Nothing Special   »   [go: up one dir, main page]

Zelio Electromechanical Relays - RUMC3AB1P7

Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

Product data sheet RUMC3AB1P7

Characteristics universal plug-in relay - Zelio RUM - 3 C/O - 230


V AC - 10 A

Main

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Range of product Zelio Relay
Series name Universal
Product or component type Plug-in relay
Device short name RUM
Contacts type and composition 3 C/O
[Uc] control circuit voltage 230 V AC
[Ithe] conventional enclosed thermal 10 A at -40...55 °C
current
Status LED Without
Control type Lockable test button
Utilisation coefficient 20 %

Complementary
Shape of pin Cylindrical
[Ui] rated insulation voltage 250 V conforming to IEC
300 V conforming to UL
300 V conforming to CSA
[Uimp] rated impulse withstand voltage 4 kV
Contacts material AgNi
[Ie] rated operational current 10 A AC-1/DC-1 (NO) conforming to IEC
5 A AC-1/DC-1 (NC) conforming to IEC
12 A at 28 V DC-1 conforming to UL
16 A at 277 V AC-1 conforming to UL
Minimum switching current 10 mA
Maximum switching voltage 250 V AC conforming to IEC
250 V DC conforming to IEC
Minimum switching voltage 17 V
Resistive rated load 10 A at 250 V AC
10 A at 28 V DC
Maximum switching capacity 2500 VA, AC circuit
280 W, DC circuit
Minimum switching capacity 170 mW
Operating rate <= 18000 cycles/hour no-load
<= 1200 cycles/hour under load

Jan 25, 2019


1
Mechanical durability 5000000 cycles
Electrical durability 100000 cycles for resistive load
Average coil consumption in VA 2...3 at 60 Hz
Drop-out voltage threshold >= 0.15 Uc AC
Operate time 20 ms
Average coil resistance 7200 Ohm at 20 °C +/- 15 %
Rated operational voltage limits 184...253 V AC
Protection category RT I
Safety reliability data B10d = 100000
Operating position Any position
Product weight 0.088 kg

Environment
Dielectric strength 1500 V AC between contacts
1550 V AC between coil and contact
1550 V AC between poles
Product certifications CSA
GOST
UL
Standards EN/IEC 61810-1
UL 508
CSA C22.2 No 14
Ambient air temperature for storage -40...85 °C
Ambient air temperature for operation -40...55 °C
Vibration resistance 3 gn (f = 10...150 Hz), amplitude +/- 1 mm (on 10 cycles in operation) conforming to EN/IEC
60068-2-27
4 gn (f = 10...150 Hz), amplitude +/- 1 mm (on 10 cycles not operating) conforming to EN/IEC
60068-2-27
IP degree of protection IP40 conforming to EN/IEC 60529
Pollution degree 3
Shock resistance 10 gn in operation
10 gn not operating

Contractual warranty
Warranty period 18 months

2
Product data sheet RUMC3AB1P7
Dimensions Drawings

Dimensions

3
Product data sheet RUMC3AB1P7
Connections and Schema

Wiring Diagram

4
Product data sheet RUMC3AB1P7
Connections and Schema

Wiring Diagram

Symbols shown in blue correspond to Nema marking.

5
Product data sheet RUMC3AB1P7
Performance Curves

Electrical Durability of Contacts

Durability (inductive load) = durability (resistive load) x reduction coefficient.


Resistive AC load

X Switching capacity (kVA)


Y Durability (Number of operating cycles)
A RUMF•••••, RUMC2•••, RUMC3A•••
B RUMC3G•••

Reduction coefficient for inductive AC load (depending on power factor cos ϕ)

Y Reduction coefficient (A)

Maximum switching capacity on resistive DC load

X Voltage DC
Y Current DC
A RUMF•••••, RUMC2•••, RUMC3A•••
B RUMC3G•••
Note : These are typical curves, actual durability depends on load, environment, duty cycle, etc.

6
Product data sheet RUMC3AB1P7
Technical Description

Technical Description

Removable lock-down door enabling forced maintaining of the contacts for test sequences or maintenance purposes.
CAUTION : Please power off power supply before removal of lock down door.

(1) Lift the lock down door


(2) Slide it inwards
(3) Remove it

RUMC3AB1P7 is replaced by:

Electromechanical relay RUMC31P7


universal plug-in relay - Zelio RUM - 3 C/O - 230 V AC - 10 A
Qty 1
Reason for Substitution: End of life | Substitution date: 11 January 2013 | -