2D51 Duct Smoke Detector For Special Applications
2D51 Duct Smoke Detector For Special Applications
2D51 Duct Smoke Detector For Special Applications
Detector for
Special Applications
The System Sensor 2D51 low-profile photoelectric smoke
detector with a B210LP base tied to the D4P120 is listed
to Underwriters Laboratories 268A specifically for use in
no-flow/low-flow air-handling systems.
Features for 2D51/B210LP/D4P120 The 2D51 can be used as a pendant mount detector in no-flow/
low-flow air-handling systems (0-4,000 FPM). The pendant /plenum
• Low-profile smoke detector design
mounted 2D51 is to be installed into a B210LP base and wired to a
• Low standby current D4P120 power board-only control unit. The D4P120 power board is
• Two LEDs blink in standby capable of controlling up to two 2D51 sensors.
• SEMS screws for easy wiring and positive wire retention Remote testing is accomplished using the RTS151, RTS151KEY,
• Removable cover and insect screen for field cleaning RTS-2 or RTS-AOS accessories connected to the D4P120 power
board.
• Remote push button Test/Reset, LEDs provide visual indications
• Onboard supervisory and alarm relays The APA151, RTS2 and RTS2-AOS Remote Annunciators with Piezo
• Accepts 24 or 120V supply voltage Alarm can also be connected to the D4P120 power board to provide
an audible and visible indication of smoke detector status.
• Interconnect up to 100 units for common functions
• C
ompatible for interconnection with System Sensor InnoviarFlex™
D4120 or D4120W duct smoke detectors and remote accessories
Agency Listings
B210LP
TAMPER PROOF
TAB BASE
TERMINAL 2
BASE
TERMINAL 3
B210LP
BASE
2 TERMINAL 1
+ –
3 1
3 2 1
SENSOR #1
TERMINALS
FIELD SELECTABLE
DIP SWITCHES FIELD INSTALLED
JUMPER WIRE
SENSOR #2 GROUND
TERMINALS SCREW
Y Y R B
TAMPER + –
1/2 SENSORS
OFF/ON TRBL SHUTDN
7/0 MIN TMPR DELAY
Y Y R B Y Y R B 120 VAC
TAMPER + - TAMPER + -
AUX OUT +, 19
24V AC/DC, 10
AUX OUT -, 20
SENSOR 1 SENSOR 2
24V AC/DC, 9
SENSOR 1
INT/AUX-, 1
ALARM, 15
R TEST, 11
R RESET, 2
INT+, 12
ACC +
ACC -
D4P120
4, C
5, NO
13, NC
3, C
14, N0
16, NC
6, C
17, NO
8, NC
18, C
7, NO
ALARM SUP AUX A AUX B
120
POWER VAC INPUT
BOARD LED 2
TEST/RESET 24 VAC/
POWER BUTTON DC INPUT
BOARD LED 1
9 10 9 10
OR OR
16 6 17 8 18 7 16 6 17 8 18 7
EOL RESISTOR
SPECIFIED BY
PANEL
SUPERVISORY CONTACTS SUPERVISORY CONTACTS MANUFACTURER
(NOTE 3) (NOTE 3)
SUP N.O. SUP C SUP N.O. SUP C
UL/FM LISTED 14 3 14 3
4-WIRE
CONTROL PANEL
+
ALARM 5 ALARM N.O. ALARM 5 ALARM N.O.
ALARM INITIATION INITIATION
INITIATION CONTACTS CONTACTS
LOOP (NOTE 4) (NOTE 4)
4 ALARM C 4 ALARM C
*Please refer to the corresponding installation manual for detailed installation instructions and accessory wiring diagrams.
HVDS00302
Ordering Information
Part No. Description
2D51 Low-profile photoelectric plug-in detector (order the base listed below)
B210LP 120 VAC detector base
D4P120 4-wire photoelectric power board component only, 24 VAC/DC, 120 VAC
RTS151 Remote test station
RTS151KEY Remote test station with key lock
APA151 Remote annunciator with Piezo alarm
RTS2-AOS Multi-signaling accessory
RA100Z Remote annunciator alarm LED
MHW Mini horn, white
AOS Add-on strobe