Engineered Nozzles
Engineered Nozzles
Engineered Nozzles
NUMBER
ENGINEERED NOZZLES
C.2.24.01
Architect and Engineer Specification
UL Listed - Ex 4623
ECARO-25TM Suppression System FM Approved 3014476
DESCRIPTION
The function of the ECARO-25 Engineered Discharge Nozzle orifice drilling must be done at the Fike factory, or
Nozzle, in a fire extinguishing system, is to distribute the other approved nozzle drill stations, only after “As-Built”
Clean Agent in a uniform, predetermined pattern and con- calculations of the installed piping system(s) have been per-
centration. The nozzles are designed to complete the dis- formed, using the ECARO-25 Flow Calculation computer
charge of Clean Agent when installed within the design limi- program.
tations of the ECARO-25 Design, Installation & Maintenance
Manual, P/N 06-238, 06-239, or 06-285 and the ECARO- The Fike Discharge Nozzle used shall be Factory Mutual
25 Flow Calculation computer program. (FM) approved and Underwriters Laboratory (UL) listed.
November, 2003
Revised Issue
704 S. 10th Street • P.O. Box 610 • Blue Springs, Missouri 64013-0610 U.S.A. • (816) 229-3405 • Fax (816) 229-0314 • www.fike.com
P.O. Box 540 • Guildford, Surrey, UK GU1 1RB • +44 (0) 8700 777 540 • Fax +44 (0) 7000 777 540 • E-Mail fps.int@Fike.com
3/8" (10mm) 1/2" - 2" (15 - 50mm)
Noz z le Area Coverage Noz z le Area Coverage
Noz z le Radius ft (m) Ceiling Height Range Noz z le Radius ft (m) Ceiling Height Range
Type ft (m) Type ft (m)
180 Degree 22.9 (6.93) 1.0 to 16.0 (0.3 to 4.9) 180 Degree 45'-8" (13.92) 1.0 to 16.0 (0.3 to 4.9)
360 Degree 14.9 (4.5) 1.0 to 16.0 (0.3 to 4.9) 360 Degree 29'-8" (9.04) 1.0 to 16.0 (0.3 to 4.9)