Nothing Special   »   [go: up one dir, main page]

3UG46321AW30 Datasheet en

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

Data sheet 3UG4632-1AW30

Digital monitoring relay Voltage monitoring, 22.5 mm from 10 to 600


V AC/DC 0vershoot and undershoot 24 to 240 V AC/DC 50 to 60 Hz
DC and AC Noise pulses delay 0.1 to 20 s Hysteresis 0.1 to 300 V 1
change-over contact with or without fault buffer screw terminal
Successor product for 3UG3532-1AL20, 3UG3532-1AG20

Product brand name SIRIUS


Product designation Voltage monitoring relay with digital setting
Product type designation 3UG4

General technical data


Product function Voltage monitoring relay
Design of the display LCD
Insulation voltage
● for overvoltage category III according to IEC
60664
— with degree of pollution 3 rated value 690 V
Type of voltage
● for monitoring AC/DC
● of the control supply voltage AC/DC
Surge voltage resistance rated value 4 kV
maximum permissible voltage for safe isolation
● between auxiliary and auxiliary circuit 300 V
● between control and auxiliary circuit 300 V
Protection class IP IP20
Shock resistance

3UG4632-1AW30 Subject to change without notice


Page 1/5 02/08/2020 © Copyright Siemens
● acc. to IEC 60068-2-27 sinusoidal half-wave 15g / 11 ms
Vibration resistance
● acc. to IEC 60068-2-6 1 ... 6 Hz: 15 mm, 6 ... 500 Hz: 2g
Mechanical service life (switching cycles)
● typical 10 000 000
Electrical endurance (switching cycles)
● at AC-15 at 230 V typical 100 000
Thermal current of the switching element with 5 A
contacts maximum
Reference code acc. to DIN 40719 extended K
according to IEC 204-2 acc. to IEC 750
Reference code acc. to DIN EN 81346-2 K
Reference code acc. to DIN EN 61346-2 K
Relative repeat accuracy 1 %

Product Function
Product function
● undervoltage detection Yes
● Overvoltage detection Yes
● Overvoltage detection 1 phase Yes
● Overvoltage detection 3 phase No
● Overvoltage detection DC Yes
● undervoltage detection 1 phase Yes
● undervoltage detection 3 phases No
● undervoltage detection DC Yes
● Voltage window recognition 1 phase Yes
● Voltage window recognition 3 phase No
● Voltage window recognition DC Yes
● Adjustable open/closed-circuit current principle Yes
● External reset Yes
● Auto-reset Yes

Control circuit/ Control


Control supply voltage at AC
● at 50 Hz rated value 24 ... 240 V
● at 60 Hz rated value 24 ... 240 V
Control supply voltage at DC
● rated value 24 ... 240 V
Operating range factor control supply voltage rated
value at DC
● initial value 0.85
● Full-scale value 1.1
Operating range factor control supply voltage rated
value at AC at 50 Hz

3UG4632-1AW30 Subject to change without notice


Page 2/5 02/08/2020 © Copyright Siemens
● initial value 0.85
● Full-scale value 1.1
Operating range factor control supply voltage rated
value at AC at 60 Hz
● initial value 0.85
● Full-scale value 1.1

Measuring circuit
Measurable line frequency 40 ... 500 Hz
Measurable voltage at DC 10 ... 600 V
Adjustable response delay time
● with lower or upper limit violation 0.1 ... 20 s
Accuracy of digital display +/-1 digit
Relative temperature-related measurement deviation 0.1 %

Precision
Relative metering precision 5 %

Auxiliary circuit
Number of NC contacts
● delayed switching 0
Number of NO contacts
● delayed switching 0
Number of CO contacts
● delayed switching 1
Operating frequency with 3RT2 contactor maximum 5 000 1/h

Main circuit
Number of poles for main current circuit 1

Outputs
Operating current at 17 V minimum 5 mA
Continuous current of the DIAZED fuse link of the 4 A
output relay

Electromagnetic compatibility
Conducted interference
● due to burst acc. to IEC 61000-4-4 2 kV
● due to conductor-earth surge acc. to IEC 2 kV
61000-4-5
● due to conductor-conductor surge acc. to IEC 1 kV
61000-4-5
Field-bound parasitic coupling acc. to IEC 61000-4-3 10 V/m
Electrostatic discharge acc. to IEC 61000-4-2 6 kV contact discharge / 8 kV air discharge

Galvanic isolation
Design of the electrical isolation Protective separation

3UG4632-1AW30 Subject to change without notice


Page 3/5 02/08/2020 © Copyright Siemens
Galvanic isolation
● between entrance and outlet Yes
● between the outputs Yes
● between the voltage supply and other circuits Yes

Connections/ Terminals
Product function
● removable terminal for auxiliary and control Yes
circuit
Type of electrical connection screw-type terminals
Type of connectable conductor cross-sections
● solid 1x (0.5 ... 4 mm2), 2x (0.5 ... 2.5 mm2)
● finely stranded with core end processing 1x (0.5 ... 2.5 mm2), 2x (0.5 ... 1.5 mm2)
● at AWG conductors solid 2x (20 ... 14)
● at AWG conductors stranded 2x (20 ... 14)
Connectable conductor cross-section
● solid 0.5 ... 4 mm²
● finely stranded with core end processing 0.5 ... 2.5 mm²
AWG number as coded connectable conductor cross
section
● solid 20 ... 14
● stranded 20 ... 14
Tightening torque
● with screw-type terminals 1.2 ... 0.8 N·m

Installation/ mounting/ dimensions


Mounting position any
Mounting type snap-on mounting
Height 92 mm
Width 22.5 mm
Depth 91 mm
Required spacing
● with side-by-side mounting
— forwards 0 mm
— Backwards 0 mm
— upwards 0 mm
— downwards 0 mm
— at the side 0 mm
● for grounded parts
— forwards 0 mm
— Backwards 0 mm
— upwards 0 mm
— at the side 0 mm

3UG4632-1AW30 Subject to change without notice


Page 4/5 02/08/2020 © Copyright Siemens
— downwards 0 mm
● for live parts
— forwards 0 mm
— Backwards 0 mm
— upwards 0 mm
— at the side 0 mm

Ambient conditions
Installation altitude at height above sea level
● maximum 2 000 m

Certificates/ approvals
General Product Approval EMC Declaration of Conformity
Miscellaneous

Test Certificates Marine / Shipping other Railway


Type Test Certific- Special Test Certi- Confirmation Vibration and Shock
ates/Test Report ficate

Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3UG4632-1AW30
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3UG4632-1AW30
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3UG4632-1AW30
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3UG4632-1AW30&lang=en

last modified: 02/05/2020

3UG4632-1AW30 Subject to change without notice


Page 5/5 02/08/2020 © Copyright Siemens

You might also like