Cable Schedules Al
Cable Schedules Al
Cable Schedules Al
0.57
no of circuits in a
No.of cable trunking
trunking/ conduit/
in a tier
duct
9 Assumption
0.50
1 0.90 Assumption
2 0.80
3 0.70
Referred 0ES-4 Page-57,
3 4 0.65
Table-2.
5 0.60
6 0.57
9 0.50 Assumption
CONSIDERATIONS
1. Current carrying capacity datas referred from OES-4, Table-4 Page-58.
2. For Multicore cables CU- XLPE Volt drop/A/m are referred from Ducab cable Catalogue. Refer Page No. 25, Table -26.
3. For single core CU/PVC wires Volt drop/A/m are referred from Ducab cable Catalogue. Refer Page No. 6, Table -2.
4. For single core CU/FR wires Volt drop/A/m are referred from Ducab cable Catalogue. Refer Page No. 4.
4. Derating factors are referred from OES4/ Ducab catalogue.
5. All cables shall be laid touching each other. Suitable Derating (Grouping) factor are considered as per OES4.
6. All MCCB rating shall be selected based on BS 5467/6004/6346.
7. Cable length shown above column is tentative only , exact length shall be ascertained as per site condition.