Nothing Special   »   [go: up one dir, main page]

Zelio Electromechanical Relays - RXG22P7

Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

Product data sheet RXG22P7

Characteristics interface plug-in relay - Zelio RXG - 2C/O


standard-230VAC-5A - with LTB and LED

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range of product Zelio Relay
Series name Interface relay
Product or component type Plug-in relay
Device short name RXG
Contacts type and composition 2 C/O

Complementary
Status LED With
Contacts material Silver alloy (AgSnO2In2O3)
Contact resistance 100 mOhm
[Ithe] conventional enclosed thermal 5 A (temperature : -40...55 °C)
current
[Ie] rated operational current 5 A at 30 V DC conforming to UL
5 A at 30 V DC conforming to IEC
5 A at 250 V AC conforming to IEC
5 A at 250 V AC conforming to UL
Maximum switching voltage 250 V AC
30 V DC
Load current 5 A at 250 V AC
Maximum switching capacity 1250 VA
Minimum switching capacity 50 mW at 10 mA, 5 V DC
Operating rate <= 18000 cycles/hour no-load
<= 1800 cycles/hour under load
Utilisation coefficient 20 %
Mechanical durability 10000000 cycles
Electrical durability 100000 cycles for NO resistive load at 55 °C
100000 cycles for NC resistive load at 55 °C
[Ui] rated insulation voltage 250 V conforming to IEC
300 V conforming to UL
300 V conforming to CSA

Jul 1, 2018
1
[Uimp] rated impulse withstand voltage 6 kV for 1.2/50 µs
Dielectric strength 5000 V AC (reinforced insulation between coil and contact)
3000 V AC (basic insulation between poles)
1000 V AC (micro disconnection between contacts)
Resistance 23500 Ohm +/- 15 %
Insulation resistance 1000 MOhm at 500 V DC
Mounting position Any position
Average consumption 0.82 VA at 60 Hz
Drop-out voltage threshold >= 0.3 Uc AC
Control circuit voltage limits 0.8...1.1 Uc, AC
Electrical insulation class Class F
Operating time 20 ms
Reset time 20 ms
[Uc] control circuit voltage 230 V AC
Safety reliability data B10d = 100000
Colour of cover Standard
Control type Lockable test button
Local signalling Flag
Product weight 0.02 kg
Device presentation Complete product

Environment
Vibration resistance 3 gn (f = 10...150 Hz), amplitude +/- 0.75 mm (in operation)
5 gn (f = 10...150 Hz), amplitude +/- 0.75 mm (not in operation)
IP degree of protection IP40
Shock resistance 20 gn in operation
100 gn not in operation
Protection category RT I
Standards UL 508
CSA C22.2 No 14
IEC 61810-1
Product certifications UL
RoHS
CE
EAC
CSA
China RoHS
REACH
Pollution degree 2
Overvoltage category III
Ambient air temperature for storage -40...85 °C
Ambient air temperature for operation -40...70 °C
Relative humidity 10...85 %

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant  - since  1426  -  Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product environmental
Product end of life instructions Need no specific recycling operations

2
Product data sheet RXG22P7
Dimensions Drawings

Dimensions

3
Product data sheet RXG22P7
Connections and Schema

Wiring Diagram

4
Product data sheet RXG22P7
Performance Curves

Performance Curves

Maximum Switching Capacity

X: Switching voltage (V)


Y: Switching current (A)
(1) AC Resistive Load
(2) AC Inductive Load cos(Ø)=0.4
(3) DC Resistive Load
(4) DC Inductive Load (L/R=7ms)

Life Expectancy
Resistive Load

X: Contact Current (A)


Y: Operating Cycle Number

Life Expectancy
Inductive Load

X: Contact Current (A)


Y: Operating Cycle Number
NOTE: These are typical curves, actual durability depends on load, environment, duty cycle, etc.

5
Product data sheet RXG22P7
Performance Curves

Coil Operating Range

AC Coil Operating Range VS Ambient Temperature

X: Ambient temperature (°C)


Y: Coil voltage (U/Uc)
(1) Permitted operating range area

You might also like