Nothing Special   »   [go: up one dir, main page]

Operating Instructions For Electromagnetic Flowmeter Model: MIM

Download as pdf or txt
Download as pdf or txt
You are on page 1of 69

Operating Instructions

for
Electromagnetic Flowmeter
Model: MIM
MIM-
We don’t accept warranty and liability claims neither upon this publication nor in
case of improper treatment of the described products.

The document may contain technical inaccuracies and typographical errors. The
content will be revised on a regular basis. These changes will be implemented in
later versions. The described products can be improved and changed at any time
without prior notice.
© Copyright
All rights reserved.

1. Contents
1.  Contents ........................................................................................................ 2 
2.  Note .............................................................................................................. 4 
2.1  Overview of the device functionality ..................................................... 4 
3.  Instrument Inspection .................................................................................... 5 
4.  Regulation Use ............................................................................................. 5 
5.  Environment .................................................................................................. 5 
6.  Operating principle ........................................................................................ 6 
6.1  General ................................................................................................ 6 
6.2  Minimum electrical conductivity / Gas bubbles .................................... 6 
6.3  Deposits ............................................................................................... 6 
6.4  Measuring electrodes .......................................................................... 6 
7.  Mechanical connection.................................................................................. 7 
7.1  Check operating conditions.................................................................. 7 
7.2  Installation............................................................................................ 7 
8.  Electrical Connection .................................................................................... 9 
8.1  General ................................................................................................ 9 
8.2  Pin assignment .................................................................................. 10 
8.3  Connection example outputs: ............................................................ 14 
9.  Operation and menu structure .................................................................... 15 
9.1  General .............................................................................................. 15 
9.2  Measuring mode ................................................................................ 16 
9.3  Menu Mode ........................................................................................ 19 
10.  Device configuration.................................................................................... 20 
10.1  Sequence of device parameterization ................................................ 20 
10.2  Language ........................................................................................... 20 
10.3  Display ............................................................................................... 21 
10.4  Measurement ..................................................................................... 23 
10.5  Dosing function .................................................................................. 27 
10.6  Outputs .............................................................................................. 27 
10.7  User service ....................................................................................... 39 
10.8  Service / Factory service.................................................................... 40 
10.9  Info ..................................................................................................... 40 
10.10 Device default settings ....................................................................... 40 
11.  Status .......................................................................................................... 41 
12.  Dosing function ........................................................................................... 42 
13.  IO-Link function ........................................................................................... 46 
13.1  Specification ...................................................................................... 46 

page 2 MIM K21/0620


MIM-
14.  Technical Information .................................................................................. 47 
15.  Order Codes ............................................................................................... 50 
16.  Dimensions ................................................................................................. 52 
17.  Appendix ..................................................................................................... 54 
17.1  IO-Link process data structure........................................................... 54 
17.2  IO-Link diagnosis information ............................................................ 55 
17.3  IO-Link system command table ......................................................... 56 
17.4  IO Link ISDU parameter table ............................................................ 57 
18.  Manufacturer’s declaration .......................................................................... 68 
19.  EU Declaration of Conformance ................................................................. 69 

Manufactured and sold by:

Kobold Messring GmbH


Nordring 22-24
D-65719 Hofheim
Tel.: +49(0)6192-2990
Fax: +49(0)6192-23398
E-Mail: info.de@kobold.com
Internet: www.kobold.com

MIM K21/0620 page 3


MIM-

2. Note
Please read these operating instructions before unpacking and putting the unit into
operation. Follow the instructions precisely as described herein.
The devices are only to be used, maintained and serviced by persons familiar with
these operating instructions and in accordance with local regulations applying to
Health & Safety and prevention of accidents.

When used in machines, the measuring unit should be used only when the
machines fulfil the EC-machine guidelines.

as per PED 2014/68/EU


In acc. with Article 4 Paragraph (3), "Sound Engineering Practice", of the PED
2014/68/EU no CE mark.
Diagram 8, Pipe, Group 1 dangerous fluids

2.1 Overview of the device functionality


Depending on the installed device firmware, the MIM device may have
different functionalities. The functional extensions are shown in the
following table.

Function extension Available from firmware version


Dosing function REV180118
Menu languages
Simulation function
User function keys REV180514
Analogue output 2-10 VDC
Analogue output behavior acc. to NAMUR NE43
IO-Link
REV190320
Control input
Additional flow units L/s and mL/s REV191030

The installed software version is displayed after starting the device below the
manufacturer logo in the form REVxxxxxx for approx. 2 sec.

page 4 MIM K21/0620


MIM-
3. Instrument Inspection
Instruments are inspected before shipping and sent out in perfect condition.
Should damage to a device be visible, we recommend a thorough inspection of the
delivery packaging. In case of damage, please inform your parcel service /
forwarding agent immediately, since they are responsible for damages during
transit.

Scope of delivery:
The standard delivery includes:
 Electromagnetic Flowmeter model: MIM
 Operating Instructions

4. Regulation Use
The MIM flowmeter has been specially developed for the measurement, display
and transmission of both, flow rates and temperature of conductive liquids. The
instrument has a graphic TFT display, rotatable in 90 ° steps and can display flow
rate, temperature, daily volume counter (resettable) and total volume counter in the
units of measurement selected by the operator. A clear menu guides the user
through the parameterization of the device, which largely eliminates the need to
look into the operating instructions.
Any use of the magnetic flowmeter, model: MIM, which exceeds the manufacturer’s
specification, may invalidate its warranty. Therefore, any resulting damage is not
the responsibility of the manufacturer. The user assumes all risk for such usage.

5. Environment
The MIM device with stainless steel housing and stainless steel electrodes is
weatherproof and conforms to protection class IP67. The meter is designed for
harsh indoor or outdoor environments and complies with Directive 2014/30/EU
(Electromagnetic Compatibility).

MIM K21/0620 page 5


MIM-

6. Operating principle

6.1 General
The new KOBOLD MIM Flowmeter is designed to measure and monitor small and
medium flows of conductive fluids in piping.
The device works on the magnetic-inductive measuring principle. According to
Faraday's law of induction, a voltage is induced in a conductor moving in a
magnetic field. The electrically conductive measuring medium corresponds to the
moving conductor in the process. The voltage induced by the measuring medium
is proportional to the flow rate and thus a measure of the volume throughput.
Prerequisite is a minimum electrical conductivity of the flowing medium. The
induced voltage is fed to a measuring amplifier via two electrodes, which are in
conductive contact with the medium. The volume flow is calculated via the defined
pipe diameter.
The measurement is independent of the medium and its physical properties such
as density, viscosity and temperature. The device can be configured via the
display. There are two outputs available, which can each be configured as alarm,
frequency, pulse, voltage, and current outputs.
The device also provides a dosing function. The dosing function can be activated
in measuring mode via the four buttons. The dosing function controls simple filling
tasks and also measures flow rate and partial amount.

6.2 Minimum electrical conductivity / Gas bubbles


For the correct function of the instrument, it is necessary that the flow channel is
always completely filled with medium. From a minimum electrical conductivity of 20
μS / cm, the MIM operates within the specified error limits. The conductivity of the
medium is constantly monitored by the device electronics. If the electronics detects
that the minimum conductivity has fallen below min. value, this is signaled by
displaying the error message 'Empty pipe' and the flow rate reading is set to '0'. Air
bubbles in the flowing medium or media with varying conductivity in the range of
the minimum conductivity can disturb the measuring function and reduce the
measuring accuracy of the MIM. Gases contained in the liquid are also measured
as a flow volume and lead to measurement errors. If necessary, install appropriate
vents in the flow of the unit.

6.3 Deposits
Minor deposits on the measuring tube generally do not affect the measuring
accuracy unless their conductivity deviates significantly from the liquid. For liquids
that have a tendency to deposit, periodically inspect the meter tube and, if
necessary, clean it.

6.4 Measuring electrodes


The MIM uses electrodes with galvanic tapping. They are in direct contact with the
medium. The standard electrodes are made of stainless steel 1.4404.

page 6 MIM K21/0620


MIM-
7. Mechanical connection

7.1 Check operating conditions


 flow rate
 max. operating pressure
 max. operating temperature
In general, MIM is subjected to the same loads as the piping into which it is
installed. The MIM should therefore be kept away from extreme loads, such as
pressure surges with strong, dynamic pipe movements, vibrations in the proximity
of centrifugal pumps, high temperature media, flooding etc.

7.2 Installation
 Remove all packing materials and transport retainers and ensure that no such
materials remain in the device.
 It can be installed in vertical, horizontal or rising pipes. Flow in direction of the
arrow.
 Avoid pressure and tensile load.
 Mechanically secure the inlet and outlet pipe at a distance of 50 mm from the
connections.
 Avoid valves or large reduction on the inlet section (this increases the
inaccuracy of measurements).
 Check the leak tightness of the connections.

While mounting MIM hold the flowmeter from spanner surface (not
from the housing) with the help of spanner.
Take into account the tightening torque.

Nominal size Tightening torque


½“ 22 to 24 Nm
¾“ 28 to 30 Nm
1“ 28 to 30 Nm

MIM K21/0620 page 7


MIM-
Inlet and outlet run

Installation from top to bottom avoid these installation locations


Gas bubbles,
particle

Free outlet

page 8 MIM K21/0620


MIM-
8. Electrical Connection

8.1 General

Attention! Make sure that the voltage values of your system


correspond with the voltage values of the measuring unit.

 Make sure that the supply wires are de-energised.


 Connect the supply voltage and the output signal to the plug PIN’s as stated
below.
 We recommend the use of wires with cross sectional area of min. 0.25 mm².

Attention! The measuring electrodes are galvanically connected


with the reference potential of the supply voltage and the signal
output.

8.1.1 Grounding/ Earthing


If the device is installed in a continuously grounded / earthed metallic pipe, no
additional grounding / earthing of the housing is generally necessary. When
installing in a plastic pipe or any ungrounded pipe, the housing must be earthed at
the side threaded hole (M4) to ensure proper functionality of the MIM. A M4 screw
(thread length max. 8 mm), a matching washer, a ring cable lug and a toothed lock
washer are required for correct installation.

These mechanical parts are not part of the delivery. 

MIM K21/0620 page 9


MIM-

8.2 Pin assignment


8.2.1 External connection with electrical connector M12x1 4-pin for
options C3T0 / Exx0 and Pxx0

8.2.2 Connection Exx0 / Pxx0 sensor

For the remote versions Pxx0 (PVC cable) and Exx0 (ETFE cable), the sensor and
transmitter are delivered ex works with the cable connected.
The on-site installation may require dismantling the cable and reconnecting it later.

Note:
In principle, the cable can be shortened by the user on the transmitter side and
connected to the transmitter again after appropriate assembly.

Attention!
A customer extension of the connection cable is not recommended because
of the necessary continuous shielding and leads to malfunction of the device.
The cable permanently connected to the sensor must not be disassembled.

page 10 MIM K21/0620


MIM-
Wiring diagram Transmitter Termination Connection cable
(PVC and ETFE cable)

MIM K21/0620 page 11


MIM-

Pin assignment see previous page

Insert pre-assembled cable through the cable gland and connect to the connector
strip

Pull back the cable and put the contact spring on the outer shield

Push the cable into the cable


gland, insert the plug connector
and tighten the hexagon nut of
the cable gland with SK key
SW 19 and lock with SW 18

page 12 MIM K21/0620


MIM-

Insert gasket, make sure gasket is seated correctly

Put the laminated seal disc on the screw


and screw the threaded connection in the
housing.
When tightening the screws, reduce the
gap between sheet metal housing and the
cover to ~ 0.5 mm

MIM K21/0620 page 13


MIM-

8.3 Connection example outputs:

OUT2: analogue output 4-20 mA


OUT1: analogue output 0-10 V

Configurable output functions:

Out 1 Out 2
analogue output 4-20 mA analogue output 4-20 mA
analogue output 0-20 mA analogue output 0-20 mA
analogue output 2-10 V analogue output 2-10 V
analogue output 0-10 V analogue output 0-10 V
alarm output alarm output
pulse output pulse output
frequency output frequency output
communication mode KofiCom
communication mode IO Link
control input
control input dosing function dosing output

page 14 MIM K21/0620


MIM-
9. Operation and menu structure

9.1 General
9.1.1 Operation of the optical buttons

Deactive optical button

Optical button active

An optical button is located at each corner of the TFT display. The operability of
the respective buttons is signaled by blue backlighting; therefore, non-backlit
buttons are disabled and cannot be operated. To operate the keys, the finger must
be placed on the key-dome and raised again. The orange background of the button
symbols is briefly displayed in blue as visual feedback for a detected key press.

To avoid accidental operation in measuring mode, the operator must hold down
the menu button for 3-5 seconds to activate the function. If the menu button is held
down for more than 3 seconds, the blue backlighting will begin to flash to alert the
user to release the button.

The operation of the optical buttons can also be done with gloves or other optically
reflective objects. Suitable types of gloves are: cotton and textile gloves, light
leather gloves, hygiene gloves made of latex and lightly rubberized work gloves.
Black-coated work gloves of all kinds are not suitable. Light dirt on the surface
usually does not interfere with the key function.

9.1.2 Function of the control buttons


The function of each control key can be recognized by the respective symbol
displayed in the corners of the TFT display.
function
key symbol designation Measuring
menu mode
mode

Activate menu
menu mode -
mode
hold 3-5 sec.
opens the info
info display -
menu
Scroll down menu /
decrease numeric
down -
value when entering
numeric value
Menu scroll up /
up -
Increase the number

MIM K21/0620 page 15


MIM-
function
key symbol designation Measuring
menu mode
mode
value for numeric
value input
Menu level lower /
forward - forward (last menu
level: Save value)
Menu function: menu
backward - level higher / back
(last step: exit menu)

9.2 Measuring mode


After applying the supply voltage, the device starts in measuring mode. In this
mode, the measured values of the respective measuring variables are continuously
recorded; the current instantaneous flow values, temperature values and the
volume counter readings are cyclically calculated and displayed according to the
type of display.
In addition to the main display, the states and configuration of the outputs are
shown in the display. If the corresponding output is configured as an alarm output,
the status is also displayed with a green or red background color. If the background
color is green, the set threshold value is exceeded; if it is red, the current value is
still under threshold.

page 16 MIM K21/0620


MIM-
Measurement Mode Display Layout 'Single'

The measurement variables are represented by their corresponding symbols:

Mesuring variables
Menu entry Description
Symbol
Flow Q Flow rate
Volume AC Accumulated totalizer
Temperature T Medium temperature
Part volume PT Partial totalizer

The outputs and their status are shown on the display as follows:

Output function OUT1/2 Symbol Representation


disable OFF
Analog output 4-20mA 4-20mA
Analog output 0-20mA 0-20mA
Analog output 0-10V 0-10V
Analog output 2-10V 2-10V
Alarm output PushPull SW+- Background grey/green
Alarm output PNP SW+ Background grey/green
Alarm output NPN SW- Background grey/green
Pulse output PLS
Frequency output FRQ
Communication mode KofiCom Use only for factory service
KofiCom (only OUT1)
Communication mode IO-Link
IO-Link (only OUT1)
Control input X CTL "X" symbol of the selected
measuring variable

The measured variables flow, temperature and volume counter can in principle be
assigned to each output function. The assignment of the respective output is
indicated by the display of the symbol of the measuring variable. The
representation of the assignment is independent of the set display layout (single,
dual).

MIM K21/0620 page 17


MIM-
Measurement Mode Display Layout 'Dual'
Out 1 configured as switching output Out 2 configured as analogue output 4-20 mA
pushpull and assigned to flow and assigned to temperature

Font white: MV within MR Measuring variables with sign for direction


Font yellow: 100% MR <=MV <=OverFlow
Font red: MV OverFlow
Unit for measuring variable

Legend:
MV - measured value
MR - measuring range

Out 1 configured as pulse output and Out 2 configured as analogue output 4-20 mA
assigned to partial totalizer and assigned to temperature

9.2.1 Display area of the flow meters


The number of digits displayed on the volume counter display (partial and total
volumetric counters) is limited to max. 8 digits. The partial and total volumetric
meters therefore have a smaller font size than the flow and temperature display. If
the 8-digit display range of the meter is exceeded, this is indicated by the display
of 8 minus characters (--------). In this case, the meter reading can no longer be
read. The user now has the option of bringing the counter reading back into the
display area by changing the volume counter unit.

page 18 MIM K21/0620


MIM-
9.3 Menu Mode
In menu mode, all device parameters can be set. The individual parameters are
arranged in menu groups by function. While the menu mode is activated, the signal
processing and the outputs are still active in the background. However, all display
parameters and outputs are updated after exiting the menu mode or in the
measuring mode.
Note: The menu mode will exit automatically after a certain time without using the
buttons, if the parameter “Menu Timeout” is set not equal to “0”.

9.3.1 Parameter setting


9.3.1.1 List Selection

Parameters with predefined selection values are defined by means of list selection.
The currently selected menu item is displayed in orange text. The selection can be
moved with the keys, the key is used to accept the selection.

To activate the menu mode, press the button for 3-5 seconds. The parameters
are divided into main groups and subgroups.
The buttons are used to select the main groups. In the main menu not all
menu groups can be shown on the display at the same time, the list of individual
menu items then scrolls up or down when the selection has reached the top or
bottom. To choose the selection, the key is pressed and the device jumps to
the corresponding submenu or parameter setting level. For selecting of predefined
parameter values and are used. After changing the value of the parameter
and confirming with the parameter is saved, and returns to the higher menu
level. To return to the main menu or to exit the menu mode, press (repeatedly).

Step 6 (exit menu) Step 5


This transition happens automatically

Step 2 Step 3 Step 4

Menu Parameter selection 1 Parameter selection 2 Apply selection


and save
Step 1 Menu button The orientation can be
press for 3-5 seconds selected with up and
down buttons

MIM K21/0620 page 19


MIM-
9.3.1.2 Numerical value input

When setting parameters with a numerical value, the assigned unit is always
displayed below the input field in square brackets in the input function. The
maximum size and the number of decimal places are fixed and cannot be changed.
After calling the input function, first the left, outer digit is displayed in orange. This
position can now be adjusted either with the keys in the value from 0 to 9.
By pressing the key , the entry point moves to the right and the next digit can
be changed. By pressing the key , the editing point can be moved to the left
again. If the editing point is on the far right, the set value is saved by pressing the
key again and switched to the higher-level menu function.

10. Device configuration

10.1 Sequence of device parameterization


The flowmeter MIM is pre-configured in factory. Changing the parameters
"Measuring range" and "Sensor constant" or "K factor" is therefore not permitted.
The adjustment of these parameters is only possible on the part of Kobold-factory.
In the event of subsequent changes to volume or throughput units, the dependent
parameters are converted and adjusted accordingly. However, the limit parameters
of the switching outputs must always be checked and adjusted manually when
adjusting volume or throughput units - these are not automatically converted.

An accidental change of the parameterization can be revised by the function "Reset


factory setting" in the menu Userservice / Reset.

10.2 Language
In this menu item the menu language can be changed in English, German,
French or Spanish (standard: English).

Parameter table language

Sublevel parameter Sub- Sub- Sub- Description Value Standard Standard


level para- para- para- range / value LPM value
meter meter meter value list GPM
level 1 level 2 level 3
English Selects English as the English
menu language
Deutsch Selects German as the
menu language
Francais Selects French as the
menu language
Espanol Selects Spanish as the
menu language

page 20 MIM K21/0620


MIM-
10.3 Display
10.3.1 Refresh
Parameter "Refresh" defines the time interval within which the measuring variables
are displayed. The "Refreshrate" can be increased in steps of 0.5 sec. to 10 sec.
An increase in the refresh rate time causes an increased "filtering" of the display
value.

10.3.2 Orientation
With the menu item "Orientation" the display can be rotated either clockwise or
counterclockwise in 90 ° increments. As the display rotates, both the display
contents and the function of the 4 control buttons are turned.

10.3.3 Layout
This parameter can be used to configure the display to either show one
measurement variable or two measurement variables.

10.3.4 Display value


With the aid of this parameter, the measurement variables provided by the
transmitter can be displayed. Depending on the 'Layout' display, either one or two
measuring variables can be displayed.

10.3.5 Keys HOTKEYs

Two independent user keys


are available, which can be
individually assigned with
different display functions.
The 2 user keys are available
in measurement mode top
right and left. If the buttons
are activated, they are backlit
in blue and the programmed
function can be executed by
touching.
The following functions are available:

reading MIN/MAX / Reset Value display / Reset


flow Yes / Yes Yes / No
Temperature Yes / Yes Yes / No
Partial quantity counter Not available Yes / Yes
Totalizer Not available Yes / No

MIM K21/0620 page 21


MIM-
The called hotkey function remains permanently activated and can only be left by
pressing the key . A direct reset function is available for the MIN / MAX measured
value function and the partial quantity counter.

10.3.6 Menu Timeout


The menu timeout time defines the time after which the menu function is automatically
exited without pressing a key. In the setting "0 s" this function is deactivated and the
menu function can only be left by hand by pressing the back key several times.

page 22 MIM K21/0620


MIM-
Parameter table Display

Sub- Sub- Sub-


Default Default
Parameter para- para- para- Value range/
Sublevel Description value value
level meter meter meter value list
LPM GPM
level 1 level 2 level 3
Sets the display refresh
Refresh value input 0.5-10 sec 0.5 sec
rate
Rotates the display 90 °
rotate CW
clockwise
Orientation Landscape
Rotates the display 90 °
rotate CCW
counterclockwise
Shows a measured value
Single
in the display area
Layout Double
Shows two measured
Double
value in the display area
Upper Sets the reading for the Flow,
list Flow
display display upper display volume,
selec-
value Lower Sets the reading for the temperature,
tion Temperature
display lower display part volume
Flow
Volume
Tem- List Sets the reading and Off, Value,
left
perature selection function for the left hotkey Min / Max
Part
volume
Hotkeys Off
Flow
Keys Volume Sets the reading and
Tem- List Off, Value,
right function for the right
perature selection Min / Max
hotkey
Part
volume
list
Sets the sensitivity for the
sensitivity selec- Low Low
optical buttons
tion
Defines the time after
which the setting menu is
Menu
value input automatically exited 0.5 to 60 s 15 s
Timeout
without pressing a key (0
= deactivated)

10.4 Measurement
The Measurement menu lists the measurement variables that the transmitter provides.
For magnetic inductive flowmeter, these are:

• Flow
• Volume (total volume counter)
• Temperature
• Part volume

Each measurement variable is still divided into its own submenu. In the submenu, all
parameters relating to the respective measuring variables can be adjusted.

MIM K21/0620 page 23


MIM-
10.4.1 Flow
10.4.1.1 Unit
The displayed unit for the flow measurement can be selected from various
predefined standard units. It is also possible to define a user-defined unit ("user"),
here the "user unit" must be in LPM (liters / min.) be programmed:
e.g. Unit User = 100 LPM, if Q = 500 LPM then the display shows 5 users.

10.4.1.2 Separation
The parameter Separation sets the flow rate below which the measured value is
set to "0". If this function is active, the flow value "0" is shown in blue colour in the
display.

10.4.1.3 Simulation mode


See section 10.4.5

10.4.2 Volume

10.4.2.1 Counter type


Absolute:
Regardless of the flow direction, the calculated partial volume is added to the
counters.
Bidirectional:
Depending on the flow direction, the calculated partial volume is added or
subtracted to the counters. If the measured flow value is negative, the volume value
goes down from measurement to measurement (possibly into the negative range).

page 24 MIM K21/0620


MIM-
10.4.2.2 Unit of the total volume counter
The parameter "Unit" determines the volume unit of the total volume counter. The
listed volume units are available. When changing the volume unit, the current
counter reading is converted to the new volume unit.

10.4.3 Temperature
10.4.3.1 Temperature Unit
The displayed unit for the temperature measurement can be selected from various
default units. It is also possible to define a user-defined unit ("user"), in which case
the "user unit" must be programmed in °C.

e.g. Unit “user” = 50 °C, if T = 50 °C then the display shows 1 user.

10.4.3.2 Simulation function


See section 10.4.5

10.4.4 Part Volume


10.4.4.1 Counter type

Absolute:
Regardless of the flow direction, the calculated partial volume is added to the
counters.
Bidirectional:
Depending on the flow direction, the calculated partial volume is added or
subtracted to the counters. If the measured flow value is negative, the volume
value goes down from measurement to measurement (possibly into the
negative range).

10.4.4.2 Unit of the part volume counter


The parameter "unit" defines the volume unit of all volume meters. The listed
volume units are available. When changing the volume unit, the current counter
readings are converted to the new volume unit.

10.4.4.3 Memory reset


In this menu, the part quantity counter can be reset.

10.4.4.4 Simulation function


See section 10.4.5

10.4.5 Simulation function


With the simulation function, all available measured values can be simulated
independently of each other for a limited time. The simulated measured values
have full effect on the displays and outputs.
Each simulation started is automatically stopped after the time set in the "Sim Auto
Stop Time" (user service) parameter (1 to 30 min) or after the programmed intervals
have expired.
The following measured values can be simulated:

MIM K21/0620 page 25


MIM-
Volume flow, temperature and part quantity counter

The simulation starts as soon as the simulation is activated and the setting menu
is exited. The simulation is interrupted or stopped, if the setting menu is called up.
There are 3 different simulation types available for each purpose:

a.) „Triangle“ mode


In "Triangle" mode, the simulation
value increases continuously in the
increment of the parameter
"Increment value" and in the interval
"Interval time" with the "Start value".
After the amount of the parameter
"intervals", the simulation value
decreases again in the same way,
in order to increase again. This
process is repeated continuously until the set time "Sim Auto Stop Time" has
expired and the simulation ends.

b.) "Monotonic" mode

In "Monotonic" mode, the simulation


value increases continuously in the step
size of the parameter "Increment value"
and in the interval "Interval time" with the
"Start value". After the amount of
"Intervals" or the expiration of "Sim Auto
Stop Time", the simulation ends.

c.) “Static” mode

In the "Static" mode, a constant value is output for the


measured values flow and temperature. The
simulation ends after the set simulation time.

In the "static" simulation for the part quantity counter,


the counter is only changed once by the set
"increment value" after the start.

When simulating the subset counter, note that in triangle mode, the submenu
counter must be in bidirectional mode to achieve the expected effect.

page 26 MIM K21/0620


MIM-
Parameter table Measuring

Sublevel Para- Subpara- Sub- Sub- Description Value range/ Default Default
meter meter level para- para- value list value value
level 1 meter meter LPM GPM
level 2 level 3
L/m, L/h, m3/h,
galUS/m,
galUS/h, galUs/
Unit List selection Sets the flow unit L/m
galUK/m, m
galUK/h, L/s,
Flow mL/s, User
sepa- Sets the value for the 0 ≤ Value ≤
value input Range start
ration low flow cutoff Range start
Simula-
tion See table Simulation mode
mode
Counter absolute/ Sets the counting
absolute
Type bidirectional mode
Volume ml, L, m3,
Unit List selection Sets the volume unit galUS, galUK, L L
User
Sets the temperature
Unit List selection °C, °F, User °C °C
Tem- unit
perature Simula-
tions- See table Simulation mode
modus
Counter absolute/ Sets the counting
absolute
Type bidirectional mode
ml, L, m3,
Unit List selection Sets the volume unit galUS, galUK, L galUs
Part
User
volume
memory Sets the counter
Yes/No
reset value to "0"
Simula-
tion See table Simulation mode
mode

10.5 Dosing function


see section 12

10.6 Outputs
The MIM flowmeter provides a total of 2 outputs that are freely configurable. The
configuration of the outputs (output 1 and output 2) is done via a wizard function.
The wizard function guides the user step by step through all necessary settings.

Steps:
• Select output
• Selection of the source or the measurement variable to be output (Flow,
Volume, Temperature, Part volume)
• Selection of an output type (4-20 mA, 0-20 mA, 0-10 V, 2-10 V, alarm, pulse,
frequency output,IO-Link, control input)
• Setting the output (scaling, thresholds)
• Save the configuration

MIM K21/0620 page 27


MIM-
The different output types are optimized for different types of applications. The
following table contains the application recommendations for the different output
types. If the outputs are not used according to the recommendations, measurement
deviations can occur and the desired functionality is not achieved.

Application Output type


Analog Frequency Pulse Alarm
output (all output output output
variants)
Telemetry device  
Limit monitoring 
Window monitoring 
External dosage 
External volumetric count 
Application table output types

10.6.1 Alarm output


The alarm outputs can be parameterized with a limit value function or a window
function.

10.6.1.1 Function
The parameter "Function" defines the basic function. Limit value function and
window function are available.
Limit value function: The switching output is active if the current flow rate value is
above the switching threshold. It remains active until the measured value has fallen
below the switching threshold minus the hysteresis.

Window function: The switching output is active if the current flow measured value
is outside a window, which is formed by the "switching threshold" and the "lower
threshold". The monitored window decreases in each case by the amount of the
"hysteresis". If the switching output is to be active within the window, the parameter
"switching function" must be changed from N/O to N/C.

page 28 MIM K21/0620


MIM-

10.6.1.2 Output type


The parameter "Output type" defines the function of the transistor output. NPN,
PNP or PP (push-pull) output types are available. The push-pull type combines
NPN and PNP and is therefore the best choice for most circuits. All outputs are
short circuit and overload protected.

10.6.1.3 Switching function


The "switching function" defines the mode of operation of the outputs. In the default
setting "normally open", the output becomes active (switched) when the measured
value exceeds the switching threshold. This feature is also referred to as N.O.
In the "Normally closed" setting, the output below the switching threshold is already
active and is deactivated when the measured value exceeds the switching
threshold. This function is also referred to as N.C.

10.6.1.4 Threshold
Threshold for limit value function and upper window point for window function.

10.6.1.5 Lower threshold


The "lower threshold" defines the lower limit when using the window function. When
using the limit value function, this parameter remains ineffective.
The switching thresholds can be set both positive and negative.

10.6.1.6 Hysteresis
The appropriate setting of the "hysteresis" parameter ensures that the switching
outputs do not switch on and off continuously when the current measured value
fluctuates around the switching threshold. The hysteresis value should therefore
always be greater than the real measured value fluctuations. As a result, a targeted
suppression can be achieved.

MIM K21/0620 page 29


MIM-
10.6.1.7 Filter factor (delay)
Further suppression of the switching outputs of fluctuating measuring signals can
be achieved by setting the parameter "Filter factor". If this parameter is selected
greater than 0, the switching of the output will be delayed accordingly. The "Supp
direction" parameter determines whether the deceleration is to be effective when
the switching threshold is exceeded or not reached (alternatively in both directions).
"High" means that the delay is active when the measured value exceeds the
switching threshold, "Down" means corresponding effect when the switching
threshold is undershot.
The measured value must stay continuously below or above the switching
threshold with the count of [SUPPRESSIONFACTOR] before the switching output
will be activated. With this function sporadic limit value overruns can be safely
suppressed.
According to the value of the parameter "filter factor", the response time of the
output generally increases.

Examples of the effect of the switching delay for window and limit function

page 30 MIM K21/0620


MIM-
10.6.2 Analogue outputs

10.6.2.1 Current output 0(4)-20 mA


The current output gives a measured variable (flow or temperature) in scaled form
as a 0 (4) -20 mA current signal.
The current output is scaled via the "Value 20 mA "and" Value 4 mA "(with current
output 0-20 mA "Value 0 mA"). By default, the "Value 20 mA" parameter is set to
the value for the end of the measuring range, but can be parameterized as desired
within the measuring range, but always bigger than the measuring range start
value. The parameters "Value 4 mA" / "Value 0 mA" define the measured values
for the starting current value, which may also be set freely in the measuring range.
Note 1: If the value is set smaller than the end of the measuring range, the accuracy
of the output voltage value is reduced.
Note 2: The burden on the current output must not exceed 500 Ω.
10.6.2.2 Voltage output 0-10 V / 2-10 V
The voltage output outputs a measurement variable (flow or temperature) in
scaled form as a 0-10 V / 2-10 V voltage signal.
The scaling of the voltage output is done via the parameter "Value 10 V "and
"Value 0 V". By default, the "Value 10 V" parameter is set to the value for the end
of the measuring range, but can be parameterized as desired within the
measuring range, but must always be bigger than the measuring range start
value.
The parameters "Value 0 V” and “Value 2 V" define the measured values for the
start voltage value, which may also be freely set in the measuring range.

Note 1: If the value is set smaller than the end of the measuring range, the
resolution and accuracy of the output voltage value are reduced.

Output behavior 4-20 mA and 2-10 V

MIM K21/0620 page 31


MIM-

Output behaviour 0-20 mA and 0-10 V

10.6.2.3 Activation of behaviour according to NAMUR


recommendation NE43
For all analogue outputs (current and voltage), the output behaviour can be
activated according to NAMUR recommendation NE43. When the function is
activated, e.g. the linear output of the 4 to 20 mA signals to 3.8 to 20.5 mA. Above
20.5 mA, the current value jumps to approx. 22 mA to signalise a measuring range
overshoot. Current output values between 3.8 and 4.0 mA indicate that the
measuring range is undershot. The output of approximately 3.6 mA signals a
device or process fault (e.g., empty tube signalling).

10.6.3 Pulse output


MIM flowmeter provides a scalable pulse output. When the pulse output is
activated, the cyclically incoming volume is available as a pulse train at the output.
The pulse width of the pulse output is constant and can be set in a range of 1 ms
up to 20 s. The pulse output is updated in a cycle of 20 ms. At the beginning of
each update, it is determined how much volume has been accumulated during the
previous update period. According to this amount and the set pulse volume, the
corresponding amount of pulses is available as a pulse train at the output.

The pulse signal is not suitable for determining the volume flow with an
external frequency measurement.

The reaction time of the pulse output is directly dependent on the flow
parameter "separation" (cutoff). The shortest reaction time is reached if this
parameter is set to the value "0.0" (factory setting: start of measuring range).

page 32 MIM K21/0620


MIM-

The electrical output type of the pulse output is push-pull, therefore HIGH and LOW
are actively switched through at the output.

Behavior on OVERFLOW:
If the volumetric flow measurement is in the OVERFLOW range, the pulse output
is switched off and a constant HIGH level is applied to the output.
Generation of the output pulse train:
The pulse volume (pulse value volume per output pulse) can be set freely within
wide ranges. Together with the adjustable pulse width and the measuring range of
the device there is a limited range in which the pulse output is instantaneous.

This is the case if the following condition is met:

/ ∗
22500

or

/ ∗
Pulse volume L

If the condition is not met, there may be a time lag of the pulse output. This is
particularly undesirable if dosing tasks are to be performed with the pulse signal.

The following table shows the different combinations of pulse volume and pulse
width for the different measuring ranges, in which the above limiting condition is
fulfilled.
MIM K21/0620 page 33
MIM-

Measuring  pulse width  min. pulse  max. pulse rate 


range [LPM]  [ms]  volume [L]  [pulse/L] 
20  0.08889  11.25 
10  0.04444  22.50 
100 
5  0.02222  45.00 
1  0.00444  225.00 
20  0.04444  22.50 
10  0.02222  45.00 
50 
5  0.01111  90.00 
1  0.00222  450.00 
20  0.02222  45.00 
10  0.01111  90.00 
25 
5  0.00556  180.00 
1  0.00111  900.00 
20  0.00889  112.50 
10  0.00444  225.00 
10 
5  0.00222  450.00 
1  0.00044  2250.00 
20  0.0026  375 
10  0.0013  750 
03 
5  0.0006  1500 
1  0.0001  7500 

The pulse output only takes place in measuring mode; while the menu mode is
active no pulses are given. The pulses accumulated in the menu mode are output
as soon as the measuring mode is active again. Depending on the situation, this
can also lead to a longer pulse lag.

10.6.3.1 Pulse volume


The parameter "Pulse volume" is defined as volume quantity for the output of a
pulse; the unit is corresponding to [volume quantity / pulse]. The likewise common
pulse rate [pulse / volume unit] corresponds to the reciprocal of the pulse volume.
Example: Desired pulse rate at the output 10 pulses / liter => pulse volume = 1 /
pulse rate = 1/10 L = 0.1 L

10.6.3.2 Volume unit


The volume unit to be set is the input unit for the "Pulse volume" parameter. The
definition of a user-defined unit ("user") is also possible and can be programmed
in "liters".
Example:
Unit "user" = 10 [L], pulse volume = 2 [user]
The total pulse volume would be 2 * 10 = 20 [L]. After 20 liters, a pulse is output.
10.6.3.1 Pulse width
The pulse width of the pulse output is flexibly adjustable from 1 to 20,000 ms.

page 34 MIM K21/0620


MIM-
10.6.4 Frequency output
The MIM flowmeter provides a scalable frequency output. When this output is
activated, the measurement variable (flow or temperature) associated with the
frequency output is output proportionally as a frequency with a 1: 1 pulse / pause
duration. The output frequency at the end of the measuring range can be set
(parameter "maximum frequency"). With the two parameters "Value for 0 Hz" and
"Value for max Hz", the frequency output in the measuring range can be freely
scaled.
Behavior on OVERFLOW:
If the measured value is in the overflow range, a constant frequency is output.

Output behavior Frequency output

10.6.5 Control input


Output 1 can be configured as a control input. This can reset the MIN / MAX
memory or the partial quantity counter depending on the assigned measurement
variable.

Function Measurement variable Control pulse


duration
MIN/MAX Reset Flow, temperature 0.5s < thigh < 4s
Part volume counter reset Part volume counter 0.5s < thigh < 4s

MIM K21/0620 page 35


MIM-
Parameter table Output 1/2 – Flow

Sub- Sub-
Sub-parameter Value range / Standard Standard
parameter parameter Description
level 1 value list value LPM value GPM
level 2 level 3
disabled Output deactivated IO-Link
Limit function /
Function Sets the basic function Limit function
window function
Output List selection Sets the electr. Output NPN/PNP/PP NPN
switching Set the log. switching
NO/NC NO
function function
Sets the switching MB start ≤ value ≤
threshold 1
threshold Full scale
Sets the lower threshold Value threshold ≤
Alarm output lower threshold 1
for window function value ≤ MB start
Defines the switching -9999,0 ≤ value ≤
hysteresis 1
hysteresis +9999,0
Factor for the switching
filter factor 0x ≤ value ≤ 60x 0
delay x100 ms
Defines the effective
direction direction of the switching Up / Down / Both Down
delay
Activates the behaviour
NAMUR activated /
according to NAMUR deactivated
Standard deactivated
NE43
4-20 mA Measured value for MB-start ≤ value ≤
Value 4 mA 0
4 mA output Wert 20 mA
Measured value for 20 Value 4 mA ≤
Value 20 mA 100
mA output value ≤ Full scale
Activates the behaviour
NAMUR Value input activated /
according to NAMUR deactivated
Standard deactivated
NE43
0-20 mA Measured value for MB start ≤ value ≤
Value 0 mA 0
0 mA output value 20 mA
Measured value for 20 Value for 0 mA ≤
Value 20 mA 100
mA output value ≤ Full scale
Activates the behaviour
NAMUR activated /
according to NAMUR deactivated
Standard deactivated
NE43
2-10 V Measured value for 2 V MB start ≤ value ≤
Value 2 V 0
output value 10 V
Measured value for 10 V Value for 2 V ≤
Value 10 V 100
output value ≤ Full scale
Activates the behaviour
NAMUR activated /
according to NAMUR deactivated
Standard deactivated
NE43
0-10 V Measured value for 0 V MB start ≤ value ≤
Value 0 V 0
output value 10 V
Measured value for 10 V Value for 0 V ≤
Value 10 V 100
output value ≤ Full scale

page 36 MIM K21/0620


MIM-
Sub- Sub-
Sub-parameter Value range / Standard Standard
parameter parameter Description
level 1 value list value LPM value GPM
level 2 level 3
Frequency output at
max. frequency 50-1000 Hz 500 Hz
"value at max. Hz"
Overflow value in % of
overflow the value 1-100 [%] 1%
Frequency "max.frequency"
Value input
output MB start ≤ value ≤
Value at 0 Hz Value at 0 Hz 0
value at max. Hz

Value at max. Value at "maximum Value for 0 Hz


100
Hz frequency" <value ≤ Full scale

Control input Control function for MIN


OFF, memory reset Aus
(only output 1) / MAX memory reset

KofiCom Factory calibration mode on output 1


IO-Link This mode activates the IO-Link function on output 1(standard factory setting)

Parameter table Output 1/2 – Volume


Sub- Sub- Sub- Standard Standard
Value range /
parameter parameter parameter Description value value
value list
level 1 level 2 level 3 LPM GPM
Output
disabled disabled
deactivated
Sets the Pulse ml, L, m3,
Pulse unit List selection Volume for galUS, galUK, L galUs
Pulse Volume User
Pulse Sets the value
Pulse
output for the pulse 0.001-999 1
volume
value input volume
Sets the pulse
Pulse width 1-20.000 1 ms
width
KofiCom Factory calibration mode on output 1
IO-Link This mode activates the IO-Link function on output 1

MIM K21/0620 page 37


MIM-
Parameter table Output 1/2 – Temperature
Sub- Sub- Sub-
Value range / Standard Standard
parameter parameter parameter Description
value list value LPM value GPM
level 1 level 2 level 3
disabled Output deactivated disabled
Sets the basic Limit function / window
Function Limit function
function function
Sets the electr.
Output List selection NPN/PNP/PP NPN
Output
Switching Sets the log.
NO/NC NO
function switching function
Sets the switching MB start ≤ value ≤ Full
Threshold 1
threshold scale
Sets the lower
lower Value threshold ≤
threshold for 1
threshold value ≤ MB start
Alarm output window function
Defines the
-9999.0 ≤ value ≤
Hysteresis switching 1
+9999.0
hysteresis
Factor for the
Filter factor switching delay 0x ≤ value ≤ 60x 0
x100 ms
Defines the
effective direction
Direction Up / Down / Both Down
of the switching
delay
Value input Measured value for MB start ≤ value ≤
Value 4 mA 0
4 mA output value 20 mA
4-20 mA
Measured value for Value 4 mA ≤ value ≤
Value 20 mA 100
20 mA output Full scale
Measured value for MB start ≤ value ≤
Value 0 mA 0
0 mA output value 20 mA
0-20 mA
Measured value for Value 0 mA ≤ value ≤
Value 20 mA 100
20 mA output Full scale
Measured value for MB start ≤ value ≤
Value 2 V 0
2 V output value 10 V
2-10 V
Measured value for Value 2 V ≤ value ≤
Value 10 V 100
10 V output Full scale
Measured value for MB start ≤ value ≤
Wert 0 V 0
0 V output value 10 V
0-10 V
Measured value for Value 0 V ≤ value ≤
Value 10 V 100
10 V output Full scale
Frequency output
max.
at "value at max. 50-1000 Hz 500 Hz
frequency
Hz"
Overflow value in %
Overflow of the “value at 1-100 [%] 1%
Frequency max. frequency"
Value input
output
MB start ≤ value ≤
Value at 0 Hz Value at 0 Hz 0
value for max. Hz

Value at max. Value at "max. Value for 0 Hz <value


100
Hz frequency" ≤ Full scale
Control function for
Control input
MIN / MAX memory OFF, memory reset OFF
(only OUT1)
reset
KofiCom
Factory calibration mode on output 1
(only OUT1)
IO-Link
This mode activates the IO-Link function on output 1
(only OUT1)

page 38 MIM K21/0620


MIM-
Parameter table Output 1/2 – Part volume
Sub- Sub- Sub- Standard
Value range / Standard
parameter parameter parameter Description value
value list value LPM
level 1 level 2 level 3 GPM
Disabled Output deactivated disabled
Sets the Pulse ml, L, m3,
List
Pulse unit Volume for Pulse galUS, galUK, L galUs
selection
Volume User
Pulse output Pulse Sets the value for the
0-999 1
volume Value input pulse volume
Pulse width Sets the pulse width 1-20.000 1 ms
Control input Control function for OFF, memory
Off
(only Out1) counter reset reset
KofiCom
Factory calibration mode on output 1
(only OUT1)
IO-Link
This mode activates the IO-Link function on output 1
(only OUT1)

10.7 User service


The user service provides the user with a reset function and password setting.
Together with the activation of a user password, therefore, the menu access for
the user on the part of a master user can be blocked.

10.7.1 User service / change password


In the factory setting the user password is set to "00000", the user functions are
thus freely accessible. If the user password is changed to other than "00000", the
password prompt becomes active the next time the user menu is entered.
If the set password is no longer known, a master password can be requested from
KOBOLD.

10.7.2 User service / factory setting


By activating this function, the user can reset the device to the factory settings. Any
user settings will then be lost and the device will be back in delivery condition.

Parameter table User menu


Standard
Parameter Value range / Standard
Sublevel Description value
level value list value LPM
GPM
Protects the user service
Password value input menu by password prompting 00000-99999 00000
if the password is not "00000"
Resets the device to factory
Factory reset Yes / No
settings
With "locked", the menu
unlocked / unlocked /
Menu lock access only takes place via unlocked
closed closed
the password prompt
Sets the time for how long
Sim Autostop Value input the simulation mode remains 1 - 31 min. 10 min.
active

MIM K21/0620 page 39


MIM-

10.8 Service / Factory service


The factory service function is password protected and not accessible to the user.

10.9 Info
10.9.1 General
This info option displays the measuring ranges of the device for flow and
temperature.

10.9.2 Version
This info option displays the hardware and software version of the device.

10.9.3 QR code link to the user manual


Here a QR code is displayed. With a suitable smartphone, the code can be
scanned and the user manual in English language downloaded directly as a PDF
and opened.
The smartphone must have a QR code scanning app and a PDF reader app
installed, as well as an internet connection.

Parameter table Info


Menu
Sublevel Description
level
General Displays the measuring ranges of the device

Version Displays the hardware and software version


Info

Manual Displays the QR code to download the instruction manual

10.10 Device default settings


The MIM flowmeter is factory set and unloaded with the following configuration:
Display - Dual IOLINK Off
Upper display - Flow
Lower display - Temperature
Out 1: IOLINK
0.000 +Q
L/m

Out 2: OFF 25.60 +T


°C
Status

Important note for MIM devices powered with software REV190320:


If output 1 should be operated as a current output, the conversion of the output
from IOLINK (factory setting) to current output must be made before the electrical
connection of the current loop. If this is not observed, the access to the menu
function is blocked and the device can no longer be configured.

page 40 MIM K21/0620


MIM-
11. Status
The electromagnetic flowmeter can detect and display various device or application
errors.
If there is a status or error message, the STATUS symbol in the display alternately
flashes orange / red. To call up the status / error information, the status key must
be pressed, then the status window that appears then lists all the messages that
have accumulated up to this point in time. By pressing the  key, the user
confirms the knowledge of the displayed errors, the status memory is cleared and
the status window is closed. If one of the displayed errors persists, it will be reported
again by flashing the status icon.
The following status / error messages are generated:

Display text Description Debugging


Check the filling of the
Measuring tube is not completely
measuring circuit or
Empty Pipe filled with medium or medium
conductivity of the medium
with too low conductivity is used.
(> 20 μs / cm)
Error in the temperature Repair by KOBOLD Service
Temp Sens Error
measuring circuit necessary
Flow measuring circuit
Meas saturated Reduce flow rate
overdriven
Repair by KOBOLD Service
No Subslave Internal hardware error
necessary
Simulation Simulation function active -

MIM K21/0620 page 41


MIM-

12. Dosing function


The standard MIM provides a simple dosing function. This can be permanently
activated or deactivated in the settings menu under the menu item "dosing". If the
dosing function is activated, fixed functions are assigned to the 2 outputs which
cannot be changed as long as the dosing function is activated:

OUT2 (Pin 2): Dosing output in push pull configuration


OUT1 (Pin 4): Control input for START/STOP/RESET function

Attention!
If the control input is not used, then OUT1 (connection pin 4) must be
connected to PIN3 (GND), the control input must not be left open!

When using the dosing function, it is recommended to set the flow parameter
"Separation" (Cutoff) to the value "0.0" in order to achieve the most accurate
results possible (factory setting: start of measuring range).

If the dosing function is deactivated, both outputs are switched to OFF


(deactivated) by default, but can then be freely configured again.

In the main display of the dosing function, the quantity to be dosed in a


preselectable unit and the current flow value are displayed on the one hand. The
progress of the dosing process is additionally represented by a graphic animation
in which the container shown fills in percent and also overfill is shown.

Softkey buttons: All softkey buttons in dosing mode must be held down by the user
for at least 2 seconds and then released again for the corresponding function to be
triggered. This is to avoid accidental operation.

page 42 MIM K21/0620


MIM-
Control input: Connection OUT1 can be used as a control input for the functions
Start / Stop / Reset when the dosing function is activated.

Function Conditions Control pulsetime


START Stop Modus 0.5 s < thigh < 4 s
STOP Run Modus 0.5 s < thigh < 4 s
RESET Stop Modus thigh > 5 s

START of dosing:
Dosing can be started either by triggering the "START" softkey or by applying a
high pulse to the control input.
After the START function has been triggered, the dosing output is switched to
active (High) and the dosing counter is counted down in the standard direction
when flow is present.
If the dosing process is stopped incompletely by hand, it can be restarted by the
START function.

STOP of dosing
If the dosing process is started, it can be stopped or interrupted by the STOP
function. Resumption of dosing to reach the total dosing quantity is possible by
START.
Like the START function, the STOP function can be remotely controlled by the
control input.

RESETTING the dosing value


If the dosing process is finished or stopped, the dosing quantity can be reset to the
default value by the function RESET.
This function can also be triggered at the control input.

MIM K21/0620 page 43


MIM-
Description of dosing parameters

Dosing quantity "Value"


Parameter "Value" determines the dosing volume. The volume unit is specified in
the "Unit" parameter.
The maximum size is limited to 9999.9 (one digit after the decimal point). The
absolute quantity can be extended or restricted by a suitable choice of dosing
unit.

Dosing unit "Unit"


Parameter "Unit" defines the dosing volume unit. The choices are: mL, L, m3,
galUS, galUK, barrel, user

Dosing correction value "Correction value"


The "Correction value" parameter can be used to correct a system-related,
constant "incorrect dosing" without having to change the actual dosing quantity.
The correction value can be both positive and negative. If the system doses a
smaller volume than intended, the correction value must be positive, but negative
for a larger real volume. e.g.
Dosing quantity = 10 L
Correction value = -1 L
In this case, the metering counter will count from 10 L to '0', but will stop at 1 L
because the quantity to be metered is 9 L calculated on the basis of the
correction value of -1 L.
With a correction value of +1 L, the dosing counter will stop counting at -1 L,
because the dosing amount is calculated to be 11 L.
10 - (- 1 L) = 11 L
The adjustable value of the correction value must always be:
(Value + Correction Value)> 0
If this condition is not met, this will be indicated by a warning message and the
correction value will be preset to the value - (Value-0.1).

Dosing parameter "Timeout"


During the dosing process, the presence of a flow value not equal to 0 is constantly
monitored. For this purpose, the parameter "Timeout" is used to set the time after
which the status message "Time Out" is triggered.
The timeout value can be set between 0.5 sec and 10 sec.

page 44 MIM K21/0620


MIM-
Parameter table Dosing
Subpara- Subpara- Subpara- Standard
Parameter Value range / Standard
Sublevel meter meter meter Description value
level value list value LPM
level 1 level 2 level 3 GPM
Dosing function
disabled
deactivated
disabled
Dosing function
Activation
activated
Value 0 ≤ Value ≤
Value 0
input 9999.99 [unit]
-999.99 ≤
Activation Correction Value
Value ≤ 0
aktivated value input
+999.99 [unit]
ml, L, m3,
List
Unit galUS, galUK, L galUs
selection
User
Value
Time out 0.5 - 10 sec 0.5 sec.
input

MIM K21/0620 page 45


MIM-

13. IO-Link function


As of firmware version REV190320, the MIM flowmeter has an IO-Link
communication interface as standard. Process and diagnostic data can be
accessed directly via this interface and the device can be parameterized.
Output 1 is factory configured for IO-Link function. If the IO-Link communication
mode is active, the "IOLINK" symbol in the status display for the outputs is
displayed in green. The setup menu remains locked when the IOLINK mode is
active and is inaccessible.
To ensure that the IO-Link device can be operated correctly on the connected IO-
Link master, it is necessary to install the device description file matching the device.
The device description files (IODD) are available in the IODDfinder, ioddfinder.io-
link.com.
Further information on IO-Link is available on the homepage www.io-link.com.

13.1 Specification
Manufacturer ID 1105 (decimal), 0x0451 (hex)
Manufacturer name Kobold Messring GmbH
IO-Link specification V1.1
bitrate COM3
Minimum cycle time 1.1 ms
SIO mode yes (OUT1 in configuration IO-Link)
block parameterisation yes
Ready for operation 10 sec.
Max. Cable length 20 m

page 46 MIM K21/0620


MIM-
14. Technical Information
Measurement process: electromagnetic
Range: see order details
Media: conductive fluids
Minimum conductivity: ≥20 µS/cm
Max. medium viscosity: 70 mm2/s
Max. pressure: 16 bar
Accuracy: <±(0.8% of reading+ 0.5% of full scale)*
Repeatability: ±0.2% of full scale
Response time flow t90
(alarm/pulse/frequency output): <100 ms
(analogue output): <1 s
Temperature measurement
Sensor: PT1000
Accuracy: ≤±2 °C (flow 0.2 m/s)
Measuring range: temperature range of medium
Response time of temperature t90
(signal output): <20 s
Mounting position: in all directions
In-/outlet: 3 x DN/2 x DN
Pressure drop (max at ME) MB 05 400 mbar
MB 10 50 mbar
MB 15 250 mbar (¾"), 30 mbar (1")
MB 20 80 mbar
MB 40 450 mbar
MB 35 120 mbar
Handling: 4 optical touch fields, useable with hand gloves**
Housing: stainless steel 1.4404,
display screen PMMA
Wetted parts
Connection fitting and housing: stainless steel 1.4404
Insulation parts: PEEK
Electrodes: stainless steel 1.4404
Seals: FKM: MIM-12xxx; EPDM: MIM-13xxx
Protection: IP 67
Media temperature: -20 °C … +70 °C ( c o m p a c t )
-20 °C … +85 °C (remote, PVC cable)
-40 °C … +140 °C (remote, ETFE cable)
Ambient temperature: -20 °C … +60 °C (compact version and display
for remote version)
-40 °C…+140 °C (sensor for remote version
with ETFE cable)
-20 °C…+85 °C (sensor for remote version
with PVC cable)

MIM K21/0620 page 47


MIM-
Electrical data
Supply voltage: 19 - 30 VDC, internal power consumption
max. 200 mA (without outputs)
Display: TFT display, 128 x 128 pixels,
1.4" display orientation in 90° steps adjustable
Display repetition rate: 0.5 ... 10 s, adjustable
Pulse output Push-Pull, freely scalable, configurable for
partial or accumulated totalizer
Frequency output Push-Pull, freely scalable,
Overflow frequency adjustable
Alarm output: NPN, PNP, Push-Pull,
configurable max. 30 VDC,
max. 200 mA short-circuit proof
Analogue output: active, 3 wire, 0(4)-20 mA,
max. load 500 Ω or 0-10 VDC, (Ri = 500 Ω)
Control input (MIN / MAX / partial volume RESET)
OUT1, high active
0 <ULow <10 VDC
15 VDC <UHigh <Vs
No internal pull-ups available,
active high / low signal necessary!
Total and partial quantity counter: overflow (reset) at 15 * 106 liters
(regardless of the set unit)
Electrical connection: plug M12x1, 4-pin
Dosing Function
Dosing value: 0.1 …9999.9 [Unit]
Dosing output OUT2
PushPull, High active
Control input: OUT1, High active
0 < ULow < 10 VDC
15 VDC < UHigh < Vs
No internal pull-ups available,
active high / low signal necessary!
START/STOP pulse: 0.5 s < thigh < 4 s
RESET pulse: thigh > 5 s
* Under reference conditions: media temperature: 15 °C ... 30 °C, 1 cSt, 500 µS/cm, 1 bar
ambience temperature: 15 °C ... 30 °C
** Limited functionally with black rubber gloves

page 48 MIM K21/0620


MIM-
Pressure Drop Curves [typical]

dP [mbar]
450 1
425
400
375
350 2
325
300
275
250
225 3
200
175
150 4
125
100 5
75 6
50
25 7
0 8
0 10 20 30 40 50 60 70 80 90 100
1: MIM-1240xx9 Q [%FS]
2: MIM-1205xG4
3: MIM-1215xG5
4: MIM-1235xx9
5: MIM-1220xG6
6: MIM-1210xG5
7: MIM-1203xG4
8: MIM-1215xG6

MIM K21/0620 page 49


MIM-

15. Order Codes

Order Details (Example: MIM-12 15G G5 C3T 0)


Model Range Connection Electronics Special version
03H1) = 0.03...3 l/min
03G2) = 0.48…48 GPH
G44) = G ½ male, DN5
05H1) = 0.04 ... 10 l/min
2)
05G = 0.01 ... 2.6 GPM C3T = compact, TFT display,
2 outputs
10H1)= 0.1…25 l/min (current/voltage/pulse/
2)
10G = 0.025…6.6 GPM frequency/alarm output
MIM-12= housing/ 1) 4)
G5 = G ¾ AG, DN10
15H = 0.2…50 l/min configurable), M12x1 plug
electrode VA,
15G2)= 0.05…13 GPM
FKM seal
P023) = remote version 0 = without
15H1)= 0.2…50 l/min TFT display, K5) = incl. calibration report
MIM-13 = housing/
15G2)= 0.05…13 GPM 2 m PVC cable,
electrode VA, 1) G6 4)
= G 1 AG, DN15
20H = 0.4 ... 100 l/min max. 85 °C
EPDM seal
20G2)= 0.1…26 GPM E023) = remote version,
TFT display,
35H1)= 1.5…350 l/min G9 = G 2 AG 2 m ETFE cable,
max. 140 °C
35G2)= 0.4…90 GPM N9 = 2” NPT IG
1)
l/min-package (nameplate (l/min, °C, bar)), calibrated range and temperature °C
2)
GPM-package (nameplate (GPM, °F, PSI)), calibrated range and temperature °F
3)
Cable length 02 = 2 m, 05 = 5 m, 10 = 10 m, 15 = 15 m, 20 = 20 m. Wall mounting brackets (brackets incl. accessories) is
included in the scope of delivery.
4)
Regulation (EC) No. 1935/2004 for materials and articles intended to come into contact with food. Not for connection code
G9/N9.
5)
Please specify number of measuring points in clear text.

Accessories
Description Model Image

Stainless steel wall mounting


kit for remote version (2
ERS-ZOK-023618
brackets, without
nuts/washers)

Description Model Dimensions [mm] Image

Clamping bracket set


for wall mounting
(stainless steel with ZUB-MIM225128
partial polyolefin
sleeve)

page 50 MIM K21/0620


MIM-
Order Details MIM Fitting Sets Accessory Kits*

Accessory kit number Meter connection Process connection Fitting set type
ZUB-AD2U15P08 G ½ cap nut ¼“ NPT male Cap nut and union
ZUB-AD2G15P15 G ½ female ½” NPT male Adapter
ZUB-AD2G15N08 G ½ female ¼” NPT female Adapter
ZUB-AD2G15N15 G ½ female ½” NPT female Adapter
ZUB-AD2U20P15 G ¾ cap nut ½” NPT male Cap nut and union
ZUB-AD2G20P20 G ¾ female ¾” NPT male Adapter
ZUB-AD2G20N15 G ¾ female ½” NPT female Adapter
ZUB-AD2G20N20 G ¾ female ¾” NPT female Adapter
ZUB-AD2U25P15 G 1 cap nut ½” NPT male Cap nut and union
ZUB-AD2U25P20 G 1 female ¾” NPT male Cap nut and union
ZUB-AD2G25N15 G 1 female ½” NPT female Adapter
ZUB-AD2G25N20 G 1 female ¾” NPT female Adapter

* Note: All fitting kits include 2x Klinger SIL® flat sealing gaskets

MIM K21/0620 page 51


MIM-

16. Dimensions

[mm]
Compact version

page 52 MIM K21/0620


MIM-

Remote version
Without wall mounting brackets

With wall mounting brackets

MIM K21/0620 page 53


MIM-

17. Appendix

17.1 IO-Link process data structure


Process data length: 9 bytes

Byte  Data  Bit count  Format  Factor  Range  Value 


no. 
0 ‐ 2  Flow  24 Bit  IntegerT  1/1000  +/‐8388,608  L/min 
3 ‐ 6  Volume  32 Bit  FloatT     +/‐1,4*10‐45 ... +/‐3,4*10+38  L 
7 ‐ 8  Temperature  12 Bit  IntegerT  1/10  +/‐204,8  °C 
reserved  1 Bit  BooleanT         
reserved  1 Bit  BooleanT         
Status OUT1  1 Bit  BooleanT         
Status OUT2  1 Bit  BooleanT         

page 54 MIM K21/0620


MIM-
17.2 IO-Link diagnosis information
Event  Event  Name  Device  Type  Definition 
Code  Code  Status 
[hex]  [dec] 
0x7710  30480  Short Circuit     Error  check installation 
0x8C10  35856  Process Variable Range Overrun     Warning  process data 
uncertain  
0x8C20  35872  Measurement Range Overrun      Error  check application 
0x8C30  35888  Process Variable Range     Warning  process data 
Underrun   uncertain 
0x1838  6200  1. Test Event For Protocol     Error  first test event 
Testing 
0x1839  6201  2. Test Event For Protocol     Error  secont test event 
Testing 
0x183A  6202  Flow MRE Overrun     Warning  flow measuring 
range overrun 
0x183B  6203  Flow MRS Underrun     Warning  flow measuring 
range underrun 
0x183C  6204  Flow Overflow Overrun  2  Warning  flow overflow  
range overrun 
0x183D  6205  Flow Underflow Underrun  2  Warning  flow underflow 
range underrun 
0x183E  6206  Flow Cutoff Out     Warning  out of flow cutoff 
range 
0x183F  6207  Temperature MRE Overrun     Warning  temperature 
measuring range 
overrun 
0x1840  6208  Temperature MRS Underrun     Warning  temperature 
measuring range 
underrun 
0x1841  6209  Temperature Overflow Overrun  2  Warning  temperature 
overflow  range 
overrun 
0x1842  6210  Temperature Underflow  2  Warning  temperature 
Underrun  underflow range 
underrun 
0x1843  6211  NVM Error  4  Error  non‐volatile 
memory is corrupt 
0x1844  6212  Subslave Lost     Error  communication to 
subslave 
interrupted 
0x1845  6213  Subslave Not Found  4  Error  cummunication to 
subslave couldn`t 
be astablished 
0x1846  6214  Emptypipe     Warning  no media in tube 
0x1847  6215  Temperature Sensor Error  4  Error  no sensor attached 
0x1848  6216  Measuring Circuit Saturated  2  Warning  ADC out of range 
0x1849  6217  Counter Overflow  2  Error  volume or 
partvolume counter 
overflowed 

MIM K21/0620 page 55


MIM-
Event  Event  Name  Device  Type  Definition 
Code  Code  Status 
[hex]  [dec] 
0x184A  6218  Dosing Timeout     Warning  indicades that the 
no flow timeout of 
the dosing function 
is active 
0x184B  6219  Simulation Active     Warning  indicades that one 
of the simulations is 
running 

17.3 IO-Link system command table


Command (hex)  Command (dec)  Command name 
0x82  130  Restore factory settings 
0xA0  160  Reset part volume counter 
0xA1  161  Start flow simulation 
0xA2  162  Stop flow simulation 
0xA3  163  Start temperature simulation 
0xA4  164  Stop temperature simulation 
0xA5  165  Start part volume simulation 
0xA6  166  Stop part volume simulation 
0xA7  167  Events Handling ON 
0xA8  168  Events Handling OFF 
0xA9  169  Reset MinMax for Flow 
0xAA  170  Reset MinMax for Temperature 
   

page 56 MIM K21/0620


MIM-
17.4 IO Link ISDU parameter table
Index  Name  Description  Factory default  Max Value  Min Value  Length  Data Type  Access 
[hex]  [Bytes] 
System 
0x0002  SystemCommand  See Table           1  UIntegerT  W 
"Comand Codes" 

Product Identification (Vendor specific parameters)  
0x0010  VendorName     Kobold Messring        max. 20  StringT  R 

0x0011  VendorText     www.kobold.com        max. 32  StringT  R 

0x0012  ProductName     MIM‐       max. 16  StringT  R 


XXXXXXXXXXX 

0x0013  ProductID     [exact model code]       max. 16  StringT  R 

0x0014  ProductText     magnetic inductive        max. 32  StringT  R 


flow meter 

0x0015  Serialnumber  only read           max. 8  StringT  R 


parameter 

0x0016  HardwareRevision              max. 8  StringT  R 

0x0017  FirmwareRevision  Firmware Revision           max. 8  StringT  R 


is constant in FW 

0x0018  ApplicationDevice  tag name is from           32  StringT  R/W 


Tag  user configurable 

0x0019  FunctionTag  function tag is           32  StringT  R/W 


from user 
configurable 

0x0020  LocationTag  location tag is           32  StringT  R/W 


from user 
configurable 

MIM K21/0620 page 57


MIM-
Index  Name  Description  Factory default  Max Value  Min Value  Length  Data Type  Access 
[hex]  [Bytes] 
Device Status Information  
0x0024  DeviceStatus  0 ‐ Device OK           1  UIntegerT  R 
1 ‐ Maintenance 
required 
2 ‐ Out of 
specification 
3 ‐ Functional 
check  
4 ‐ Failure 

0x0025  DetaildDevice              max. 20  ArrayT of   R 


Status  OctetString 
T3 

Display Configuration  
0x0100  DisplayOrientation  Orientation of  1  (0) ‐ Landscape  1  UIntegerT  R/W 
display  (1) ‐ Portrait Flip 
(2) ‐ Landscape Flip 
(3) ‐ Portrait 
0x0103  DisplayLayout  Single or dual  1  (0) ‐ single  1  UIntegerT  R/W 
layout  (1) ‐ dual 

0x0104  UpperDisplay  Source for the  0  (0) ‐ Flow  1  UIntegerT  R/W 


upper display   (1) ‐ Volume 
(2) ‐ Temperature 
(3) ‐ Part Volume 
0x0105  LowerDisplay  Source for the  2  (0) ‐ Flow  1  UIntegerT  R/W 
lower display   (1) ‐ Volume 
(2) ‐ Temperature 
(3) ‐ Part Volume 
0x0106  DisplayRefresh  Refresh intervall  0,5  10,0  0,5  4  FloatT  R/W 
Time  for the display [s] 

0x010A  LeftHotkey  Function for left  0  (0) ‐ Off  1  UIntegerT  R/W 


Function  hotkey  (1) ‐ Value 
(2) ‐ MinMax 

0x010B  RightHotkey  Function for right  0  (0) ‐ Off  1  UIntegerT  R/W 


Function  hotkey  (1) ‐ Value 
(2) ‐ MinMax 

0x010C  LeftHotkeySource  Source for the left  0  (0) ‐ Flow  1  UIntegerT  R/W 


hotkey  (1) ‐ Volume 
(2) ‐ Temperature 
(3) ‐ Part Volume 
0x010D  RightHotkeySource  Source for the  0  (0) ‐ Flow  1  UIntegerT  R/W 
right hotkey  (1) ‐ Volume 
(2) ‐ Temperature 
(3) ‐ Part Volume 
0x010E  SensitivityOptical  Sensitivity for the  0  (0) ‐ low  1  UIntegerT  R/W 
Keys  optical keys  (1) ‐ middle 
(2) ‐ high 

0x010F  AutomaticMenu  Automatic menu  0  60  0  1  UIntegerT  R/W 


Leave  leave if the 
timeout [s] is hit.  
0 = timeout not 
active 
Output 1 (In IO‐Link mode output 1 can be parameterized individual, operating mode can only be changed manually)   

page 58 MIM K21/0620


MIM-
Index  Name  Description  Factory default  Max Value  Min Value  Length  Data Type  Access 
[hex]  [Bytes] 
0x0110  OUT1Source  Source for the  0  (0) ‐ Flow  1  UIntegerT    
output   (1) ‐ Volume 
(production  (2) ‐ Temperature 
setting)  (3) ‐ Part Volume 

0x0111  OUT1Type  Configuration of  8  (0) ‐ disabled  1  UIntegerT    


the output: 0‐ (1) ‐ Alarm Output 
20mA, Pulse,  (2) ‐ 4‐20mA 
Frequency   (3) ‐ 0‐20mA 
(production  (4) ‐ 2‐10V 
setting)  (5) ‐ 0‐10V 
(6) ‐ Pulse Output 
(7) ‐ Frequency Output 
(8) ‐ M12COM 
(9) ‐ IO‐Link 
(10) ‐ Control Input 
0x0112  OUT1Alarm  Limit or window  0  (0) ‐ Limit  1  UIntegerT  R/W 
Function  function for the  (1) ‐ Window 
alarm output 

0x0113  OUT1AlarmOutput Alarmoutput NPN,  0  (0) ‐ NPN  1  UIntegerT  R/W 


Type  PNP or Pushpull  (1) ‐ PNP 
(2) ‐ PushPull 

0x0114  OUT1AlarmSwitch  Alarmoutput  0  (0) ‐ normally opened  1  UIntegerT  R/W 


Function  normally opened  (1) ‐ normally closed 
or closed 

0x0115  OUT1Alarm  Threshold for the  1,0  MRE  MRS  4  FloatT  R/W 


Threshold  alarmoutput 

0x0119  OUT1AlarmLower  Threshold for the  1,0  OUT1AlarmT MRS  4  FloatT  R/W 


Threshold  alarmoutput used  hreshold 
by the 
windowfunction 

0x011D  OUT1Alarm  Switching  1,0  9999,0  ‐9999,0  4  FloatT  R/W 


Hysteresis  hysteresis for the 
alarmoutput 

0x0121  OUT1Alarm  How many times  0  60  0  1  UIntegerT  R/W 


SuppressionFactor  the threshold must 
be hit in order to 
switch the alarm 
output 

0x0122  OUT1Alarm  for which direction  0  (0) ‐ Up  1  UIntegerT  R/W 


Suppression  the suppression  (1) ‐ Down 
Direction  factor is used  (2) ‐ Both 

MIM K21/0620 page 59


MIM-
Index  Name  Description  Factory default  Max Value  Min Value  Length  Data Type  Access 
[hex]  [Bytes] 
0x0123  OUT1Analog  If enabled (1) the  1  (0) ‐ NAMUR disabled   1  UIntegerT  R/W 
NamurStandard  analogoutput  (1) ‐ NAMUR enabled 
conforms with the 
NAMUR Standard 
NE42. If disabled 
(0) the 
analogoutput stays 
in his equivalent 
range (e.g. 4‐
20mA) 

0x0124  OUT1AnalogValue The value from the  0,0  OUT1Analog MRS  4  FloatT  R/W 


0mA  slot used for the  Value20mA 
0mA scaling point 

0x0128  OUT1AnalogValue The value from the  0,0  OUT1Analog MRS  4  FloatT  R/W 


4mA  slot used for the  Value20mA 
4mA scaling point 

0x012C  OUT1AnalogValue The value from the  100,0  MRE  OUT1Analog 4  FloatT  R/W 


20mA  slot used for the  Value0mA 
20mA scaling point 

0x0130  OUT1AnalogValue The value from the  0,0  OUT1Analog MRS  4  FloatT  R/W 


0V  slot used for the  Value10V 
0V scaling point 

0x0134  OUT1AnalogValue The value from the  0,0  OUT1Analog MRS  4  FloatT  R/W 


2V  slot used for the  Value10V 
2V scaling point 

0x0138  OUT1AnalogValue The value from the  100,0  MRE  OUT1Analog 4  FloatT  R/W 


10V  slot used for the  Value0V 
10V scaling point 

0x013C  OUT1PulseVolume  The volume  1,0  999,9  0,0  4  FloatT  R/W 


represented by 
one pulse  

0x0140  OUT1PulseVolume Unit used for the  1  (0) ‐ USER  1  UIntegerT  R/W 


Unit  pulse output   (1) ‐ L 
(2) ‐ mL 
(3) ‐ m3 
(4) ‐ galUS 
(5) ‐ galUK 
(6) ‐ Barrel       
0x0141  OUT1PulseVolume User Unit used for  1,0  9999,9  0,0  4  FloatT  R/W 
UnitUser  the pulse output  

0x0145  OUT1PulseWidth  Width of each  1  20000  1  2  UIntegerT  R/W 


pulse 

page 60 MIM K21/0620


MIM-
Index  Name  Description  Factory default  Max Value  Min Value  Length  Data Type  Access 
[hex]  [Bytes] 
0x0147  OUT1Frequencyat  Max. frequency in  500  1000  50  2  UIntegerT  R/W 
FS  Hz for the output 

0x0149  OUT1Frequency  Overflow  1  100  0  1  UIntegerT  R/W 


Overflow  frequency in 
percent of the max 
frequency 

0x014A  OUT1Frequency  Value from source  0,0  OUT1  MRS  4  FloatT  R/W 


Value0Hz  used for 0 Hz  Frequency 
scaling point  ValueMaxHz 

0x014E  OUT1Frequency  Value from source  100,0  MRE  OUT1  4  FloatT  R/W 


ValueMaxHz  used for max. Hz  Frequency 
scaling point  Value0Hz 

0x0152  OUT1CtrlFunction  Controlinput‐ 0  (0) ‐ Off  1  UIntegerT  R/W 


function ‐> Off or  (1) ‐ Memoryreset 
Memoryreset 

Output 2 
0x0163  OUT2Source  Source for the  0  (0) ‐ Flow  1  UIntegerT  R/W 
output  (1) ‐ Volume 
(2) ‐ Temperature 
(3) ‐ Part Volume 
0x0164  OUT2Type  Configuration of  0  (0) ‐ disabled  1  UIntegerT  R/W 
the output ‐>  (1) ‐ Alarm Output 
 0‐20mA, Pulse,  (2) ‐ 4‐20mA 
Frequency, etc.  (3) ‐ 0‐20mA 
(4) ‐ 2‐10V 
(5) ‐ 0‐10V 
(6) ‐ Pulse Output 
(7) ‐ Frequency Output 

0x0165  OUT2Alarm  Limit or window  0  (0) ‐ Limit  1  UIntegerT  R/W 


Function  function for the  (1) ‐ Window 
alarm output 

0x0166  OUT2AlarmOutput Alarmoutput NPN,  0  (0) ‐ NPN  1  UIntegerT  R/W 


Type  PNP or Pushpull  (1) ‐ PNP 
(2) ‐ PushPull 

0x0167  OUT2AlarmSwitch  Alarmoutput  0  (0) ‐ normally opened  1  UIntegerT  R/W 


Function  normally opened  (1) ‐ normally closed 
or closed 

0x0168  OUT2Alarm  Threshold for the  1,0  MRE  MRS  4  FloatT  R/W 


Threshold  alarmoutput 
0x016C  OUT2AlarmLower  Threshold for the  1,0  OUT2AlarmT MRS  4  FloatT  R/W 
Threshold  alarmoutput used  hreshold 
by the 
windowfunction 

MIM K21/0620 page 61


MIM-
Index  Name  Description  Factory default  Max Value  Min Value  Length  Data Type  Access 
[hex]  [Bytes] 
0x0170  OUT2Alarm  Switching  1,0  9999,0  ‐9999,0  4  FloatT  R/W 
Hysteresis  hysteresis for the 
alarmoutput 

0x0174  OUT2Alarm  How many times  0  60  0  1  UIntegerT  R/W 


SuppressionFactor  the threshold must 
be hit in order to 
switch the alarm 
output 

0x0175  OUT2Alarm  for which direction  0  (0) ‐ Up  1  UIntegerT  R/W 


Suppression  the suppression  (1) ‐ Down 
Direction  factor is used  (2) ‐ Both 

0x0176  OUT2Analog  If enabled (1) the  1  (0) ‐ NAMUR disabled   1  UIntegerT  R/W 


NamurStandard  analogoutput  (1) ‐ NAMUR enabled 
conforms with the 
NAMUR Standard 
NE42. If disabled 
(0) the 
analogoutput stays 
in his equivalent 
range (e.g. 4‐
20mA) 

0x0177  OUT2AnalogValue The value from the  0,0  OUT2Analog MRS  4  FloatT  R/W 


0mA  slot used for the  Value20mA 
0mA scaling point 
0x017B  OUT2AnalogValue The value from the  0,0  OUT2Analog MRS  4  FloatT  R/W 
4mA  slot used for the  Value20mA 
4mA scaling point 

0x017F  OUT2AnalogValue The value from the  100,0  MRE  OUT2Analog 4  FloatT  R/W 


20mA  slot used for the  Value0mA 
20mA scaling point 

0x0183  OUT2AnalogValue The value from the  0,0  OUT2Analog MRS  4  FloatT  R/W 


0V  slot used for the  Value10V 
0V scaling point 

0x0187  OUT2AnalogValue The value from the  0,0  OUT2Analog MRS  4  FloatT  R/W 


2V  slot used for the  Value10V 
2V scaling point 

0x018B  OUT2AnalogValue The value from the  100,0  MRE  OUT2Analog 4  FloatT  R/W 


10V  slot used for the  Value0V 
10V scaling point 

page 62 MIM K21/0620


MIM-
Index  Name  Description  Factory default  Max Value  Min Value  Length  Data Type  Access 
[hex]  [Bytes] 
0x018F  OUT2PulseVolume  The volume  1,0  999,9  0,0  4  FloatT  R/W 
represented by 
one pulse  

0x0193  OUT2PulseVolume Unit used for the  1  (0) ‐ USER  1  UIntegerT  R/W 


Unit  pulse output   (1) ‐ L 
(2) ‐ mL 
(3) ‐ m3 
(4) ‐ galUS 
(5) ‐ galUK 
(6) ‐ Barrel            
0x0194  OUT2PulseVolume User Unit used for  1,0  9999,9  0,0  4  FloatT  R/W 
UnitUser  the pulse output  

0x0198  OUT2PulseWidth  The width of each  1  20000  1  2  UIntegerT  R/W 


pulse 

0x019A  OUT2Frequencyat  The max.  500  1000  50  2  UIntegerT  R/W 


FS  frequency in Hz for 
the output 

0x019C  OUT2Frequency  The overflow  1  100  0  1  UIntegerT  R/W 


Overflow  frequency in 
percent of the max 
frequency 

0x019D  OUT2Frequency  The value from the  0,0  OUT2  MRS  4  FloatT  R/W 


Value0Hz  slot used for the  Frequency 
0Hz scaling point  ValueMaxHz 

0x01A1  OUT2Frequency  The value from the  100,0  MRE  OUT2  4  FloatT  R/W 


ValueMaxHz  slot used for the  Frequency 
max Hz scaling  Value0Hz 
point 

Dosing 
0x01B6  DosingValue  Dosingvalue  0,0  9999,9  0,0  4  FloatT  R/W 

0x01BA  DosingCorrection  Correction value  0,0  Dosing Value  minus Dosing  4  FloatT  R/W 


Value  which is added to  Value 
the dosing value 
for the complete 
dosing counter 

0x01BE  DosingUnit  Unit used for the  1  (0) ‐ USER  1  UIntegerT  R/W 


dosing function   (1) ‐ L 
(2) ‐ mL 
(3) ‐ m3 
(4) ‐ galUS 
(5) ‐ galUK 
(6) ‐ Barrel           

MIM K21/0620 page 63


MIM-
Index  Name  Description  Factory default  Max Value  Min Value  Length  Data Type  Access 
[hex]  [Bytes] 
0x01BF  DosingUnitUser  User Unit used for  1,0  9999,9  0,0  4  FloatT  R/W 
the dosing 
function 

0x01C3  DosingTimeout  Timeout in  0,5  10,0  0,5  4  FloatT  R/W 


seconds for no 
flow 

0x01C7  DosingCounter  Saved dosing  0,0  999999,0  ‐999999,0  4  FloatT  R 


volume counter 
stats 

Service 
0x01CB  ServiceUser  Password for user  0  99999  0  4  UIntegerT  R/W 
Password  service menu and 
main menu 

0x01CF  ServiceUserMenu  Whether main  0  (0) ‐ not locked  1  UIntegerT  R/W 


Locked  menu is locked or  (1) ‐ locked 
not 

0x01D0  SimulationAuto  Auto stop for  10  31  1  1  UIntegerT  R/W 


Stop  Simulation after 
time in minute 

Misc 
0x01D2  LanguageSelection  Language selection  0  (0) ‐ English  1  UIntegerT  R/W 
(1) ‐ German 
(2) ‐ French 
(3) ‐ Spanish 
0x0262  OperatingHours  Operating hours  0  4294967296  0  4  UIntegerT  R 
Count  counter 

Flow 
0x02F6  CutOff  Cut off for flow  0,0  MRE  0,0  4  FloatT  R/W 
value 

0x02FA  Unit  Unit used for flow  1  (0) ‐ USER  1  UIntegerT  R/W 


(1) ‐ L/m 
(2) ‐ mL/m 
(3) ‐ L/h 
(4) ‐ m3/h 
(5) ‐ galUS/m 
(6) ‐ galUS/h 
(7) ‐ galUK/m 
(8) ‐ galUK/h 
(9) – L/s 
(10) – mL/s 
0x02FB  UserUnit  User Unit used for  1,0  9999,9  0,0  4  FloatT  R/W 
flow 

0x0314  SimMode  Mode of the  0  (0) ‐ Static  1  UIntegerT  R/W 


Simulation:   (1) ‐ Triangle 
Static, Triangle or  (2) ‐ Monotonic 
Monotonic 

page 64 MIM K21/0620


MIM-
Index  Name  Description  Factory default  Max Value  Min Value  Length  Data Type  Access 
[hex]  [Bytes] 
0x0315  SimStartValue  Value to start with  0,0  9999,0  ‐9999,0  4  FloatT  R/W 
the simulation 

0x0319  SimIncrement  Incrementation  10,0  999,0  ‐999,0  4  FloatT  R/W 


Value  value of the 
simulation 

0x031D  SimNumber  Number of  20  65000  1  2  UIntegerT  R/W 


Intervals  intervals to 
simulation 

0x031F  SimTimingIntervals  Timinig in ms  50  50000  50  2  UIntegerT  R/W 


between intervals 

0x0321  ValueInSiUnit  Saved flow value in  0,0  999999,0  ‐999999,0  4  FloatT  R 


SI unit [L/min] 

0x0325  MinValueInSiUnit  Saved min flow  0,0  999999,0  ‐999999,0  4  FloatT  R 


value in SI unit 
[L/min] 

0x0329  MaxValueInSiUnit  Saved max flow  0,0  999999,0  ‐999999,0  4  FloatT  R 


value in SI unit 
[L/min] 

Volume 
0x0359  CountingType  counting type for a  0  (0) ‐ absolute  1  UIntegerT  R/W 
volume slot ‐>   (1) ‐ bidirectional 
absolute or 
bidirectional 

0x035E  Unit  Unit used for  1  (0) ‐ USER  1  UIntegerT  R/W 


volume  (1) ‐ L 
(2) ‐ mL 
(3) ‐ m3 
(4) ‐ galUS 
(5) ‐ galUK 
(6) ‐ Barrel         
0x035F  UserUnit  User Unit used for  1,0  9999,9  0,0  4  FloatT  R/W 
volume 

0x0385  ValueInSiUnit  Saved volume  0,0  999999,0  ‐999999,0  4  FloatT  R 


value in SI unit [L] 

Temperature 

MIM K21/0620 page 65


MIM-
Index  Name  Description  Factory default  Max Value  Min Value  Length  Data Type  Access 
[hex]  [Bytes] 
0x03C2  Unit  Unit used for  1  (0) ‐ USER  1  UIntegerT  R/W 
temperature  (1) ‐ °C 
(2) ‐ °F 

0x03C3  UserUnit  User Unit used for  1,0  9999,9  0,0  4  FloatT  R/W 


temperature 

0x03DC  SimMode  Mode of the  0  (0) ‐ Static  1  UIntegerT  R/W 


Simulation:   (1) ‐ Triangle 
Static,Triangle or  (2) ‐ Monotonic 
Monotonic 

0x03DD  SimStartValue  Value to start with  0,0  9999,0  ‐9999,0  4  FloatT  R/W 


the simulation 

0x03E1  SimIncrement  Incrementation  10,0  999,0  ‐999,0  4  FloatT  R/W 


Value  value of the 
simulation 

0x03E5  SimNumber  Number of  20  65000  1  2  UIntegerT  R/W 


Intervals  intervals to 
simulation 

0x03E7  SimTimingIntervals  Timinig [ms]  50  50000  50  2  UIntegerT  R/W 


between intervals 

0x03E9  ValueInSiUnit  Saved temperature  0,0  999999,0  ‐999999,0  4  FloatT  R 


value in SI unit [°C] 

0x03ED  MinValueInSiUnit  Saved min  0,0  999999,0  ‐999999,0  4  FloatT  R 


temperature value 
in SI unit [°C] 

0x03F1  MaxValueInSiUnit  Saved max  0,0  999999,0  ‐999999,0  4  FloatT  R 


temperature value 
in SI unit [°C] 

Part Volume 
0x0421  CountingType  counting type for a  0  (0) ‐ absolute  1  UIntegerT  R/W 
volume slot ‐>   (1) ‐ bidirectional 
absolute or 
bidirectional 

0x0426  Unit  Unit used for part  1  (0) ‐ USER  1  UIntegerT  R/W 


volume  (1) ‐ L 
(2) ‐ mL 
(3) ‐ m3 
(4) ‐ galUS 
(5) ‐ galUK 
(6) ‐ Barrel            

page 66 MIM K21/0620


MIM-
Index  Name  Description  Factory default  Max Value  Min Value  Length  Data Type  Access 
[hex]  [Bytes] 
0x0427  UserUnit  User Unit used for  1,0  9999,9  0,0  4  FloatT  R/W 
part volume 

0x0440  SimMode  Mode of the  0  (0) ‐ Static  1  UIntegerT  R/W 


Simulation:   (1) ‐ Triangle 
Static, Triangle or  (2) ‐ Monotonic 
Monotonic 

0x0441  SimStartValue  Value to start with  0,0  9999,0  ‐9999,0  4  FloatT  R/W 


the simulation 

0x0445  SimIncrement  Incrementation  10,0  999,0  ‐999,0  4  FloatT  R/W 


Value  value of the 
simulation 

0x0449  SimNumber  Number of  20  65000  1  2  UIntegerT  R/W 


Intervals  intervals to 
simulation 

0x044B  SimTimingIntervals  Timinig [ms]  50  50000  50  2  UIntegerT  R/W 


between intervals 

0x044D  ValueInSiUnit  Saved part volume  0,0  999999,0  ‐999999,0  4  FloatT  R 


value in SI unit [L] 

Legend
MRE Measuring Range End
MRS Measuring Range Start

MIM K21/0620 page 67


MIM-

18. Manufacturer’s declaration

MANUFACTURER'S
DECLARATION OF
CONFORMITY
We:

Kobold Messring GmbH


Nordring 22-24
65719 Hofheim
Germany

declare under our own responsibility that the product(s):

MIM-1********** (IO-Link Device)

to which this declaration refers conform to:

  IO-Link Interface and System Specification, V1.1,


July 2013 (NOTE 1,2)
 IO Device Description, V1.1, August 2011
  IO-Link Interface and System Specification, V1.0,
January 2009 (NOTE 1)
 IO Device Description, V1.0.1, March 2010

The conformity tests are documented in the test report:


IO-Link_Device_TestReport_MIM_190301.pdf

Issued at Hofheim, 01.03.2019

Harald Peters Manfred Wenzel


General Manager Proxy Holder

Reproduction and all distribution without written authorization prohibited

NOTE 1 Relevant Test specification is V1.1, July 2014


NOTE 2 Additional validity in Corrigendum Package 2015

page 68 MIM K21/0620


MIM-
19. EU Declaration of Conformance
We, KOBOLD Messring GmbH, Hofheim-Ts, Germany, declare under our sole
responsibility that the product:

Electromagnetic Flowmeter Model: MIM -1xxxxxxxxxx

to which this declaration relates is in conformity with the standards noted below:

EN 61326-1:2013 Electrical equipment for measurement, control and


laboratory use - EMC requirements - Part 1: General
requirements

EN 60529:2014 Degrees of protection provided by enclosures (IP Code)

EN 50581:2012 Technical documentation for the assessment of electrical


and electronic products with respect to the restriction of
hazardous substances

Also the following EC guidelines are fulfilled:

2014/30/EU EMC Directive

2011/65/EU RoHS (category 9)

2015/863/EU Delegated Directive (RoHS III)

Additional for MIM-13xxx:

Regulation (EC) No 1935/2004 materials and articles intended to come into


contact with food and repealing

Hofheim, 31 July 2019


H. Peters M. Wenzel
General Manager Proxy Holder

MIM K21/0620 page 69

You might also like