Data sheet 7KM4211-1BA00-3AA0

SENTRON, measuring device, 7KM PAC4200, LCD, L-L: 500 V, L-N: 289
V, 5 A, 3-phase, Modbus TCP, optional Modbus RTU / PROFINET /
PROFIBUS / DI/DO, apparent/active/reactive energy / cos phi, harmonics:
2.-64., THD, class 0.2 acc. to IEC61557-12 or cl. 0.2S acc. to IEC62053-
22, ext-low volt. pwr sup. unit DC, screw terminals

Model
product brand name SENTRON
product designation 7KM PAC4200
design of the product compact
product type designation Measuring instrument
Measurements
measuring procedure
● for voltage measurement TRMS
● for current measurement TRMS
type of measured value detection complete
voltage curve Sinusoidal or distorted
measurable line frequency
● initial value 45 Hz
● full-scale value 65 Hz
operating mode for measured value detection automatic Yes
line frequency detection
operating mode for measured value detection
● set at 50 Hz No
● set to 60 Hz No
Supply voltage
design of the power supply Extra-low voltage power supply unit
type of voltage of the supply voltage DC
Degree of protection protection class
protection class IP on the front IP65
operating resource protection class when installed safety class II
Suitability
suitability for operation Installation in stationary control panels in closed rooms
Product Functions
product function
● voltage measurement Yes
● current measurement Yes
● active power measurement Yes
● reactive power measurement Yes
● frequency measurement Yes
Display and operation
design of the display LCD
height of the display 54 mm
width of the display 72 mm
color of the background of the display white

7KM42111BA003AA0 Subject to change without notice


10/7/2021
Page 1/5 © Copyright Siemens
illuminance of display backlight adjustable Yes
time-controlled reduction of the illuminance of display Yes
backlight possible
display contrast adjustable Yes
national language on the display screen is supported ger, en, fr, spa, ita, por, tur, rus, chi, pol
number of keys 4
Communication
number of interfaces acc. to Fast Ethernet 1
type of electrical connection of the fast Ethernet interface RJ45 (8P8C)
protocol at the Ethernet interface is supported MODBUS TCP
transfer rate 1 for Ethernet 10 Mbit/s
transfer rate 2 for Ethernet 100 Mbit/s
Fault limits
reference condition for metering accuracy Acc. to IEC61557-12
formula for relative total measurement inaccuracy
● for measured variable voltage +/- 0,2 %
● for measured variable current +/- 0,2 %
● for measured variable output factor +/- 2 %
● for measured variable active energy Class 0.2 according to IEC61557-12 and/or class 0.2S according to
IEC62053-22
● for measured variable reactive energy Class 2 according to IEC61557-12 and/or IEC62053-23
Inputs Outputs
number of digital inputs 2
type of electrical connection at the digital inputs screw-type terminals
operating conditions for digital inputs external voltage Yes
supply
input voltage at digital input at DC maximum 30 V
number of digital outputs 2
type of switching output solid state
digital output version switching or pulse output function
operating voltage as output voltage at DC maximum 30 V
permissible
type of electrical connection at the digital outputs screw-type terminals
output current
● at digital output with signal <0> maximum 0.2 mA
● at digital output for signal <1> maximum 27 mA
● at the digital outputs at DC limited to 100 ms 300 mA
maximum
internal resistance at the digital outputs 55 Ω
standard for pulse emitter according to IEC62053-31
pulse duration
● initial value 30 ms
● full-scale value 500 ms
adjustable time period minimum 10 ms
switching frequency at digital output maximum 20 Hz
property of the output short-circuit proof Yes
measuring category for digital signals CATI
Measuring inputs
measurable supply voltage between (PE)N and L at AC 289 V
maximum rated value
measurable supply voltage between (PE)N and L at AC
● minimum 11.5 V
● maximum 346 V
measurable supply voltage between the line conductors at 500 V
AC maximum rated value
measurable supply voltage between the line conductors at
AC
● minimum 20 V
● maximum 600 V
voltage measuring range extension with external voltage yes
transformers
line conductors and neutral conductors internal resistance 1.05 MΩ

7KM42111BA003AA0 Subject to change without notice


10/7/2021
Page 2/5 © Copyright Siemens
for voltage measurement
measuring category for voltage measurement CATIII
measurable current
● 1 at AC rated value 1A
● 2 at AC rated value 5A
relative measurable current at AC
● minimum 1%
● maximum 120 %
current measuring range extension with external current yes
transformers
zero point suppression for current measurement 0 ... 10 %
measuring category for current measurement CATIII
Connections
type of connectable conductor cross-sections
● at the measurement inputs for voltage solid 1x (0.5 ... 4 mm²), 2x (0.5 ... 2.5 mm²)
● at the measurement inputs for voltage finely 1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
stranded with core end processing
● at the measurement inputs for voltage at AWG 2x 20 to 14
cables solid
● at the measurement inputs for current solid 1x (0.5 ... 4 mm²), 2x (0.5 ... 2.5 mm²)
● at the measurement inputs for current finely 1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
stranded with core end processing
● at the measurement inputs for current at AWG 2x 20 to 14
cables solid
type of electrical connection
● at the measurement inputs for voltage screw-type terminals
● at the measurement inputs for current screw-type terminals
Mechanical Design
fastening method standard rail mounting No
size of Power Monitoring Device size 96
height 96 mm
width 96 mm
depth 82 mm
installation depth 77 mm
net weight 537 g
mounting position vertical
Environmental conditions
ambient temperature during operation
● minimum -10 °C
● maximum 55 °C
ambient temperature during storage
● minimum -25 °C
● maximum 70 °C
relative humidity at 25 °C without condensation during 95 %
operation maximum
installation altitude at height above sea level maximum 2 000 m
degree of pollution 2
Certificates
certificate of suitability as EC Declaration of Conformity IEC 61010-1: 2001 (2nd Ed.) with Corr. 1, EN 61010-1: 2001 (2nd Ed.)
and DIN EN 61010-1:2002 with "Berichtigung 1"
reference code acc. to DIN EN 61346-2 P
General Product Approval EMC Declaration of Conformity other

UK Declaration of Confirmation
Conformity

other Dangerous Good

7KM42111BA003AA0 Subject to change without notice


10/7/2021
Page 3/5 © Copyright Siemens
Miscellaneous Dangerous Goods
Information

Further information
Information- and Downloadcenter (catalogues, leaflets,...)
http://www.siemens.com/energy-automation
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=7KM4211-1BA00-3AA0
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/7KM4211-1BA00-3AA0
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)
http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=7KM4211-1BA00-3AA0
CAx-Online-Generator
http://www.siemens.com/cax
Tender specifications
http://www.siemens.com/specifications

99
96 77
96

90

-P V1 V2 V3 VN L/+ N/- FE DIC DI1 DI0 DOC DO1 DO0


-X2 -X4
LAN

-X3

-X1 IL1/k IL1/l IL2/k IL2/l IL3/k IL3/l

7KM42111BA003AA0 Subject to change without notice


10/7/2021
Page 4/5 © Copyright Siemens
7KM42111BA003AA0 Subject to change without notice
10/7/2021
Page 5/5 © Copyright Siemens