AC-N Power Neutral Wire
CN12 Outdoor Ambient Sensor
CN14 Condenser Temp. Sensor
CN25 Exhaust Temp. Sensor
X2(LPP) LV Protection Switch
ZB1 WZ4D35 X4(OVC1) HV Protection Switch
ZB1 WZ4D15 X8(LVCC) Overload Protection Switch on Compressor
X11 4-way Valve
X13 AC Contactor
X15 Outdoor Fan
X16 Compressor with Electric Heater
CN17 Electronic Expansion Valve
CN65、CN66、CN67 Communication Wire
Fig 1 ZB1 WZ4D35, ZB1 WZ4D15 PCB Interface Diagram
Silkscreen Interface
X2 Power Live Wire
X1 Power Neutral Wire
CN4 Outdoor Ambient Sensor
CN6 Condenser Temp. Sensor
CN5 Tube Temp. Sensor
WZ4D35A X5﹑X6 Overload Protection Switch on Compressor
WZ4D15A X14 4-way Valve
X12﹑X13 Outdoor Fan
X8、X9、X10 Compressor Interface
X3、X4、X15、X24 PFC Inductance Interface
CN11 Electronic Expansion Valve
CN8、CN9、CN10 Communication Wire
Fig 2 Interface Diagram for Mainboard 50 or Below
Silkscreen Interface
X1 DC-BUS(+)
X2 DC-BUS(-)
J8 Capacitance Positive
J7 Capacitance Cathode
J3 AC-L
J4 AC-N
X1 PFC Interface
X5 Capacitance Positive
X6 Capacitance Negative
X4 AC-L
X2 AC-N
X1 DC-BUS(+)
X2 DC-BUS(-)
X3 Compressor Interface
LED
Connect to
Z814B PCB
CN8
Silkscreen Interface
P To DC bus, for measuring the Vdc.
CN15 Power supply from switch power
U14 Quick connector of module
CN1 Power supply from switch power
485 communication, for communicating
WZ863
with main control board (Different
CN8,CN9,CN3
interface shall be selected if matched to
different main control boards)
CN11 Power 220V
CN2 AC contactor control interface
IU To U-phase current sensor
IV To V-phase current sensor
CN17 Radiator Temp. Sensor
Fig.7 Three-phase Inverter (ZB WZ863) Interface Diagram
Connect to
WZ863
PCB CN1
Power N
Power L Connect to
WZ863 PCB
CN15
Silkscreen Interface
X1 Live Wire
X2 Neutral Wire
Z814B CN8 To 14-cord Wire
CN3 To 3-cord Wire
Fig8 ZB Z814B Interface Diagram
用 FinePrint 打印 - 可在 www.fineprint.com.cn 订购
Power Out N L3 L2 L1
GND
Power IN N L3 L2 L1
Silkscreen Interface
AC_L1 Inlet L1
AC_L2 Inlet L2
AC_L3 Inlet L3
N Inlet N
L1_OUT Outlet L1
WZ814A
L2_OUT Outlet L2
L3_OUT Outlet L3
N_OUT Outlet N
Fig9 ZB WZ814A Interface Diagram
3 Installation and Debugging
Fig.3-1-1
The unit shall so installed that enough space shall be maintained around to ensure good
air return and heat radiation. To ensure proper operation of the unit, the selection of
installing position must be in strict accordance with the following principles:
◆The outdoor unit shall be installed at a position where the exhaust air will not flow back.
Around the machine, maintain enough space for repair work.
◆ The install position must be well ventilated so that the machine can suck and discharge
enough air. Ensure there is no obstruction at the air inlet and outlet of the machine. If any,
remove the obstructions blocking the air flow.
◆ The installing position shall be strong enough to support the weight of outdoor unit.
Sound insulation and shock absorption shall be provided. Make sure that the outlet air
and noise from the unit will not affect the neighbor.
◆ The outdoor unit must be lifted from the designated hoisting hole. During lift, take care
to protect the machine. To prevent rusting in the future, it is prohibited to damage the
plating parts.
◆Avoid direct sunshine.
◆The installing positions must be able to drain the rainwater and defrost water.
◆ The installing position shall ensure that the machine will not be buried under the snow
or affected by wastes or oil fog.
◆ To meet the noise and vibration requirements, install the outdoor unit with rubber
damping cushion or spring damper.
◆The installation size shall conform to the specification. The outdoor unit must be fixed at
the position where it is installed.
The installation shall be carried out by professional technicians.
3.1.2 Precautions on Installation of Outdoor Unit
1) Fix the outdoor unit with M10 bolts and nuts if it is installed on solid ground like
concrete. And ensure that the outdoor unit is vertically standing and well leveled.
2) Do not install the unit at the top of the construction.
3) If noise is heard from vibration, please add rubber cushion between outdoor unit and
installation base.
4) When operating under heating or defrosting mode, the outdoor unit shall be provided
with water drainage treatment.
5) To install the water drainage pipe, please insert the drainage connector to the
drainage hole on the chassis of outdoor unit and then connect a drainage hose to the
drainage connector. (If drainage connector is used, the installing height of outdoor
unit shall be 5cm at least).
3.1.3 Installation of Connection Pipe
Selection of connection pipe, as shown in Table 3-1
Table 3-1
Item Pipe Size (mm) Max. Max. Height Difference Additional Refrigerant
Pipe between Indoor and (Excessive Length of
Model Liquid Pipe
Gas Pipe Length (m) Outdoor Unit (m) Pipe)
管 (管长超标部分)
URS-09 1/4" 3/8" 20 15 15
URS-12
1/4" 1/2" 20 15 20
URS-18
The layout of connection pipes shall be based on site conditions in reference to the
following principles:
4. If the connection pipe is longer than 20m, it is needed to check if the lubricating oil of
5. The refrigerant quantity inside this unit is suitable to connecting pipe 7m long. If the
accordingly. For each increase of the pipe length by 1m, the quantity of refrigerant to
outdoor units is more than 10m, one oil return elbow shall be installed every 6 meters.
The height of indoor unit is different from that of outdoor unit, please arrange the pipes
Outdoor unit
pipeGas Pipegas
One oil elbow
Pipegas PipeGas Pipe
every 4~6m
Oil-kept bend of gas
pipe
Indoor unit
Outdoor unit higher than indoor unit
Fig. 3-1-2
1) Connection of Pipe
Fig. 3-1-3
b) Align the flare of copper tube with the center of threaded connector and
adequately tighten the flaring nut with your hands.
c) Use torque wrench to tighten the flaring nut until a “KA TA” sound is heard, as
shown in Fig. 3-4. The torque for tightening of nut is shown in 3-1-5.
Gas 1-way
Liquid valve valveGa valve
s valve
Indoor pipe Flaring nut Pipe
Valve
cap
Valve
Inner hexagonal stem
Screwdriver
wrench
Wrench Torque wrench
d) The bend of pipe shall not be too small; otherwise the pipe might be cracked.
Please use pipe bender to bend the pipe.
e) The pipe shall be welded by facing the joint upward or horizontally. Avoid facing
the pipe opening downward during weld (The downward welding is easy to
cause defect and affect quality, or even cause leakage).
Fig. 3-1-6
f) Use sponge to wrap the connection pipe and connectors and tie with plastic
tapes.
压力计
Pressure gauge 压力计
Pressure gauge
"LO"旋钮
LO Knob "HI"旋钮
HI Knob
液阀
Liquid valve
Vacuum
真空泵pump
连接软管 hose
Connection
气阀valve
Gas
Fig. 3-1-7
3) Installation of Protective Sheath on Connection Pipe
a) To avoid condensing or leakage on connection pipe, the gas pipe and liquid pipe
must be insulated from the air by wrapping with hat insulation and adhesive
tapes.
b) The connector to indoor unit shall be wrapped by heat insulation materials to
ensure no clearance with the wall of indoor unit, as shown in Fig. 3-1-8.
No
无间隙clearance
c) Use adhesive tape to bundle the connection pipe and cable together. To avoid
outflow of condensate water from the drainage pipe, the drainage pipe shall be
separated from connection pipe and cable.
d) Wrap heat insulation tape from the bottom of outdoor unit until the upper end of
the pipe is deep into the wall. When wrapping the heat insulation tape, please
compress each circle to half of the previous circle, as shown in Fig. 3-1-9.
e) Use the pipe clamp to fix the wrapped pipe onto the wall.
Note: 1. After the pipe is properly protected, never bend the pipe to a very small angle;
otherwise the pipe might be cracked or broken.
2. Wrapping of the protective tape too tight may reduce the heat insulation
effect. Make sure that the condensate drainage pipe is separated from the
pipe bundle.
3. After completing the protection work and wrapping the pipe properly, use
sealing materials to seal the holes in the wall, thus to prevent rain from
invasion into the room.
Heat insulation materials for air connector 1 For gas pipe connector of indoor unit
Heat insulation materials for liquid connector 1 For liquid pipe connector of indoor unit
Heat insulation materials for drainage pipe 2 For condensate water pipe and rubber plug
Nut M8 with washer 8 For fixing the hook
String 4 or 8 pcs 4 pcs for 2hp unit and 8 pcs for others
Wired Controller 1
Remote controller 1
Battery 2
0 for 2hp unit, 2 pcs for 2.5-3hp unit and 4
Corrugated pipe 0, 2 pcs or 4 pcs
pcs for 4-5 hp unit
Power cable 1-2 pcs 2 pcs for 4-5 hp unit and 1 pc for others
Connection wires 2-3 pcs 3 pcs for 4-5hp unit and 2 pcs for others
Indoor Unit
Fig. 3-2-1
3.2.3 Installation of Indoor Unit
3.2.3.1 Select the location of installation
1) Ensure that the top hanger frame has enough strength to support the weight of
the unit.
2) The drainage pipe shall be easy to drain water.
3) There shall be no obstacle at the inlet and outlet so as to keep the air in good
circulation.
4) Ensure the space needed for installation, repair and maintenance works.
5) Select a place far from heat source, flammable gas or smoke.
6) The machine is ceiling mounted (Concealed installed in the ceiling).
7) The indoor unit, outdoor unit, power cord and connection cable shall be kept 1m
at least from the TV set or radio. This is to prevent image interference and noise
on above appliances.
3.2.3.2 Installation of Air Conditioner Body and Check of Indoor Unit Level
1) Install the expansion bolt
Drill four holes (Dia. 10mm approx.) on the ceiling. Refer to Fig. 3-2-2 for the spacing
between the holes. Insert M10 expansion bolt into the hole and then punch the iron nail
into the bolt as shown in Fig. 3-2-3.
吊装螺钉
Mounting screw 机组
Unit
挂钩
Hook
螺杆
Screw rod
挂钩
Hook
螺母
Nut
Air 送风口
outlet 螺母
Nut
Fig. 3-2-4
≤48mm
Fig. 3-2-5
Fig. 3-2-6
3.2.3.3 Installation of Duct
1) Install the rectangular duct. See Fig. 3-2-7
1 3 6
2
回风
Air Intake Air 回风
Intake Air 送风
Outlet
3
5 7
4
Fig. 3-2-7
S/N Description S/N Description
1 Hanger Bar 5 Filter
2 Intake Pipe 6 Main Outlet Pipe
3 Canvas Duct 7 Air Outlet
4 Air Intake
2) Install the round duct. See Fig.3-2-8
1
2
3
4 5 6 7 8 9
S/N Description S/N Description
1 Hanger Bar 6 Transition Duct
2 Intake Pipe 7 Air Outlet Pipe
3 Canvas Duct 8 Diffuser
4 Intake Louver 9 Diffuser connector
5 Air Outlet
Fig. 3-2-8
Note: Shown above is the installation of rear air intake. Bottom air intake may be used
according to the needs of actual installation. The installation method is similar to that of
rear air intake. In all intake pipes, at least one shall be kept open. Round duct may also be
adopted and round heat insulation hose may be used to blow the air to each room. Heat
insulation shall be provided for both outlet pipe and intake pipe.
3.2.3.4 Installation of Fresh Air Pipe (Limited to extra residual pressure unit with a
cooling capacity over 6000W)
1) To connect the fresh air pipe, cut off the fresh air baffle firstly, as shown in Fig. 3-2-9
(a). If fresh air pipe is not required, use sponge to seal the seam on fresh air baffle.
2) Mount a round flange for connection of fresh air pipe. See Fig. 3-2-9 (b).
3) Both the duct and round flange need good sealing and heat insulation.
4) The fresh air shall be filtered air.
去除 Round Duct
Remove 圆形风管
新风挡板
Fresh air baffle
去除
Remove
(a) (b)
Fig. 3-2 -9
3.2.3.5 Installation of Intake Pipe
1) The square flange is factory mounted at the rear part, while the cover of air intake is
后部回风
Rear Air Intake
下部回风
Bottom Air Intake
回风盖板
Air Intake Cover Plate
Fig. 3-2-10
2) If bottom air intake is required, just change the position of square flange and air intake
cover.
3) Rivet the intake pipe to the air intake of indoor unit and another end to the intake
window. For free adjustment of the height, you may fabricate a section of canvas duct
and reinforce with 8# iron wires in folded form. The user may select the installation
method in unified consideration of the constructions and maintainability. See Fig.
3-2-11.
5 4 5 3
送风 2 送风
Air Outlet Air Outlet
4 6 1 回风
1 Air Intake
回风
Air Intake
Fig. 3-2-11
Roof
Hoisting stand
Within 300mm 1-1.5m below280mm
Drain hose
below500mm
Drain raising
.
hose
220mm
.
Ceiling Clamp(attachment)
管盖
Pipe Cove
Fig. 3-5-1
wire.
2) For open installation of the communication wire between Wired Controller (85 X 85
X16) and indoor unit, you may use 1# PVC pipe and set up an appropriate groove in
the wall (See Fig. 3-5-2(a)). For concealed installation, you may use 1#PVC pipe
3) Fig. 3-5-3 shall be followed no matter for open installation or for concealed installation.
Firstly, refer to the spacing of mounting holes (60mm) on the base panel of Wired
Controller and drill 2 holes (kept level) in the wall. Then, knock a wood plug into each
hole and fix the base panel of Wired Controller onto the wall. After that, insert the
communication wire into the control board. Finally, cover up the front panel of Wired
Controller.
Note:
When installing the base panel of Wired Controller, take special care on the direction of
base panel. The side with 2 notches must face downward; otherwise it will be impossible
to mount the Wired Controller panel correctly.
PVC管
PVC Pipe
1 2 3 4
S/N Description
1 Wall
2 Base Panel of Wired Controller
3 Screw M4X10
4 Front Panel of Wired Controller
A.单支线
Single-cord wire B.多股绞合线
Stranded wire
接线端子
Terminal
25
10
绝缘层Layer
Insulation
Fig. 3-5-4
Notes:
a) If the power cord or signal wire is damaged, be sure to replace with special cord.
b) Please identify the voltage indicated on the nameplate before starting cable
connection according to the wiring diagram.
c) The air conditioner shall be provided with special power cable and equipped with
leakage switch and air switch to respond to any overloading.
d) The air conditioner must be properly earthed to avoid the harm caused by
insulation failure.
e) All wires must be connected via press terminal or single wire. Direct connection
of stranded wire to the terminal board may cause spark.
f) All cables shall be correctly connected in accordance with the wiring diagram.
Wrong connection may cause malfunction or damage to the air conditioner.
g) Prevent the cables from contacting the refrigerant pipe, compressor, fan or other
moving parts.
h) Do not change the cable connection inside the air conditioner. The manufacturer
is not liable for any loss or abnormal operation thus arising.
3.5.4 Connection of Power Cable
1) For air conditioner using 1-phase supply:
a) Remove the front side plate of outdoor unit.
b) Open the cable-cross hole of outdoor unit and mount a rubber ring.
c) Insert the cable through rubber ring.
d) Connect the power cable to “L”, “N” terminals and earth screw.
e) Fix the cable with tie strap.
2) For air conditioner using 3-phase supply:
a) Remove the front side plate of outdoor unit.
b) Open the cable-cross hole of outdoor unit and mount a rubber ring.
c) Insert the cable through rubber ring.
d) Connect the power cable to “L1”, “L2”, “L3”, “N” terminals and earth screw.
e) Fix the cable securely with cable clamp.
Notes: For the air conditioner with auxiliary electric heater, the power cable shall also be
connected to “L1” , “L2”, “L3”, “N” terminals and earth screw in the electric box of indoor
unit.
3.5.5 Connection of Wired Controller Signal Wire
1) Open the electric box of indoor unit.
2) Insert the Wired Controller signal wire through the rubber ring.
3) Insert the Wired Controller signal wire into the 4-bit seat.
4) Fix the signal wire of Wired Controller tightly with tie strap.
Notes:
a) To prevent the air conditioner from malfunction due to electromagnetic
interference, be sure to take special care when performing the cable connection
below.
b) The signal wire of Wired Controller shall be separated from power cable and
indoor/outdoor connection cable.
c) If the air conditioner is installed at a place subject to electromagnetic interference,
it is best to use the shield wire and twisted pair as the signal wire of Wired
Controller.
3.5.6 Cable Connection
1) Remove the right side plate of outdoor unit and open the cable-cross hole. Install the
cable-cross loop.
2) Remove the cable clamp. Connect the power cable to the terminals and fix.
3) Use wire clamp to fix the power cable and signal control wire. Then, connect
correctly.
4) Check if the cable is properly fixed.
5) Reinstall the front side plate.
3.5.7 Drainage of Outdoor Condensate Water (No for cooling-only unit)
When the air conditioner is working under HEAT mode, the condensate water generated
by the outdoor unit and the defrosting water during defrosting mode operation will be
drained to a proper place via drainage pipe.
How to Install: Clamp the outdoor drainage connector to φ25 hole on the base, as shown
in Fig. 3-5-5. Then, connect the drainage pipe to drainage nozzle, so that the condensate
water and defrosting water can be drained to an appropriate place.
室外机底板
Outdoor Base Plate
室外机接头
Outdoor Connector
Fig. 3-5-5
3.5.8 Precautions on Installation
1. Follow the illustrated requirements to ensure there is enough space and good
ventilation for operation, repair and maintenance of the unit.
2. Drainage ditch shall be provided on the ground of outdoor unit.
3. To meet the restrictions of noise and vibration, the outdoor unit shall be installed with
rubber damping cushion, spring damper or rubber connector.
4. The beam and frame to lift the indoor unit shall be able to support 4 times the weight.
The bolts, caps and other fasteners shall be subjected to antirust treatment. Soft
connector shall be added at the connection of duct, thus to reduce the vibration.
5. The duct shall be designed in reference to data provided in the data sheet and the
computation method described in Part 1 of this manual. Heat insulation and sound
insulation shall be provided. It is recommended to use air flow regulation valve to
adjust the air flow at different positions of the air outlet system, making the unit run
under optimum state.
6. Be sure to lift the indoor and outdoor unit by using the designated lifting holes. During
lift, take care to protect the unit and avoid knocking the plates, thus to prevent possible
rusting in the future.
7. INVENTOR will not provide the copper tube, power cable and signal wire. Please
prepare according to technical parameters, and connect the pipe, power supply and
circuits correctly.
8. The unit must be tested by professional technicians or the user’s people with air
conditioner knowledge under the instructions of INVENTOR’s professional
technicians.
9. Before installing the indoor and outdoor connecting pipe, do not remove the plug
sealing the pipe.
10. To prevent dust or moisture entering into the system, connect the pipe quickly after
removing the seal plug.
11. The pipe must be installed in a wall-cross tube when passing the wall.
12. The shorter the connecting pipe is, the better. The smaller the height difference
between indoor unit and outdoor unit is, the better. The fewer the pipe bends, the
better. The bending radius shall be as large as possible.
13. When laying the pipes along the designated route, do not flatten the pipe. The
bending radius must be over 200MM. The connecting pipe shall not frequently bent or
stretched; otherwise it will become hardened. One pipe shall not be bent at the same
position over 3 times the maximum.
3.5.9 Precautions on Installation of Indoor Condensate Pipe
It is usually found that the condensate water of duct type air conditioner cannot be drained
out. Through our investigation and analysis, it is because the relative high-speed air flow
generated under negative pressure inside the unit that disturbs the normal drain of
condensate water. Therefore, we need to install a section of water seal at the drainage
outlet.
As shown in Fig. 3-5-6, the height of water seal depends on the pressure inside the
section where the condensate pipe is located.
P
When the section of condensate pipe is under negative pressure, h=x≥ 10 +20(mm)
Unit
To condensate pipe
3. The condensate pipe shall be kept an inclination 5~10° for easier drain of
During test, check if the water flows through the pipe correctly. Check the
of the ceiling.
3.5.10 Trial Run and Checks after Installation
Trial Run
1) Preparations for Trial Run
a) Do not connect to the power supply unless all installation works has been
completed.
b) The control circuit is correctly connected and all cables are fixed securely.
c) The valve of gas pipe and liquid pipe shall be open.
d) All scattered articles, especially the metal scraps and threads, shall be removed
from the unit.
2) Method of Trial Run
a) Switch on the power and press the ON/OFF button on the remote controller to
start the test run.
b) Press MODE button and select COOL, HEAT and FAN mode to check if the run
is normal.
c) Emergency run.
Table 3-4
If the installation is secure? The unit may fall, vibrate or give out noise
If the refrigerant pipe length and refrigerant fill are recorded? Unable to control the quantity of refrigerant filled
3.6 Electric Installation
Working environment of electrical devices:
☆Be sure the electric supply that user applies is beyond the bounds of tolerances
(+/-10%, +/-1Hz).
☆The ambient temperature should be at 5-40°C ,and the humidity be at 30-95% .
☆Transport/storage temperature should be at -25-55°C and for short period not
exceeding 24h at up to +70°C.
☆ The installation altitude beyond the hight of 1000m.
Cautions on Electric Installation:
Caution: Before installing the electrical equipment, please pay attention to the
following matters which have been specially pointed out by our
designers:
(1) Check to see if the power supply used conforms to the rated power supply
specified on the nameplate.
(2) The capacity of the power supply must be large enough. The section area of
fitting line in the room shall be larger than 2.5mm2.
(3) The lines must be installed by professional personnel.
An electricity leakage protection switch and an air switch with gap between electrode
heads larger than 3 mm shall be installed in the fixed line.
1. Connection of single wire
(2) Use wire stripper to strip the insulation layer (25mm long) from the end of the
single wire.
(3) Remove the screw at the terminal board of the air-conditioning unit.
(4) User pliers to bend the end of the single wire so that a loop matching the
screw size is formed.
(5) Put the screw through the loop of the single wire and fix the loop at the
terminal board.
2.Connection of multiple twisted wires
(1) Use wire stripper to strip the insulation layer (10mm long) from the end of the
multiple twisted wires.
(2) Remove the screw at the terminal board of the air-conditioning unit.
(3) Use crimping pliers to connect a terminal (matching the size of the screw) at
the end of the multiple twisted wires.
(4) Put the screw through the terminal of the multiple twisted wires and fix the
terminal at the terminal board.
Warning:
If the power supply flexible line or the signal line of the equipment is damaged, only
use special flexible line to replace it.
1. Before connecting lines, read the voltages of the relevant parts on the
nameplate. Then carry out line connection according to the schematic
diagram.
2. The air-conditioning unit shall have special power supply line which
shall be equipped with electricity leakage switch and air switch, so as to
deal with overload conditions.
3. The air-conditioning unit must have grounding to avoid hazard owing to
insulation failure.
4. All fitting lines must use crimp terminals or single wire. If multiple
twisted wires are connected to terminal board, arc may arise.
5. All line connections must conform to the schematic diagram of lines.
Wrong connection may cause abnormal operation or damage of the
air-conditioning unit.
6. Do not let any cable contact the refrigerant pipe, the compressor and
moving parts such as fan.
Do not change the internal line connections inside the air-conditioning
unit. The manufacturer shall not be liable for any loss or abnormal
operation arising from wrong line connections.
7. shall not be liable for any loss or abnormal operation arising from wrong
line connections.
H.Power Cord Connection Caution:
For air-conditioner with auxiliary
1. Air-conditioning unit with single-phase power supply heater, it is required to connect the
power cable to the “L1, L2 L3
(1) Remove the front-side panel of the outdoor unit.
“ terminals and the grounding screw.
(2) Pass the cable though rubber ring.
(3) Connect the power supply cable to the “L, N” terminals and
(3) Pass the cable though rubber ring. connecting line between the indoor unit and
the outdoor unit.
(4) Connect the power cable to the terminal and earthing
(2) In case the unit is installed in a place
screws marked “L1, L2, L3 & N”. vulnerable by electromagnetic interference, it
is better to use shielded cable or
(5) Use cable fastener to bundle and fix the cable.
double-twisted cable as the signal line of the
I.Connection of Signal Line of Wire Controller wire controller.
2. Pull the signal cable of the wire controller through the rubber ring.
3. Plug the signal line of the wire controller onto the 4-bit pin socket at the circuit board
4. Use cable fastener to bundle and fix the signal cable of the wire controller.
Wiring layout
☆Installation should be conducted by National Wiring Regulation.
☆The rated voltage and exclusive power supply must be adopted for the air conditioners.
☆ The power cable should be reliable and fixed, in order to avoid the wiring terminal be
suffered from force. And do not drag the power cable forcibly.
☆ The wire diameter of power cable should be large enough, if power cable and
connection wire
be damaged, it should be replaced by the exclusive cable.
☆All electric installation must be done by professional personnel according to local law,
regulation and this manual.
☆It should be reliably earthed, and it should be connected to the special earth device, the
installation work should be operated by the professional.
☆The creepage protect switch and air switch must be installed.
Air switch should have the thermal dropout and magnetic dropout function, in order to
avoid the short circuit and overload.
☆ The on spot connection should refer to the circuit diagram, which is stuck on the unit
body.
Below is the recommended air switch capacity for related power cable diameters (For the
diameter of power cables for each unit, please see the attached instruction manual).
Dia. Of
Dia. Of Power Air Switch Capacity Air Switch Capacity
Power
Cable (A) (A)
Cable
2.5mm2 16A 4 mm2 20A
2 2
6 mm 25A;32A 10 mm 40A
2 2
16 mm 50A 25mm 63A
Condition for model selection above: The specification of power cable refers to the
specification of the BV single-cord cable (2 – 4 pcs) is paved in plastic pipe and used
under an ambient temperature of 40℃. The air switch is used under 40℃ and the type
of air switch is “D”. In case of any change in the actual installation conditions on site,
please follow the specifications of power cables and air switch provided by the
manufacturer and use for reduced capacity.
● Requirement for ground
☆ Air conditioner is the I class electric appliance, thus please do conduct reliable
grounding measure.
☆ The yellow-green two-color wiring of air conditioner is grounding wire and can not be
used for other purposes. It cannot be cut off and be fixed by screw, otherwise it would
cause electric shock.
☆ The user must offer the reliable grounding terminal. Please don’t connect the
grounding wire
to the following places:
① Water pipe;
② Gas pipe;
③ Blowing pipe;
④ Other places that professional personnel consider them unreliable.
Power Supply to Indoor and Outdoor Unit:
The power cable, communication wire connection between indoor and
outdoor
The power distribution for complete unit is as follows. The actual connection of earthing
wires shall be based on the circuit diagram attached on each unit.
Single-phase Outdoor Unit:
Three-phase Outdoor Unit: 5
Circuit Diagram:
Outdoor Unit:
URS-09¬ (Compatible with 09-18 Ceiling-seated and Duct Type Unit and 18 Well Type Unit):
URS-24 (Compatible with 24 Ceiling-seated and Duct Type Unit and Well Type Unit):
URS-36~50 (Compatible with 36-48 Ceiling-seated and Duct Type Unit and Well Type Unit):
URT-36~60 (Compatible with 36-60 Ceiling-seated and Duct Type Unit and Well Type Unit):
Indoor Unit:
Duct Type Indoor Unit:
VDI-09~60 (Except 18):
VDI-18
Note: The bold line indicates the main circuit and the fine line indicates the control circuit.
The element on actual model shall be based on the actual circuit diagram.