Uniquefire Catalog Chapter 08
Uniquefire Catalog Chapter 08
Suppression System
The clean agent fire suppression system and its components are agency tested for total flooding
applications and should be used in accordance with the guidelines contained in National Fire
Protection Association (NFPA) 2001: Standard on Clean Agent Fire Extinguishing Systems.
The clean agent fire suppression systems are safe for people, electrically non-conductive,
non-corrosive and free of residue and have zero ozone depletion potential (ODP) to
the environment.
CLEAN AGENT FIRE SUPPRESSION SYSTEM
The system and its components are agency tested for total flooding applications and should be used in
accordance with the guidelines contained in NFPA 2001. The design of such a system requires that the
FM-200 chemical agent be discharged from its container within 10 seconds and be thoroughly mixed
throughout the protected volume, reaching a minimum concentration level of 7%, but not exceeding
9% in normally occupied spaces.
S 6
H
2
3
S
8
9
1
10
11
FM-200 is stored in specially designed cylinder assemblies. Beta series cylinders are available in three different
capacities and are charged with FM-200 to a filling density up to 1121 kg/m3 of cylinder volume. All cylinders are
superpressurized with dry nitrogen to a pressure of 360 psig (2482 kPa), at 21°C. Each cylinder is equipped with an
identification nameplate indicating the quantity of FM-200.
Fill Capacity
Cylinder Part No. Min. Max
No
Size
lb kg lb kg
1 40 lb 10480992 21 9.5 41 18.6
2 55 lb 10480980 28 12.7 55 24.9
1 2 3
Nozzle
No Size Part No.
1 10mm Nozzle 360° 10371415
2 13mm Nozzle 360° 10371416
3 19mm Nozzle 360° 10371417
4 25mm Nozzle 360° 10371418
5 32mm Nozzle 360° 10371419
6 38mm Nozzle 360° 10371420
7 51mm Nozzle 360° 10371421
Gamma Series cylinders are available in four different capacities and are charged with FM-200
to a filling density up to 1121 kg/m3 of cylinder volume. All cylinders are superpressurized with dry
nitrogen to a pressure of 360 psig (2482 kPa), at 21°C. Each cylinder is equipped with an
identification nameplate indicating the quantity of FM-200.
Fill Capacity
Cylinder Part No. Min. Max
No
Size
lb kg lb kg
1 150 lb 10480993 82 37.2 163 73.9
2 250 lb 10480982 138 62.6 274 124.3
Nozzle
10
Components Part No.
4 No.
6 11 Primary Completer Kit 20480644
Sigma Series cylinders are available in three different capacities and are charged with FM-200 to a filling
density up to 1121 kg/m3 of cylinder volume. All cylinders are superpressurized with dry nitrogen to a pressure
of 360 psig (2482 kPa), at 21°C. Each cylinder is equipped with an identification nameplate indicating the
quantity of FM-200
Fill Capacity
Cylinder Part No. Min. Max
No
Size
lb kg lb kg
1 600 lb 10481454 304 137.9 607 275.3
2 750 lb 10481455 455 206.4 910 412.8
1 2 3
Nozzle
6
7
Components Part No.
5 No.
Primary Completer Kit 20480754
1 Solenoid Valve with Pressure Gauge 20610276
4 2 Manual - Pneumatic Actuator 10610729
2
3 3 3/16” Flex Hose 28” Long 10260303
1
4 3” 90° Grooved Elbow 70390542
5 3” Grooved Coupling 70390540
6 3” NPT Adapter Nipple 70400133
5 4
3 Components Part No.
No.
Slave Completer Kit 20480756
2 1 Pressure Gauge Assembly 20240041
3” Victaulic Connection Kit
1
- 3” 90° Grooved Elbow 70390542
2
- 3” Grooved Coupling 70390540
- 3” NPT Adapter Nipple 70400133
3 3/16” Flex Hose 28” Long 10260303
4 1/4” Flare x 1/8” MNPT Male Connector 50440029
5 1/4” Flare x 1/4” MNPT Male Connector 50440028
Backup Battery
Part No. GPP-1272
Nominal Voltage 12V
Capacity 7.2AH 12AH, 17 AH.
Design Life 4 years
Operating Temperature -10°C to 55°C
Part No. TD
Input Voltage 24VDC
Size (mm) 180(W) x 90(D) x 204(H)
Material Aluminium Alloy
Finishing Red Polyester