KCD RR Manual
KCD RR Manual
KCD RR Manual
KCD2-RR2-Ex1
< 1-channel isolated barrier
< 24 V DC supply (Power Rail)
< Resistance and RTD input (Pt100, Pt500, Pt1000)
< Resistance output
< Accuracy 0.1 %
< Line fault detection (LFD) for Pt100
< Housing width 12.5 mm
< SIL 2 (SC 3) acc. to IEC/EN 61508
Function
Connection
KCD2-RR2-Ex1
4+ 6+
3+ 8+ mA
1- 7-
2- 5-
9+
10-
24 V DC
Zone 0, 1, 2 24 V DC Zone 2
Release date: 2021-12-13 Date of issue: 2021-12-13 Filename: 314455_eng.pdf
Technical Data
General specifications
Signal type Analog input
Functional safety related parameters
Safety Integrity Level (SIL) SIL 2
Systematic capability (SC) SC 3
Supply
Connection Power Rail or terminals 9+, 10-
Rated voltage Ur 19 ... 30 V DC
Ripple within the supply tolerance
Rated current Ir < 28 mA
Power consumption 0.35 W (24 V and 1 mA sense current), 0.85 W (30 V and 10 mA sense current)
Ambient conditions
Ambient temperature -40 ... 70 °C (-40 ... 158 °F)
Mechanical specifications
Degree of protection IP20
Connection screw terminals
Mass approx. 100 g
Dimensions 12.5 x 119 x 114 mm (0.5 x 4.7 x 4.5 inch) (W x H x D) , housing type A2
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificate BASEEFA 10 ATEX 0061X
Marking 1 II (1)G [Ex ia Ga] IIC
1 II (1)D [Ex ia Da] IIIC
1 I (M1) [Ex ia Ma] I
Input [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Voltage Uo 9.5 V
Current Io 39.22 mA
Assembly
Front view
Removable terminals
blue
1 2 LED green:
3 4
Power supply
KCD2-RR2-
Ex1
PWR
Release date: 2021-12-13 Date of issue: 2021-12-13 Filename: 314455_eng.pdf
S1
I II
Switch S1
5 6
7 8
9 10
Removable terminals
green
UPR-03 Universal Power Rail with end caps and cover, 3 conductors, length: 2 m
UPR-03-M Universal Power Rail with end caps and cover, 3 conductors, length: 1,6 m
UPR-03-S Universal Power Rail with end caps and cover, 3 conductors, length: 0.8 m
K-DUCT-BU-UPR-03 Profile rail with UPR-03- * insert, 3 conductors, wiring comb field side, blue
Accessories
KC-ST-5GN Terminal block for KC modules, 2-pin screw terminal, green
Configuration
PWR
S1
I II
S1
I II
Switch position
Additional Information
Function
When a signal converter, a DCS or PLC is connected to terminals 5, 6, 7, and 8 (control side), the measuring current is
transferred to terminals 2 and 4 (field side). The resulting voltage at terminals 1, and 3 is transferred to terminals 5, 6, 7, and 8.
In the case of fast multiplex input cards, transmission problems might be experienced in connection with low resistance values
and/or high sensor currents. For data see rise time.
The quoted accuracy is for a 4-wire technique connection. The accuracy in 3-wire technique will depend on the matching of the
line resistance.
8 6 5 7 8 6 5 7 8 6 5 7 8 6 5 7
+ + - - + + - - + + - - + + - -
5
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
Resistance Repeater KCD2-RR2-Ex1
• 2-wire technique:
Link terminals 1 and 2 and terminals 3 and 4. Connect the resistance to terminal 4 and terminal 2. Switch S1 in the position II.
• 3-wire technique:
Link terminals 1 and 2. Connect the resistance to terminals 3 and 4 and terminal 2. Switch S1 in the position I.
• 4-wire technique
Connect the resistance to terminals 3 and 4 and terminals 1 and 2. Switch S1 in the position II.
Measurement range
The resistance repeater can convey a maximum of 10 mA and a maximum of 4.2 V. The maximum connectable resistance value
can be calculated with the following equation: resistance value = 4.2 V / measuring current
The measuring current is determined by control.
Measuring current
I (mA)
10
0.5
2 4 6 8 8.4 10 12 kΩ
Max. resistance
of sensor
6
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com