1MRK511404-BEN B en Product Guide Bay Control REC670 Version 2.2 PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 143

R E L I O N ® 670 SERIES

Bay control REC670


Version 2.2
Product guide
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Contents

1. Application..................................................................... 3 15. Monitoring................................................................... 38


2. Available functions..........................................................9 16. Metering......................................................................41
3. Control......................................................................... 25 17. Human machine interface............................................42
4. Differential protection.................................................... 28 18. Basic IED functions..................................................... 42
5. Wide area measurement system...................................28 19. Ethernet...................................................................... 42
6. Current protection........................................................ 28 20. Station communication ...............................................43
7. Voltage protection........................................................ 30 21. Remote communication.............................................. 44
8. Frequency protection....................................................31 22. Hardware description.................................................. 45
9. Multipurpose protection................................................32 23. Connection diagrams.................................................. 48
10. General calculation...................................................... 32 24. Technical data............................................................. 49
11. Secondary system supervision.................................... 32 25. Ordering for customized IED......................................121
12. Control........................................................................ 33 26. Ordering for pre-configured IED.................................132
13. Scheme communication..............................................35 27. Ordering for Accessories........................................... 138
14. Logic...........................................................................36

Disclaimer

The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any
errors that may appear in this document. Drawings and diagrams are not binding.
© Copyright 2017 ABB.
All rights reserved.
Trademarks

ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
2 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2 Issued: March 2018
Revision: B

1. Application Duplex communication channels for transfer of up to 192


M13637-3 v13
The Intelligent Electronic Device (IED) is used for the control, intertrip and binary signals are available on each remote-end
protection and monitoring of different types of bays in power data communication card (LDCM). Typical applications are
networks. The IED is especially suitable for applications in the communication between IEDs inside the station or with
control systems where the IEC 61850–8–1 Ed 1 or Ed 2 IEDs in a remote station as remote I/O.
station bus features of the IED can be fully utilized. It is used
for station-wide interlocking via GOOSE messages and The IED can be used in applications with the IEC/UCA
vertical client-server MMS communication to a local station or 61850-9-2LE process bus with up to eight Merging Units
remote SCADA operator workplace. This supports the (MU). Each MU has eight analogue channels, four current and
architecture with distributed control IEDs in all bays with high four voltages. Conventional input transformer module and
demands on reliability. Redundant communication is obtained Merging Unit channels can be mixed freely in your application.
through the built-in PRP and HSR features which can be used
Logic is prepared with a graphical tool. The advanced logic
in star or ringbus architectures. The IED can be used on all
capability allows special applications such as automatic
voltage levels. It is suitable for the control of all apparatuses
opening of disconnectors in multi-breaker arrangements,
in any type of switchgear arrangement.
closing of breaker rings, load transfer logics and so on. The
The control is performed from remote (SCADA/Station) graphical configuration tool ensures simple and fast testing
through the IEC 61850–8–1 Ed1 or Ed2 station and commissioning.
communication or from the built-in multi-display local HMI.
Forcing of binary inputs and outputs is a convenient way to
Cyber security measures are implemented to secure safe
test wiring in substations as well as testing configuration logic
autonomous operation of the protection and control functions
in the IEDs. Basically it means that all binary inputs and
even if simultaneous cyber attacks occur. For all common
outputs on the IED I/O modules (BOM, BIM, IOM & SOM) can
types of switchgear arrangements, there are different pre-
be forced to arbitrary values.
configurations for control and interlocking. One control IED
can be used for single bay or multi-bay applications. The Central Account Management is an authentication
control operation is based on the select-before-execute infrastructure that offers a secure solution for enforcing
principle to give highest possible security. There are access control to IEDs and other systems within a substation.
synchrocheck functions available to assist optimal breaker This incorporates management of user accounts, roles and
closing at the right instance in synchronous as well as certificates and the distribution of such, a procedure
asynchronous networks. completely transparent to the user.

A number of protection functions are available for flexibility in Flexible Product Naming allows the customer to use an IED-
use for different station types and busbar arrangements. To vendor independent IEC 61850 model of the IED. This
fulfil the user's application requirements, the IED features, for customer model will be used as the IEC 61850 data model,
example, up to six instantaneous phase and earth overcurrent but all other aspects of the IED will remain unchanged (e.g.,
functions, 4–step directional or non-directional delayed-phase names on the local HMI and names in the tools). This offers
and earth overcurrent functions, thermal overload and significant flexibility to adapt the IED to the customers'
frequency functions, two instances of 2–step under- and system and standard solution.
overvoltage functions, autorecloser functions and several SEMOD51278-4 v11

different measuring functions. This, together with the multi- Four packages have been defined for following applications:
display local HMI that can show one or more pages per
feeder allows using the IED for protection and control for up • Single breaker (double or single bus) arrangement (A30)
to six bays in a substation. • Double breaker arrangement (B30)
• 1 ½ breaker arrangement for a complete diameter (C30)
The auto-reclose for single-, two-, and/or three-phase reclose • Single breaker (double bus) arrangement with PMU
includes priority circuits for multi-breaker arrangements. It co- functionality (D30)
operates with the synchrocheck function with high-speed or
delayed reclosing. Several breaker failure functions are Optional functions are available in PCM600 Application
available to provide a breaker failure function independent Configuration Tool and can be configured by the user.
from the protection IEDs, also for a complete one- and a half Interface to analog and binary IO:s are configurable without
breaker diameter. need of configuration changes. Analog and control circuits
have been pre-defined. Other signals need to be applied as
Disturbance recording and fault locator are available to allow required for each application. The main differences between
independent post-fault analysis after primary disturbances in the packages above are the interlocking modules and the
case of a failure in the protection system. number of apparatuses to control.

ABB 3
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Description of configuration A30


M15200-3 v7

WA1 REC670 A30 – Double busbar in single breaker arrangement 12AI (6I + 6U)

WA2 3 Control 3 Control 3 Control


S CILO S CSWI S XSWI
QB1 QB2
3 Control 3 Control 3 Control
S CILO S CSWI S XSWI

WA2_VT MET UN
VN MMXU

QC1 WA1_VT 3 Control 3 Control 3 Control


S CILO S CSWI S XSWI

QA1 3 Control 3 Control 3 Control MET UN 25 SC/VC


S CILO S CSWI S XCBR VN MMXU SES RSYN

QC2
3 Control 3 Control 3 Control
S CILO S CSWI S XSWI

LINE_CT Control
Control
Control MET I MET Isqi MET P/Q U>/I<
SSSCBR
S SCBR
SCBR C MMXU C MSQI CV MMXN FUF SPVC

3 Control 3 Control 3 Control MET W/Varh


S CILO S CSWI S XSWI ETP MMTR
QB9
3 Control 3 Control 3 Control 63 71
S CILO S CSWI S XSWI S SIMG S SIML
QC9
DFR/SER DR 3 Control 3 Control

LINE_VT DRP RDRE Q CBAY Q CRSV

MET U MET Usqi MET UN


V MMXU V MSQI VN MMXU

Other Functions available from the function library

46 Iub> 52PD PD 87 INd/I 21FL FL 27 3U< 3 Control 94 1 0 84 84


BRC PTOC CC PDSC CCS SPVC LMB RFLO LOV PTUV R ESIN SMP PTRC TCL YLTC TCM YLTC

60 Ud>
VDC PTOV

Optional Functions

50BF 3I>BF 2(I>/U<) 85 85 50N IN>> 51N_67N 4(IN>) 32 P> 37 P< 87 Id>
CC RBRF CV GAPC EC PSCH ECRW PSCH EF PIOC EF4 PTOC GOP PDOP GUP PDUP HZ PDIF

26 θ> 26 θ> 46I2 4(I2>) 51_67 4(3I>) 59 2(3U>) 50 3I>> 59N 2(U0>) 81 df/dt<>
LC PTTR LF PTTR NS4 PTOC OC4 PTOC OV2 PTOV PH PIOC PMU REP ROV2 PTOV SA PFRC

81 f> 81 f< 67N IN> 79 5(0 1) 50STB 3I>STB 49 θ> 90 U↑↓ 90 U↑↓ 27 2(3U<)
SA PTOF SA PTUF SDE PSDE SMB RREC STB PTOC TR PTTR TR1 ATCC TR8 ATCC UV2 PTUV

60 Ud> 51V 2(I>/U<) 85 85


VD SPVC VR PVOC ZCLC PSCH ZC PSCH ZCRW PSCH

IEC05000837-5-en.vsd

IEC05000837 V5 EN-US

Figure 1. Configuration diagram for configuration A30

4 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Description of configuration B30


M15200-12 v5

WA1
REC670 B30 - Double breaker arrangement 12AI (6I + 6U)
WA2

3 Control 3 Control 3 Control


S CILO S CSWI S XSWI
WA2_VT
QB1 QB2
3 Control 3 Control 3 Control MET UN 25 SC/VC

WA1_VT S CILO S CSWI S XSWI VN MMXU SES RSYN

3 Control 3 Control 3 Control MET UN 25 SC/VC


S CILO S CSWI S XCBR VN MMXU SES RSYN
QA1 QA2
3 Control 3 Control 3 Control
S CILO S CSWI S XCBR

LINE_CT1 Control
Control
Control
SSSSCBR
SCBR
SCBR
MET I MET Isqi U>/I<

LINE_CT2 C MMXU C MSQI FUF SPVC


Control
Control
Control
SSSSCBR
SCBR
SCBR

3 Control 3 Control 3 Control MET P/Q


QB61 QB62
S CILO S CSWI S XSWI CV MMXN

3 Control 3 Control 3 Control MET W/Varh


S CILO S CSWI S XSWI ETP MMTR

3 Control 3 Control 3 Control


S CILO S CSWI S XSWI

3 Control 3 Control 3 Control


QB9 S CILO S CSWI S XSWI
QC9
DFR/SER DR 3 Control 3 Control 63 71
LINE_VT DRP RDRE Q CBAY Q CRSV S SIMG S SIML

MET U MET Usqi MET UN


V MMXU V MSQI VN MMXU

Other Functions available from the function library


46 Iub> 52PD PD 87 INd/I 21FL FL 27 3U< 3 Control 94 1 0 84 84
BRC PTOC CC PSDC CCS SPVC LMB RFLO LOV PTUV R ESIN SMP PTRC TCL YLTC TCM YLTC

60 Ud>
VDC PTOV

Optional Functions
50BF 3I>BF 2(I>/U<) 85 85 50N IN>> 51N_67N 4(IN>) 32 P> 37 P< 87 Id>
CC RBRF CV GAPC EC PSCH ECRW PSCH EF PIOC EF4 PTOC GOP PDOP GUP PDUP HZ PDIF

26 θ 26 θ 46I2 4(I2>) 51_67 4(3I>) 59 2(3U>) 50 3I>> 59N 2(U0>) 81 df/dt<>


LC PTTR LF PTTR NS4 PTOC OC4 PTOC OV2 PTOV PH PIOC PMU REP ROV2 PTOV SA PFRC

f> f< θ U↑↓ U↑↓ 2(3U<)


81 81 67N IN> 79 5(0 1) 50STB 3I>STB 49 90 90 27


SA PTOF SA PTUF SDE PSDE SMB RREC STB PTOC TR PTTR TR1 ATCC TR8 ATCC UV2 PTUV

60 Ud> 51V 2(I>/U<) 85 85


VD SPVC VR PVOC ZCLC PSCH ZC PSCH ZCRW PSCH

=IEC05000838=5=en=Original.vsd
IEC05000838 V5 EN-US

Figure 2. Configuration diagram for configuration B30

ABB 5
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Description of configuration C30


M15200-24 v5

WA1
REC670C30 – Complete one-and a half breaker diameter arrangement 24AI (6I + 6U, 6I+6U)

QB1 3 Control 3 Control 3 Control


S CILO S CSWI S XSWI
WA1_VT

WA1_QA1 3 Control 3 Control 3 Control MET UN 25 SC


25 SC
25 SC/VC
S CILO S CSWI S XCBR VN MMXU SES RSYN
SES RSYN
SES RSYN
WA1_CT Control
Control
Control
SSSCBR
S SCBR
SCBR
MET I MET Isqi MET P/Q U>/I<
Σ
C MMXU C MSQI CV MMXN FUF SPVC
Control
Control
Control
WA1_QB6
SSSCBR
S SCBR
SCBR
LINE1_QB9
3 Control 3 Control 3 Control MET W/Varh
S CILO S CSWI S XSWI ETP MMTR

3 Control 3 Control 3 Control


QB61 S CILO S CSWI S XSWI
LINE1_QC9
3 Control 3 Control 3 Control
S CILO S CSWI S XSWI
LINE1_VT
3 Control 3 Control 3 Control
S CILO S CSWI S XSWI

TIE_QA1
3 Control 3 Control 3 Control MET U MET Usqi MET UN
S CILO S CSWI S XCBR V MMXU V MSQI VN MMXU
TIE_CT
MET I MET Isqi MET P/Q U>/I<
Control
Control
Σ
Control C MMXU C MSQI CV MMXN FUF SPVC
QB62
SSSCBR
S SCBR
SCBR
LINE2_QB9
3 Control 3 Control 3 Control MET W/Varh
S CILO S CSWI S XSWI ETP MMTR

3 Control 3 Control 3 Control

WA2_QB6 S CILO S CSWI S XSWI


WA2_CT
LINE2_QC9
3 Control 3 Control 3 Control DFR/SER DR

LINE2_VT S CILO S CSWI S XSWI DRP RDRE

3 Control 3 Control 3 Control MET U MET Usqi MET UN


S CILO S CSWI S XSWI V MMXU V MSQI VN MMXU

3 Control 3 Control 3 Control 63 71


WA2_QA1 S CILO S CSWI S XCBR S SIMG S SIML
WA2_VT

3 Control 3 Control 3 Control MET UN


S CILO S CSWI S XSWI VN MMXU
QB2
3 Control 3 Control
WA2 Q CBAY Q CRSV

Other Functions available from the function library


46 Iub> 52PD PD 87 INd/I 21FL FL 27 3U< 3 Control 94 1 0 84 84 60 Ud>
BRC PTOC CC PDSC CCS SPVC LMB RFLO LOV PTUV R ESIN SMP PTRC TCL YLTC TCM YLTC VDC PTOV

Optional Functions
50BF 3I>BF U</I> 85 85 50N IN>> 51N_67N 4(IN>) 32 P> 37 P< 87 Id> 26 θ>
CC RBRF CV GAPC EC PSCH ECRW PSCH EF PIOC EF4 PTOC GOP PDOP GUP PDUP HZ PDIF LC PTTR

26 θ> 46I2 4(I2>) 51_67 4(3I>) 59 2(3U>) 50 3I>> 59N 2(U0>) 81 df/dt<> 81 f> 81 f<
LF PTTR NS4 PTOC OC4 PTOC OV2 PTOV PH PIOC PMU REP ROV2 PTOV SA PFRC SA PTOF SA PTUF

67N IN> 79 5(0 1) 50STB 3I>STB 49 θ> 90 U↑↓ 90 U↑↓ 27 2(3U<) 60 Ud> 51V 2(I>/U<)

SDE PSDE SMB RREC STB PTOC TR PTTR TR1 ATCC TR8 ATCC UV2 PTUV VD SPVC VR PVOC ZCLC PSCH

85 85
ZC PSCH ZCRW PSCH

IEC05000839-5-en.vsd

IEC05000839 V5 EN-US

Figure 3. Configuration diagram for configuration C30

6 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Description of configuration D30


GUID-15D86A4C-4D37-432E-8DC2-518814830097 v1

WA1 REC670 D30 – Double busbar in single breaker arrangement with PMU functionality
12AI (6I + 6U)

WA2 3 Control 3 Control 3 Control

S CILO S CSWI S XSWI


QB1 QB2
3 Control 3 Control 3 Control

S CILO S CSWI S XSWI

WA2_VT MET UN
VN MMXU

QC1 WA1_VT 3 Control 3 Control 3 Control

S CILO S CSWI S XSWI

QA1 3 Control 3 Control 3 Control MET UN 25 SC/VC


S CILO S CSWI S XCBR VN MMXU SES RSYN
QC2
3 Control 3 Control 3 Control

S CILO S CSWI S XSWI

LINE_CT Control
Control
Control MET I MET Isqi MET P/Q U>/I<
SSCBR
S
S SCBR
SCBR C MMXU C MSQI CV MMXN FUF SPVC

3 Control 3 Control 3 Control MET W/Varh


S CILO S CSWI S XSWI ETP MMTR
QB9
3 Control 3 Control 3 Control

S CILO S CSWI S XSWI


QC9 Pha sor data
DFR/SER DR 3 Control 3 Control IEEE Std 1344

LINE_VT DRP RDRE Q CBAY Q CRSV PMU REP IEEE Std C37.118

MET U MET Usqi MET UN


V MMXU V MSQI VN MMXU

Other Functions available from the function library


46 Iub> 52PD PD 87 INd/I 21FL FL 27 3U< 3 Control 94 1 0 84 84
BRC PTOC CC PDSC CCS SPVC LMB RFLO LOV PTUV R ESIN SMP PTRC TCL YLTC TCM YLTC

60 Ud>
VDC PTOV

Optional Functions

50BF 3I>BF 2(I>/U<) 85 85 50N IN>> 51N_67N 4(IN>) 32 P> 37 P< 87 Id>
CC RBRF CV GAPC EC PSCH ECRW PSCH EF PIOC EF4 PTOC GOP PDOP GUP PDUP HZ PDIF

26 θ> 26 θ> 46I2 4(I2>) 51_67 4(3I>) 59 2(3U>) 50 3I>> 59N 2(U0>) 81 df/dt<> 81 f>
LC PTTR LF PTTR NS4 PTOC OC4 PTOC OV2 PTOV PH PIOC ROV2 PTOV SA PFRC SA PTOF

81 f< 67N IN> 79 5(0 1) 50STB 3I>STB 49 θ> 90 U↑↓ 90 U↑↓ 27 2(3U<) 60 Ud>
SA PTUF SDE PSDE SMB RREC STB PTOC TR PTTR TR1 ATCC TR8 ATCC UV2 PTUV VD SPVC

51V 2(I>/U<) 85 85
VR PVOC ZCLC PSCH ZC PSCH ZCRW PSCH
IEC16000194=IEC16000194=1=en=Original
.vsdx

IEC16000194 V1 EN-US

Figure 4. Configuration diagram for configuration D30

GUID-79B8BC84-4AAB-44E7-86CD-FF63098B009D v2

ABB 7
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

The basic delivery includes one binary input module and one are specific to the system, object or application. Optional
binary output module, which is sufficient for the default functions and optional IO ordered will not be configured at
configured IO to trip and close circuit breaker. All IEDs can be delivery. It should be noted that the standard only includes
reconfigured with the help of the application configuration tool one binary input and one binary output module and only the
in PCM600. The IED can be adapted to special applications key functions such as tripping are connected to the outputs
and special logic can be developed, such as logic for in the signal matrix tool. The required total IO must be
automatic opening of disconnectors and closing of ring bays, calculated and specified at ordering.
automatic load transfer from one busbar to the other, and so
on. The configurations are as far as found necessary provided
with application comments to explain why the signals have
The basic IED configuration is provided with the signal matrix, been connected in the special way. On request, ABB is
single line diagram and the application configuration prepared available to support the re-configuration work, either directly
for the functions included in the product by default. All or to do the design checking.
parameters should be verified by the customer, since these

8 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

2. Available functions
GUID-F5776DD1-BD04-4872-BB89-A0412B4B5CC3 v1
are not exposed to the user or do not need
to be configured are not described in this
The following tables list all the functions manual.
available in the IED. Those functions that

Main protection functions


GUID-66BAAD98-851D-4AAC-B386-B38B57718BD2 v13

Table 1. Example of quantities

2 = number of basic instances


0-3 = option quantities
3-A03 = optional function included in packages A03 (refer to ordering details)

IEC 61850 or ANSI Function description Bay control


function name

REC670 (C30)

REC670 (D30)
REC670 (B30)
REC670 (A30)
REC670
(Customized)

Differential protection

HZPDIF 87 High impedance differential protection, 0-6 3-A02 3-A02 6-A07 3-A02
single phase

ABB 9
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Back-up protection functions


GUID-A8D0852F-807F-4442-8730-E44808E194F0 v13

IEC 61850 or ANSI Function description Bay control


function name

REC670 (C30)

REC670 (D30)
REC670 (B30)
REC670 (A30)
REC670
(Customized)

Current protection

PHPIOC 50 Instantaneous phase overcurrent 0-6 1-C51 2-C52 2-C53 1-C51


protection

OC4PTOC 51_671) Directional phase overcurrent protection, 0-6 1-C51 2-C52 2-C53 1-C51
four steps

EFPIOC 50N Instantaneous residual overcurrent 0-6 1-C51 2-C52 2-C53 1-C51
protection

EF4PTOC 51N Directional residual overcurrent 0-6 1-C51 2-C52 2-C53 1-C51
67N2) protection, four steps

NS4PTOC 46I2 Four step directional negative phase 0-6 1-C51 2-C52 2-C53 1-C51
sequence overcurrent protection

SDEPSDE 67N Sensitive directional residual overcurrent 0-6 1-C16 1–C16 1-C16 1-C16
and power protection

LCPTTR 26 Thermal overload protection, one time 0-6 1-C51 1-C52 2-C53 1-C51
constant, Celsius

LFPTTR 26 Thermal overload protection, one time 0-6 1-C51 1-C52 2-C53 1-C51
constant, Fahrenheit

TRPTTR 49 Thermal overload protection, two time 0-6 1-C51 1-C52 2-C53 1-C51
constants

CCRBRF 50BF Breaker failure protection 0-6 1-C51 2-C52 3-C53 1-C51

STBPTOC 50STB Stub protection 0-6 1-B27 2-B25 2-B25 1-B27

CCPDSC 52PD Pole discordance protection 0-6 1 2 3 1

GUPPDUP 37 Directional underpower protection 0-2 1-C35 1-C35 1-C35 1-C35

GOPPDOP 32 Directional overpower protection 0-2 1-C35 1-C35 1-C35 1-C35

BRCPTOC 46 Broken conductor check 0-1 1 1 1 1

CBPGAPC Capacitor bank protection 0-3

VRPVOC 51V Voltage restrained overcurrent protection 0-3 1-C35 1-C35 1-C35 1-C35

Voltage protection

UV2PTUV 27 Two step undervoltage protection 0-2 2-D02 2-D02 2-D02 2-D02

OV2PTOV 59 Two step overvoltage protection 0-2 2-D02 2-D02 2-D02 2-D02

ROV2PTOV 59N Two step residual overvoltage protection 0-2 2-D02 2-D02 2-D02 2-D02

VDCPTOV 60 Voltage differential protection 0-6 2 2 2 2

LOVPTUV 27 Loss of voltage check 0-2 1 1 2 1

Frequency protection

10 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

IEC 61850 or ANSI Function description Bay control


function name

REC670 (C30)

REC670 (D30)
REC670 (B30)
REC670 (A30)
REC670
(Customized)

SAPTUF 81 Underfrequency protection 0-6 6-E01 6-E01 6-E01 6-E01

SAPTOF 81 Overfrequency protection 0-6 6-E01 6-E01 6-E01 6-E01

SAPFRC 81 Rate-of-change of frequency protection 0-6 6-E01 6-E01 6-E01 6-E01

FTAQFVR 81A Frequency time accumulation protection 0-12

Multipurpose protection

CVGAPC General current and voltage protection 0-9 4-F01 4-F01 4-F01 4-F01

General calculation

SMAIHPAC Multipurpose filter 0-6

1) 67 requires voltage
2) 67N requires voltage

ABB 11
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Control and monitoring functions


GUID-E3777F16-0B76-4157-A3BF-0B6B978863DE v16

IEC 61850 or ANSI Function description Bay control


function name

REC670 (C30)

REC670 (D30)
REC670 (B30)
REC670 (A30)
REC670
(Customized)

Control

SESRSYN 25 Synchrocheck, energizing 0-6 1 2 3 1


check and synchronizing

SMBRREC 79 Autorecloser 0-6 1-H04 2-H05 3-H06 1-H04

APC10 3 Control functionality for a 0-1 1 1


single bay, max 10 objects
(1CB), including
interlocking (see Table 3)

APC15 3 Control functionality for a 0-1 1


single bay, max 15 objects
(2CB), including
interlocking (see Table 4)

APC30 3 Control functionality for up 0-1 1


to 6 bays, max 30 objects
(6CBs), including
interlocking (see Table 5)

QCBAY Bay control 1+5/APC30 1 1 1+5/ 1


APC30

LOCREM Handling of LR-switch 1+5/APC30 1 1 1+5/ 1


positions APC30

LOCREMCTRL LHMI control of PSTO 1 1 1 1 1

SXCBR Circuit breaker 18 3 6 18 3

TR1ATCC 90 Automatic voltage control 0-4 1-H11 1-H11 2-H16 1-H11


for tap changer, single
control

TR8ATCC 90 Automatic voltage control 0-4 1-H15 1-H15 2-H18 1-H15


for tap changer, parallel
control

TCMYLTC 84 Tap changer control and 0-4 4 4 4 4


supervision, 6 binary
inputs

TCLYLTC 84 Tap changer control and 0-4 4 4 4 4


supervision, 32 binary
inputs

SLGAPC Logic rotating switch for 15 15 15 15 15


function selection and
LHMI presentation

VSGAPC Selector mini switch 30 30 30 30 30

DPGAPC Generic communication 16 16 16 16 16


function for Double Point
indication

SPC8GAPC Single point generic 5 5 5 5 5


control function 8 signals
12 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

IEC 61850 or ANSI Function description Bay control


function name

REC670 (C30)

REC670 (D30)
REC670 (B30)
REC670 (A30)
REC670
(Customized)

AUTOBITS Automation bits, command 3 3 3 3 3


function for DNP3.0

SINGLECMD Single command, 16 4 4 4 4 4


signals

I103CMD Function commands for 1 1 1 1 1


IEC 60870-5-103

I103GENCMD Function commands 50 50 50 50 50


generic for IEC
60870-5-103

I103POSCMD IED commands with 50 50 50 50 50


position and select for IEC
60870-5-103

I103POSCMDV IED direct commands with 50 50 50 50 50


position for IEC
60870-5-103

I103IEDCMD IED commands for IEC 1 1 1 1 1


60870-5-103

I103USRCMD Function commands user 4 4 4 4 4


defined for IEC
60870-5-103

Secondary system
supervision

CCSSPVC 87 Current circuit supervision 0-6 1 2 3 1

FUFSPVC Fuse failure supervision 0-4 3 3 3 3

VDSPVC 60 Fuse failure supervision 0-2 1-G03 1-G03 1-G03 1-G03


based on voltage
difference

Logic

SMPPTRC 94 Tripping logic 12 12 12 12 12

SMAGAPC General start matrix block 12 12 12 12 12

STARTCOMB Start combinator 32 32 32 32 32

TMAGAPC Trip matrix logic 12 12 12 12 12

ALMCALH Logic for group alarm 5 5 5 5 5

WRNCALH Logic for group warning 5 5 5 5 5

INDCALH Logic for group indication 5 5 5 5 5

AND, GATE, INV, Basic configurable logic 40-420 40-420 40-420 40-420 40-420
LLD, OR, blocks (see Table 2)
PULSETIMER,
RSMEMORY,
SRMEMORY,
TIMERSET, XOR

ABB 13
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

IEC 61850 or ANSI Function description Bay control


function name

REC670 (C30)

REC670 (D30)
REC670 (B30)
REC670 (A30)
REC670
(Customized)

ANDQT, Configurable logic blocks 0-1 1 1 1 1


INDCOMBSPQT, Q/T (see Table 6)
INDEXTSPQT,
INVALIDQT,
INVERTERQT,
ORQT,
PULSETIMERQT,
RSMEMORYQT,
SRMEMORYQT,
TIMERSETQT,
XORQT

AND, GATE, INV, Extension logic package 0-1


LLD, OR, (see Table 7)
PULSETIMER,
RSMEMORY,
SLGAPC,
SRMEMORY,
TIMERSET,
VSGAPC, XOR

FXDSIGN Fixed signal function block 1 1 1 1 1

B16I Boolean to integer 18 18 18 18 18


conversion, 16 bit

BTIGAPC Boolean to integer 16 16 16 16 16


conversion with logical
node representation, 16 bit

IB16 Integer to Boolean 16 18 18 18 18 18


conversion

ITBGAPC Integer to Boolean 16 16 16 16 16 16


conversion with Logic
Node representation

TEIGAPC Elapsed time integrator 12 12 12 12 12


with limit transgression
and overflow supervision

INTCOMP Comparator for integer 30 30 30 30 30


inputs

REALCOMP Comparator for real inputs 30 30 30 30 30

14 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Table 2. Total number of instances for basic configurable logic blocks

Basic configurable logic block Total number of instances

AND 280

GATE 40

INV 420

LLD 40

OR 298

PULSETIMER 40

RSMEMORY 40

SRMEMORY 40

TIMERSET 60

XOR 40

Table 3. Number of function instances in APC10

Function name Function description Total number of instances

SCILO Interlocking 10

BB_ES 3

A1A2_BS 2

A1A2_DC 3

ABC_BC 1

BH_CONN 1

BH_LINE_A 1

BH_LINE_B 1

DB_BUS_A 1

DB_BUS_B 1

DB_LINE 1

ABC_LINE 1

AB_TRAFO 1

SCSWI Switch controller 10

SXSWI Circuit switch 9

QCRSV Apparatus control 2

RESIN1 1

RESIN2 59

POS_EVAL Evaluation of position indication 10

XLNPROXY Proxy for signals from switching device via 12


GOOSE

GOOSEXLNRCV GOOSE function block to receive a switching 12


device

ABB 15
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Table 4. Number of function instances in APC15

Function name Function description Total number of instances

SCILO Interlocking 15

BB_ES 3

A1A2_BS 2

A1A2_DC 3

ABC_BC 1

BH_CONN 1

BH_LINE_A 1

BH_LINE_B 1

DB_BUS_A 1

DB_BUS_B 1

DB_LINE 1

ABC_LINE 1

AB_TRAFO 1

SCSWI Switch controller 15

SXSWI Circuit switch 14

QCRSV Apparatus control 2

RESIN1 1

RESIN2 59

POS_EVAL Evaluation of position indication 15

XLNPROXY Proxy for signals from switching device via 20


GOOSE

GOOSEXLNRCV GOOSE function block to receive a switching 20


device

16 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Table 5. Number of function instances in APC30

Function name Function description Total number of instances

SCILO Interlocking 30

BB_ES 6

A1A2_BS 4

A1A2_DC 6

ABC_BC 2

BH_CONN 2

BH_LINE_A 2

BH_LINE_B 2

DB_BUS_A 3

DB_BUS_B 3

DB_LINE 3

ABC_LINE 6

AB_TRAFO 4

SCSWI Switch controller 30

SXSWI Circuit switch 24

QCRSV Apparatus control 6

RESIN1 1

RESIN2 59

POS_EVAL Evaluation of position indication 30

QCBAY Bay control 5

LOCREM Handling of LR-switch positions 5

XLNPROXY Proxy for signals from switching device via 42


GOOSE

GOOSEXLNRCV GOOSE function block to receive a switching 42


device

Table 6. Total number of instances for configurable logic blocks Q/T

Configurable logic blocks Q/T Total number of instances

ANDQT 120

INDCOMBSPQT 20

INDEXTSPQT 20

INVALIDQT 22

INVERTERQT 120

ORQT 120

PULSETIMERQT 40

RSMEMORYQT 40

SRMEMORYQT 40

TIMERSETQT 40

XORQT 40

ABB 17
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Table 7. Total number of instances for extended logic package

Extended configurable logic block Total number of instances

AND 180

GATE 49

INV 180

LLD 49

OR 180

PULSETIMER 89

RSMEMORY 40

SLGAPC 74

SRMEMORY 130

TIMERSET 109

VSGAPC 120

XOR 89

18 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

IEC 61850 or ANSI Function description Bay control


function name

REC670 (C30)

REC670 (D30)
REC670 (B30)
REC670 (A30)
REC670
(Customized)

Monitoring

CVMMXN Power system 6 6 6 6 6


measurement

CMMXU Current measurement 10 10 10 10 10

VMMXU Voltage measurement 6 6 6 6 6


phase-phase

CMSQI Current sequence 6 6 6 6 6


measurement

VMSQI Voltage sequence 6 6 6 6 6


measurement

VNMMXU Voltage measurement 6 6 6 6 6


phase-earth

EVENT Event function 20 20 20 20 20

DRPRDRE, Disturbance report 1 1 1 1 1


A4RADR,

SPGAPC Generic communication 64 64 64 64 64


function for Single Point
indication

SP16GAPC Generic communication 24 24 24 24 24


function for Single Point
indication 16 inputs

MVGAPC Generic communication 24 24 24 24 24


function for measured
values

BINSTATREP Logical signal status report 3 3 3 3 3

RANGE_XP Measured value expander 66 66 66 66 66


block

SSIMG 63 Insulation supervision for 21 21 21 21 21


gas medium

SSIML 71 Insulation supervision for 3 3 3 3 3


liquid medium

SSCBR Circuit breaker condition 0-18 3 6 9 3


monitoring

LMBRFLO Fault locator 0-1 1 1 1 1

LOLSPTR 26/49 Transformer insulation 0-4 4-M21 4-M21 4-M21 4-M21


HS loss of life monitoring

I103MEAS Measurands for IEC 1 1 1 1 1


60870-5-103

I103MEASUSR Measurands user defined 3 3 3 3 3


signals for IEC
60870-5-103

ABB 19
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

IEC 61850 or ANSI Function description Bay control


function name

REC670 (C30)

REC670 (D30)
REC670 (B30)
REC670 (A30)
REC670
(Customized)

I103AR Function status auto- 1 1 1 1 1


recloser for IEC
60870-5-103

I103EF Function status earth-fault 1 1 1 1 1


for IEC 60870-5-103

I103FLTPROT Function status fault 1 1 1 1 1


protection for IEC
60870-5-103

I103IED IED status for IEC 1 1 1 1 1


60870-5-103

I103SUPERV Supervison status for IEC 1 1 1 1 1


60870-5-103

I103USRDEF Status for user defined 20 20 20 20 20


signals for IEC
60870-5-103

L4UFCNT Event counter with limit 30 30 30 30 30


supervision

TEILGAPC Running hour meter 6 6 6 6 6

Metering

PCFCNT Pulse-counter logic 16 16 16 16 16

ETPMMTR Function for energy 6 6 6 6 6


calculation and demand
handling

20 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Communication
GUID-5F144B53-B9A7-4173-80CF-CD4C84579CB5 v16

IEC 61850 or ANSI Function description Bay control


function name

REC670 (C30)

REC670 (D30)
REC670 (B30)
REC670 (A30)
REC670
(Customized)

Station communication

LONSPA, SPA SPA communication protocol 1 1 1 1 1

ADE LON communication protocol 1 1 1 1 1

HORZCOMM Network variables via LON 1 1 1 1 1

DNPGEN DNP3.0 communication general protocol 1 1 1 1 1

MST1TCP, DNP3.0 for TCP/IP communication protocol 1 1 1 1 1


MST2TCP,
MST3TCP, MST4TCP

IEC 61850-8-1 IEC 61850 1 1 1 1 1

GOOSEINTLKRCV Horizontal communication via GOOSE for 59 59 59 59 59


interlocking

GOOSEBINRCV GOOSE binary receive 16 16 16 16 16

GOOSEDPRCV GOOSE function block to receive a double 64 64 64 64 64


point value

GOOSEINTRCV GOOSE function block to receive an integer 32 32 32 32 32


value

GOOSEMVRCV GOOSE function block to receive a 60 60 60 60 60


measurand value

GOOSESPRCV GOOSE function block to receive a single 64 64 64 64 64


point value

VCTRSEND Horizontal communication via GOOSE for 1 1 1 1 1


VCTR

GOOSEVCTRRCV Horizontal communication via GOOSE for 7 7 7 7 7


VCTR

GOOSEVCTRCONF GOOSE VCTR configuration for send and 1 1 1 1 1


receive

MULTICMDRCV, Multiple command and transmit 60/10 60/10 60/10 60/10 60/10
MULTICMDSND

OPTICAL103 IEC 60870-5-103 Optical serial 1 1 1 1 1


communication

RS485103 IEC 60870-5-103 serial communication for 1 1 1 1 1


RS485

AGSAL Generic security application component 1 1 1 1 1

LD0LLN0 IEC 61850 LD0 LLN0 1 1 1 1 1

SYSLLN0 IEC 61850 SYS LLN0 1 1 1 1 1

LPHD Physical device information 1 1 1 1 1

PCMACCS IED configuration protocol 1 1 1 1 1

ABB 21
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

IEC 61850 or ANSI Function description Bay control


function name

REC670 (C30)

REC670 (D30)
REC670 (B30)
REC670 (A30)
REC670
(Customized)

FSTACCS Field service tool access 1 1 1 1 1

IEC 61850-9-2 Process bus 0-1 1-P30 1-P30 1-P30 1-P30


communication, 8 merging units

ACTIVLOG Activity logging 1 1 1 1 1

ALTRK Service tracking 1 1 1 1 1

PRP IEC 62439-3 Parallel redundancy protocol 0-1 1-P23 1-P23 1-P23 1-P23

HSR IEC 62439-3 High-availability seamless 0-1 1-P24 1-P24 1-P24 1-P24
redundancy

PMUCONF, Synchrophasor report, 8 phasors (see 0-1 1-P32 1-P32 1-P32 1


PMUREPORT, Table 8)
PHASORREPORT1,
ANALOGREPORT1
BINARYREPORT1,
SMAI1 - SMAI12
3PHSUM
PMUSTATUS

PTP Precision time protocol 1 1 1 1 1

SCHLCCH Access point diagnostic for non-redundant 6 6 6 6 6


Ethernet port

RCHLCCH Access point diagnostic for redundant 3 3 3 3 3


Ethernet ports

QUALEXP IEC 61850 quality expander 96 96 96 96 96

Remote communication

BinSignRec1_1 Binary signal transfer receive 3/3/6 3/3/6 3/3/6 3/3/6 3/3/6
BinSignRec1_2
BinSignReceive2

Scheme communication

ZCPSCH 85 Scheme communication logic with delta 0-1 1-K01 1-K01 1-K01 1-K01
based blocking scheme signal transmit

ZCRWPSCH 85 Current reversal and weak-end infeed logic 0-1 1-K01 1-K01 1-K01 1-K01
for distance protection

ZCLCPSCH Local acceleration logic 0-1 1-K01 1-K01 1-K01 1-K01

ECPSCH 85 Scheme communication logic for residual 0-1 1-C51 1-C52 1-C53 1-C51
overcurrent protection

ECRWPSCH 85 Current reversal and weak-end infeed logic 0-1 1-C51 1-C52 1-C53 1-C51
for residual overcurrent protection

22 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Table 8. Number of function instances in Synchrophasor report, 8 phasors

Function name Function description Number of instances

PMUCONF Configuration parameters for C37.118 2011 and IEEE1344 protocol 1

PMUREPORT Protocol reporting via IEEE 1344 and C37.118 1

PHASORREPORT1 Protocol reporting of phasor data via IEEE 1344 and C37.118, phasors 1-8 1

ANALOGREPORT1 Protocol reporting of analog data via IEEE 1344 and C37.118, analogs 1-8 1

BINARYREPORT1 Protocol reporting of binary data via IEEE 1344 and C37.118, binary 1-8 1

SMAI1–SMAI12 Signal matrix for analog inputs 1

3PHSUM Summation block 3 phase 6

PMUSTATUS Diagnostics for C37.118 2011 and IEEE1344 protocol 1

ABB 23
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Basic IED functions


GUID-C8F0E5D2-E305-4184-9627-F6B5864216CA v13

Table 9. Basic IED functions

IEC 61850 or function Description


name

INTERRSIG Self supervision with internal event list

TIMESYNCHGEN Time synchronization module

BININPUT, SYNCHCAN, Time synchronization


SYNCHGPS,
SYNCHCMPPS,
SYNCHLON,
SYNCHPPH,
SYNCHPPS, SNTP,
SYNCHSPA

TIMEZONE Time synchronization

IRIG-B Time synchronization

SETGRPS Number of setting groups

ACTVGRP Parameter setting groups

TESTMODE Test mode functionality

CHNGLCK Change lock function

SMBI Signal matrix for binary inputs

SMBO Signal matrix for binary outputs

SMMI Signal matrix for mA inputs

SMAI1 - SMAI12 Signal matrix for analog inputs

3PHSUM Summation block 3 phase

ATHSTAT Authority status

ATHCHCK Authority check

AUTHMAN Authority management

FTPACCS FTP access with password

ALTMS Time master supervision

ALTIM Time management

COMSTATUS Protocol diagnostic

24 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Table 10. Local HMI functions

IEC 61850 or function ANSI Description


name

LHMICTRL Local HMI signals

LANGUAGE Local human machine language

SCREEN Local HMI Local human machine screen behavior

FNKEYTY1–FNKEYTY5 Parameter setting function for HMI in PCM600


FNKEYMD1–
FNKEYMD5

LEDGEN General LED indication part for LHMI

OPENCLOSE_LED LHMI LEDs for open and close keys

GRP1_LED1– Basic part for CP HW LED indication module


GRP1_LED15
GRP2_LED1–
GRP2_LED15
GRP3_LED1–
GRP3_LED15

3. Control • high-speed and/or delayed auto reclosing


• single and/or three phase auto reclosing
Synchrocheck, energizing check, and synchronizing • support for single or multi-breaker applications.
SESRSYN
M12480-3 v16
The Synchronizing function allows closing of asynchronous
networks at the correct moment including the breaker closing The auto recloser can be used for delayed busbar restoration.
time, which improves the network stability.
Up to five reclosing shots can be performed. The first shot
Synchrocheck, energizing check, and synchronizing can be single-, two-, and /or three-phase depending on the
(SESRSYN) function checks that the voltages on both sides of type of the fault and the selected auto reclosing mode.
the circuit breaker are in synchronism, or with at least one
Several auto reclosing functions can be provided for multi-
side dead to ensure that closing can be done safely.
breaker arrangements. A priority circuit allows one circuit
SESRSYN function includes a built-in voltage selection breaker to reclose first and the second will only close if the
scheme for double bus and 1½ breaker or ring busbar fault proved to be transient.
arrangements.
Each auto reclosing function can be configured to co-operate
Manual closing as well as automatic reclosing can be with the synchrocheck function.
checked by the function and can have different settings.
Apparatus control APC
M13444-3 v15

For systems, which can run asynchronously, a synchronizing The apparatus control functions are used for control and
feature is also provided. The main purpose of the supervision of circuit breakers, disconnectors and earthing
synchronizing feature is to provide controlled closing of circuit switches within a bay. Permission to operate is given after
breakers when two asynchronous systems are in phase and evaluation of conditions from other functions such as
can be connected. The synchronizing feature evaluates interlocking, synchrocheck, operator place selection and
voltage difference, phase angle difference, slip frequency and external or internal blockings.
frequency rate of change before issuing a controlled closing
Apparatus control features:
of the circuit breaker. Breaker closing time is a setting.
• Select-Execute principle to give high reliability
Autorecloser SMBRREC • Selection function to prevent simultaneous operation
M12390-3 v17
The auto recloser (SMBRREC) function provides: • Selection and supervision of operator place
• Command supervision
• Block/deblock of operation
• Block/deblock of updating of position indications
ABB 25
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

• Substitution of position and quality indications Each apparatus control function has interlocking modules
• Overriding of interlocking functions included for different switchyard arrangements, where each
• Overriding of synchrocheck function handles interlocking of one bay. The interlocking
• Operation counter function is distributed to each IED and is not dependent on
• Suppression of mid position any central function. For the station-wide interlocking, the
IEDs communicate via the system-wide interbay bus (IEC
61850-8-1) or by using hard wired binary inputs/outputs. The
Two types of command models can be used:
interlocking conditions depend on the circuit configuration
• Direct with normal security
and apparatus position status at any given time.
• SBO (Select-Before-Operate) with enhanced security
For easy and safe implementation of the interlocking function,
Normal security means that only the command is evaluated the IED is delivered with standardized and tested software
and the resulting position is not supervised. Enhanced interlocking modules containing logic for the interlocking
security means that the command is evaluated with an conditions. The interlocking conditions can be altered, to
additional supervision of the status value of the control meet the customer’s specific requirements, by adding
object. The command sequence with enhanced security is configurable logic by means of the graphical configuration
always terminated by a CommandTermination service tool.
primitive and an AddCause telling if the command was
The following interlocking modules are available:
successful or if something went wrong.
• Line for double and transfer busbars, ABC_LINE
Control operation can be performed from the local HMI with
• Bus coupler for double and transfer busbars, ABC_BC
authority control if so defined.
• Transformer bay for double busbars, AB_TRAFO
M16909-3 v3
Features of the apparatus control function are: • Bus-section breaker for double busbars, A1A2_BS
• Bus-section disconnector for double busbars, A1A2_DC
• Operation of primary apparatuses • Busbar earthing switch, BB_ES
• Select-Execute principle to give high reliability • Double CB Bay, DB_BUS_A, DB_LINE, DB_BUS_B
• Selection and reservation function to prevent • 1 1/2-CB diameter, BH_LINE_A, BH_CONN, BH_LINE_B
simultaneous operation
• Selection and supervision of operator place
Switch controller SCSWI
• Command supervision M13486-3 v10
The Switch controller (SCSWI) initializes and supervises all
• Block/deblock of operation
functions to properly select and operate switching primary
• Block/deblock of updating of position indications
apparatuses. The Switch controller may handle and operate
• Substitution of position indications
on one multi-phase device or up to three one-phase devices.
• Overriding of interlocking functions
• Overriding of synchrocheck Circuit breaker SXCBR
• Pole discordance supervision
M13489-3 v6
The purpose of Circuit breaker (SXCBR) is to provide the
• Operation counter actual status of positions and to perform the control
operations, that is, pass all the commands to primary
The apparatus control function is realized by means of a
apparatuses in the form of circuit breakers via binary output
number of function blocks designated:
boards and to supervise the switching operation and position.
• Bay control QCBAY
Circuit switch SXSWI
• Switch controller SCSWI M16492-3 v6
The purpose of Circuit switch (SXSWI) function is to provide
• Circuit breaker SXCBR
the actual status of positions and to perform the control
• Circuit switch SXSWI
operations, that is, pass all the commands to primary
The three latter functions are logical nodes according to IEC apparatuses in the form of disconnectors or earthing switches
61850-8-1. To realize the reservation function also the via binary output boards and to supervise the switching
function blocks Reservation input (RESIN) and Bay reserve operation and position.
(QCRSV) are included in the apparatus control function.
Reservation function QCRSV
M13506-3 v5

Interlocking The purpose of the reservation (QCRSV) function is primarily


to transfer interlocking information between IEDs in a safe
M13531-3 v4
The interlocking function blocks the possibility to operate
primary switching devices, for instance when a disconnector way and to prevent double operation in a bay, switchyard
is under load, in order to prevent material damage and/or part, or complete substation.
accidental human injury.

26 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Voltage control includes many extra features such as the


Reservation input RESIN possibility to avoid simultaneous tapping of parallel
M16501-3 v5
The Reservation input (RESIN) function receives the transformers, hot stand by regulation of a transformer in a
reservation information from other bays. The number of group which regulates it to a correct tap position even though
instances is the same as the number of involved bays (up to the LV CB is open, compensation for a possible capacitor
60 instances are available). bank on the LV side bay of a transformer, extensive tap
changer monitoring including contact wear and hunting
Bay control QCBAY
M13447-3 v8
detection, monitoring of the power flow in the transformer so
The Bay control (QCBAY) function is used together with Local
that, for example, the voltage control can be blocked if the
remote and local remote control functions to handle the
power reverses, etc.
selection of the operator place per bay. QCBAY also provides
blocking functions that can be distributed to different Logic rotating switch for function selection and LHMI
apparatuses within the bay. presentation SLGAPC
SEMOD114908-4 v11
The logic rotating switch for function selection and LHMI
Proxy for signals from switching device via GOOSE
presentation (SLGAPC) (or the selector switch function block)
XLNPROXY
GUID-11F9CA1C-8E20-489B-822B-34DACC59553A v1
is used to get an enhanced selector switch functionality
The proxy for signals from switching device via GOOSE
compared to the one provided by a hardware selector switch.
(XLNPROXY) gives an internal representation of the position
Hardware selector switches are used extensively by utilities,
status and control response for a switch modelled in a
in order to have different functions operating on pre-set
breaker IED. This representation is identical to that of an
values. Hardware switches are however sources for
SXCBR or SXSWI function.
maintenance issues, lower system reliability and an extended
GOOSE function block to receive a switching device purchase portfolio. The selector switch function eliminates all
GOOSEXLNRCV these problems.
GUID-5AC7DE11-CB95-4565-A8AE-FB23D59FD717 v1
The GOOSE XLN Receive component is used to collect
Selector mini switch VSGAPC
information from another device’s XCBR/XSWI logical node SEMOD158756-5 v10
The Selector mini switch (VSGAPC) function block is a
sent over process bus via GOOSE. The GOOSE XLN Receive
multipurpose function used for a variety of applications, as a
component includes 12 different outputs (and their respective
general purpose switch.
channel valid bits) with defined names to ease the 61850
mapping of the GOOSE signals in the configuration process. VSGAPC can be controlled from the menu, from a symbol on
the single line diagram (SLD) on the local HMI or from Binary
Local remote LOCREM/Local remote control LOCREMCTRL
M17086-3 v10
inputs.
The signals from the local HMI or from an external local/
remote switch are connected via the function blocks local Generic communication function for Double Point indication
remote (LOCREM) and local remote control (LOCREMCTRL) DPGAPC
to the Bay control (QCBAY) function block. The parameter SEMOD55850-5 v7
Generic communication function for Double Point indication
ControlMode in function block LOCREM is set to choose if (DPGAPC) function block is used to send double point
the switch signals are coming from the local HMI or from an position indications to other systems, equipment or functions
external hardware switch connected via binary inputs. in the substation through IEC 61850-8-1 or other
communication protocols. It is especially intended to be used
Voltage control TR1ATCC/TR8ATCC , TCMYLTC/TCLYLTC
M5864-3 v12
in the interlocking station-wide logics.
Automatic voltage control for tap changer, single control
(TR1ATCC), Automatic voltage control for tap changer, Single point generic control 8 signals SPC8GAPC
parallel control (TR8ATCC), Tap changer control and The Single point generic control 8 signals (SPC8GAPC)
SEMOD176462-4 v11

supervision, 6 binary inputs (TCMYLTC) and Tap changer function block is a collection of 8 single point commands that
control and supervision, 32 binary inputs (TCLYLTC) are used can be used for direct commands for example reset of LEDs
for control of power transformers with an on-load tap or putting IED in "ChangeLock" state from remote. In this
changer. The functions provide automatic regulation of the way, simple commands can be sent directly to the IED
voltage on the secondary side of transformers or alternatively outputs, without confirmation. Confirmation (status) of the
on a load point further out in the network. result of the commands is supposed to be achieved by other
means, such as binary inputs and SPGAPC function blocks.
Control of a single transformer, as well as control of up to
The commands can be pulsed or steady with a settable pulse
eight transformers in parallel is possible. For parallel control of
time.
power transformers, three alternative methods are available:
the master-follower method, the circulating current method Automation bits, command function for DNP3.0 AUTOBITS
and the reverse reactance method. The first two methods SEMOD158591-5 v8
Automation bits function for DNP3 (AUTOBITS) is used within
require exchange of information between the parallel PCM600 to get into the configuration of the commands
transformers and this is provided for within IEC 61850-8-1. coming through the DNP3 protocol. The AUTOBITS function

ABB 27
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

plays the same role as functions GOOSEBINRCV (for IEC GUID-8DF29209-252A-4E51-9F4A-B14B669E71AB v4

61850) and MULTICMDRCV (for LON). The phasor measurement reporting block moves the phasor
calculations into an IEEE C37.118 and/or IEEE 1344
Single command, 16 signals synchrophasor frame format. The PMUREPORT block
M12446-6 v5
The IEDs can receive commands either from a substation contains parameters for PMU performance class and
automation system or from the local HMI. The command reporting rate, the IDCODE and Global PMU ID, format of the
function block has outputs that can be used, for example, to data streamed through the protocol, the type of reported
control high voltage apparatuses or for other user defined synchrophasors, as well as settings for reporting analog and
functionality. digital signals.

The message generated by the PMUREPORT function block


4. Differential protection is set in accordance with the IEEE C37.118 and/or IEEE 1344
standards.
High impedance differential protection, single phase HZPDIF
M13071-3 v13
High impedance differential protection, single phase (HZPDIF) There are settings for Phasor type (positive sequence,
functions can be used when the involved CT cores have the negative sequence or zero sequence in case of 3-phase
same turns ratio and similar magnetizing characteristics. It phasor and L1, L2 or L3 in case of single phase phasor),
utilizes an external CT secondary current summation by PMU's Service class (Protection or Measurement), Phasor
wiring. Actually all CT secondary circuits which are involved in representation (polar or rectangular) and the data types for
the differential scheme are connected in parallel. External phasor data, analog data and frequency data.
series resistor, and a voltage dependent resistor which are
both mounted externally to the IED, are also required. Synchrophasor data can be reported to up to 8 clients over
TCP and/or 6 UDP group clients for multicast or unicast
The external resistor unit shall be ordered under IED transmission of phasor data from the IED. More information
accessories in the Product Guide. regarding synchrophasor communication structure and
TCP/UDP configuration is available in Application Manual
HZPDIF can be used to protect tee-feeders or busbars,
under section C37.118 Phasor Measurement Data Streaming
reactors, motors, auto-transformers, capacitor banks and so
Protocol Configuration.
on. One such function block is used for a high-impedance
restricted earth fault protection. Three such function blocks Multiple PMU functionality can be configured in the IED,
are used to form three-phase, phase-segregated differential which can stream out same or different data at different
protection. reporting rates or different performance (service) classes.

5. Wide area measurement system 6. Current protection

Synchrophasor report, 8 phasors Instantaneous phase overcurrent protection PHPIOC


GUID-7539462D-A3D6-492D-9926-E67C5B7C72D9 v1
M12910-3 v14
The instantaneous three phase overcurrent (PHPIOC) function
Configuration parameters for IEEE1344 and C37.118 protocol
has a low transient overreach and short tripping time to allow
PMUCONF
GUID-33694C62-A109-4D8F-9063-CEFA5D0E78BC v4 use as a high set short-circuit protection function.
The IED supports the following IEEE synchrophasor
standards: Directional phase overcurrent protection, four steps
• IEEE 1344-1995 (Both measurements and data OC4PTOC
communication) Directional phase overcurrent protection, four steps
M12846-3 v17

• IEEE Std C37.118-2005 (Both measurements and data (OC4PTOC) has an inverse or definite time delay for each
communication) step.
• IEEE Std C37.118.1–2011 and C37.118.1a-2014
(Measurements) All IEC and ANSI inverse time characteristics are available
• IEEE Std C37.118.2-2011 (Data communication) together with an optional user defined time characteristic.

The directional function needs voltage as it is voltage


PMUCONF contains the PMU configuration parameters for polarized with memory. The function can be set to be
both IEEE C37.118 and IEEE 1344 protocols. This means all directional or non-directional independently for each of the
the required settings and parameters in order to establish and steps.
define a number of TCP and/or UDP connections with one or
more PDC clients (synchrophasor client). This includes port A second harmonic blocking level can be set for the function
numbers, TCP/UDP IP addresses, and specific settings for and can be used to block each step individually.
IEEE C37.118 as well as IEEE 1344 protocols.

Protocol reporting via IEEE 1344 and C37.118 PMUREPORT

28 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

NS4PTOC can also be used to provide a system backup for


Instantaneous residual overcurrent protection EFPIOC example, in the case of the primary protection being out of
M12701-3 v16
The Instantaneous residual overcurrent protection (EFPIOC) service due to communication or voltage transformer circuit
has a low transient overreach and short tripping times to failure.
allow the use for instantaneous earth-fault protection, with the
reach limited to less than the typical eighty percent of the line Directional operation can be combined together with
at minimum source impedance. EFPIOC is configured to corresponding communication logic in permissive or blocking
measure the residual current from the three-phase current teleprotection scheme. The same logic as for directional zero
inputs and can be configured to measure the current from a sequence current can be used. Current reversal and weak-
separate current input. end infeed functionality are available.

Directional residual overcurrent protection, four steps Sensitive directional residual overcurrent and power
EF4PTOC protection SDEPSDE
M13667-3 v19 SEMOD171438-5 v6
Directional residual overcurrent protection, four steps In isolated networks or in networks with high impedance
(EF4PTOC) can be used as main protection for phase-to- earthing, the earth fault current is significantly smaller than
earth faults. It can also be used to provide a system back-up, the short circuit currents. In addition to this, the magnitude of
for example, in the case of the primary protection being out of the fault current is almost independent on the fault location in
service due to communication or voltage transformer circuit the network. The protection can be selected to use either the
failure. residual current or residual power component 3U0·3I0·cos j,
for operating quantity with maintained short circuit capacity.
EF4PTOC has an inverse or definite time delay independent There is also available one nondirectional 3I0 step and one
for each step. 3U0 overvoltage tripping step.
All IEC and ANSI time-delayed characteristics are available No specific sensitive current input is needed. Sensitive
together with an optional user-defined characteristic. directional residual overcurrent and power protection
(SDEPSDE) can be set as low 0.25% of IBase.
EF4PTOC can be set to be directional or non-directional
independently for each step. Thermal overload protection, one time constant LCPTTR/
LFPTTR
IDir, UPol and IPol can be independently selected to be either M12020-4 v14
The increasing utilization of the power system closer to the
zero sequence or negative sequence.
thermal limits has generated a need of a thermal overload
A second harmonic blocking can be set individually for each protection for power lines.
step.
A thermal overload will often not be detected by other
Directional operation can be combined together with the protection functions and the introduction of the thermal
corresponding communication logic in permissive or blocking overload protection can allow the protected circuit to operate
teleprotection scheme. The current reversal and weak-end closer to the thermal limits.
infeed functionality are available as well.
The three-phase current measuring protection has an I 2 t
The residual current can be calculated by summing the three- characteristic with settable time constant and a thermal
phase currents or taking the input from the neutral CT. memory. The temperature is displayed in either Celsius or
Fahrenheit, depending on whether the function used is
Four step directional negative phase sequence overcurrent Thermal overload protection (LCPTTR) (Celsius) or (LFPTTR)
protection NS4PTOC (Fahrenheit).
GUID-485E9D36-0032-4559-9204-101539A32F47 v6
Four step directional negative phase sequence overcurrent
protection (NS4PTOC) has an inverse or definite time delay An alarm level gives early warning to allow operators to take
independent for each step separately. action well before the line is tripped.

All IEC and ANSI time delayed characteristics are available Estimated time to trip before operation, and estimated time to
together with an optional user defined characteristic. reclose after operation are presented.

The directional function is voltage polarized. Thermal overload protection, two time constants TRPTTR
M13243-3 v12
If a power transformer reaches very high temperatures the
NS4PTOC can be set directional or non-directional equipment might be damaged. The insulation within the
independently for each of the steps. transformer will experience forced ageing. As a consequence
of this the risk of internal phase-to-phase or phase-to-earth
NS4PTOC can be used as main protection for unsymmetrical
faults will increase.
fault; phase-phase short circuits, phase-phase-earth short
circuits and single phase earth faults.

ABB 29
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

The thermal overload protection (TRPTTR) estimates the Normally the own breaker is tripped to correct such a
internal heat content of the transformer (temperature) situation. If the situation persists the surrounding breakers
continuously. This estimation is made by using a thermal should be tripped to clear the unsymmetrical load situation.
model of the transformer with two time constants, which is
based on current measurement. The Pole discordance protection function (CCPDSC) operates
based on information from auxiliary contacts of the circuit
Two warning levels are available. This enables actions in the breaker for the three phases with additional criteria from
power system to be done before dangerous temperatures are unsymmetrical phase currents when required.
reached. If the temperature continues to increase to the trip
value, the protection initiates a trip of the protected Directional over/underpower protection GOPPDOP/
transformer. GUPPDUP
SEMOD175421-4 v7
The directional over-/under-power protection (GOPPDOP/
The estimated time to trip before operation is presented. GUPPDUP) can be used wherever a high/low active, reactive
or apparent power protection or alarming is required. The
Breaker failure protection CCRBRF functions can alternatively be used to check the direction of
M11550-6 v17
Breaker failure protection (CCRBRF) ensures a fast backup active or reactive power flow in the power system. There are
tripping of the surrounding breakers in case the own breaker a number of applications where such functionality is needed.
fails to open. CCRBRF can be current-based, contact-based Some of them are:
or an adaptive combination of these two conditions.
• detection of reversed active power flow
A current check with extremely short reset time is used as • detection of high reactive power flow
check criterion to achieve high security against unwanted
operation. Each function has two steps with definite time delay.

Contact check criteria can be used where the fault current Broken conductor check BRCPTOC
SEMOD171446-5 v2
through the breaker is small. The main purpose of the function Broken conductor check
(BRCPTOC) is the detection of broken conductors on
CCRBRF can be single- or three-phase initiated to allow use protected power lines and cables (series faults). Detection
with single phase tripping applications. For the three-phase can be used to give alarm only or trip the line breaker.
version of CCRBRF the current criteria can be set to operate
only if two out of four for example, two phases or one phase Voltage-restrained time overcurrent protection VRPVOC
GUID-935E1CE8-601F-40E2-8D22-2FF68420FADF v6
plus the residual current start. This gives a higher security to Voltage-restrained time overcurrent protection (VRPVOC)
the back-up trip command. function can be used as generator backup protection against
short-circuits.
CCRBRF function can be programmed to give a single- or
three-phase re-trip of its own breaker to avoid unnecessary The overcurrent protection feature has a settable current level
tripping of surrounding breakers at an incorrect initiation due that can be used either with definite time or inverse time
to mistakes during testing. characteristic. Additionally, it can be voltage controlled/
restrained.
Stub protection STBPTOC
M12902-3 v10
When a power line is taken out of service for maintenance One undervoltage step with definite time characteristic is also
and the line disconnector is opened in multi-breaker available within the function in order to provide functionality
arrangements the voltage transformers will mostly be outside for overcurrent protection with undervoltage seal-in.
on the disconnected part. The primary line distance
protection will thus not be able to operate and must be Capacitor bank protection CBPGAPC
GUID-D55CEBF7-9377-4E36-BD8B-533609048A1E v3

blocked. Shunt Capacitor Banks (SCB) are used in a power system to


provide reactive power compensation and power factor
The stub protection (STBPTOC) covers the zone between the correction. They are as well used as integral parts of Static
current transformers and the open disconnector. The three- Var Compensators (SVC) or Harmonic Filters installations.
phase instantaneous overcurrent function is released from a Capacitor bank protection (CBPGAPC) function is specially
normally open, NO (b) auxiliary contact on the line designed to provide protection and supervision features for
disconnector. SCBs.

Pole discordance protection CCPDSC


M13269-3 v15
An open phase can cause negative and zero sequence 7. Voltage protection
currents which cause thermal stress on rotating machines
Two-step undervoltage protection UV2PTUV
and can cause unwanted operation of zero sequence or M13789-3 v12
Undervoltages can occur in the power system during faults or
negative sequence current functions.
abnormal conditions. The two-step undervoltage protection
function (UV2PTUV) can be used to open circuit breakers to
30 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

prepare for system restoration at power outages or as a long- 8. Frequency protection


time delayed back-up to the primary protection.
Underfrequency protection SAPTUF
M13349-3 v13

UV2PTUV has two voltage steps, each with inverse or definite Underfrequency occurs as a result of a lack of generation in
time delay. the network.

It has a high reset ratio to allow settings close to the system Underfrequency protection (SAPTUF) measures frequency
service voltage. with high accuracy, and is used for load shedding systems,
remedial action schemes, gas turbine startup and so on.
Two step overvoltage protection OV2PTOV Separate definite time delays are provided for operate and
M13798-3 v16
Overvoltages may occur in the power system during abnormal restore.
conditions such as sudden power loss, tap changer
regulating failures, and open line ends on long lines. SAPTUF is provided with undervoltage blocking.

Two step overvoltage protection (OV2PTOV) function can be The operation is based on positive sequence voltage
used to detect open line ends, normally then combined with a measurement and requires two phase-phase or three phase-
directional reactive over-power function to supervise the neutral voltages to be connected.
system voltage. When triggered, the function will cause an
alarm, switch in reactors, or switch out capacitor banks. Overfrequency protection SAPTOF
M14953-3 v12
Overfrequency protection function (SAPTOF) is applicable in
OV2PTOV has two voltage steps, each of them with inverse all situations, where reliable detection of high fundamental
or definite time delayed. power system frequency is needed.

OV2PTOV has a high reset ratio to allow settings close to Overfrequency occurs because of sudden load drops or
system service voltage. shunt faults in the power network. Close to the generating
plant, generator governor problems can also cause over
Two step residual overvoltage protection ROV2PTOV frequency.
M13808-3 v11
Residual voltages may occur in the power system during
earth faults. SAPTOF measures frequency with high accuracy, and is used
mainly for generation shedding and remedial action schemes.
Two step residual overvoltage protection (ROV2PTOV) It is also used as a frequency stage initiating load restoring. A
function calculates the residual voltage from the three-phase definite time delay is provided for operate.
voltage input transformers or measures it from a single
voltage input transformer fed from an open delta or neutral SAPTOF is provided with an undervoltage blocking.
point voltage transformer.
The operation is based on positive sequence voltage
ROV2PTOV has two voltage steps, each with inverse or measurement and requires two phase-phase or three phase-
definite time delay. neutral voltages to be connected.

A reset delay ensures operation for intermittent earth faults. Rate-of-change of frequency protection SAPFRC
M14965-3 v13
The rate-of-change of frequency protection function
Voltage differential protection VDCPTOV (SAPFRC ) gives an early indication of a main disturbance in
SEMOD153862-5 v7
A voltage differential monitoring function is available. It the system. SAPFRC measures frequency with high accuracy,
compares the voltages from two three phase sets of voltage and can be used for generation shedding, load shedding and
transformers and has one sensitive alarm step and one trip remedial action schemes. SAPFRC can discriminate between
step. Alternatively, it can be used as voltage differential a positive or negative change of frequency. A definite time
protection (VDCPTOV) for shunt capacitor banks. delay is provided for operate.

Loss of voltage check LOVPTUV SAPFRC is provided with an undervoltage blocking. The
SEMOD171457-5 v8
Loss of voltage check (LOVPTUV ) is suitable for use in operation is based on positive sequence voltage
networks with an automatic system restoration function. measurement and requires two phase-phase or three phase-
LOVPTUV issues a three-pole trip command to the circuit neutral voltages to be connected.
breaker, if all three phase voltages fall below the set value for
a time longer than the set time and the circuit breaker Frequency time accumulation protection FTAQFVR
GUID-020CE8CF-9BEA-455D-ACBD-13023B93B4D1 v5

remains closed. Frequency time accumulation protection (FTAQFVR) is based


on measured system frequency and time counters. FTAQFVR
The operation of LOVPTUV is supervised by the fuse failure for generator protection provides the START output for a
supervision FUFSPVC. particular settable frequency limit, when the system frequency
falls in that settable frequency band limit and positive
sequence voltage within settable voltage band limit. The
ABB 31
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

START signal triggers the individual event timer, which is the with the neutral point current on a separate input taken from
continuous time spent within the given frequency band, and another set of cores on the current transformer.
the accumulation timer, which is the cumulative time spent
within the given frequency band. Once the timers reach their A detection of a difference indicates a fault in the circuit and
limit, an alarm or trip signal is activated to protect the turbine is used as alarm or to block protection functions expected to
against the abnormal frequency operation. This function is give inadvertent tripping.
blocked during generator start-up or shut down conditions by
Fuse failure supervision FUFSPVC
monitoring the circuit breaker position and current threshold SEMOD113820-4 v12
The aim of the fuse failure supervision function (FUFSPVC) is
value. The function is also blocked when the system positive
to block voltage measuring functions at failures in the
sequence voltage magnitude deviates from the given voltage
secondary circuits between the voltage transformer and the
band limit which can be enabled by EnaVoltCheck setting.
IED in order to avoid inadvertent operations that otherwise
It is possible to create functionality with more than one might occur.
frequency band limit by using multiple instances of the
The fuse failure supervision function basically has three
function. This can be achieved by a proper configuration
different detection methods, negative sequence and zero
based on the turbine manufacturer specification.
sequence based detection and an additional delta voltage
and delta current detection.
9. Multipurpose protection
The negative sequence detection algorithm is recommended
General current and voltage protection CVGAPC for IEDs used in isolated or high-impedance earthed
M13083-11 v9
The General current and voltage protection (CVGAPC) can be networks. It is based on the negative-sequence quantities.
utilized as a negative sequence current protection detecting
unsymmetrical conditions such as open phase or The zero sequence detection is recommended for IEDs used
unsymmetrical faults. in directly or low impedance earthed networks. It is based on
the zero sequence measuring quantities.
CVGAPC can also be used to improve phase selection for
high resistive earth faults, outside the distance protection The selection of different operation modes is possible by a
reach, for the transmission line. Three functions are used, setting parameter in order to take into account the particular
which measures the neutral current and each of the three earthing of the network.
phase voltages. This will give an independence from load
A criterion based on delta current and delta voltage
currents and this phase selection will be used in conjunction
measurements can be added to the fuse failure supervision
with the detection of the earth fault from the directional earth
function in order to detect a three phase fuse failure, which in
fault protection function.
practice is more associated with voltage transformer
switching during station operations.
10. General calculation
Fuse failure supervision VDSPVC
GUID-6AF2219A-264F-4971-8D03-3B8A9D0CB284 v5
Multipurpose filter SMAIHPAC Different protection functions within the protection IED
GUID-EB0B11C3-FF79-4B8D-A335-649623E832F9 v3
The multi-purpose filter function block (SMAIHPAC) is operates on the basis of measured voltage at the relay point.
arranged as a three-phase filter. It has very much the same Some example of protection functions are:
user interface (e.g. inputs and outputs) as the standard pre-
processing function block SMAI. However the main difference • Distance protection function.
is that it can be used to extract any frequency component • Undervoltage function.
from the input signal. Thus it can, for example, be used to • Energisation function and voltage check for the weak
build sub-synchronous resonance protection for synchronous infeed logic.
generator.
These functions can operate unintentionally, if a fault occurs
in the secondary circuits between voltage instrument
11. Secondary system supervision transformers and the IED. These unintentional operations can
be prevented by fuse failure supervision (VDSPVC).
Current circuit supervision CCSSPVC
M12444-3 v10
Open or short circuited current transformer cores can cause VDSPVC is designed to detect fuse failures or faults in voltage
unwanted operation of many protection functions such as measurement circuit, based on phase wise comparison of
differential, earth-fault current and negative-sequence current voltages of main and pilot fused circuits. VDSPVC blocking
functions. output can be configured to block functions that need to be
blocked in case of faults in the voltage circuit.
Current circuit supervision (CCSSPVC) compares the residual
current from a three phase set of current transformer cores

32 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

12. Control • Select-Execute principle to give high reliability


• Selection function to prevent simultaneous operation
Synchrocheck, energizing check, and synchronizing • Selection and supervision of operator place
SESRSYN • Command supervision
M12480-3 v16
The Synchronizing function allows closing of asynchronous • Block/deblock of operation
networks at the correct moment including the breaker closing • Block/deblock of updating of position indications
time, which improves the network stability. • Substitution of position and quality indications
• Overriding of interlocking functions
Synchrocheck, energizing check, and synchronizing
• Overriding of synchrocheck
(SESRSYN) function checks that the voltages on both sides of
• Operation counter
the circuit breaker are in synchronism, or with at least one
• Suppression of mid position
side dead to ensure that closing can be done safely.

SESRSYN function includes a built-in voltage selection Two types of command models can be used:
scheme for double bus and 1½ breaker or ring busbar • Direct with normal security
arrangements. • SBO (Select-Before-Operate) with enhanced security
Manual closing as well as automatic reclosing can be
checked by the function and can have different settings. Normal security means that only the command is evaluated
and the resulting position is not supervised. Enhanced
For systems, which can run asynchronously, a synchronizing security means that the command is evaluated with an
feature is also provided. The main purpose of the additional supervision of the status value of the control
synchronizing feature is to provide controlled closing of circuit object. The command sequence with enhanced security is
breakers when two asynchronous systems are in phase and always terminated by a CommandTermination service
can be connected. The synchronizing feature evaluates primitive and an AddCause telling if the command was
voltage difference, phase angle difference, slip frequency and successful or if something went wrong.
frequency rate of change before issuing a controlled closing
of the circuit breaker. Breaker closing time is a setting. Control operation can be performed from the local HMI with
authority control if so defined.
Autorecloser SMBRREC
M12390-3 v17 M16909-3 v3
The auto recloser (SMBRREC) function provides: Features of the apparatus control function are:
• high-speed and/or delayed auto reclosing
• single and/or three phase auto reclosing • Operation of primary apparatuses
• support for single or multi-breaker applications. • Select-Execute principle to give high reliability
• Selection and reservation function to prevent
simultaneous operation
The auto recloser can be used for delayed busbar restoration. • Selection and supervision of operator place
• Command supervision
Up to five reclosing shots can be performed. The first shot
• Block/deblock of operation
can be single-, two-, and /or three-phase depending on the
• Block/deblock of updating of position indications
type of the fault and the selected auto reclosing mode.
• Substitution of position indications
Several auto reclosing functions can be provided for multi- • Overriding of interlocking functions
breaker arrangements. A priority circuit allows one circuit • Overriding of synchrocheck
breaker to reclose first and the second will only close if the • Pole discordance supervision
fault proved to be transient. • Operation counter

Each auto reclosing function can be configured to co-operate The apparatus control function is realized by means of a
with the synchrocheck function. number of function blocks designated:

Apparatus control APC • Bay control QCBAY


M13444-3 v15
The apparatus control functions are used for control and • Switch controller SCSWI
supervision of circuit breakers, disconnectors and earthing • Circuit breaker SXCBR
switches within a bay. Permission to operate is given after • Circuit switch SXSWI
evaluation of conditions from other functions such as
The three latter functions are logical nodes according to IEC
interlocking, synchrocheck, operator place selection and
61850-8-1. To realize the reservation function also the
external or internal blockings.
function blocks Reservation input (RESIN) and Bay reserve
Apparatus control features: (QCRSV) are included in the apparatus control function.

ABB 33
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

M13506-3 v5
Interlocking The purpose of the reservation (QCRSV) function is primarily
M13531-3 v4
The interlocking function blocks the possibility to operate to transfer interlocking information between IEDs in a safe
primary switching devices, for instance when a disconnector way and to prevent double operation in a bay, switchyard
is under load, in order to prevent material damage and/or part, or complete substation.
accidental human injury.
Reservation input RESIN
M16501-3 v5
Each apparatus control function has interlocking modules The Reservation input (RESIN) function receives the
included for different switchyard arrangements, where each reservation information from other bays. The number of
function handles interlocking of one bay. The interlocking instances is the same as the number of involved bays (up to
function is distributed to each IED and is not dependent on 60 instances are available).
any central function. For the station-wide interlocking, the
IEDs communicate via the system-wide interbay bus (IEC Bay control QCBAY
M13447-3 v8

61850-8-1) or by using hard wired binary inputs/outputs. The The Bay control (QCBAY) function is used together with Local
interlocking conditions depend on the circuit configuration remote and local remote control functions to handle the
and apparatus position status at any given time. selection of the operator place per bay. QCBAY also provides
blocking functions that can be distributed to different
For easy and safe implementation of the interlocking function, apparatuses within the bay.
the IED is delivered with standardized and tested software
interlocking modules containing logic for the interlocking Proxy for signals from switching device via GOOSE
conditions. The interlocking conditions can be altered, to XLNPROXY
GUID-11F9CA1C-8E20-489B-822B-34DACC59553A v1

meet the customer’s specific requirements, by adding The proxy for signals from switching device via GOOSE
configurable logic by means of the graphical configuration (XLNPROXY) gives an internal representation of the position
tool. status and control response for a switch modelled in a
breaker IED. This representation is identical to that of an
The following interlocking modules are available: SXCBR or SXSWI function.

• Line for double and transfer busbars, ABC_LINE GOOSE function block to receive a switching device
• Bus coupler for double and transfer busbars, ABC_BC GOOSEXLNRCV
GUID-5AC7DE11-CB95-4565-A8AE-FB23D59FD717 v1
• Transformer bay for double busbars, AB_TRAFO The GOOSE XLN Receive component is used to collect
• Bus-section breaker for double busbars, A1A2_BS information from another device’s XCBR/XSWI logical node
• Bus-section disconnector for double busbars, A1A2_DC sent over process bus via GOOSE. The GOOSE XLN Receive
• Busbar earthing switch, BB_ES component includes 12 different outputs (and their respective
• Double CB Bay, DB_BUS_A, DB_LINE, DB_BUS_B channel valid bits) with defined names to ease the 61850
• 1 1/2-CB diameter, BH_LINE_A, BH_CONN, BH_LINE_B mapping of the GOOSE signals in the configuration process.

Local remote LOCREM/Local remote control LOCREMCTRL


Switch controller SCSWI The signals from the local HMI or from an external local/
M17086-3 v10

M13486-3 v10
The Switch controller (SCSWI) initializes and supervises all remote switch are connected via the function blocks local
functions to properly select and operate switching primary remote (LOCREM) and local remote control (LOCREMCTRL)
apparatuses. The Switch controller may handle and operate to the Bay control (QCBAY) function block. The parameter
on one multi-phase device or up to three one-phase devices. ControlMode in function block LOCREM is set to choose if
the switch signals are coming from the local HMI or from an
Circuit breaker SXCBR
M13489-3 v6
external hardware switch connected via binary inputs.
The purpose of Circuit breaker (SXCBR) is to provide the
actual status of positions and to perform the control Voltage control TR1ATCC/TR8ATCC , TCMYLTC/TCLYLTC
operations, that is, pass all the commands to primary Automatic voltage control for tap changer, single control
M5864-3 v12

apparatuses in the form of circuit breakers via binary output (TR1ATCC), Automatic voltage control for tap changer,
boards and to supervise the switching operation and position. parallel control (TR8ATCC), Tap changer control and
supervision, 6 binary inputs (TCMYLTC) and Tap changer
Circuit switch SXSWI
M16492-3 v6
control and supervision, 32 binary inputs (TCLYLTC) are used
The purpose of Circuit switch (SXSWI) function is to provide
for control of power transformers with an on-load tap
the actual status of positions and to perform the control
changer. The functions provide automatic regulation of the
operations, that is, pass all the commands to primary
voltage on the secondary side of transformers or alternatively
apparatuses in the form of disconnectors or earthing switches
on a load point further out in the network.
via binary output boards and to supervise the switching
operation and position. Control of a single transformer, as well as control of up to
eight transformers in parallel is possible. For parallel control of
Reservation function QCRSV
power transformers, three alternative methods are available:
34 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

the master-follower method, the circulating current method


and the reverse reactance method. The first two methods Automation bits, command function for DNP3.0 AUTOBITS
SEMOD158591-5 v8

require exchange of information between the parallel Automation bits function for DNP3 (AUTOBITS) is used within
transformers and this is provided for within IEC 61850-8-1. PCM600 to get into the configuration of the commands
coming through the DNP3 protocol. The AUTOBITS function
Voltage control includes many extra features such as the plays the same role as functions GOOSEBINRCV (for IEC
possibility to avoid simultaneous tapping of parallel 61850) and MULTICMDRCV (for LON).
transformers, hot stand by regulation of a transformer in a
group which regulates it to a correct tap position even though Single command, 16 signals
M12446-6 v5

the LV CB is open, compensation for a possible capacitor The IEDs can receive commands either from a substation
bank on the LV side bay of a transformer, extensive tap automation system or from the local HMI. The command
changer monitoring including contact wear and hunting function block has outputs that can be used, for example, to
detection, monitoring of the power flow in the transformer so control high voltage apparatuses or for other user defined
that, for example, the voltage control can be blocked if the functionality.
power reverses, etc.
13. Scheme communication
Logic rotating switch for function selection and LHMI
presentation SLGAPC Scheme communication logic with delta based blocking
SEMOD114908-4 v11
The logic rotating switch for function selection and LHMI scheme signal transmit ZCPSCH
M13860-3 v11
presentation (SLGAPC) (or the selector switch function block) To achieve instantaneous fault clearance for all line faults,
is used to get an enhanced selector switch functionality scheme communication logic is provided. All types of
compared to the one provided by a hardware selector switch. communication schemes for permissive underreaching,
Hardware selector switches are used extensively by utilities, permissive overreaching, blocking, delta based blocking,
in order to have different functions operating on pre-set unblocking and intertrip are available.
values. Hardware switches are however sources for
maintenance issues, lower system reliability and an extended The built-in communication module (LDCM) can be used for
purchase portfolio. The selector switch function eliminates all scheme communication signaling when included.
these problems.
Current reversal and weak-end infeed logic for distance
Selector mini switch VSGAPC protection ZCRWPSCH
SEMOD158756-5 v10 M13896-3 v15

The Selector mini switch (VSGAPC) function block is a The ZCRWPSCH function provides the current reversal and
multipurpose function used for a variety of applications, as a weak end infeed logic functions that supplement the standard
general purpose switch. scheme communication logic. It is not suitable for standalone
use as it requires inputs from the distance protection
VSGAPC can be controlled from the menu, from a symbol on functions and the scheme communications function included
the single line diagram (SLD) on the local HMI or from Binary within the terminal.
inputs.
On detection of a current reversal, the current reversal logic
Generic communication function for Double Point indication provides an output to block the sending of the teleprotection
DPGAPC signal to the remote end, and to block the permissive tripping
SEMOD55850-5 v7
Generic communication function for Double Point indication at the local end. This blocking condition is maintained long
(DPGAPC) function block is used to send double point enough to ensure that no unwanted operation will occur as a
position indications to other systems, equipment or functions result of the current reversal.
in the substation through IEC 61850-8-1 or other
communication protocols. It is especially intended to be used On verification of a weak end infeed condition, the weak end
in the interlocking station-wide logics. infeed logic provides an output for sending the received
teleprotection signal back to the remote sending end and
Single point generic control 8 signals SPC8GAPC other output(s) for local tripping. For terminals equipped for
SEMOD176462-4 v11
The Single point generic control 8 signals (SPC8GAPC) single- and two-pole tripping, outputs for the faulted phase(s)
function block is a collection of 8 single point commands that are provided. Undervoltage detectors are used to detect the
can be used for direct commands for example reset of LEDs faulted phase(s).
or putting IED in "ChangeLock" state from remote. In this
way, simple commands can be sent directly to the IED Local acceleration logic ZCLCPSCH
M13823-3 v7

outputs, without confirmation. Confirmation (status) of the To achieve fast clearing of faults on the whole line, when no
result of the commands is supposed to be achieved by other communication channel is available, local acceleration logic
means, such as binary inputs and SPGAPC function blocks. (ZCLCPSCH) can be used. This logic enables fast fault
The commands can be pulsed or steady with a settable pulse clearing and re-closing during certain conditions, but
time. naturally, it can not fully replace a communication channel.

ABB 35
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

The logic can be controlled either by the autorecloser (zone 14. Logic
extension) or by the loss-of-load current (loss-of-load
acceleration). Tripping logic SMPPTRC
M12275-3 v14
A function block for protection tripping and general start
Scheme communication logic for residual overcurrent indication is always provided as a basic function for each
protection ECPSCH circuit breaker. It provides a settable pulse prolongation time
M13918-4 v11
To achieve fast fault clearance of earth faults on the part of to ensure a trip pulse of sufficient length, as well as all
the line not covered by the instantaneous step of the residual functionality necessary for correct co-operation with
overcurrent protection, the directional residual overcurrent autoreclosing functions.
protection can be supported with a logic that uses
communication channels. The trip function block includes a settable latch function for
the trip signal and circuit breaker lockout.
In the directional scheme, information of the fault current
direction must be transmitted to the other line end. With The trip function can collect start and directional signals from
directional comparison, a short operate time of the protection different application functions. The aggregated start and
including a channel transmission time, can be achieved. This directional signals are mapped to the IEC 61850 logical node
short operate time enables rapid autoreclosing function after data model.
the fault clearance.
General start matrix block SMAGAPC
GUID-BA516165-96DE-4CD9-979B-29457C7653C0 v3

The communication logic module for directional residual The Start Matrix (SMAGAPC) merges start and directional
current protection enables blocking as well as permissive output signals from different application functions and creates
under/overreaching, and unblocking schemes. The logic can a common start and directional output signal (STDIR ) to be
also be supported by additional logic for weak-end infeed and connected to the Trip function.
current reversal, included in Current reversal and weak-end
The purpose of this functionality is to provide general start
infeed logic for residual overcurrent protection (ECRWPSCH)
and directional information for the IEC 61850 trip logic data
function.
model SMPPTRC.
Current reversal and weak-end infeed logic for residual
Trip matrix logic TMAGAPC
overcurrent protection ECRWPSCH M15321-3 v13
M13928-3 v8 The trip matrix logic (TMAGAPC) function is used to route trip
The Current reversal and weak-end infeed logic for residual
signals and other logical output signals to different output
overcurrent protection (ECRWPSCH) is a supplement to
contacts on the IED.
Scheme communication logic for residual overcurrent
protection ECPSCH. The trip matrix logic function has 3 output signals and these
outputs can be connected to physical tripping outputs
To achieve fast fault clearing for all earth faults on the line, the
according to the specific application needs for settable pulse
directional earth fault protection function can be supported
or steady output.
with logic that uses tele-protection channels.
Group alarm logic function ALMCALH
This is why the IEDs have available additions to the scheme GUID-16E60E27-F7A8-416D-8648-8174AAC49BB5 v4
The group alarm logic function (ALMCALH) is used to route
communication logic.
several alarm signals to a common indication, LED and/or
If parallel lines are connected to common busbars at both
M13928-6 v2
contact, in the IED.
terminals, overreaching permissive communication schemes
Group warning logic function WRNCALH
can trip unselectively due to fault current reversal. This GUID-F7D9A012-3AD4-4D86-BE97-DF2A99BE5383 v4
The group warning logic function (WRNCALH) is used to route
unwanted tripping affects the healthy line when a fault is
several warning signals to a common indication, LED and/or
cleared on the other line. This lack of security can result in a
contact, in the IED.
total loss of interconnection between the two buses. To avoid
this type of disturbance, a fault current reversal logic Group indication logic function INDCALH
GUID-D8D1A4EE-A87F-46C6-8529-277FC1ADA9B0 v4
(transient blocking logic) can be used. The group indication logic function (INDCALH) is used to
M13928-8 v5 route several indication signals to a common indication, LED
Permissive communication schemes for residual overcurrent
and/or contact, in the IED.
protection can basically operate only when the protection in
the remote IED can detect the fault. The detection requires a Basic configurable logic blocks
M11396-4 v17
sufficient minimum residual fault current, out from this IED. The basic configurable logic blocks do not propagate the time
The fault current can be too low due to an opened breaker or stamp and quality of signals (have no suffix QT at the end of
high-positive and/or zero-sequence source impedance their function name). A number of logic blocks and timers are
behind this IED. To overcome these conditions, weak-end always available as basic for the user to adapt the
infeed (WEI) echo logic is used. The weak-end infeed echo is configuration to the specific application needs. The list below
limited to 200 ms to avoid channel lockup. shows a summary of the function blocks and their features.
36 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

These logic blocks are also available as part of an extension • ANDQT AND function block. The function also
logic package with the same number of instances. propagates the time stamp and the quality of input
signals. Each block has four inputs and two outputs
• AND function block. The AND function is used to form where one is inverted.
general combinatory expressions with boolean variables.
The AND function block has up to four inputs and two • INDCOMBSPQT combines single input signals to group
outputs. One of the outputs is inverted. signal. Single position input is copied to value part of
SP_OUT output. TIME input is copied to time part of
• GATE function block is used for whether or not a signal SP_OUT output. Quality input bits are copied to the
should be able to pass from the input to the output. corresponding quality part of SP_OUT output.

• INVERTER function block that inverts the input signal to the • INDEXTSPQT extracts individual signals from a group
output. signal input. The value part of single position input is
copied to SI_OUT output. The time part of single
• LLD function block. Loop delay used to delay the output
position input is copied to TIME output. The quality bits
signal one execution cycle.
in the common part and the indication part of inputs
• OR function block. The OR function is used to form general signal are copied to the corresponding quality output.
combinatory expressions with boolean variables. The OR
• INVALIDQT function which sets quality invalid of outputs
function block has up to six inputs and two outputs. One of
according to a "valid" input. Inputs are copied to
the outputs is inverted.
outputs. If input VALID is 0, or if its quality invalid bit is
• PULSETIMER function block can be used, for example, for set, all outputs invalid quality bit will be set to invalid.
pulse extensions or limiting of operation of outputs, settable The time stamp of an output will be set to the latest time
pulse time. stamp of INPUT and VALID inputs.

• RSMEMORY function block is a flip-flop that can reset or • INVERTERQT function block that inverts the input signal
set an output from two inputs respectively. Each block has and propagates the time stamp and the quality of the
two outputs where one is inverted. The memory setting input signal.
controls if, after a power interruption, the flip-flop resets or
• ORQT OR function block that also propagates the time
returns to the state it had before the power interruption.
stamp and the quality of the input signals. Each block
RESET input has priority.
has six inputs and two outputs where one is inverted.
• SRMEMORY function block is a flip-flop that can set or
• PULSETIMERQT Pulse timer function block can be used,
reset an output from two inputs respectively. Each block
for example, for pulse extensions or limiting of operation
has two outputs where one is inverted. The memory setting
of outputs. The function also propagates the time stamp
controls if, after a power interruption, the flip-flop resets or
and the quality of the input signal.
returns to the state it had before the power interruption.
The SET input has priority. • RSMEMORYQT function block is a flip-flop that can reset
or set an output from two inputs respectively. Each
• TIMERSET function has pick-up and drop-out delayed
block has two outputs where one is inverted. The
outputs related to the input signal. The timer has a settable
memory setting controls if the block after a power
time delay.
interruption should return to the state before the
• XOR is used to generate combinatory expressions with interruption, or be reset. The function also propagates
boolean variables. XOR has two inputs and two outputs. the time stamp and the quality of the input signal.
One of the outputs is inverted. The output signal OUT is 1 if
• SRMEMORYQT function block is a flip-flop that can set
the input signals are different and 0 if they are the same.
or reset an output from two inputs respectively. Each
block has two outputs where one is inverted. The
Configurable logic blocks Q/T memory setting controls if the block after a power
GUID-0CA6511A-E8BD-416E-9B59-5C6BD98C60B7 v5
The configurable logic blocks QT propagate the time stamp interruption should return to the state before the
and the quality of the input signals (have suffix QT at the end interruption, or be reset. The function also propagates
of their function name). the time stamp and the quality of the input signal.

The function blocks assist the user to adapt the IEDs' • TIMERSETQT function has pick-up and drop-out delayed
configuration to the specific application needs. The list below outputs related to the input signal. The timer has a
shows a summary of the function blocks and their features. settable time delay. The function also propagates the
time stamp and the quality of the input signal.

ABB 37
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

• XORQT XOR function block. The function also


propagates the time stamp and the quality of the input Comparator for integer inputs INTCOMP
GUID-A93564FA-0017-4939-A9C1-095DA0FD9832 v1

signals. Each block has two outputs where one is The function gives the possibility to monitor the level of
inverted. integer values in the system relative to each other or to a
fixed value. It is a basic arithmetic function that can be used
for monitoring, supervision, interlocking and other logics.
Extension logic package
GUID-144BAAA3-A5EF-49AF-8876-93CC5F3D0234 v1
The logic extension block package includes additional trip Comparator for real inputs REALCOMP
GUID-E17A88D7-D095-4F36-9CD5-64EBFD2A1DEA v1
matrix logic and configurable logic blocks. The function gives the possibility to monitor the level of real
value signals in the system relative to each other or to a fixed
Fixed signal function block FXDSIGN value. It is a basic arithmetic function that can be used for
M15322-3 v15
The Fixed signals function (FXDSIGN) has nine pre-set (fixed) monitoring, supervision, interlocking and other logics.
signals that can be used in the configuration of an IED, either
for forcing the unused inputs in other function blocks to a
certain level/value, or for creating certain logic. Boolean, 15. Monitoring
integer, floating point, string types of signals are available.
Measurements CVMMXN, CMMXU, VNMMXU, VMMXU,
One FXDSIGN function block is included in all IEDs. CMSQI, VMSQI
M12024-3 v9
The measurement functions are used to get on-line
Elapsed time integrator with limit transgression and overflow information from the IED. These service values make it
supervision TEIGAPC possible to display on-line information on the local HMI and
GUID-2D64874A-F266-4251-8EED-E813F40513D7 v3
The Elapsed time integrator function (TEIGAPC) is a function on the substation automation system about:
that accumulates the elapsed time when a given binary signal
has been high. • measured voltages, currents, frequency, active, reactive
and apparent power and power factor
The main features of TEIGAPC • measured analog values from merging units
• primary phasors
• Applicable to long time integration (≤999 999.9 • positive, negative and zero sequence currents and
seconds). voltages
• Supervision of limit transgression conditions and • mA, input currents
overflow. • pulse counters
• Possibility to define a warning or alarm with the
resolution of 10 milliseconds.
• Retaining of the integration value. Supervision of mA input signals
M16054-3 v2

• Possibilities for blocking and reset. The main purpose of the function is to measure and process
• Reporting of the integrated time. signals from different measuring transducers. Many devices
used in process control represent various parameters such as
frequency, temperature and DC battery voltage as low current
Boolean to integer conversion, 16 bit B16I values, usually in the range 4-20 mA or 0-20 mA.
SEMOD175725-4 v5
Boolean to integer conversion, 16 bit (B16I) is used to
transform a set of 16 boolean (logical) signals into an integer. Alarm limits can be set and used as triggers, e.g. to generate
trip or alarm signals.
Boolean to integer conversion with logical node
representation, 16 bit BTIGAPC The function requires that the IED is equipped with the mA
SEMOD175781-4 v8
Boolean to integer conversion with logical node input module.
representation, 16 bit (BTIGAPC) is used to transform a set of
16 boolean (logical) signals into an integer. The block input Disturbance report DRPRDRE
M12153-3 v14

will freeze the output at the last value. Complete and reliable information about disturbances in the
primary and/or in the secondary system together with
Integer to Boolean 16 conversion IB16 continuous event-logging is accomplished by the disturbance
SEMOD158373-5 v6
Integer to boolean 16 conversion function (IB16) is used to report functionality.
transform an integer into a set of 16 boolean (logical) signals.
Disturbance report (DRPRDRE), always included in the IED,
Integer to Boolean 16 conversion with logic node acquires sampled data of all selected analog input and binary
representation ITBGAPC signals connected to the function block with a maximum of
SEMOD158421-5 v9
Integer to boolean conversion with logic node representation 40 analog and 352 binary signals.
function (ITBGAPC) is used to transform an integer which is
transmitted over IEC 61850 and received by the function to The Disturbance report functionality is a common name for
16 boolean (logic) output signals. several functions:

38 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

• Event list term (for example corrective actions) and in the long term (for
• Indications example functional analysis).
• Event recorder
• Trip value recorder The event recorder logs all selected binary input signals
• Disturbance recorder connected to the Disturbance recorder function. Each
• Fault locator recording can contain up to 150 time-tagged events.
• Settings information
The event recorder information is available for the
The Disturbance report function is characterized by great disturbances locally in the IED.
flexibility regarding configuration, starting conditions,
The event recording information is an integrated part of the
recording times, and large storage capacity.
disturbance record (Comtrade file).
A disturbance is defined as an activation of an input to the
Trip value recorder DRPRDRE
AnRADR or BnRBDR function blocks, which are set to trigger M12128-3 v7
Information about the pre-fault and fault values for currents
the disturbance recorder. All connected signals from start of
and voltages are vital for the disturbance evaluation.
pre-fault time to the end of post-fault time will be included in
the recording. Disturbance record will have visible settings The Trip value recorder calculates the values of all selected
from all function instances that are configured in the analog input signals connected to the Disturbance recorder
application configuration tool. function. The result is magnitude and phase angle before and
during the fault for each analog input signal.
Every disturbance report recording is saved in the IED in the
standard Comtrade format as a reader file HDR, a The trip value recorder information is available for the
configuration file CFG, and a data file DAT. The same applies disturbances locally in the IED.
to all events, which are continuously saved in a ring-buffer.
The local HMI is used to get information about the recordings. The trip value recorder information is an integrated part of the
The disturbance report files can be uploaded to PCM600 for disturbance record (Comtrade file).
further analysis using the disturbance handling tool.
Disturbance recorder DRPRDRE
M12156-3 v12

Event list DRPRDRE The Disturbance recorder function supplies fast, complete
M12412-6 v8
Continuous event-logging is useful for monitoring the system and reliable information about disturbances in the power
from an overview perspective and is a complement to specific system. It facilitates understanding system behavior and
disturbance recorder functions. related primary and secondary equipment during and after a
disturbance. Recorded information is used for different
The event list logs all binary input signals connected to the purposes in the short perspective (for example corrective
Disturbance recorder function. The list may contain up to actions) and long perspective (for example functional
1000 time-tagged events stored in a ring-buffer. analysis).

Indications DRPRDRE The Disturbance recorder acquires sampled data from


M12030-3 v7
To get fast, condensed and reliable information about selected analog and binary signals connected to the
disturbances in the primary and/or in the secondary system it Disturbance recorder function (maximum 40 analog and 352
is important to know, for example binary signals that have binary signals). The binary signals available are the same as
changed status during a disturbance. This information is used for the event recorder function.
in the short perspective to get information via the local HMI in
a straightforward way. The function is characterized by great flexibility and is not
dependent on the operation of protection functions. It can
There are three LEDs on the local HMI (green, yellow and record disturbances not detected by protection functions. Up
red), which will display status information about the IED and to ten seconds of data before the trigger instant can be saved
the Disturbance recorder function (triggered). in the disturbance file.

The Indication list function shows all selected binary input The disturbance recorder information for up to 100
signals connected to the Disturbance recorder function that disturbances are saved in the IED and the local HMI is used
have changed status during a disturbance. to view the list of recordings .

Event recorder DRPRDRE Event function


M12033-3 v8
M12805-6 v11
Quick, complete and reliable information about disturbances When using a Substation Automation system with LON or
in the primary and/or in the secondary system is vital, for SPA communication, time-tagged events can be sent at
example, time-tagged events logged during disturbances. change or cyclically from the IED to the station level. These
This information is used for different purposes in the short events are created from any available signal in the IED that is

ABB 39
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

connected to the Event function (EVENT). The EVENT wear, travel time, number of operation cycles and estimate
function block is used for LON and SPA communication. the accumulated energy during arcing periods.

Analog, integer and double indication values are also


transferred through the EVENT function. Fault locator LMBRFLO
M13970-3 v13
The accurate fault locator is an essential component to
Generic communication function for Single Point indication minimize the outages after a persistent fault and/or to pin-
SPGAPC point a weak spot on the line.
SEMOD55713-5 v8
Generic communication function for Single Point indication
(SPGAPC) is used to send one single logical signal to other The fault locator is an impedance measuring function giving
systems or equipment in the substation. the distance to the fault in km, miles or % of line length. The
main advantage is the high accuracy achieved by
Generic communication function for measured values compensating for load current and for the mutual zero-
MVGAPC sequence effect on double circuit lines.
SEMOD55872-5 v10
Generic communication function for measured values
(MVGAPC) function is used to send the instantaneous value The compensation includes setting of the remote and local
of an analog signal to other systems or equipment in the sources and calculation of the distribution of fault currents
substation. It can also be used inside the same IED, to attach from each side. This distribution of fault current, together with
a RANGE aspect to an analog value and to permit recorded load (pre-fault) currents, is used to exactly calculate
measurement supervision on that value. the fault position. The fault can be recalculated with new
source data at the actual fault to further increase the
Measured value expander block RANGE_XP accuracy.
SEMOD52450-4 v8
The current and voltage measurements functions (CVMMXN,
CMMXU, VMMXU and VNMMXU), current and voltage Especially on heavily loaded long lines, where the source
sequence measurement functions (CMSQI and VMSQI) and voltage angles can be up to 35-40 degrees apart, the
IEC 61850 generic communication I/O functions (MVGAPC) accuracy can be still maintained with the advanced
are provided with measurement supervision functionality. All compensation included in fault locator.
measured values can be supervised with four settable limits:
Event counter with limit supervison L4UFCNT
low-low limit, low limit, high limit and high-high limit. The GUID-13157EAB-1686-4D2E-85DF-EC89768F3572 v6
The Limit counter (L4UFCNT) provides a settable counter with
measure value expander block (RANGE_XP) has been
four independent limits where the number of positive and/or
introduced to enable translating the integer output signal from
negative flanks on the input signal are counted against the
the measuring functions to 5 binary signals: below low-low
setting values for limits. The output for each limit is activated
limit, below low limit, normal, above high limit or above high-
when the counted value reaches that limit.
high limit. The output signals can be used as conditions in the
configurable logic or for alarming purpose. Overflow indication is included for each up-counter.

Insulation supervision for gas medium function SSIMG Running hour-meter TEILGAPC
GUID-0692CD0D-F33E-4370-AC91-B216CAAAFC28 v6 GUID-464FB24F-B367-446C-963A-A14841943B87 v2
Insulation supervision for gas medium (SSIMG) is used for The Running hour-meter (TEILGAPC) function is a function
monitoring the circuit breaker condition. Binary information that accumulates the elapsed time when a given binary signal
based on the gas pressure in the circuit breaker is used as has been high.
input signals to the function. In addition, the function
generates alarms based on received information. The main features of TEILGAPC are:

Insulation supervision for liquid medium SSIML • Applicable to very long time accumulation (≤ 99999.9
GUID-3B1A665F-60A5-4343-85F4-AD9C066CBE8D v7
Insulation supervision for liquid medium (SSIML) is used for hours)
monitoring the oil insulated device condition. For example, • Supervision of limit transgression conditions and rollover/
transformers, shunt reactors, and so on. Binary information overflow
based on the oil level in the oil insulated devices are used as • Possibility to define a warning and alarm with the
input signals to the function. In addition, the function resolution of 0.1 hours
generates alarms based on the received information. • Retain any saved accumulation value at a restart
• Possibilities for blocking and reset
Circuit breaker condition monitoring SSCBR • Possibility for manual addition of accumulated time
GUID-E1FD74C3-B9B6-4E11-AA1B-7E7F822FB4DD v13
The circuit breaker condition monitoring function (SSCBR) is • Reporting of the accumulated time
used to monitor different parameters of the breaker condition.
The breaker requires maintenance when the number of
Estimation of transformer winding insulation life LOLSPTR
operations reaches a predefined value. For a proper GUID-CDE89397-8E99-4873-9701-FF642101A308 v2
Estimation of transformer winding insulation life (LOLSPTR) is
functioning of the circuit breaker, it is essential to monitor the
used to calculate transformer winding hot spot temperature
circuit breaker operation, spring charge indication or breaker
using the empirical formulae. It is also used to estimate
40 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

transformer loss of life from the winding hot spot temperature generated as pulses. Maximum demand power values are
value. The transformer winding insulation is degraded when also calculated by the function. This function includes zero
the winding hot spot temperature exceeds certain limit. point clamping to remove noise from the input signal. As
LOLSPTR gives warning and alarm signals when the winding output of this function: periodic energy calculations,
hot spot temperature reaches a set value. integration of energy values, calculation of energy pulses,
alarm signals for limit violation of energy values and maximum
Hot spot temperature calculation requires top oil temperature power demand, can be found.
at a given time. This value can either be a measured value
taken through sensors or the one calculated by the function. The values of active and reactive energies are calculated from
This decision is made based on the top oil temperature the input power values by integrating them over a selected
sensor quality. Top oil temperature calculation is done using time tEnergy. The integration of active and reactive energy
the method explained in IEC 60076-7 standard. values will happen in both forward and reverse directions.
These energy values are available as output signals and also
Inputs required for hot spot temperature calculation are: as pulse outputs. Integration of energy values can be
• Transformer oil time constant controlled by inputs (STARTACC and STOPACC) and EnaAcc
• Winding time constant setting and it can be reset to initial values with RSTACC
• Loss ratio at different tap positions input.
• Ambient temperature around the transformer
The maximum demand for active and reactive powers are
calculated for the set time interval tEnergy and these values
The oil and winding time constants can be calculated by the
are updated every minute through output channels. The
function based on transformer parameters if the inputs are
active and reactive maximum power demand values are
not available from the transformer manufacturer.
calculated for both forward and reverse direction and these
Ambient temperature to the function can either be provided values can be reset with RSTDMD input.
through the sensor or monthly average ambient temperature
settings. This decision is made based on the ambient
temperature sensor quality. Additionally, LOLSPTR function
provides difference between measured value and calculated
value of the top oil temperature.

Additionally, the function calculates loss of life in form of days


and years. This information is updated at settable intervals,
for example, hourly or daily. Transformer winding percentage
loss of life is calculated every day and the information is
provided as total percentage loss of life from the installation
date and yearly percentage loss of life.

16. Metering

Pulse-counter logic PCFCNT


M13394-3 v7
Pulse-counter logic (PCFCNT) function counts externally
generated binary pulses, for instance pulses coming from an
external energy meter, for calculation of energy consumption
values. The pulses are captured by the binary input module
and then read by the PCFCNT function. A scaled service
value is available over the station bus. The special Binary
input module with enhanced pulse counting capabilities must
be ordered to achieve this functionality.

Function for energy calculation and demand handling


ETPMMTR
GUID-6898E29B-DA70-421C-837C-1BBED8C63A7A v3
Power system measurement (CVMMXN) can be used to
measure active as well as reactive power values. Function for
energy calculation and demand handling (ETPMMTR) uses
measured active and reactive power as input and calculates
the accumulated active and reactive energy pulses, in forward
and reverse direction. Energy values can be read or

ABB 41
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

M11345-3 v11
17. Human machine interface
Precision time protocol PTP
Local HMI PTP according to IEEE 1588-2008 and specifically its profile
AMU0600442 v15
IEC/IEEE 61850-9-3 for power utility automation is a
synchronization method that can be used to maintain a
common time within a station. This time can be synchronized
to the global time using, for instance, a GPS receiver. If PTP
is enabled on the IEDs and the switches that connect the
station are compatible with IEEE 1588, the station will
become synchronized to one common time with an accuracy
of under 1us. Using an IED as a boundary clock between
several networks will keep 1us accuracy on three levels or
when using an HSR, 15 IEDs can be connected in a ring
without losing a single microsecond in accuracy.

19. Ethernet

Access points
GUID-6E5D2696-A8EE-43E7-A94B-69C3D0612127 v2
An access point is an Ethernet communication interface for
single or redundant station communication. Each access
point is allocated with one physical Ethernet port, two
physical Ethernet ports are allocated if redundant
communication is activated for the access point.

Device 1 Device 1

AP1 AP2 AP3 AP1 AP2 AP3


SFP_301 SFP_302 SFP_303 SFP_301 SFP_302 SFP_303
IEC13000239-3-en.vsd

IEC13000239 V3 EN-US
IEC16000092-1-en.vsdx

Figure 5. Local human-machine interface IEC16000092 V1 EN-US

Figure 6. Access points, non redundant (left) and redundant


communication (right)
The LHMI of the IED contains the following elements
• Graphical display capable of showing a user defined single
line diagram and provide an interface for controlling Access points diagnostics
switchgear. GUID-20F64A6D-AA8C-47D7-AA7D-4810996B2FF2 v2
The access point diagnostics function blocks (RCHLCCH,
• Navigation buttons and five user defined command buttons SCHLCCH and FRONTSTATUS) supervise communication.
to shortcuts in the HMI tree or simple commands. SCHLCCH is used for communication over the rear Ethernet
• 15 user defined three-color LEDs. ports, RCHLCCH is used for redundant communications over
• Communication port for PCM600. the rear Ethernet ports and FRONTSTATUS is used for
communication over the front port. All access point function
The LHMI is used for setting, monitoring and controlling. blocks include output signal for denial of service.

Redundant communication
GUID-A90FDBA7-D4D7-4CBD-9F05-13DCC9971779 v7
18. Basic IED functions
IEC 62439-3 redundant communication PRP
Time synchronization Redundant communication according to IEC 62439-3 PRP-0,
M11344-3 v11
The time synchronization function is used to select a common IEC 62439-3 PRP-1 parallel redundancy protocol (PRP) is
source of absolute time for the synchronization of the IED available as an option when ordering IEDs. PRP according to
when it is a part of a control and a protection system. This IEC 62439-3 uses two optical Ethernet ports.
makes it possible to compare events and disturbance data
between all IEDs within a station automation system and in IEC 62439-3 High-availability seamless redundancy HSR
between sub-stations. A common source shall be used for Redundant station bus communication according to IEC
IED and merging unit when IEC/UCA 61850-9-2LE process 62439-3 Edition 2 High-availability seamless redundancy
bus communication is used. (HSR) is available as an option when ordering IEDs.
Redundant station bus communication according to IEC
62439-3 uses two optical Ethernet ports.

42 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

The HSR ring supports the connection of up to 30 relays. If The front port is only intended for PCM600
more than 30 relays are to be connected, it is recommended communication, maintenance, training and
to split the network into several rings to guarantee the test purposes due to risk of interference
performance for real-time applications. during normal operation.

Routes
GUID-95F9C7BA-92F8-489F-AD0A-047410B5E66F v1
A route is a specified path for data to travel between the IEC 61850 quality expander QUALEXP
source device in a subnetwork to the destination device in a GUID-9C5DC78E-041B-422B-9668-320E62B847A2 v1
The quality expander component is used to display the
different subnetwork. A route consists of a destination detailed quality of an IEC/UCA 61850-9-2LE analog channel.
address and the address of the gateway to be used when The component expands the channel quality output of a
sending data to the destination device, see Figure 7. Merging Unit analog channel received in the IED as per the
IEC 61850-7-3 standard. This component can be used during
the ACT monitoring to get the particular channel quality of the
Merging Unit.

IEC/UCA 61850-9-2LE communication protocol


GUID-C3AA21B4-730F-4327-943A-3C77102A80A0 v4
Default gateway Optical Ethernet port communication standard IEC/UCA
61850-9-2LE for process bus is supported. IEC/UCA
61850-9-2LE allows Non Conventional Instrument
Gateway Transformers (NCIT) with Merging Units (MUs) or stand-alone
MUs to exchange information with the IED, and simplifies SA
Source Destination engineering. IEC/UCA 61850-9-2LE uses the same port as
IEC16000095-1-en.vsdx
IEC16000095 V1 EN-US
IEC 61850-8-1.
Figure 7. Route from source to destination through gateway
LON communication protocol
SEMOD120140-5 v3
Existing stations with ABB station bus LON can be extended
with use of the optical LON interface (glass or plastic). This
20. Station communication allows full SA functionality including peer-to-peer messaging
and cooperation between the IEDs.
Communication protocols
M14815-3 v14
Each IED is provided with several communication interfaces SPA communication protocol
SEMOD120134-5 v1

enabling it to connect to one or many substation level A single glass or plastic port is provided for the ABB SPA
systems or equipment, either on the Substation Automation protocol. This allows extensions of simple substation
(SA) bus or Substation Monitoring (SM) bus. automation systems but the main use is for Substation
Monitoring Systems SMS.
Available communication protocols are:
IEC 60870-5-103 communication protocol
SEMOD120137-5 v4
• IEC 61850-8-1 communication protocol A single glass or plastic port is provided for the IEC
• IEC/UCA 61850-9-2LE communication protocol 60870-5-103 standard. This allows design of simple
• LON communication protocol substation automation systems including equipment from
• SPA communication protocol different vendors. Disturbance files uploading is provided.
• IEC 60870-5-103 communication protocol
Measurands for IEC 60870-5-103 I103MEAS
Several protocols can be combined in the same IED. 103MEAS is a function block that reports all valid measuring
types depending on the connected signals. The set of
IEC 61850-8-1 communication protocol
M14787-3 v16 connected inputs will control which ASDUs (Application
IEC 61850 Ed.1 or Ed.2 can be chosen by a setting in
Service Data Units) are generated.
PCM600. The IED is equipped with up to six (order
dependent) optical Ethernet rear ports for IEC 61850-8-1 Measurands user-defined signals for IEC 60870-5-103
station bus communication.The IEC 61850-8-1 I103MEASUSR
communication is also possible from the electrical Ethernet I103MEASUSR is a function block with user-defined input
front port. IEC 61850-8-1 protocol allows intelligent electrical measurands in monitor direction. These function blocks
devices (IEDs) from different vendors to exchange information include the FunctionType parameter for each block in the
and simplifies system engineering. IED-to-IED communication private range, and the Information number parameter for each
using GOOSE and client-server communication over MMS are block.
supported. Disturbance recording file (COMTRADE) uploading
can be done over MMS or FTP.

ABB 43
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

range, and the Information number parameter for each output


Function status auto-recloser for IEC 60870-5-103 I103AR signal.
I103AR is a function block with defined functions for
autorecloser indications in monitor direction. This block Function commands generic for IEC 60870-5-103
includes the FunctionType parameter, and the information I103GENCMD
number parameter is defined for each output signal. I103GENCMD is used for transmitting generic commands
over IEC 60870-5-103. The function has two output signals,
Function status earth-fault for IEC 60870-5-103 I103EF CMD_OFF and CMD_ON, that can be used to implement
I103EF is a function block with defined functions for earth double-point command schemes.
fault indications in monitor direction. This block includes the
FunctionType parameter; the information number parameter The I103GENCMD component can be configured as either 2
is defined for each output signal. pulsed ON/OFF or 2 steady ON/OFF outputs. The ON output
is pulsed with a command with value 2, while the OFF output
Function status fault protection for IEC 60870-5-103 is pulsed with a command with value 1. If in steady mode is
I103FLTPROT ON asserted and OFF deasserted with command 2 and vice
I103FLTPROT is used for fault indications in monitor versa with command 1.
direction. Each input on the function block is specific for a
certain fault type and therefore must be connected to a IED commands with position and select for IEC 60870-5-103
correspondent signal present in the configuration. For I103POSCMD
example: 68_TRGEN represents the General Trip of the I103POSCMD has double-point position indicators that are
device and must be connected to the general trip signal getting the position value as an integer (for example, from the
SMPPTRC_TRIP or equivalent. POSITION output of the SCSWI function block) and sending it
over IEC 60870-5-103 (1=OPEN; 2=CLOSE). The standard
IED status for IEC 60870-5-103 I103IED does not define the use of values 0 and 3. However, when
I103IED is a function block with defined IED functions in connected to a switching device, these values are
monitor direction. This block uses the parameter transmitted.
FunctionType; the information number parameter is defined
for each input signal. The BLOCK input will block only the signals in monitoring
direction (the position information), not the commands via IEC
Supervison status for IEC 60870-5-103 I103SUPERV 60870-5-103. The SELECT input is used to indicate that the
I103SUPERV is a function block with defined functions for monitored apparatus has been selected (in a select-before-
supervision indications in monitor direction. This block operate type of control).
includes the FunctionType parameter; the information number
parameter is defined for each output signal. DNP3.0 communication protocol
SEMOD153688-5 v3
An electrical RS485 serial port, optical serial ports on the
Status for user-defined signals for IEC 60870-5-103 serial communication module (SLM), optical Ethernet ports
I103USRDEF are available for DNP3.0 communication. DNP3.0 Level 2
I103USRDEF comprises function blocks with user-defined communication with unsolicited events, time synchronization
input signals in monitor direction. These function blocks and disturbance reporting is provided for communication to
include the FunctionType parameter for each block in the RTUs, Gateways or HMI systems.
private range, and the information number parameter for each
input signal. Multiple command and transmit
M14791-3 v3
When IEDs are used in Substation Automation systems with
Function commands for IEC 60870-5-103 I103CMD LON, SPA or IEC 60870-5-103 communication protocols, the
I103CMD is a command function block in control direction Event and Multiple Command function blocks are used as the
with pre-defined output signals. The signals are in steady communication interface for vertical communication to station
state, not pulsed, and stored in the IED in case of restart. HMI and gateway, and as interface for horizontal peer-to-peer
communication (over LON only).
IED commands for IEC 60870-5-103 I103IEDCMD
I103IEDCMD is a command block in control direction with
defined IED functions. All outputs are pulsed and they are 21. Remote communication
NOT stored. Pulse-time is a hidden parameter.
Analog and binary signal transfer to remote end
M12449-6 v3
Function commands user-defined for IEC 60870-5-103 Three analog and eight binary signals can be exchanged
I103USRCMD between two IEDs. This functionality is mainly used for the
I103USRCMD is a command block in control direction with line differential protection. However it can be used in other
user-defined output signals. These function blocks include products as well. An IED can communicate with up to 4
the FunctionType parameter for each block in the private remote IEDs.

44 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Binary input module BIM


Binary signal transfer M1769-3 v4
The binary input module has 16 optically isolated inputs and
SEMOD52522-4 v8
The remote end data communication is used for the is available in two versions, one standard and one with
transmission of analog values for line differential protection or enhanced pulse counting capabilities on the inputs to be
for the transmission of only binary signals between IEDs. The used with the pulse counter function. The binary inputs are
binary signals are freely configurable and can thus be used freely programmable and can be used for the input of logical
for any purpose, such as communication scheme related signals to any of the functions. They can also be included in
signals, transfer trip and/or other binary signals between the disturbance recording and event-recording functions. This
IEDs. enables extensive monitoring and evaluation of operation of
the IED and for all associated electrical circuits.
Communication between two IEDs requires that each IED is
equipped with a Line Data Communication Module (LDCM). Binary output module BOM
The LDCM then acts as an interface to 64 kbit/s and 2Mbit/s M6938-3 v4
The binary output module has 24 independent output relays
communication channels for duplex communication between and is used for trip output or any signaling purpose.
the IEDs. In 2Mbit/s mode, each LDCM can send and receive
up to 9 analog and up to 192 binary signals simultaneously. Static binary output module SOM
SEMOD174196-4 v4
In 64kbit/s mode, the LDCM can be configured to work in The static binary output module has six fast static outputs
either analog mode or binary mode. In analog mode, the IED and six change over output relays for use in applications with
can send and receive up to 3 analog signals and up to 8 high speed requirements.
binary signals. In binary mode, the LDCM can send and
receive only binary data (up to 192 binary signals). Binary input/output module IOM
M6939-3 v6
The binary input/output module is used when only a few input
The IED can be equipped with up to two short range, medium and output channels are needed. The ten standard output
range or long range LDCMs. channels are used for trip output or any signaling purpose.
The two high speed signal output channels are used for
Line data communication module, short, medium and long applications where short operating time is essential. Eight
range LDCM optically isolated binary inputs cater for required binary input
SEMOD168481-4 v10
The line data communication module (LDCM) is used for information.
communication between the IEDs situated at a distance <110
km/68 miles or from the IED to the optical-to-electrical mA input module MIM
M15020-3 v4
converter with G.703 or G.703E1 interface located at a The milli-ampere input module is used to interface transducer
distance < 3 km/1.9 miles away. The LDCM module sends signals in the –20 to +20 mA range from for example OLTC
and receives data to and from another LDCM module. The position, temperature or pressure transducers. The module
IEEE/ANSI C37.94 standard format is used. has six independent, galvanically separated channels.

Galvanic interface G.703 resp G.703E1 Optical Ethernet module


M16035-3 v5 M16073-3 v8
The external galvanic data communication converter G. The optical Ethernet module (OEM) provides two additional
703/G.703E1 makes an optical-to-galvanic conversion for optical ethernet ports. The port connectors are of LC type.
connection to a multiplexer. These units are designed for 64
kbit/s resp 2Mbit/s operation. The converter is delivered with Serial and LON communication module (SLM) for SPA/IEC
19” rack mounting accessories. 60870-5-103, LON and DNP 3.0
M14933-3 v6
The Serial and LON communication module (SLM) is used for
SPA, IEC 60870-5-103, DNP3 and LON communication. SLM
22. Hardware description has two optical communication ports for plastic/plastic,
plastic/glass or glass/glass fiber cables. One port is used for
Hardware modules
IP14529-1 v1
serial communication (SPA, IEC 60870-5-103 or DNP3 port)
Numeric processing module NUM
M12643-3 v4
and the other port is used for LON communication.
The numeric processing module (NUM) is a CPU module that
handles all protection functions and logic. Line data communication module LDCM
M16075-3 v5
Each module has one optical port, one for each remote end
NUM provides up to 4 optical (type LC) or galvanic (type
to which the IED communicates.
RJ45) Ethernet ports(one basic and three optional).
Alternative modules for Long range (1550 nm single mode),
Power supply module PSM
M11595-3 v6
Medium range (1310 nm single mode) and Short range (850
The power supply module is used to provide the correct
nm multi mode) are available.
internal voltages and full isolation between the IED and the
battery system. An internal fail alarm output is available. Galvanic RS485 serial communication module
SEMOD158664-5 v3
The Galvanic RS485 communication module (RS485) is used
Alternative connectors of Ring lug or Compression type can
for DNP3.0 and IEC 60870-5-103 communication. The
be ordered.
ABB 45
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

M15243-4 v7
module has one RS485 communication port. The RS485 is a
balanced serial communication that can be used either in 2-
wire or 4-wire connections. A 2-wire connection uses the
same signal for RX and TX and is a multidrop communication
with no dedicated Master or slave. This variant requires
E
however a control of the output. The 4-wire connection has
separated signals for RX and TX multidrop communication
with a dedicated Master and the rest are slaves. No special
control signal is needed in this case.

GPS time synchronization module GTM A


M14851-3 v5 D
This module includes a GPS receiver used for time
synchronization. The GTM has one SMA contact for
connection to an antenna. It also includes an optical PPS ST-
connector output.

IRIG-B Time synchronizing module


SEMOD141113-4 v8
The IRIG-B time synchronizing module is used for accurate
B
time synchronizing of the IED from a station clock. C
Electrical (BNC) and optical connection (ST) for 0XX and 12X
IRIG-B support.
IEC08000163-2-en.vsd
Transformer input module TRM IEC08000163 V2 EN-US
M14875-3 v9
The transformer input module is used to galvanically separate Figure 8. Case with rear cover
and adapt the secondary currents and voltages generated by
the measuring transformers. The module has twelve inputs in
different combinations of currents and voltage inputs.

Alternative connectors of Ring lug or Compression type can


be ordered.
K
High impedance resistor unit
M16727-3 v2
The high impedance resistor unit, with resistors for pick-up F
value setting and a voltage dependent resistor, is available in
a single phase unit and a three phase unit. Both are mounted
on a 1/1 19 inch apparatus plate with compression type
terminals.

Layout and dimensions


IP14539-1 v1
Dimensions
IP14826-1 v1

G
J
H

IEC08000165-2-en.vsdx
IEC08000165 V2 EN-US

Figure 9. Case with rear cover and 19” rack mounting kit

46 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

M15243-12 v9

IEC06000182-2-en.vsd
IEC06000182 V2 EN-US

Figure 10. A 1/2 x 19” size IED side-by-side with RHGS6.

Case size A B C D E F G H J K
(mm)/(inches)

6U, 1/2 x 19” 265.9/ 223.7/ 242.1/ 255.8/ 205.7/ 190.5/ 203.7/ - 228.6/ -
10.47 8.81 9.53 10.07 8.10 7.50 8.02 9.00

6U, 3/4 x 19” 265.9/ 336.0/ 242.1/ 255.8/ 318.0/ 190.5/ 316.0/ - 228.6/ -
10.47 13.23 9.53 10.07 12.52 7.50 12.4 9.00

6U, 1/1 x 19” 265.9/ 448.3/ 242.1/ 255.8/ 430.3/ 190.5/ 428.3/ 465.1/ 228.6/ 482.6/19.00
10.47 17.65 9.53 10.07 16.86 7.50 16.86 18.31 9.00

The H and K dimensions are defined by the 19” rack mounting kit.

Mounting alternatives See ordering for details about available mounting alternatives.
M16079-3 v14
• 19” rack mounting kit
• Flush mounting kit with cut-out dimensions:
– 1/2 case size (h) 254.3 mm/10.01” (w) 210.1 mm/
8.27”
– 3/4 case size (h) 254.3 mm/10.01” (w) 322.4 mm/
12.69”
– 1/1 case size (h) 254.3 mm/10.01” (w) 434.7 mm/
17.11”
• Wall mounting kit

ABB 47
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

23. Connection diagrams Connection diagram, REC670 2.2, A30X00 1MRK002807-CA


GUID-CF4EFFA5-3081-4FC7-9A14-ED127C3C0FDE v7
The connection diagrams are delivered in the IED Connectivity
package as part of the product delivery. Connection diagram, REC670 2.2, B30X00 1MRK002807-CB

The latest versions of the connection diagrams can be Connection diagram, REC670 2.2, C30X00 1MRK002807-CC
downloaded from http://www.abb.com/protection-control.
Connection diagram, REC670 2.2, D30X00 1MRK002807-CE
Connection diagrams for IEC Customized products
Connection diagrams for ANSI Customized products
Connection diagram, 670 series 2.2 1MRK002801-AG
Connection diagram, 670 series 2.2 1MRK002802-AG
Connection diagrams for Configured products

48 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

24. Technical data

General
M10993-1 v3 IP11376-1 v2

Definitions

Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment

Nominal range The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the
specified requirements

Operative range The range of values of a given energizing quantity for which the equipment, under specified conditions, is able to perform its
intended functions according to the specified requirements

Presumptions for Technical Data 6. Parameter SBase used by the tested function is set
GUID-1E949E38-E04D-4374-A086-912C25E9F93C v2
The technical data stated in this document are only valid equal to:
under the following circumstances: – √3 × IBase × UBase
7. The rated secondary quantities have the following
1. Main current transformers with 1 A or 2 A secondary values:
rating are wired to the IED 1 A rated CT inputs. – Rated secondary phase current I r is either 1 A or 5 A
2. Main current transformer with 5 A secondary rating are
depending on selected TRM.
wired to the IED 5 A rated CT inputs.
– Rated secondary phase-to-phase voltage U r is within
3. CT and VT ratios in the IED are set in accordance with
the range from 100 V to 120 V.
the associated main instrument transformers. Note that
– Rated secondary power for three-phase system S r =
for functions which measure an analogue signal which
√3 × U r × Ir
do not have corresponding primary quantity the 1:1 ratio
shall be set for the used analogue inputs on the IED. 8. For operate and reset time testing, the default setting
Example of such functions are: HZPDIF, ROTIPHIZ and values of the function are used if not explicitly stated
STTIPHIZ. otherwise.
4. Parameter IBase used by the tested function is set 9. During testing, signals with rated frequency have been
equal to the rated CT primary current. injected if not explicitly stated otherwise.
5. Parameter UBase used by the tested function is set
equal to the rated primary phase-to-phase voltage.

ABB 49
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Energizing quantities, rated values and limits


Analog inputs
M16988-1 v11 IP15842-1 v1

Table 11. TRM - Energizing quantities, rated values and limits for protection transformer

Description Value

Frequency

Rated frequency fr 50/60 Hz

Operating range fr ± 10%

Current inputs

Rated current Ir 1 or 5 A

Operating range (0-100) x Ir

Thermal withstand 100 × Ir for 1 s *)


30 × Ir for 10 s
10 × Ir for 1 min
4 × Ir continuously

Dynamic withstand 250 × Ir one half wave

Burden < 20 mVA at Ir = 1 A


< 150 mVA at Ir = 5 A

*) max. 350 A for 1 s when COMBITEST test switch is included.

Voltage inputs **)

Rated voltage Ur 110 or 220 V

Operating range 0 - 340 V

Thermal withstand 450 V for 10 s


420 V continuously

Burden < 20 mVA at 110 V


< 80 mVA at 220 V

**) all values for individual voltage inputs

Note! All current and voltage data are specified as RMS values at rated frequency

50 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Table 12. TRM - Energizing quantities, rated values and limits for measuring transformer

Description Value

Frequency

Rated frequency fr 50/60 Hz

Operating range fr ± 10%

Current inputs

Rated current Ir 1A 5A

Operating range (0-1.8) × Ir (0-1.6) × Ir

Thermal withstand 80 × Ir for 1 s 65 × Ir for 1 s


25 × Ir for 10 s 20 × Ir for 10 s
10 × Ir for 1 min 8 × Ir for 1 min
1.8 × Ir for 30 min 1.6 × Ir for 30 min
1.1 × Ir continuously 1.1 × Ir continuously

Burden < 200 mVA at Ir < 350 mVA at Ir

Voltage inputs *)

Rated voltage Ur 110 or 220 V

Operating range 0 - 340 V

Thermal withstand 450 V for 10 s


420 V continuously

Burden < 20 mVA at 110 V


< 80 mVA at 220 V

*) all values for individual voltage inputs

Note! All current and voltage data are specified as RMS values at rated frequency
M6389-1 v5

Table 13. MIM - mA input module

Quantity: Rated value: Nominal range:

Input resistance Rin = 194 Ohm -

Input range ±5, ±10, ±20 mA -


0-5, 0-10, 0-20, 4-20 mA

Power consumption -
each mA board £2W
each mA input £ 0.1 W

Auxiliary DC voltage
M12286-1 v8 IP15843-1 v3

Table 14. PSM - Power supply module

Quantity Rated value Nominal range

Auxiliary DC voltage, EL (input) EL = (24-60) V EL ±20%


EL = (100-250) V EL ±20%

Power consumption 50 W typically -

Auxiliary DC power in-rush < 10 A during 0.1 s -

Supply interruption bridging time < 50 ms -

ABB 51
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Binary inputs and outputs


M12576-1 v11 IP15844-1 v1

Table 15. BIM - Binary input module

Quantity Rated value Nominal range

Binary inputs 16 -

DC voltage, RL 24/30 V RL ±20%


48/60 V RL ±20%
110/125 V RL ±20%
220/250 V RL ±20%

Power consumption
24/30 V, 50 mA max. 0.05 W/input -
48/60 V, 50 mA max. 0.1 W/input
110/125 V, 50 mA max. 0.2 W/input
220/250 V, 50 mA max. 0.4 W/input
220/250 V, 110 mA max. 0.5 W/input

Counter input frequency 10 pulses/s max -

Oscillating signal discriminator Blocking settable 1–40 Hz


Release settable 1–30 Hz

Debounce filter Settable 1–20 ms

Binary input operate time 3 ms -


(Debounce filter set to 0 ms)

Maximum 176 binary input channels may The stated operate time for functions
be activated simultaneously with influencing include the operating time for the binary
factors within nominal range. inputs and outputs.

M50609-2 v8

Table 16. BIM - Binary input module with enhanced pulse counting capabilities

Quantity Rated value Nominal range

Binary inputs 16 -

DC voltage, RL 24/30 V RL ±20%


48/60 V RL ±20%
110/125 V RL ±20%
220/250 V RL ±20%

Power consumption
24/30 V max. 0.05 W/input -
48/60 V max. 0.1 W/input
110/125 V max. 0.2 W/input
220/250 V max. 0.4 W/input

Counter input frequency 10 pulses/s max -

Balanced counter input frequency 40 pulses/s max -

Oscillating signal discriminator Blocking settable 1–40 Hz


Release settable 1–30 Hz

Debounce filter Settable 1-20 ms

Binary input operate time 3 ms -


(Debounce filter set to 0 ms)

52 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Maximum 176 binary input channels may The stated operate time for functions
be activated simultaneously with influencing include the operating time for the binary
factors within nominal range. inputs and outputs.

M12573-1 v10

Table 17. IOM - Binary input/output module

Quantity Rated value Nominal range

Binary inputs 8 -

DC voltage, RL 24/30 V RL ±20%


48/60 V RL ±20%
110/125 V RL ±20%
220/250 V RL ±20%

Power consumption -
24/30 V, 50 mA max. 0.05 W/input
48/60 V, 50 mA max. 0.1 W/input
110/125 V, 50 mA max. 0.2 W/input
220/250 V, 50 mA max. 0.4 W/input
220/250 V, 110 mA max. 0.5 W/input

Counter input frequency 10 pulses/s max

Oscillating signal discriminator Blocking settable 1-40 Hz


Release settable 1-30 Hz

Debounce filter Settable 1-20 ms

Binary input operate time 3 ms -


(Debounce filter set to 0 ms)

ABB 53
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Maximum 176 binary input channels may The stated operate time for functions
be activated simultaneously with influencing include the operating time for the binary
factors within nominal range. inputs and outputs.

M12318-1 v9

Table 18. IOM - Binary input/output module contact data (reference standard: IEC 61810-2)

Function or quantity Trip and signal relays Fast signal relays (parallel
reed relay)

Binary outputs 10 2

Max system voltage 250 V AC, DC 250 V DC

Test voltage across open contact, 1 min 1000 V rms 800 V DC

Current carrying capacity


Per relay, continuous 8A 8A
Per relay, 1 s 10 A 10 A
Per process connector pin, continuous 12 A 12 A

Making capacity at inductive load with L/R > 10 ms

0.2 s
1.0 s 30 A 0.4 A
10 A 0.4 A

Making capacity at resistive load


220–250 V/0.4 A
0.2 s 30 A 110–125 V/0.4 A
1.0 s 10 A 48–60 V/0.2 A
24–30 V/0.1 A

Breaking capacity for AC, cos φ > 0.4 250 V/8.0 A 250 V/8.0 A

Breaking capacity for DC with L/R < 40 ms 48 V/1 A 48 V/1 A


110 V/0.4 A 110 V/0.4 A
125 V/0.35 A 125 V/0.35 A
220 V/0.2 A 220 V/0.2 A
250 V/0.15 A 250 V/0.15 A

Maximum capacitive load - 10 nF

Operating time < 6 ms <= 1 ms

Maximum 72 outputs may be activated temperature rise will adversely affect the
simultaneously with influencing factors hardware life. Maximum two relays per
within nominal range. After 6 ms an BOM/IOM/SOM should be activated
additional 24 outputs may be activated. continuously due to power dissipation.
The activation time for the 96 outputs must
not exceed 200 ms. 48 outputs can be
activated during 1 s. Continued activation
is possible with respect to current
consumption but after 5 minutes the

54 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

M12584-1 v9

The stated operate time for functions


include the operating time for the binary
inputs and outputs.

Table 19. IOM with MOV and IOM 220/250 V, 110mA - contact data (reference standard: IEC 61810-2)

Function or quantity Trip and Signal relays Fast signal relays (parallel reed relay)

Binary outputs IOM: 10 IOM: 2

Max system voltage 250 V AC, DC 250 V DC

Test voltage across open 250 V rms 250 V rms


contact, 1 min

Current carrying capacity


Per relay, continuous 8A 8A
Per relay, 1 s 10 A 10 A
Per process connector pin, 12 A 12 A
continuous

Making capacity at inductive


loadwith L/R > 10 ms
0.2 s 30 A 0.4 A
1.0 s 10 A 0.4 A

Making capacity at resistive load


220–250 V/0.4 A
0.2 s 30 A 110–125 V/0.4 A
1.0 s 10 A 48–60 V/0.2 A
24–30 V/0.1 A

Breaking capacity for AC, cos j 250 V/8.0 A 250 V/8.0 A


> 0.4

Breaking capacity for DC with 48 V/1 A 48 V/1 A


L/R < 40 ms 110 V/0.4 A 110 V/0.4 A
220 V/0.2 A 220 V/0.2 A
250 V/0.15 A 250 V/0.15 A

Maximum capacitive load - 10 nF

Operating time < 6 ms <= 1 ms

Maximum 72 outputs may be activated temperature rise will adversely affect the
simultaneously with influencing factors hardware life. Maximum two relays per
within nominal range. After 6 ms an BOM/IOM/SOM should be activated
additional 24 outputs may be activated. continuously due to power dissipation.
The activation time for the 96 outputs must
not exceed 200 ms. 48 outputs can be
activated during 1 s. Continued activation
is possible with respect to current
consumption but after 5 minutes the

ABB 55
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

SEMOD175395-2 v8

The stated operate time for functions


include the operating time for the binary
inputs and outputs.

Table 20. SOM - Static Output Module (reference standard: IEC 61810-2): Static binary outputs

Function of quantity Static binary output trip

Rated voltage 48-60 VDC 110-250 VDC

Number of outputs 6 6

Impedance open state ~300 kΩ ~810 kΩ

Test voltage across open contact, 1 min No galvanic separation No galvanic separation

Current carrying capacity:

Continuous 5A 5A

1.0 s 10 A 10 A

Making capacity at capacitive load with the


maximum capacitance of 0.2 μF :

0.2 s 30 A 30 A

1.0 s 10 A 10 A

Breaking capacity for DC with L/R ≤ 40 ms 48 V/1 A 110 V/0.4 A

60 V/0.75 A 125 V/0.35 A

220 V/0.2 A

250 V/0.15 A

Operating time < 1 ms < 1 ms

Table 21. SOM - Static Output module data (reference standard: IEC 61810-2): Electromechanical relay outputs

Function of quantity Trip and signal relays

Max system voltage 250 V AC/DC

Number of outputs 6

Test voltage across open contact, 1 min 1000 V rms

Current carrying capacity:

Continuous 8A

1.0 s 10 A

Making capacity at capacitive load with the maximum capacitance of


0.2 μF:

0.2 s 30 A

1.0 s 10 A

Breaking capacity for DC with L/R ≤ 40 ms 48 V/1 A

110 V/0.4 A

125 V/0.35 A

220 V/0.2 A

250 V/0.15 A

Operating time < 6 ms

56 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

M12441-1 v9

The stated operate time for functions


include the operating time for the binary
inputs and outputs.

Table 22. BOM - Binary output module contact data (reference standard: IEC 61810-2)

Function or quantity Trip and Signal relays

Binary outputs 24

Max system voltage 250 V AC, DC

Test voltage across open contact, 1 min 1000 V rms

Current carrying capacity


Per relay, continuous 8A
Per relay, 1 s 10 A
Per process connector pin, continuous 12 A

Making capacity at inductive load with L/R > 10 ms


0.2 s 30 A
1.0 s 10 A

Breaking capacity for AC, cos j > 0.4 250 V/8.0 A

Breaking capacity for DC with L/R < 40 ms 48 V/1 A


110 V/0.4 A
125 V/0.35 A
220 V/0.2 A
250 V/0.15 A

Operating time < 6 ms

The stated operate time for functions


include the operating time for the binary
inputs and outputs.

Influencing factors
M16705-1 v15 IP15846-1 v1

Table 23. Temperature and humidity influence

Parameter Reference value Nominal range Influence

Ambient temperature, operate +20°C -25°C to +55°C 0.02%/°C


value

Relative humidity 10-90% 10-90% -


Operative range 0-95%

Storage temperature - -40°C to +70°C -

ABB 57
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Table 24. Auxiliary DC supply voltage influence on functionality during operation

Dependence on Reference value Within nominal Influence


range

Ripple, in DC auxiliary voltage max. 2% 15% of EL 0.01%/%


Operative range Full wave rectified

Auxiliary voltage dependence, operate ±20% of EL 0.01%/%


value

Interrupted auxiliary DC voltage 24-60 V DC ± 20%

100-250 V DC ±20%
Interruption
interval
0–50 ms No restart

0–∞ s Correct behaviour at power down

Restart time < 300 s

Table 25. Frequency influence (reference standard: IEC 60255–1)

Dependence on Within nominal range Influence

Frequency dependence, operate value fr ±2.5 Hz for 50 Hz ±1.0%/Hz


fr ±3.0 Hz for 60 Hz

Harmonic frequency dependence (20% content) 2nd, 3rd and 5th harmonic of fr ±2.0%

Harmonic frequency dependence for high impedance differential 2nd, 3rd and 5th harmonic of fr ±10.0%
protection (10% content)

Harmonic frequency dependence for overcurrent protection 2nd, 3rd and 5th harmonic of fr ±3.0%

Type tests according to standards


M16706-1 v13 IP15778-1 v1

58 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Table 26. Electromagnetic compatibility

Test Type test values Reference standards

1 MHz burst disturbance 2.5 kV IEC 60255-26

100 kHz slow damped oscillatory wave immunity test 2.5 kV IEC 61000-4-18, Class III

Ring wave immunity test, 100 kHz 2-4 kV IEC 61000-4-12, Class IV

Surge withstand capability test 2.5 kV, oscillatory IEEE/ANSI C37.90.1


4.0 kV, fast transient

Electrostatic discharge 15 kV air discharge IEC 60255-26


Direct application 8 kV contact discharge
Indirect application 8 kV contact discharge IEC 61000-4-2, Class IV

Electrostatic discharge 15 kV air discharge IEEE/ANSI C37.90.1


Direct application 8 kV contact discharge
Indirect application 8 kV contact discharge

Fast transient disturbance 4 kV IEC 60255-26, Zone A


2 kV, SFP galvanic RJ45
2 kV, MIM mA-inputs IEC 60255-26, Zone B

Surge immunity test 2-4 kV, 1.2/50ms high energy IEC 60255-26, Zone A
1-2 kV, BOM and IRF outputs IEC 60255-26, Zone B

Power frequency immunity test 150-300 V, 50 Hz IEC 60255-26, Zone A

Conducted common mode immunity test 15 Hz-150 kHz IEC 61000-4-16, Class IV

Power frequency magnetic field test 1000 A/m, 3 s IEC 61000-4-8, Class V
100 A/m, cont.

Pulse magnetic field immunity test 1000 A/m IEC 61000–4–9, Class V

Damped oscillatory magnetic field test 100 A/m IEC 61000-4-10, Class V

Radiated electromagnetic field disturbance 20 V/m, 80-1000 MHz IEC 60255-26

1.4-2.7 GHz

Radiated electromagnetic field disturbance 20 V/m IEEE/ANSI C37.90.2


80-1000 MHz
10 V/m, 5.1-6.0 GHz EN 50121-5

Conducted electromagnetic field disturbance 10 V, 0.15-80 MHz IEC 60255-26

Radiated emission 30-5000 MHz IEC 60255-26

Radiated emission 30-5000 MHz IEEE/ANSI C63.4, FCC

Conducted emission 0.15-30 MHz IEC 60255-26

Table 27. Insulation

Test Type test values Reference standard

Dielectric test 2.0 kV AC, 1 min. IEC 60255-27


(SFP galvanic RJ45: 1.0 ANSI C37.90
kVrms, 1 min.) IEEE 802.3-2015,
Environment A
Impulse voltage test 5 kV, 1.2/50ms, 0.5 J
1 kV, 1.2/50 ms 0.5 J, SFP
galvanic RJ45

Insulation resistance > 100 MW at 500 VDC

ABB 59
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Table 28. Environmental tests

Test Type test value Reference standard

Cold operation test Test Ad for 16 h at -25°C IEC 60068-2-1

Cold storage test Test Ab for 16 h at -40°C IEC 60068-2-1

Dry heat operation test Test Bd for 16 h at +70°C IEC 60068-2-2

Dry heat storage test Test Bb for 16 h at +85°C IEC 60068-2-2

Change of temperature test Test Nb for 5 cycles at -25°C to +70°C IEC 60068-2-14

Damp heat test, steady state Test Ca for 10 days at +40°C and humidity 93% IEC 60068-2-78

Damp heat test, cyclic Test Db for 6 cycles at +25 to +55°C and humidity 93 to 95% (1 cycle = IEC 60068-2-30
24 hours)

Table 29. CE compliance

Test According to

Immunity EN 60255–26

Emissivity EN 60255–26

Low voltage directive EN 60255–27

Table 30. Mechanical tests

Test Type test values Reference standards

Vibration response test Class II IEC 60255-21-1

Vibration endurance test Class I IEC 60255-21-1

Shock response test Class I IEC 60255-21-2

Shock withstand test Class I IEC 60255-21-2

Bump test Class I IEC 60255-21-2

Seismic test Class II IEC 60255-21-3

60 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Differential protection
M13081-1 v12

Table 31. High impedance differential protection, single phase HZPDIF

Function Range or value Accuracy

Operate voltage (10-900) V ±1.0% of Ir at I ≤ Ir


I=U/R ±1.0% of I at I > Ir

Reset ratio >95% at (30-900) V -

Maximum continuous power U>Trip2/SeriesResistor ≤200 W -

Operate time at 0 to 10 x Ud Min. = 5 ms


Max. = 15 ms

Reset time at 10 x Ud to 0 Min. = 75 ms


Max. = 95 ms

Critical impulse time 2 ms typically at 0 to 10 x Ud -

Operate time at 0 to 2 x Ud Min. = 25 ms


Max. = 35 ms

Reset time at 2 x Ud to 0 Min. = 50 ms


Max. = 70 ms

Critical impulse time 15 ms typically at 0 to 2 x Ud -

ABB 61
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Wide area measurement system


GUID-F0BAEBD8-E361-4D50-9737-7DF8B043D66A v4

Table 32. Protocol reporting via IEEE 1344 and C37.118 PMUREPORT

Influencing quantity Range Accuracy

Signal frequency ± 0.1 x fr ≤ 1.0% TVE

Signal magnitude:
Voltage phasor (0.1–1.2) x Ur
Current phasor (0.5–2.0) x Ir

Phase angle ± 180°

Harmonic distortion 10% from 2nd – 50th

Interfering signal:
Magnitude 10% of fundamental signal
Minimum frequency 0.1 x fr
Maximum frequency 1000 Hz

62 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Current protection
M12336-1 v13

Table 33. Instantaneous phase overcurrent protection PHPIOC

Function Range or value Accuracy

Operate current (5-2500)% of lBase ±1.0% of Ir at I ≤ Ir


±1.0% of I at I > Ir

Reset ratio > 95% at (50–2500)% of IBase -

Operate time at 0 to 2 x Iset Min. = 15 ms -


Max. = 25 ms

Reset time at 2 x Iset to 0 Min. = 15 ms -


Max. = 25 ms

Critical impulse time 10 ms typically at 0 to 2 x Iset -

Operate time at 0 to 10 x Iset Min. = 5 ms -


Max. = 15 ms

Reset time at 10 x Iset to 0 Min. = 25 ms -


Max. = 40 ms

Critical impulse time 2 ms typically at 0 to 10 x Iset -

Dynamic overreach < 5% at t = 100 ms -

ABB 63
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

M12342-1 v21

Table 34. Directional phase overcurrent protection, four steps OC4PTOC

Function Range or value Accuracy

Operate current, step 1-4 (5-2500)% of lBase ±1.0% of Ir at I ≤ Ir


±1.0% of I at I > Ir

Reset ratio > 95% at (50–2500)% of lBase -

Minimum operate current, step 1-4 (1-10000)% of lBase ±1.0% of Ir at I ≤ Ir


±1.0% of I at I > Ir

Relay characteristic angle (RCA) (40.0–65.0) degrees ±2.0 degrees

Relay operating angle (ROA) (40.0–89.0) degrees ±2.0 degrees

Second harmonic blocking (5–100)% of fundamental ±2.0% of Ir

Independent time delay at 0 to 2 x Iset, step (0.000-60.000) s ±0.2% or ±35 ms whichever is greater
1-4

Minimum operate time for inverse curves , (0.000-60.000) s ±0.2% or ±35 ms whichever is greater
step 1-4

Inverse time characteristics, see table 155, 16 curve types See table 155, table 156 and table 157
table 156 and table 157

Operate time, start non-directional at 0 to 2 x Min. = 15 ms -


Iset
Max. = 30 ms

Reset time, start non-directional at 2 x Iset to 0 Min. = 15 ms -

Max. = 30 ms

Operate time, start non-directional at 0 to 10 x Min. = 5 ms -


Iset Max. = 20 ms

Reset time, start non-directional at 10 x Iset to Min. = 20 ms -


0 Max. = 35 ms

Critical impulse time 10 ms typically at 0 to 2 x Iset -

Impulse margin time 15 ms typically -

Operate frequency, directional overcurrent 38-83 Hz -

Operate frequency, non-directional 10-90 Hz -


overcurrent

64 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

M12340-2 v9

Table 35. Instantaneous residual overcurrent protection EFPIOC

Function Range or value Accuracy

Operate current (5-2500)% of lBase ±1.0% of Ir at I ≤ Ir


±1.0% of I at I > Ir

Reset ratio > 95% at (50–2500)% of lBase -

Operate time at 0 to 2 x Iset Min. = 15 ms -


Max. = 25 ms

Reset time at 2 x Iset to 0 Min. = 15 ms -


Max. = 25 ms

Critical impulse time 10 ms typically at 0 to 2 x Iset -

Operate time at 0 to 10 x Iset Min. = 5 ms -


Max. = 15 ms

Reset time at 10 x Iset to 0 Min. = 25 ms -


Max. = 35 ms

Critical impulse time 2 ms typically at 0 to 10 x Iset -

Dynamic overreach < 5% at t = 100 ms -

ABB 65
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

M15223-1 v17

Table 36. Directional residual overcurrent protection, four steps EF4PTOC

Function Range or value Accuracy

Operate current, step 1-4 (1-2500)% of IBase ±1.0% of Ir at I ≤ Ir


±1.0% of I at I > Ir

Reset ratio > 95% at (10-2500)% of IBase -

Relay characteristic angle (-180 to 180) degrees ±2.0 degrees


(RCA)

Operate current for directional release (1–100)% of IBase For RCA ±60 degrees:
±2.5% of Ir at I ≤ Ir
±2.5% of I at I > Ir

Independent time delay at 0 to 2 x Iset, step (0.000-60.000) s ±0.2% or ±35 ms whichever is greater
1-4

Minimum operate time for inverse curves, (0.000 - 60.000) s ±0.2% or ±35 ms whichever is greater
step 1-4

Inverse time characteristics, see Table 155, 16 curve types See Table 155, Table 156 and Table 157
Table 156 and Table 157

Second harmonic blocking (5–100)% of fundamental ±2.0% of Ir

Minimum polarizing voltage (1–100)% of UBase ±0.5% of Ur

Minimum polarizing current (2-100)% of IBase ±1.0% of Ir

Real part of source Z used for current (0.50-1000.00) W/phase -


polarization

Imaginary part of source Z used for current (0.50–3000.00) W/phase -


polarization

Operate time, start non-directional at 0 to 2 x Min. = 15 ms -


Iset Max. = 30 ms

Reset time, start non-directional at 2 x Iset to Min. = 15 ms -


0 Max. = 30 ms

Operate time, start non-directional at 0 to 10 Min. = 5 ms -


x Iset Max. = 20 ms

Reset time, start non-directional at 10 x Iset to Min. = 20 ms -


0 Max. = 35 ms

Critical impulse time 10 ms typically at 0 to 2 x Iset -

Impulse margin time 15 ms typically -

66 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

GUID-E83AD807-8FE0-4244-A50E-86B9AF92469E v6

Table 37. Four step directional negative phase sequence overcurrent protection NS4PTOC

Function Range or value Accuracy

Operate current, step 1 - 4 (1-2500)% of lBase ±1.0% of Ir at I £ Ir


±1.0% of I at I > Ir

Reset ratio > 95% at (10-2500)% of IBase -

Independent time delay at 0 to 2 x Iset, (0.000-60.000) s ±0.2% or ±35 ms whichever is greater


step 1 - 4

Minimum operate time for inverse curves, (0.000 - 60.000) s ±0.2% or ±35 ms whichever is greater
step 1 - 4

Inverse time characteristics, see table 16 curve types See table 155, table 156 and table 157
155, table 156 and table 157

Minimum operate current, step 1 - 4 (1.00 - 10000.00)% of IBase ±1.0% of Ir at I ≤ Ir


±1.0% of I at I > Ir

Relay characteristic angle (RCA) (-180 to 180) degrees ±2.0 degrees

Operate current for directional release (1–100)% of IBase For RCA ±60 degrees:
±2.5% of Ir at I ≤ Ir
±2.5% of I at I > Ir

Minimum polarizing voltage (1–100)% of UBase ±0.5% of Ur

Real part of negative sequence source (0.50-1000.00) W/phase -


impedance used for current polarization

Imaginary part of negative sequence (0.50–3000.00) W/phase -


source impedance used for current
polarization

Operate time, start non-directional at 0 to Min. = 15 ms -


2 x Iset Max. = 30 ms

Reset time, start non-directional at 2 x Iset Min. = 15 ms -


to 0 Max. = 30 ms

Operate time, start non-directional at 0 to Min. = 5 ms -


10 x Iset Max. = 20 ms

Reset time, start non-directional at 10 x Min. = 20 ms -


Iset to 0 Max. = 35 ms

Critical impulse time 10 ms typically at 0 to 2 x Iset -

Impulse margin time 15 ms typically -

Transient overreach <10% at τ = 100 ms -

ABB 67
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

SEMOD173350-2 v16

Table 38. Sensitive directional residual overcurrent and power protection SDEPSDE

Function Range or value Accuracy

Operate level for 3I0·cosj directional residual (0.25-200.00)% of IBase ±1.0% of Ir at I £ Ir


overcurrent ±1.0% of I at I > Ir

Operate level for ·3I0·3U0 cosj directional (0.25-200.00)% of SBase ±1.0% of Sr at S £ Sr


residual power ±1.0% of S at S > Sr

Operate level for 3I0 and j residual (0.25-200.00)% of IBase ±1.0% of Ir at £ Ir


overcurrent ±1.0% of I at I > Ir

Operate level for non-directional overcurrent (1.00-400.00)% of IBase ±1.0% of Ir at I £ Ir


±1.0% of I at I > Ir

Operate level for non-directional residual (1.00-200.00)% of UBase ±0.5% of Ur at U £ Ur


overvoltage ±0.5% of U at U > Ur

Residual release current for all directional (0.25-200.00)% of IBase ±1.0% of Ir at I £ Ir


modes ±1.0% of I at I > Ir

Residual release voltage for all directional (1.00-300.00)% of UBase ±0.5% of Ur at U £ Ur


modes ±0.5% of U at U > Ur

Operate time for non-directional residual Min. = 40 ms


overcurrent at 0 to 2 x Iset
Max. = 65 ms

Reset time for non-directional residual Min. = 40 ms


overcurrent at 2 x Iset to 0
Max. = 65 ms

Operate time for directional residual Min. = 110 ms


overcurrent at 0 to 2 x Iset
Max. = 160 ms

Reset time for directional residual overcurrent Min. = 20 ms


at 2 x Iset to 0
Max. = 60 ms

Independent time delay for non-directional (0.000 – 60.000) s ±0.2% or ± 75 ms whichever is greater
residual overvoltage at 0.8 x Uset to 1.2 x Uset

Independent time delay for non-directional (0.000 – 60.000) s ±0.2% or ± 75 ms whichever is greater
residual overcurrent at 0 to 2 x Iset

Independent time delay for directional (0.000 – 60.000) s ±0.2% or ± 170 ms whichever is greater
residual overcurrent at 0 to 2 x Iset

Inverse characteristics, see table 158, 16 curve types See Table 158, Table 159 and Table 160
Table 159 and Table 160

Relay characteristic angle (RCADir) (-179 to 180) degrees ±2.0 degrees

Relay operate angle (ROADir) (0 to 90) degrees ±2.0 degrees

68 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

M12352-1 v15

Table 39. Thermal overload protection, one time constant LCPTTR/LFPTTR

Function Range or value Accuracy

Reference current (2-400)% of IBase ±1.0% of Ir

Reference temperature (0-300)°C, (0 - 600)°F ±1.0°C, ±2.0°F

Operate time: Time constant t = (1–1000) IEC 60255-149, ±5.0% or ±200 ms whichever is greater
minutes
 
 I , Ip
2 2 
t < σ ln  
 2 TTrip , TAmb 2 
I , T √ I ref

 ref 
EQUATION13000039 V3 EN-US (Equation 1)

TTrip= set operate temperature


TAmb = ambient temperature
Tref = temperature rise above ambient at Iref
Iref = reference load current
I = actual measured current
Ip = load current before overload occurs

Alarm temperature (0-200)°C, (0-400)°F ±2.0°C, ±4.0°F

Operate temperature (0-300)°C, (0-600)°F ±2.0°C, ±4.0°F

Reset level temperature (0-300)°C, (0-600)°F ±2.0°C, ±4.0°F


M13266-2 v9

Table 40. Thermal overload protection, two time constants TRPTTR

Function Range or value Accuracy

Base current 1 and 2 (30–250)% of IBase ±1.0% of Ir

Operate time: Time constant τ = (0.10–500.00) ±5.0% or ±200 ms whichever is greater


minutes
∑ I 2 , I p2 ⌡
t < σ √ ln  2 
 I , ITrip 2 
 
EQUATION1356 V3 EN-US (Equation 2)

I = actual measured current


Ip = load current before overload
occurs
ITrip = steady state operate
current level in % of IBasex

Alarm level 1 and 2 (50–99)% of heat content ±2.0% of heat content trip
operate value

Operate current (50–250)% of IBase ±1.0% of Ir

Reset level temperature (10–95)% of heat content trip ±2.0% of heat content trip

ABB 69
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

M12353-1 v14

Table 41. Breaker failure protection CCRBRF

Function Range or value Accuracy

Operate phase current (5-200)% of lBase ±1.0% of Ir at I £ Ir


±1.0% of I at I > Ir

Reset ratio, phase current > 95% -

Operate residual current (2-200)% of lBase ±1.0% of Ir at I £ Ir


±1.0% of I at I > Ir

Reset ratio, residual current > 95% -

Phase current level for blocking of contact function (5-200)% of lBase ±1.0% of Ir at I £ Ir
±1.0% of I at I > Ir

Reset ratio > 95% -

Operate time for current detection 10 ms typically -

Reset time for current detection 15 ms maximum -

Time delay for re-trip at 0 to 2 x Iset (0.000-60.000) s ±0.2% or ±15 ms whichever is greater

Time delay for back-up trip at 0 to 2 x Iset (0.000-60.000) s ±0.2% or ±15 ms whichever is greater

Time delay for back-up trip at multi-phase start at (0.000-60.000) s ±0.2% or ±20 ms whichever is greater
0 to 2 x Iset

Additional time delay for a second back-up trip at (0.000-60.000) s ±0.2% or ±20 ms whichever is greater
0 to 2 x Iset

Time delay for alarm for faulty circuit breaker (0.000-60.000) s ±0.2% or ±15 ms whichever is greater
M12350-1 v12

Table 42. Stub protection STBPTOC

Function Range or value Accuracy

Operating current (5-2500)% of IBase ±1.0% of Ir at I ≤ Ir


±1.0% of I at I > Ir

Reset ratio > 95% at (50-2500)% of IBase -

Independent time delay at 0 to 2 x Iset (0.000-60.000) s ±0.2% or ±30 ms whichever is greater

Operate time, start at 0 to 2 x Iset Min. = 10 ms -


Max. = 20 ms

Reset time, start at 2 x Iset to 0 Min. = 10 ms -


Max. = 20 ms

Critical impulse time 10 ms typically at 0 to 2 x Iset -

Impulse margin time 15 ms typically -


M13279-1 v10

Table 43. Pole discordance protection CCPDSC

Function Range or value Accuracy

Operate current (0–100)% of IBase ±1.0% of Ir

Independent time delay (0.000-60.000) s ±0.2% or ± 30 ms whichever is greater


between trip condition and trip
signal

70 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

SEMOD175152-2 v11

Table 44. Directional underpower protection GUPPDUP

Function Range or value Accuracy

Power level (0.0–500.0)% of SBase ±1.0% of Sr at S ≤ Sr


for Step 1 and Step 2 ±1.0% of S at S > Sr
where

S r = 1.732 × U r × I r

Characteristic angle (-180.0–180.0) degrees ±2.0 degrees


for Step 1 and Step 2

Independent time delay to operate for Step 1 (0.01-6000.00) s ±0.2% or ±40 ms whichever is greater
and Step 2 at 2 x Sr to 0.5 x Sr and k=0.000
SEMOD175159-2 v9

Table 45. Directional overpower protection GOPPDOP

Function Range or value Accuracy

Power level (0.0–500.0)% of SBase ±1.0% of Sr at S ≤ Sr


for Step 1 and Step 2 ±1.0% of S at S > Sr

Characteristic angle (-180.0–180.0) degrees ±2.0 degrees


for Step 1 and Step 2

Operate time, start at 0.5 x Sr to 2 x Sr and Min. =10 ms


k=0.000
Max. = 25 ms

Reset time, start at 2 x Sr to 0.5 x Sr and Min. = 35 ms


k=0.000
Max. = 55 ms

Independent time delay to operate for Step 1 (0.01-6000.00) s ±0.2% or ±40 ms whichever is greater
and Step 2 at 0.5 x Sr to 2 x Sr and k=0.000
SEMOD175200-2 v7

Table 46. Broken conductor check BRCPTOC

Function Range or value Accuracy

Minimum phase current for operation (5–100)% of IBase ±1.0% of Ir

Unbalance current operation (50–90)% of maximum current ±1.0% of Ir

Independent operate time delay (0.000-60.000) s ±0.2% or ±45 ms whichever is greater

Independent reset time delay (0.010-60.000) s ±0.2% or ±30 ms whichever is greater

Start time at current change from Ir to 0 Min. = 25 ms -


Max. = 35 ms

Reset time at current change from 0 to Ir Min. = 5 ms -


Max. = 20 ms

ABB 71
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

GUID-6A7DA510-E145-4C5B-A7DC-97BC4258E621 v9

Table 47. Capacitor bank protection CBPGAPC

Function Range or value Accuracy

Operate value, overcurrent (10-900)% of lBase ±2.0% of Ir at I ≤ Ir


±2.0% of I at I > Ir

Reset ratio, overcurrent >95% at (100-900)% of IBase -

Start time, overcurrent, at 0.5 x Iset Min. = 5 ms -


to 2 x Iset Max. = 20 ms

Reset time, overcurrent, at 2 x Iset to Min. = 25 ms -


0.5 x Iset Max. = 40 ms

Critical impulse time, overcurrent 2 ms typically at 0.5 x Iset to 2 x Iset -


protection start 1 ms typically at 0.5 x Iset to 10 x Iset

Impulse margin time, overcurrent 10 ms typically


protection start

Operate value, undercurrent (5-100)% of IBase ±2.0% of Ir

Reset ratio, undercurrent <105% at (30-100)% of IBase -

Operate value, reconnection inhibit (4-1000)% of IBase ±1.0% of Ir at I ≤ Ir


function ±1.0% of I at I > Ir

Operate value, reactive power (10-900)% ±1.0% of Sr at S ≤ Sr


overload function ±1.0% of S at S > Sr

Operate value, voltage protection (10-500)% ±0.5% of Ur at U ≤ Ur


function for harmonic overload ±0.5% of U at U > Ur
(Definite time)

Operate value, voltage protection (80-200)% ±0.5% of Ur at U ≤ Ur


function for harmonic overload ±0.5% of U at U > Ur
(Inverse time)

Inverse time characteristic According to IEC 60871-1 (2005) and ±20% or ±200 ms whichever is greater
IEEE/ANSI C37.99 (2000)

Maximum trip delay, harmonic (0.05-6000.00) s ±20% or ±200 ms whichever is greater


overload IDMT

Minimum trip delay, harmonic (0.05-60.00) s ±20% or ±200 ms whichever is greater


overload IDMT

Independent time delay, overcurrent (0.00-6000.00) s ±0.2% or ±30 ms whichever is greater


at 0 to 2 x Iset

Independent time delay, undercurrent (0.00-6000.00) s ±0.2% or ±60 ms whichever is greater


at 2 x Iset to 0

Independent time delay, reactive (1.00-6000.00) s ±0.2% or ±100 ms whichever is greater


power overload function at 0 to 2 x
QOL>

Independent time delay, harmonic (0.00-6000.00) s ±0.2% or ±35 ms whichever is greater


overload at 0 to 2 x HOL>

72 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

GUID-7EA9731A-8D56-4689-9072-D72D9CDFD795 v8

Table 48. Voltage-restrained time overcurrent protection VRPVOC

Function Range or value Accuracy

Start overcurrent (2.0 - 5000.0)% of IBase ±1.0% of Ir at I ≤ Ir


±1.0% of I at I > Ir

Reset ratio, overcurrent > 95% -

Operate time, start overcurrent at 0 to 2 x Iset Min. = 15 ms -

Max. = 30 ms

Reset time, start overcurrent at 2 x Iset to 0 Min. = 15 ms -

Max. = 30 ms

Operate time, start overcurrent at 0 to 10 x Min. = 5 ms -


Iset Max. = 20 ms

Reset time, start overcurrent at 10 x Iset to 0 Min. = 20 ms -


Max. = 35 ms

Independent time delay to operate at 0 to 2 x (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is greater
Iset

Inverse time characteristics, 13 curve types See tables 155 and 156
see tables 155 and 156

Minimum operate time for inverse time (0.00 - 60.00) s ±0.2% or ±35 ms whichever is greater
characteristics

High voltage limit, voltage dependent (30.0 - 100.0)% of UBase ±1.0% of Ur


operation

Start undervoltage (2.0 - 100.0)% of UBase ±0.5% of Ur

Reset ratio, undervoltage < 105% -

Operate time start undervoltage at 2 x Uset to Min. = 15 ms -


0
Max. = 30 ms

Reset time start undervoltage at 0 to 2 x Uset Min. = 15 ms -

Max. = 30 ms

Independent time delay to operate, (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is greater
undervoltage at 2 x Uset to 0

Internal low voltage blocking (0.0 - 5.0)% of UBase ±0.25% of Ur

Overcurrent: -
Critical impulse time 10 ms typically at 0 to 2 x Iset
Impulse margin time 15 ms typically

Undervoltage: -
Critical impulse time 10ms typically at 2 x Uset to 0
Impulse margin time 15 ms typically

ABB 73
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Voltage protection
M13290-1 v15

Table 49. Two step undervoltage protection UV2PTUV

Function Range or value Accuracy

Operate voltage, low and high step (1.0–100.0)% of UBase ±0.5% of Ur

Absolute hysteresis (0.0–50.0)% of UBase ±0.5% of Ur

Internal blocking level, step 1 and step 2 (1–50)% of UBase ±0.5% of Ur

Inverse time characteristics for step 1 - See table 164


and step 2, see table 164

Definite time delay, step 1 at 1.2 x Uset to (0.00-6000.00) s ±0.2% or ±40ms whichever is greater
0

Definite time delay, step 2 at 1.2 x Uset to (0.000-60.000) s ±0.2% or ±40ms whichever is greater
0

Minimum operate time, inverse (0.000–60.000) s ±0.5% or ±40ms whichever is greater


characteristics

Operate time, start at 2 x Uset to 0 Min. = 15 ms -


Max. = 30 ms

Reset time, start at 0 to 2 x Uset Min. = 15 ms -


Max. = 30 ms

Operate time, start at 1.2 x Uset to 0 Min. = 5 ms -


Max. = 25 ms

Reset time, start at 0 to 1.2 x Uset Min. = 15 ms -


Max. = 35 ms

Critical impulse time 5 ms typically at 1.2 x Uset to 0 -

Impulse margin time 15 ms typically -

74 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

M13304-1 v14

Table 50. Two step overvoltage protection OV2PTOV

Function Range or value Accuracy

Operate voltage, step 1 and 2 (1.0-200.0)% of UBase ±0.5% of Ur at U ≤ Ur


±0.5% of U at U > Ur

Absolute hysteresis (0.0–50.0)% of UBase ±0.5% of Ur at U ≤ Ur


±0.5% of U at U > Ur

Inverse time characteristics for steps 1 and - See table 163


2, see table 163

Definite time delay, low step (step 1) at 0 (0.00 - 6000.00) s ±0.2% or ±45 ms whichever is greater
to 1.2 x Uset

Definite time delay, high step (step 2) at 0 (0.000-60.000) s ±0.2% or ±45 ms whichever is greater
to 1.2 x Uset

Minimum operate time, Inverse (0.000-60.000) s ±0.2% or ±45 ms whichever is greater


characteristics

Operate time, start at 0 to 2 x Uset Min. = 15 ms -


Max. = 30 ms

Reset time, start at 2 x Uset to 0 Min. = 15 ms -


Max. = 30 ms

Operate time, start at 0 to 1.2 x Uset Min. = 20 ms -


Max. = 35 ms

Reset time, start at 1.2 x Uset to 0 Min. = 5 ms -


Max. = 25 ms

Critical impulse time 10 ms typically at 0 to 2 x Uset -

Impulse margin time 15 ms typically -

ABB 75
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

M13317-2 v14

Table 51. Two step residual overvoltage protection ROV2PTOV

Function Range or value Accuracy

Operate voltage, step 1 - step 2 (1.0-200.0)% of UBase ± 0.5% of Ur at U ≤ Ur


± 0.5% of U at U > Ur

Absolute hysteresis (0.0–50.0)% of UBase ± 0.5% of Ur at U ≤ Ur


± 0.5% of U at U > Ur

Inverse time characteristics for low and - See table 165


high step, see table 165

Definite time delay low step (step 1) at 0 (0.00–6000.00) s ± 0.2% or ± 45 ms whichever is greater
to 1.2 x Uset

Definite time delay high step (step 2) at 0 (0.000–60.000) s ± 0.2% or ± 45 ms whichever is greater
to 1.2 x Uset

Minimum operate time (0.000-60.000) s ± 0.2% or ± 45 ms whichever is greater

Operate time, start at 0 to 2 x Uset Min. = 15 ms -


Max. = 30 ms

Reset time, start at 2 x Uset to 0 Min. = 15 ms -


Max. = 30 ms

Operate time, start at 0 to 1.2 x Uset Min. = 20 ms -


Max. = 35 ms

Reset time, start at 1.2 x Uset to 0 Min. = 5 ms -


Max. = 25 ms

Critical impulse time 10 ms typically at 0 to 2 x Uset -

Impulse margin time 15 ms typically -


SEMOD166919-2 v7

Table 52. Voltage differential protection VDCPTOV

Function Range or value Accuracy

Voltage difference for alarm and trip (2.0–100.0) % of UBase ±0.5% of Ur

Under voltage level (1.0–100.0) % of UBase ±0.5% of Ur

Independent time delay for voltage (0.000–60.000)s ±0.2% or ±40 ms whichever is greater
differential alarm at 0.8 x UDAlarm to 1.2 x
UDAlarm

Independent time delay for voltage (0.000–60.000)s ±0.2% or ±40 ms whichever is greater
differential trip at 0.8 x UDTrip to 1.2 x
UDTrip

Independent time delay for voltage (0.000–60.000)s ±0.2% or ±40 ms whichever is greater
differential reset at 1.2 x UDTrip to 0.8 x
UDTrip

76 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

SEMOD175210-2 v6

Table 53. Loss of voltage check LOVPTUV

Function Range or value Accuracy

Operate voltage (1–100)% of UBase ±0.5% of Ur

Pulse timer when disconnecting (0.050–60.000) s ±0.2% or ±15 ms whichever is greater


all three phases

Time delay for enabling the (0.000–60.000) s ±0.2% or ±35 ms whichever is greater
functions after restoration

Operate time delay when (0.000–60.000) s ±0.2% or ±35 ms whichever is greater


disconnecting all three phases

Time delay to block when all (0.000–60.000) s ±0.2% or ±35 ms whichever is greater
three phase voltages are not low

ABB 77
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Frequency protection
M13360-1 v15

Table 54. Underfrequency protection SAPTUF

Function Range or value Accuracy

Operate value, start function, at symmetrical three (35.00-75.00) Hz ±2.0 mHz


phase voltage

Operate time, start at fset + 0.02 Hz to fset - 0.02 Hz Min. = 80 ms


fn = 50 Hz
Max. = 95 ms
-
Min. = 65 ms
fn = 60 Hz
Max. = 80 ms

Reset time, start at fset - 0.02 Hz to fset + 0.02 Hz Min. = 15 ms


-
Max. = 30 ms

Operate time, definite time function at fset + 0.02 Hz (0.000-60.000)s ±0.2% or ±100 ms whichever is greater
to fset - 0.02 Hz

Reset time, definite time function at fset - 0.02 Hz to (0.000-60.000)s ±0.2% or ±120 ms whichever is greater
fset + 0.02 Hz

Voltage dependent time delay Settings: ±1.0% or ±100 ms whichever is greater


UNom=(50-150)% of Ubase
UMin=(50-150)% of Ubase
Exponent=0.0-5.0
tMax=(0.010–60.000)s
tMin=(0.010–60.000)s

Exponent
é U - UMin ù
t=ê × ( tMax - tMin ) + tMin
ë UNom - UMin úû
EQUATION1182 V1 EN-US (Equation 3)

U=Umeasured
M14964-1 v12

Table 55. Overfrequency protection SAPTOF

Function Range or value Accuracy

Operate value, start function at symmetrical three-phase voltage (35.00-90.00) Hz ±2.0 mHz

Operate time, start at fset -0.02 Hz to fset +0.02 Hz Min. = 80 ms -


fn = 50Hz
Max. = 95 ms

Min. = 65 ms
fn = 60 Hz
Max. = 80 ms

Reset time, start at fset +0.02 Hz to fset -0.02 Hz Min. = 15 ms -


Max. = 30 ms

Operate time, definite time function at fset -0.02 Hz to fset +0.02 Hz (0.000-60.000)s ±0.2% ±100 ms
whichever is greater

Reset time, definite time function at fset +0.02 Hz to fset -0.02 Hz (0.000-60.000)s ±0.2% ±120 ms,
whichever is greater

78 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

M14976-1 v10

Table 56. Rate-of-change of frequency protection SAPFRC

Function Range or value Accuracy

Operate value, start function (-10.00-10.00) Hz/s ±10.0 mHz/s

Operate value, restore enable frequency (45.00-65.00) Hz ±2.0 mHz

Definite restore time delay (0.000-60.000) s ±0.2% or ±100 ms whichever is


greater

Definite time delay for frequency gradient trip (0.000-60.000) s ±0.2% or ±120 ms whichever is
greater

Definite reset time delay (0.000-60.000) s ±0.2% or ±250 ms whichever is


greater
GUID-E8D0EE7C-D7B8-46C3-9C0D-363FFC75DE93 v5

Table 57. Frequency accumulation protection FTAQFVR

Function Range or value Accuracy

Operate value, frequency high limit level at (35.00 – 90.00) Hz ±2.0 mHz
symmetrical three phase voltage

Operatevalue, frequency low limit level at (30.00 – 85.00) Hz ±2.0 mHz


symmetrical three phase voltage

Operate value, voltage high and low limit (0.0 – 200.0)% of UBase ±0.5% of Ur at U ≤ Ur
for voltage band limit check ±0.5% of U at U > Ur

Operate value, current start level (5.0 – 100.0)% of IBase ±1.0% of Ir or 0.01 A at I≤Ir

Independent time delay for the continuous (0.0 – 6000.0) s ±0.2% or ±250 ms whichever is
time limit at fset+0.02 Hz to fset-0.02 Hz greater

Independent time delay for the (10.0 – 90000.0) s ±0.2% or ±250 ms whichever is
accumulation time limit at fset+0.02 Hz to greater
fset-0.02 Hz

ABB 79
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Multipurpose protection
M13095-2 v10

80 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Table 58. General current and voltage protection CVGAPC

Function Range or value Accuracy

Measuring current input phase1, phase2, phase3, PosSeq, - -


NegSeq, -3*ZeroSeq, MaxPh, MinPh,
UnbalancePh, phase1-phase2,
phase2-phase3, phase3-phase1,
MaxPh-Ph, MinPh-Ph, UnbalancePh-
Ph

Measuring voltage input phase1, phase2, phase3, PosSeq, - -


NegSeq, -3*ZeroSeq, MaxPh, MinPh,
UnbalancePh, phase1-phase2,
phase2-phase3, phase3-phase1,
MaxPh-Ph, MinPh-Ph, UnbalancePh-
Ph

Start overcurrent, step 1 - 2 (2 - 5000)% of IBase ±1.0% of Ir at I ≤ Ir


±1.0% of I at I > Ir

Start undercurrent, step 1 - 2 (2 - 150)% of IBase ±1.0% of Ir at I ≤ Ir


±1.0% of I at I > Ir

Independent time delay, overcurrent at 0 (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is greater
to 2 x Iset, step 1 - 2

Independent time delay, undercurrent at (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is greater
2 x Iset to 0, step 1 - 2

Overcurrent (non-directional):

Start time at 0 to 2 x Iset Min. = 15 ms -


Max. = 30 ms

Reset time at 2 x Iset to 0 Min. = 15 ms -


Max. = 30 ms

Start time at 0 to 10 x Iset Min. = 5 ms -


Max. = 20 ms

Reset time at 10 x Iset to 0 Min. = 20 ms -


Max. = 35 ms

Undercurrent:

Start time at 2 x Iset to 0 Min. = 15 ms -


Max. = 30 ms

Reset time at 0 to 2 x Iset Min. = 15 ms -


Max. = 30 ms

Overcurrent:

Inverse time characteristics, see table 16 curve types See table 155, 156 and table 157
155, 156 and table 157

Overcurrent:

Minimum operate time for inverse curves, (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is greater
step 1 - 2

Voltage level where voltage memory (0.0 - 5.0)% of UBase ±0.5% of Ur


takes over

Start overvoltage, step 1 - 2 (2.0 - 200.0)% of UBase ±0.5% of Ur at U ≤ Ur


±0.5% of U at U > Ur

Start undervoltage, step 1 - 2 (2.0 - 150.0)% of UBase ±0.5% of Ur at U ≤ Ur


±0.5% of U at U > Ur

ABB 81
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Table 58. General current and voltage protection CVGAPC , continued


Function Range or value Accuracy

Independent time delay, overvoltage at (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is greater
0.8 x Uset to 1.2 x Uset, step 1 - 2

Independent time delay, undervoltage at (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is greater
1.2 x Uset to 0.8 x Uset, step 1 - 2

Overvoltage:

Start time at 0.8 x Uset to 1.2 x Uset Min. = 15 ms -


Max. = 30 ms

Reset time at 1.2 x Uset to 0.8 x Uset Min. = 15 ms -


Max. = 30 ms

Undervoltage:

Start time at 1.2 x Uset to 0.8 x Uset Min. = 15 ms -


Max. = 30 ms

Reset time at 1.2 x Uset to 0.8 x Uset Min. = 15 ms -


Max. = 30 ms

Overvoltage:

Inverse time characteristics, see table 4 curve types See table 163
163

Undervoltage:

Inverse time characteristics, see table 3 curve types See table 164
164

High and low voltage limit, voltage (1.0 - 200.0)% of UBase ±1.0% of Ur at U ≤ Ur
dependent operation, step 1 - 2 ±1.0% of U at U > Ur

Directional function Settable: NonDir, forward and -


reverse

Relay characteristic angle (-180 to +180) degrees ±2.0 degrees

Relay operate angle (1 to 90) degrees ±2.0 degrees

Reset ratio, overcurrent > 95% -

Reset ratio, undercurrent < 105% -

Reset ratio, overvoltage > 95% -

Reset ratio, undervoltage < 105% -

Operate frequency 10-90 Hz -

Overcurrent:

Critical impulse time 10 ms typically at 0 to 2 x Iset -

Impulse margin time 15 ms typically -

Undercurrent:

Critical impulse time 10 ms typically at 2 x Iset to 0 -

Impulse margin time 15 ms typically -

Overvoltage:

Critical impulse time 10 ms typically at 0.8 x Uset to 1.2 x -


Uset

Impulse margin time 15 ms typically -

82 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Table 58. General current and voltage protection CVGAPC , continued


Function Range or value Accuracy

Undervoltage:

Critical impulse time 10 ms typically at 1.2 x Uset to 0.8 x -


Uset

Impulse margin time 15 ms typically -

ABB 83
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Secondary system supervision


M12358-1 v10

Table 59. Current circuit supervision CCSSPVC

Function Range or value Accuracy

Operate current (10-200)% of IBase ±10.0% of Ir at I ≤ Ir


±10.0% of I at I > Ir

Reset ratio, Operate current >90%

Block current (20-500)% of IBase ±5.0% of Ir at I ≤ Ir


±5.0% of I at I > Ir

Reset ratio, Block current >90% at (50-500)% of IBase


M16069-1 v12

Table 60. Fuse failure supervision FUFSPVC

Function Range or value Accuracy

Operate voltage, zero sequence (1-100)% of UBase ±0.5% of Ur

Operate current, zero sequence (1–100)% of IBase ±0.5% of Ir

Operate voltage, negative sequence (1-100)% of UBase ±0.5% of Ur

Operate current, negative sequence (1–100)% of IBase ±0.5% of Ir

Operate voltage change level (1-100)% of UBase ±10.0% of Ur

Operate current change level (1–100)% of IBase ±10.0% of Ir

Operate phase voltage (1-100)% of UBase ±0.5% of Ur

Operate phase current (1–100)% of IBase ±0.5% of Ir

Operate phase dead line voltage (1-100)% of UBase ±0.5% of Ur

Operate phase dead line current (1–100)% of IBase ±0.5% of Ir

Operate time, start, 1 ph, at 1 x Ur to 0 Min. = 10 ms -


Max. = 25 ms

Reset time, start, 1 ph, at 0 to 1 x Ur Min. = 15 ms -


Max. = 30 ms

84 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

GUID-E2EA8017-BB4B-48B0-BEDA-E71FEE353774 v5

Table 61. Fuse failure supervision VDSPVC

Function Range or value Accuracy

Operate value, block of main fuse failure (10.0-80.0)% of UBase ±0.5% of Ur

Reset ratio <110%

Operate time, block of main fuse failure at 1 x Ur to 0 Min. = 5 ms –

Max. = 15 ms

Reset time, block of main fuse failure at 0 to 1 x Ur Min. = 15 ms –

Max. = 30 ms

Operate value, alarm for pilot fuse failure (10.0-80.0)% of UBase ±0.5% of Ur

Reset ratio <110% –

Operate time, alarm for pilot fuse failure at 1 x Ur to 0 Min. = 5 ms –

Max. = 15 ms

Reset time, alarm for pilot fuse failure at 0 to 1 x Ur Min. = 15 ms –

Max. = 30 ms

ABB 85
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Control
M12359-1 v15

Table 62. Synchronizing, synchrocheck and energizing check SESRSYN

Function Range or value Accuracy

Phase shift, jline - jbus (-180 to 180) degrees -

Voltage high limit for synchronizing and synchrocheck (50.0-120.0)% of UBase ±0.5% of Ur at U ≤ Ur
±0.5% of U at U > Ur

Reset ratio, synchrocheck > 95% -

Frequency difference limit between bus and line for synchrocheck (0.003-1.000) Hz ±2.5 mHz

Phase angle difference limit between bus and line for synchrocheck (5.0-90.0) degrees ±2.0 degrees

Voltage difference limit between bus and line for synchronizing and (0.02-0.5) p.u ±0.5% of Ur
synchrocheck

Time delay output for synchrocheck when angle difference between bus (0.000-60.000) s ±0.2% or ±35 ms whichever is
and line jumps from “PhaseDiff” + 2 degrees to “PhaseDiff” - 2 degrees greater

Frequency difference minimum limit for synchronizing (0.003-0.250) Hz ±2.5 mHz

Frequency difference maximum limit for synchronizing (0.050-1.000) Hz ±2.5 mHz

Maximum closing angle between bus and line for synchronizing (15-30) degrees ±2.0 degrees

Breaker closing pulse duration (0.050-1.000) s ±0.2% or ±15 ms whichever is


greater

tMaxSynch, which resets synchronizing function if no close has been (0.000-6000.00) s ±0.2% or ±35 ms whichever is
made before set time greater

Minimum time to accept synchronizing conditions (0.000-60.000) s ±0.2% or ±35 ms whichever is


greater

Voltage high limit for energizing check (50.0-120.0)% of UBase ±0.5% of Ur at U ≤ Ur


±0.5% of U at U > Ur

Reset ratio, voltage high limit > 95% -

Voltage low limit for energizing check (10.0-80.0)% of UBase ±0.5% of Ur

Reset ratio, voltage low limit < 105% -

Maximum voltage for energizing (50.0-180.0)% of UBase ±0.5% of Ur at U ≤ Ur


±0.5% of U at U > Ur

Time delay for energizing check when voltage jumps from 0 to 90% of (0.000-60.000) s ±0.2% or ±100 ms whichever is
Urated greater

Operate time for synchrocheck function when angle difference between Min. = 15 ms –
bus and line jumps from “PhaseDiff” + 2 degrees to “PhaseDiff” - 2 Max. = 30 ms
degrees

Operate time for energizing function when voltage jumps from 0 to 90% Min. = 70 ms –
of Urated Max. = 90 ms

86 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

M12379-1 v13

Table 63. Autorecloser SMBRREC

Function Range or value Accuracy

Dead time:
shot 1 “t1 1Ph” (0.000-120.000) s ±0.2% or ±35 ms
shot 1 “t1 2Ph” whichever is greater
shot 1 “t1 3Ph “
shot 1 “t1 3PhHS”

Dead time: (0.00-6000.00) s ±0.2% or ±35 ms


shot 2 “t2 3Ph” whichever is greater
shot 3 “t3 3Ph”
shot 4 “t4 3Ph”
shot 5 “t5 3Ph”

Extend three-phase dead time duration “tExtended t1” (0.000-60.000) s ±0.2% or ±35 ms
whichever is greater

Minimum time that circuit breaker must be closed before new sequence is allowed (0.00-6000.00) s ±0.2% or ±35 ms
“tCBClosedMin” whichever is greater

Wait time for the slave to close when WAIT input has reset “tSlaveDeadTime” (0.100-60.000) s ±0.2% or ±35 ms
whichever is greater

Maximum allowed start pulse duration “tLongStartInh” (0.000-60.000) s ±0.2% or ±15 ms


whichever is greater

Circuit breaker closing pulse duration “tPulse” (0.000-60.000) s ±0.2% or ±15 ms


whichever is greater

Reclaim time ”tReclaim” (0.00-6000.00) s ±0.2% or ±15 ms


whichever is greater

Maximum wait time for release from master “tWaitForMaster” (0.00-6000.00) s ±0.2% or ±15 ms
whichever is greater

Reset time for reclosing inhibit “tInhibit” (0.000-60.000) s ±0.2% or ±45 ms


whichever is greater

Wait time after close command before proceeding to next shot “tAutoContWait” (0.000-60.000) s ±0.2% or ±45 ms
whichever is greater

Maximum wait time for fulfilled synchrocheck conditions “tSync” (0.00-6000.00) s ±0.2% or ±45 ms
whichever is greater

Delay time before indicating successful reclosing “tSuccessful” (0.000-60.000) s ±0.2% or ±50 ms
whichever is greater

Maximum wait time for circuit breaker closing before indicating unsuccessful “tUnsucCl” (0.00-6000.00) s ±0.2% or ±45 ms
whichever is greater

ABB 87
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

SEMOD175215-2 v14

Table 64. Voltage control TR1ATCC/TR8ATCC , TCMYLTC/TCLYLTC

Function Range or value Accuracy

Transformer reactance (0.1–200.0) Ω, primary -

Time delay for lower command when fast step down mode is activated (1.0–100.0) s -

Voltage control set voltage (85.0–120.0)% of UBase ±0.25% of Ur

Outer voltage deadband (0.2–9.0)% of UBase -

Inner voltage deadband (0.1–9.0)% of UBase -

Upper limit of busbar voltage (80–180)% of UBase ±0.5% of Ur

Lower limit of busbar voltage (70–120)% of UBase ±0.5% of Ur

Undervoltage block level (50–120)% of UBase ±0.5% of Ur

Time delay (long) for automatic control commands (3–1000) s ±0.2% or ±600 ms
whichever is greater

Time delay (short) for automatic control commands (1–1000) s ±0.2% or ±600 ms
whichever is greater

Minimum operating time in inverse mode (3–120) s ±0.2% or ±600 ms


whichever is greater

Line resistance (0.00–150.00) Ω, primary -

Line reactance (-150.00–150.00) Ω, primary -

Load voltage adjustment constants (-20.0–20.0)% of UBase -

Load voltage auto correction (-20.0–20.0)% of UBase -

Duration time for the reverse action block signal (30–6000) s ±0.2% or ±600 ms
whichever is greater

Current limit for reverse action block (0–100)% of I1Base -

Overcurrent block level (5–250)% of I1Base ±1.0% of Ir at I≤Ir


±1.0% of I at I>Ir

Level for number of counted raise/lower within one hour (0–30) operations/hour -

Level for number of counted raise/lower within 24 hours (0–100) operations/day -

Time window for hunting alarm (1–120) minutes -

Hunting detection alarm, max. operations/window (3–30) operations/window -

Alarm level of active power in forward and reverse direction at (-9999.99–9999.99) MW ±1.0% of Sr
(10-200)% of Sr and (85-120)% of UBase

Alarm level of reactive power in forward and reverse direction at (-9999.99–9999.99) MVAr ±1.0% of Sr
(10-200)% of Sr and (85-120)% of UBase

Time delay for alarms from power supervision (1–6000) s ±0.2% or ±600 ms
whichever is greater

Tap position for lowest and highest voltage (1–63) -

mA for lowest and highest voltage tap position (0.000–25.000) mA -

Type of code conversion BIN, BCD, GRAY, SINGLE, mA -

88 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Table 64. Voltage control TR1ATCC/TR8ATCC , TCMYLTC/TCLYLTC , continued


Function Range or value Accuracy

Time after position change before the value is accepted (1–60) s ±0.2% or ±200 ms
whichever is greater

Tap changer constant time-out (1–120) s ±0.2% or ±200 ms


whichever is greater

Raise/lower command output pulse duration (0.5–10.0) s ±0.2% or ±200 ms


whichever is greater

ABB 89
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Scheme communication
M16038-1 v14

Table 65. Scheme communication logic with delta based blocking scheme signal transmit ZCPSCH

Function Range or value Accuracy

Scheme type Off -


Intertrip
Permissive UR
Permissive OR
Blocking
DeltaBlocking

Operate voltage, Delta U (0–100)% of UBase ±5.0% of ΔU

Operate current, Delta I (0–200)% of IBase ±5.0% of ΔI

Operate zero sequence voltage, (0–100)% of UBase ±10.0% of Δ3U0


Delta 3U0

Operate zero sequence current, (0–200)% of IBase ±10.0% of Δ3I0


Delta 3I0

Co-ordination time for blocking (0.000-60.000) s ±0.2% or ±15 ms whichever is greater


communication scheme

Minimum duration of a carrier send (0.000-60.000) s ±0.2% or ±45 ms whichever is greater


signal

Security timer for loss of guard (0.000-60.000) s ±0.2% or ±15 ms whichever is greater
signal detection

Operation mode of unblocking logic Off -


NoRestart
Restart
M16039-1 v16

Table 66. Current reversal and weak-end infeed logic for distance protection ZCRWPSCH

Function Range or value Accuracy

Detection level phase-to-neutral (10-90)% of UBase ±0.5% of Ur


voltage

Detection level phase-to-phase (10-90)% of UBase ±0.5% of Ur


voltage

Operate time for current reversal (0.000-60.000) s ±0.2% or ±15 ms whichever is greater
logic

Delay time for current reversal (0.000-60.000) s ±0.2% or ±15 ms whichever is greater

Coordination time for weak-end (0.000-60.000) s ±0.2% or ±15 ms whichever is greater


infeed logic
M16049-1 v10

Table 67. Scheme communication logic for residual overcurrent protection ECPSCH

Function Range or value Accuracy

Scheme type Permissive Underreaching -


Permissive Overreaching
Blocking

Communication scheme (0.000-60.000) s ±0.2% or ±20 ms whichever is greater


coordination time

90 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

GUID-CC9A02C2-AAE8-4B8C-A091-D4ED584A2EA7 v1

Table 68. Local acceleration logic ZCLCPSCH

Function Range or value Accuracy

Operate current, LoadCurr (1–100)% of IBase ±1.0% of Ir

Operate current, MinCurr (1–100)% of IBase ±1.0% of Ir

Delay time on pick-up for current release (0.000–60.000) s ±0.2% or ±35 ms whichever is greater

Delay time on drop-off for current release (0.000–60.000) s ±0.2% or ±35 ms whichever is greater

Delay time on pick-up for MinCurr value (0.000–60.000) s ±0.2% or ±35 ms whichever is greater
M16051-2 v11

Table 69. Current reversal and weak-end infeed logic for residual overcurrent protection ECRWPSCH

Function Range or value Accuracy

Operate mode of WEI logic Off -


Echo
Echo & Trip

Operate voltage 3U0 for WEI trip (5-70)% of UBase ±0.5% of Ur

Operate time for current reversal (0.000-60.000) s ±0.2% or ±30 ms whichever is greater
logic

Delay time for current reversal (0.000-60.000) s ±0.2% or ±30 ms whichever is greater

Coordination time for weak-end (0.000–60.000) s ±0.2% or ±30 ms whichever is greater


infeed logic

ABB 91
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Logic
M12380-1 v13

Table 70. Tripping logic common 3-phase output SMPPTRC

Function Range or value Accuracy

Trip action 3-ph, 1/3-ph, 1/2/3-ph -

Minimum trip pulse length (0.000-60.000) s ±0.2% or ±15 ms whichever is greater

3-pole trip delay (0.020-0.500) s ±0.2% or ±15 ms whichever is greater

Evolving fault delay (0.000-60.000) s ±0.2% or ±15 ms whichever is greater


GUID-1E1A829D-1F26-433A-8813-1F5A6F225418 v1

Table 71. Number of SMAGAPC instances

Function Quantity with cycle time

3 ms 8 ms 100 ms

SMAGAPC 12 - -

Table 72. Number of STARTCOMB instances

Function Quantity with cycle time

3 ms 8 ms 100 ms

STARTCOMB 32 - -
GUID-3AB1EE95-51BF-4CC4-99BD-F4ECDAACB75A v2

Table 73. Number of TMAGAPC instances

Function Quantity with cycle time

3 ms 8 ms 100 ms

TMAGAPC 6 6 -
GUID-A05AF26F-DC98-4E62-B96B-E75D19F20767 v2

Table 74. Number of ALMCALH instances

Function Quantity with cycle time

3 ms 8 ms 100 ms

ALMCALH - - 5
GUID-70B7357D-F467-4CF5-9F73-641A82D334F5 v2

Table 75. Number of WRNCALH instances

Function Quantity with cycle time

3 ms 8 ms 100 ms

WRNCALH - - 5
GUID-EAA43288-01A5-49CF-BF5B-9ABF6DC27D85 v2

Table 76. Number of INDCALH instances

Function Quantity with cycle time

3 ms 8 ms 100 ms

INDCALH - 5 -

92 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

GUID-D1179280-1D99-4A66-91AC-B7343DBA9F23 v3

Table 77. Number of AND instances

Logic block Quantity with cycle time

3 ms 8 ms 100 ms

AND 60 60 160
GUID-45DF373F-DC39-4E1B-B45B-6B454E8E0E50 v3

Table 78. Number of GATE instances

Logic block Quantity with cycle time

3 ms 8 ms 100 ms

GATE 10 10 20
GUID-0EC4192A-EF03-47C0-AEC1-09B68B411A98 v3

Table 79. Number of INV instances

Logic block Quantity with cycle time

3 ms 8 ms 100 ms

INV 90 90 240
GUID-B2E6F510-8766-4381-9618-CE02ED71FFB6 v2

Table 80. Number of LLD instances

Logic block Quantity with cycle time

3 ms 8 ms 100 ms

LLD 10 10 20
GUID-35A795D7-A6BD-4669-A023-43C497DBFB01 v4

Table 81. Number of OR instances

Logic block Quantity with cycle time

3 ms 8 ms 100 ms

OR 78 60 160
GUID-E05E5FB1-23E7-4816-84F2-1FBFFDFF2B43 v2

Table 82. Number of PULSETIMER instances

Logic block Quantity with cycle time Range or Value Accuracy

3 ms 8 ms 100 ms

PULSETIMER 10 10 20 (0.000–90000.000) s ±0.5% ±10 ms


GUID-BE6FD540-E96E-4F15-B2A2-12FFAE6C51DB v2

Table 83. Number of RSMEMORY instances

Logic block Quantity with cycle time

3 ms 8 ms 100 ms

RSMEMORY 10 10 20
GUID-7A0F4327-CA83-4FB0-AB28-7C5F17AE6354 v2

Table 84. Number of SRMEMORY instances

Logic block Quantity with cycle time

3 ms 8 ms 100 ms

SRMEMORY 10 10 20

ABB 93
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

GUID-C6C98FE0-F559-45EE-B853-464516775417 v3

Table 85. Number of TIMERSET instances

Logic block Quantity with cycle time Range or Value Accuracy

3 ms 8 ms 100 ms

TIMERSET 15 15 30 (0.000–90000.000) s ±0.5% ±10 ms


GUID-0B07F78C-10BD-4070-AFF0-6EE36454AA03 v2

Table 86. Number of XOR instances

Logic block Quantity with cycle time

3 ms 8 ms 100 ms

XOR 10 10 20
GUID-23D4121A-4C9A-4072-BBE3-6DB076EDAB79 v1

Table 87. Number of ANDQT instances

Logic block Quantity with cycle time

3 ms 8 ms 100 ms

ANDQT - 20 100
GUID-27DF23C0-A0B2-4BB0-80B5-FC7B7F7FE448 v1

Table 88. Number of INDCOMBSPQT instances

Logic block Quantity with cycle time

3 ms 8 ms 100 ms

INDCOMBSPQT - 10 10
GUID-C1E61AE5-22CF-4198-97CF-8C8043EE96D2 v1

Table 89. Number of INDEXTSPQT instances

Logic block Quantity with cycle time

3 ms 8 ms 100 ms

INDEXTSPQT - 10 10
GUID-77FEBE9B-0882-4E85-8B1A-7671807BFC02 v2

Table 90. Number of INVALIDQT instances

Logic block Quantity with cycle time

3 ms 8 ms 100 ms

INVALIDQT 10 6 6
GUID-F25B94C6-9CC9-48A0-A7A3-47627D2B56E2 v1

Table 91. Number of INVERTERQT instances

Logic block Quantity with cycle time

3 ms 8 ms 100 ms

INVERTERQT - 20 100
GUID-88B27B3C-26D2-47AF-9878-CC19018171B1 v1

Table 92. Number of ORQT instances

Logic block Quantity with cycle time

3 ms 8 ms 100 ms

ORQT - 20 100

94 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

GUID-61263951-53A8-4113-82B5-3DB3BF0D9449 v1

Table 93. Number of PULSETIMERQT instances

Logic block Quantity with cycle time Range or Value Accuracy

3 ms 8 ms 100 ms

PULSETIMERQT - 10 30 (0.000–90000.000) s ±0.5% ±10 ms


GUID-94C803B4-6C5A-4072-AB5C-20DDE98C9A70 v1

Table 94. Number of RSMEMORYQT instances

Logic block Quantity with cycle time

3 ms 8 ms 100 ms

RSMEMORYQT - 10 30
GUID-341562FB-6149-495B-8A63-200DF16A5590 v1

Table 95. Number of SRMEMORYQT instances

Logic block Quantity with cycle time

3 ms 8 ms 100 ms

SRMEMORYQT - 10 30
GUID-B6231B97-05ED-40E8-B735-1E1A50FDB85F v1

Table 96. Number of TIMERSETQT instances

Logic block Quantity with cycle time Range or Value Accuracy

3 ms 8 ms 100 ms

TIMERSETQT - 10 30 (0.000–90000.000) s ±0.5% ±10 ms


GUID-1C381E02-6B9E-44DC-828F-8B3EA7EDAA54 v1

Table 97. Number of XORQT instances

Logic block Quantity with cycle time

3 ms 8 ms 100 ms

XORQT - 10 30

ABB 95
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

GUID-19810098-1820-4765-8F0B-7D585FFC0C78 v7

Table 98. Number of instances in the extension logic package

Logic block Quantity with cycle time

3 ms 8 ms 100 ms

SLGAPC 10 10 54

VSGAPC 10 10 100

AND 40 40 100

OR 40 40 100

PULSETIMER 20 20 49

GATE — — 49

TIMERSET 30 30 49

XOR 10 10 69

LLD — — 49

SRMEMORY 10 10 110

INV 40 40 100

RSMEMORY 10 10 20
GUID-65A2876A-F779-41C4-ACD7-7662D1E7F1F2 v3

Table 99. Number of B16I instances

Function Quantity with cycle time

3 ms 8 ms 100 ms

B16I 6 4 8
GUID-3820F464-D296-4CAD-8491-F3F997359D79 v2

Table 100. Number of BTIGAPC instances

Function Quantity with cycle time

3 ms 8 ms 100 ms

BTIGAPC 4 4 8
GUID-B45901F4-B163-4696-8220-7F8CAC84D793 v2

Table 101. Number of IB16 instances

Function Quantity with cycle time

3 ms 8 ms 100 ms

IB16 6 4 8
GUID-A339BBA3-8FD0-429D-BB49-809EAC4D53B0 v2

Table 102. Number of ITBGAPC instances

Function Quantity with cycle time

3 ms 8 ms 100 ms

ITBGAPC 4 4 8

96 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

GUID-B258726E-1129-47C9-94F9-BE634A2085FA v4

Table 103. Elapsed time integrator with limit transgression and overflow supervision TEIGAPC

Function Cycle time (ms) Range or value Accuracy

Elapsed time integration 3 0 ~ 999999.9 s ±0.2% or ±20 ms whichever is


greater

8 0 ~ 999999.9 s ±0.2% or ±100 ms whichever is


greater

100 0 ~ 999999.9 s ±0.2% or ±250 ms whichever is


greater

Table 104. Number of TEIGAPC instances

Function Quantity with cycle time

3 ms 8 ms 100 ms

TEIGAPC 4 4 4
GUID-CEA332FF-838D-42B7-AEFC-C1E87809825E v3

Table 105. Number of INTCOMP instances

Function Quantity with cycle time

3 ms 8 ms 100 ms

INTCOMP 10 10 10
GUID-3FDD7677-1D86-42AD-A545-B66081C49B47 v4

Table 106. Number of REALCOMP instances

Function Quantity with cycle time

3 ms 8 ms 100 ms

REALCOMP 10 10 10

ABB 97
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Monitoring
M12386-1 v16

Table 107. Power system measurement CVMMXN

Function Range or value Accuracy

Frequency (0.95-1.05) x fr ±2.0 mHz

Voltage (10 to 300) V ±0.3% of U at U≤ 50 V


±0.2% of U at U> 50 V

Current (0.1-4.0) x Ir ±0.8% of I at 0.1 x Ir< I < 0.2 x Ir


± 0.5% of I at 0.2 x Ir< I < 0.5 x Ir
±0.2% of I at 0.5 x Ir< I < 4.0 x Ir

Active power, P (10 to 300) V ±0.5% of Sr at S ≤0.5 x Sr


(0.1-4.0) x Ir ±0.5% of S at S > 0.5 x Sr

(100 to 220) V ±0.2% of P


(0.5-2.0) x Ir
cos φ> 0.7

Reactive power, Q (10 to 300) V ±0.5% of Sr at S ≤0.5 x Sr


(0.1-4.0) x Ir ±0.5% of S at S > 0.5 x Sr

(100 to 220) V ±0.2% of Q


(0.5-2.0) x Ir
cos φ< 0.7

Apparent power, S (10 to 300) V ±0.5% of Sr at S ≤0.5 x Sr


(0.1-4.0) x Ir ±0.5% of S at S >0.5 x Sr

(100 to 220) V ±0.2% of S


(0.5-2.0) x Ir

Power factor, cos (φ) (10 to 300) V <0.02


(0.1-4.0) x Ir

(100 to 220) V <0.01


(0.5-2.0) x Ir
GUID-5E04B3F9-E1B7-4974-9C0B-DE9CD4A2408F v6

Table 108. Current measurement CMMXU

Function Range or value Accuracy

Current at symmetrical load (0.1-4.0) × Ir ±0.3% of Ir at I ≤ 0.5 × Ir


±0.3% of I at I > 0.5 × Ir

Phase angle at symmetrical load (0.1-4.0) × Ir ±1.0 degrees at 0.1 × Ir < I ≤ 0.5 × Ir
±0.5 degrees at 0.5 × Ir < I ≤ 4.0 × Ir
GUID-374C2AF0-D647-4159-8D3A-71190FE3CFE0 v5

Table 109. Voltage measurement phase-phase VMMXU

Function Range or value Accuracy

Voltage (10 to 300) V ±0.5% of U at U ≤ 50 V


±0.2% of U at U > 50 V

Phase angle (10 to 300) V ±0.5 degrees at U ≤ 50 V


±0.2 degrees at U > 50 V

98 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

GUID-ED634B6D-9918-464F-B6A4-51B78129B819 v6

Table 110. Voltage measurement phase-earth VNMMXU

Function Range or value Accuracy

Voltage (5 to 175) V ±0.5% of U at U ≤ 50 V


±0.2% of U at U > 50 V

Phase angle (5 to 175) V ±0.5 degrees at U ≤ 50 V


±0.2 degrees at U > 50 V
GUID-9B8A7FA5-9C98-4CBD-A162-7112869CF030 v5

Table 111. Current sequence measurement CMSQI

Function Range or value Accuracy

Current positive sequence, I1 (0.1–4.0) × Ir ±0.3% of Ir at I ≤ 0.5 × Ir


Three phase settings ±0.3% of I at I > 0.5 × Ir

Current zero sequence, 3I0 (0.1–1.0) × Ir ±0.3% of Ir at I ≤ 0.5 × Ir


Three phase settings ±0.3% of I at I > 0.5 × Ir

Current negative sequence, I2 (0.1–1.0) × Ir ±0.3% of Ir at I ≤ 0.5 × Ir


Three phase settings ±0.3% of I at I > 0.5 × Ir

Phase angle (0.1–4.0) × Ir ±1.0 degrees at 0.1 × Ir < I ≤ 0.5 × Ir


±0.5 degrees at 0.5 × Ir < I ≤ 4.0 × Ir
GUID-47094054-A828-459B-BE6A-D7FA1B317DA7 v6

Table 112. Voltage sequence measurement VMSQI

Function Range or value Accuracy

Voltage positive sequence, U1 (10 to 300) V ±0.5% of U at U ≤ 50 V


±0.2% of U at U > 50 V

Voltage zero sequence, 3U0 (10 to 300) V ±0.5% of U at U ≤ 50 V


±0.2% of U at U > 50 V

Voltage negative sequence, U2 (10 to 300) V ±0.5% of U at U ≤ 50 V


±0.2% of U at U > 50 V

Phase angle (10 to 300) V ±0.5 degrees at U ≤ 50 V


±0.2 degrees at U > 50 V
M16080-1 v5

Table 113. Supervision of mA input signals

Function Range or value Accuracy

mA measuring function ±5, ±10, ±20 mA ±0.1 % of set value ±0.005 mA


0-5, 0-10, 0-20, 4-20 mA

Max current of transducer to (-20.00 to +20.00) mA


input

Min current of transducer to (-20.00 to +20.00) mA


input

Alarm level for input (-20.00 to +20.00) mA

Warning level for input (-20.00 to +20.00) mA

Alarm hysteresis for input (0.0-20.0) mA

ABB 99
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

M12760-1 v11

Table 114. Disturbance report DRPRDRE

Function Range or value Accuracy

Pre-fault time (0.05–9.90) s -

Post-fault time (0.1–10.0) s -

Limit time (0.5–10.0) s -

Maximum number of recordings 100, first in - first out -

Time tagging resolution 1 ms See table 150

Maximum number of analog inputs 30 + 10 (external + internally -


derived)

Maximum number of binary inputs 352 -

Maximum number of phasors in the Trip Value recorder per recording 30 -

Maximum number of indications in a disturbance report 352 -

Maximum number of events in the Event recording per recording 150 -

Maximum number of events in the Event list 1000, first in - first out -

Maximum total recording time (3.4 s recording time and maximum number of 340 seconds (100 recordings) at -
channels, typical value) 50 Hz, 280 seconds (80
recordings) at 60 Hz

Sampling rate 1 kHz at 50 Hz -


1.2 kHz at 60 Hz

Recording bandwidth (5-300) Hz -


GUID-F034B396-6600-49EF-B0A5-8ED96766A6A0 v8

Table 115. Insulation supervision for gas medium function SSIMG

Function Range or value Accuracy

Pressure alarm level 1.00-100.00 ±10.0% of set value

Pressure lockout level 1.00-100.00 ±10.0% of set value

Temperature alarm level -40.00-200.00 ±2.5% of set value

Temperature lockout level -40.00-200.00 ±2.5% of set value

Time delay for pressure alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater

Reset time delay for pressure alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater

Time delay for pressure lockout (0.000-60.000) s ±0.2% or ±250ms whichever is greater

Time delay for temperature alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater

Reset time delay for temperature alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater

Time delay for temperature lockout (0.000-60.000) s ±0.2% or ±250ms whichever is greater

100 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

GUID-83B0F607-D898-403A-94FD-7FE8D45C73FF v8

Table 116. Insulation supervision for liquid medium function SSIML

Function Range or value Accuracy

Oil alarm level 1.00-100.00 ±10.0% of set value

Oil lockout level 1.00-100.00 ±10.0% of set value

Temperature alarm level -40.00-200.00 ±2.5% of set value

Temperature lockout level -40.00-200.00 ±2.5% of set value

Time delay for oil alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater

Reset time delay for oil alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater

Time delay for oil lockout (0.000-60.000) s ±0.2% or ±250ms whichever is greater

Time delay for temperature alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater

Reset time delay for temperature alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater

Time delay for temperature lockout (0.000-60.000) s ±0.2% or ±250ms whichever is greater
GUID-B6799420-D726-460E-B02F-C7D4F1937432 v9

Table 117. Circuit breaker condition monitoring SSCBR

Function Range or value Accuracy

Alarm level for open and close travel time (0 – 200) ms ±3 ms

Alarm level for number of operations (0 – 9999) -

Independent time delay for spring charging (0.00 – 60.00) s ±0.2% or ±30 ms whichever is greater
time alarm

Independent time delay for gas pressure alarm (0.00 – 60.00) s ±0.2% or ±30 ms whichever is greater

Independent time delay for gas pressure (0.00 – 60.00) s ±0.2% or ±30 ms whichever is greater
lockout

CB Contact Travel Time, opening and closing ±3 ms

Remaining Life of CB ±2 operations

Accumulated Energy ±1.0% or ±0.5 whichever is greater


M14987-1 v6

Table 118. Fault locator LMBRFLO

Function Value or range Accuracy

Reactive and resistive reach (0.001-1500.000) Ω/phase ±2.0% static accuracy


Conditions:
Voltage range: (0.1-1.1) x Ur
Current range: (0.5-30) x Ir

Phase selection According to input signals -

Maximum number of fault 100 -


locations

ABB 101
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

GUID-F6B6ED6B-2488-483C-B068-3F4631F34DC8 v1

Table 119. Transformer loss of life LOLSPTR

Function Range or value Accuracy

Service value, hot spot – ±2.0% of expected value


temperature

Service value, top oil – ±2.0% of expected value


temperature

Service value, loss of life – ±2.0% of expected value

Operate level , Warning level 1 (50 - 700)°C/°F of hot spot temperature ±2.0% of hot spot temperature
and 2

Operate time, Warning level 1 (50 - 700)°C/°F of hot spot temperature ±200 ms typically
and 2

Operate time, definite time (0.0 - 6000.0) s ±250 ms typically


function (ALARMx)
M12700-1 v4

Table 120. Event list

Function Value

Buffer capacity Maximum number of events in the list 1000

Resolution 1 ms

Accuracy Depending on time synchronizing


M13765-1 v5

Table 121. Indications

Function Value

Buffer capacity Maximum number of indications presented for single disturbance 352

Maximum number of recorded disturbances 100


M12702-1 v4

Table 122. Event recorder

Function Value

Buffer capacity Maximum number of events in disturbance report 150

Maximum number of disturbance reports 100

Resolution 1 ms

Accuracy Depending on time


synchronizing
M13747-1 v5

Table 123. Trip value recorder

Function Value

Buffer capacity Maximum number of analog inputs 30

Maximum number of disturbance reports 100

102 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

M12384-1 v7

Table 124. Disturbance recorder

Function Value

Buffer capacity Maximum number of analog inputs 40

Maximum number of binary inputs 352

Maximum number of disturbance reports 100

Maximum total recording time (3.4 s recording time and maximum number 340 seconds (100 recordings) at 50 Hz
of channels, typical value) 280 seconds (80 recordings) at 60 Hz
GUID-C43B8654-60FE-4E20-8328-754C238F4AD0 v3

Table 125. Event counter with limit supervision L4UFCNT

Function Range or value Accuracy

Counter value 0-65535 -

Max. count up speed 30 pulses/s (50% duty cycle) -


GUID-F5E124E3-0B85-41AC-9830-A2362FD289F2 v1

Table 126. Running hour-meter TEILGAPC

Function Range or value Accuracy

Time limit for alarm supervision, tAlarm (0 - 99999.9) hours ±0.1% of set value

Time limit for warning supervision, tWarning (0 - 99999.9) hours ±0.1% of set value

Time limit for overflow supervision Fixed to 99999.9 hours ±0.1%

ABB 103
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Metering
M13404-2 v5

Table 127. Pulse-counter logic PCFCNT

Function Setting range Accuracy

Input frequency See Binary Input Module (BIM) -

Cycle time for report of counter (1–3600) s -


value
SEMOD153707-2 v5

Table 128. Function for energy calculation and demand handling ETPMMTR

Function Range or value Accuracy

Energy metering kWh Export/Import, kvarh Export/ Input from MMXU. No extra error at steady load
Import

104 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Station communication
M15031-1 v9

Table 129. Communication protocols

Function Value

Protocol IEC 61850-8-1

Communication speed for the IEDs 100BASE-FX

Protocol IEC 60870–5–103

Communication speed for the IEDs 9600 or 19200 Bd

Protocol DNP3.0

Communication speed for the IEDs 300–115200 Bd

Protocol TCP/IP, Ethernet

Communication speed for the IEDs 100 Mbit/s

Protocol LON

Communication speed for the IEDs 1.25 Mbit/s

Protocol SPA

Communication speed for the IEDs 300–38400 Bd


GUID-E8B5405C-241C-4DC2-8AB1-3FA77343A4DE v2

Table 130. IEC 61850-9-2 communication protocol

Function Value

Protocol IEC 61850-9-2

Communication speed for the IEDs 100BASE-FX


M11927-1 v2

Table 131. LON communication protocol

Function Value

Protocol LON

Communication speed 1.25 Mbit/s


M11901-1 v2

Table 132. SPA communication protocol

Function Value

Protocol SPA

Communication speed 300, 1200, 2400, 4800, 9600, 19200 or 38400 Bd

Slave number 1 to 899


M11921-1 v4

Table 133. IEC 60870-5-103 communication protocol

Function Value

Protocol IEC 60870-5-103

Communication speed 9600, 19200 Bd

ABB 105
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

M12589-1 v4

Table 134. SLM – LON port

Quantity Range or value

Optical connector Glass fiber: type ST


Plastic fiber: type HFBR snap-in

Fiber, optical budget Glass fiber: 11 dB (1000m/3000 ft typically *)


Plastic fiber: 7 dB (10m/35ft typically *)

Fiber diameter Glass fiber: 62.5/125 mm


Plastic fiber: 1 mm

*) depending on optical budget calculation


SEMOD117441-2 v5

Table 135. SLM – SPA/IEC 60870-5-103/DNP3 port

Quantity Range or value

Optical connector Glass fiber: type ST


Plastic fiber: type HFBR snap-in

Fiber, optical budget Glass fiber: 11 dB (1000m/3000ft m typically *)


Plastic fiber: 7 dB (25m/80ft m typically *)

Fiber diameter Glass fiber: 62.5/125 mm


Plastic fiber: 1 mm

*) depending on optical budget calculation


SEMOD158710-2 v2

Table 136. Galvanic RS485 communication module

Quantity Range or value

Communication speed 2400–19200 bauds

External connectors RS-485 6-pole connector


Soft ground 2-pole connector
SEMOD55310-2 v13

Table 137. SFP - Optical ethernet port

Quantity Rated value

Number of channels Up to 6 single or 3 redundant or a combination of single and redundant links for
communication using any protocol

Standard IEEE 802.3u 100BASE-FX

Type of fiber 62.5/125 mm multimode fiber

Wave length 1310 nm, Class 1 laser safety

Optical connector Type LC

Communication speed Fast Ethernet 100 Mbit/s

106 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Table 138. SFP - Galvanic RJ45

Quantity Rated value

Number of channels Up to 6 single or 3 redundant or a combination of single and redundant links for
communication using any protocol

Standard IEEE 802.3u 100BASE-TX

Type of cable Cat5e FTP

Connector Type RJ45

Communication Speed Fast Ethernet 100 Mbit/s


GUID-8651FF22-C007-4D53-B7E3-686A30F37CB6 v6

Table 139. Ethernet redundancy protocols, IEC 62439-3

Function Value

Protocol IEC 62439-3 Ed.1 Parallel Redundancy Protocol (PRP-0)

Communication speed 100Base-FX

Protocol IEC 62439-3 Ed.2 Parallel Redundancy Protocol (PRP-1)

Communication speed 100Base-FX

Protocol IEC 62439-3 Ed.2 High-availability Seamless Redundancy (HSR)

Communication speed 100Base-FX

Connectors Optical, type LC

ABB 107
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

M12756-1 v11

Remote communication

Table 140. Line data communication module

Characteristic Range or value

Type of LDCM Short range (SR) Medium range (MR) Long range (LR)

Type of fiber Multi-mode fiber Single-mode fiber Single-mode fiber


glass 62.5/125 µm glass 9/125 µm glass 9/125 µm

Multi-mode fiber
glass 50/125 µm

Peak Emission Wave length


Nominal 820 nm 1310 nm 1550 nm
Maximum 865 nm 1330 nm 1580 nm
Minimum 792 nm 1290 nm 1520 nm

Optical budget 18.8 dB (typical 26.8 dB (typical 28.7 dB (typical


Multi-mode fiber glass 62.5/125 mm distance about 3 distance 80 km/50 distance 120 km/68
km/2 mile *) mile *) mile *)

Multi-mode fiber glass 50/125 mm 11.5 dB (typical


distance about 2
km/1 mile *)

Optical connector Type ST Type FC/PC Type FC/PC

Protocol C37.94 C37.94 C37.94


implementation **) implementation **)

Data transmission Synchronous Synchronous Synchronous

Transmission rate / Data rate 2 Mbit/s / 64 kbit/s 2 Mbit/s / 64 kbit/s 2 Mbit/s / 64 kbit/s

Clock source Internal or derived Internal or derived Internal or derived


from received signal from received signal from received signal

*) depending on optical budget calculation


**) C37.94 originally defined just for multi-mode; using same header, configuration and data format as C37.94

108 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Hardware
IED
M11778-1 v7 SEMOD53385-1 v1

Table 141. Case

Material Steel sheet

Front plate Stainless steel with cut-out for HMI

Surface treatment Aluzink preplated steel

Finish Light grey (RAL 7035)


M12327-1 v5

Table 142. Water and dust protection level according to IEC 60529

Front IP40 (IP54 with sealing strip)

Sides, top and bottom IP40

Rear side IP20 with screw compression type


IP10 with ring lug terminals
M11777-1 v7

Table 143. Weight

Case size Weight

6U, 1/2 x 19” £ 7.5 kg/16 lb

6U, 3/4 x 19” £ 15 kg/33 lb

6U, 1/1 x 19” £ 15 kg/33 lb

Electrical safety
GUID-1CF5B10A-CF8B-407D-8D87-F4B48B43C2B2 v2 GUID-2825B541-DD31-4DAF-B5B3-97555F81A1C2 v1

Table 144. Electrical safety according to IEC 60255-27

Equipment class I (protective earthed)

Overvoltage category III

Pollution degree 2 (normally only non-conductive pollution occurs except that occasionally a temporary conductivity caused by
condensation is to be expected)

Connection system
SEMOD53376-2 v6 SEMOD53371-1 v1

Table 145. CT and VT circuit connectors

Connector type Rated voltage and current Maximum conductor area

Screw compression type 250 V AC, 20 A 4 mm2 (AWG12)


2 x 2.5 mm2 (2 x AWG14)

Terminal blocks suitable for ring lug terminals 250 V AC, 20 A 4 mm2 (AWG12)
M12583-1 v7

Table 146. Auxiliary power supply and binary I/O connectors

Connector type Rated voltage Maximum conductor area

Screw compression type 250 V AC 2.5 mm2 (AWG14)


2 × 1 mm2 (2 x AWG18)

Terminal blocks suitable for ring lug terminals 300 V AC 3 mm2 (AWG14)

Because of limitations of space, when ring


lug terminal is ordered for Binary I/O

ABB 109
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

GUID-96676D5D-0835-44DA-BC22-058FD18BDF34 v3
connections, one blank slot is necessary
between two adjacent IO modules. Please
refer to the ordering particulars for details.

Table 147. NUM: Communication ports

NUM 4 Ethernet ports


1 Basic, 3 Optional

Ethernet connection type SFP Optical LC or Galvanic RJ45

Carrier modules supported OEM, LDCM


GUID-4876834C-CABB-400B-B84B-215F65D8AF92 v3

Table 148. OEM: Number of Ethernet ports

OEM 2 Ethernet Ports

Ethernet connection type SFP Optical LC or Galvanic RJ45

110 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Basic IED functions


M11963-1 v5

Table 149. Self supervision with internal event list

Data Value

Recording manner Continuous, event controlled

List size 40 events, first in-first out


M12331-1 v9

Table 150. Time synchronization, time tagging

Function Value

Time tagging accuracy of the synchrophasor data ± 1 µs

Time tagging resolution, events and sampled measurement values 1 ms

Time tagging error with synchronization once/min (minute pulse synchronization), events and sampled ± 1.0 ms typically
measurement values

Time tagging error with SNTP synchronization, sampled measurement values ± 1.0 ms typically
GUID-8AEB81D0-1731-46DF-A206-D2E758823575 v2

Table 151. Time synchronization PTP: IEC/IEEE 61850-9-3

Supported types of clock Boundary Clock (BC), Ordinary Clock (OC), Transparent Clock (TC)

Accuracy According to standard IEC/IEEE 61850-9-3

Number of nodes According to standard IEC/IEEE 61850-9-3

Ports supported All rear Ethernet ports


SEMOD55660-2 v3

Table 152. GPS time synchronization module (GTM)

Function Range or value Accuracy

Receiver – ±1µs relative UTC

Time to reliable time reference with antenna in new <30 minutes –


position or after power loss longer than 1 month

Time to reliable time reference after a power loss <15 minutes –


longer than 48 hours

Time to reliable time reference after a power loss <5 minutes –


shorter than 48 hours
SEMOD55693-2 v5

Table 153. GPS – Antenna and cable

Function Value

Max antenna cable attenuation 26 db @ 1.6 GHz

Antenna cable impedance 50 ohm

Lightning protection Must be provided externally

Antenna cable connector SMA in receiver end


TNC in antenna end

Accuracy +/-1μs

ABB 111
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

SEMOD141136-2 v9

Table 154. IRIG-B

Quantity Rated value

Number of channels IRIG-B 1

Number of optical channels 1

Electrical connector:

Electrical connector IRIG-B BNC

Pulse-width modulated 5 Vpp

Amplitude modulated
– low level 1-3 Vpp
– high level 3 x low level, max 9 Vpp

Supported formats IRIG-B 00x, IRIG-B 12x

Accuracy +/-10μs for IRIG-B 00x and +/-100μs for IRIG-B 12x

Input impedance 100 k ohm

Optical connector:

Optical connector IRIG-B Type ST

Type of fiber 62.5/125 μm multimode fiber

Supported formats IRIG-B 00x

Accuracy +/- 1μs

112 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Inverse characteristic
M12388-1 v23

Table 155. ANSI Inverse time characteristics

Function Range or value Accuracy

Operating characteristic: 0.05 ≤ k ≤ 999.00 ANSI/IEEE C37.112 ,


1.5 x Iset ≤ I ≤ 20 x Iset ±2.0% or ±40 ms
æ A ö whichever is greater
t =ç P + B÷×k
è (
ç I -1 ÷
ø )
EQUATION1249-SMALL V3 EN-US

Reset characteristic:

tr
t = ×k
(I 2
-1)
EQUATION1250-SMALL V1 EN-US

I = Imeasured/Iset

ANSI Extremely Inverse A=28.2, B=0.1217, P=2.0 , tr=29.1

ANSI Very inverse A=19.61, B=0.491, P=2.0 , tr=21.6

ANSI Normal Inverse A=0.0086, B=0.0185, P=0.02, tr=0.46

ANSI Moderately Inverse A=0.0515, B=0.1140, P=0.02, tr=4.85

ANSI Long Time Extremely Inverse A=64.07, B=0.250, P=2.0, tr=30

ANSI Long Time Very Inverse A=28.55, B=0.712, P=2.0, tr=13.46

ANSI Long Time Inverse A=0.086, B=0.185, P=0.02, tr=4.6

ABB 113
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Table 156. IEC Inverse time characteristics

Function Range or value Accuracy

Operating characteristic: 0.05 ≤ k ≤ 999.00 IEC 60255-151, ±2.0%


1.5 x Iset ≤ I ≤ 20 x Iset or ±40 ms whichever is
æ A ö greater
t = ç P ÷×k
ç ( I - 1) ÷
è ø
EQUATION1251-SMALL V1 EN-US

I = Imeasured/Iset

IEC Normal Inverse A=0.14, P=0.02

IEC Very inverse A=13.5, P=1.0

IEC Inverse A=0.14, P=0.02

IEC Extremely inverse A=80.0, P=2.0

IEC Short time inverse A=0.05, P=0.04

IEC Long time inverse A=120, P=1.0

Programmable characteristic k = (0.05-999) in steps of 0.01


Operate characteristic: A=(0.005-200.000) in steps of 0.001
B=(0.00-20.00) in steps of 0.01
æ A ö C=(0.1-10.0) in steps of 0.1
t = ç P + B÷ × k P=(0.005-3.000) in steps of 0.001
ç (I - C ) ÷
è ø TR=(0.005-100.000) in steps of 0.001
EQUATION1370-SMALL V1 EN-US CR=(0.1-10.0) in steps of 0.1
Reset characteristic: PR=(0.005-3.000) in steps of 0.001

TR
t = ×k
(I PR
- CR )
EQUATION1253-SMALL V1 EN-US

I = Imeasured/Iset

The parameter setting Characteristn = used, since this parameter setting is for
Reserved (where, n = 1 - 4) shall not be future use and not implemented yet.

114 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Table 157. RI and RD type inverse time characteristics

Function Range or value Accuracy

RI type inverse characteristic 0.05 ≤ k ≤ 999.00 IEC 60255-151, ±2.0%


1.5 x Iset ≤ I ≤ 20 x Iset or ±40 ms whichever is
1 greater
t = ×k
0.236
0.339 -
I
EQUATION1137-SMALL V1 EN-US

I = Imeasured/Iset

RD type logarithmic inverse characteristic

æ I ö
t = 5.8 - ç 1.35 × In ÷
è k ø
EQUATION1138-SMALL V1 EN-US

I = Imeasured/Iset
GUID-19F8E187-4ED0-48C3-92F6-0D9EAA2B39BB v4

Table 158. ANSI Inverse time characteristics for Sensitive directional residual overcurrent and power protection

Function Range or value Accuracy

Operating characteristic: 0.05 ≤ k ≤ 2.00 ANSI/IEEE C37.112 ,


1.5 x Iset ≤ I ≤ 20 x Iset ±5.0% or ±160 ms
æ A ö whichever is greater
t =ç P + B÷×k
è (
ç I -1 ÷
ø )
EQUATION1249-SMALL V3 EN-US

Reset characteristic:

tr
t = ×k
(I 2
-1 )
EQUATION1250-SMALL V1 EN-US

I = Imeasured/Iset

ANSI Extremely Inverse A=28.2, B=0.1217, P=2.0 , tr=29.1

ANSI Very inverse A=19.61, B=0.491, P=2.0 , tr=21.6

ANSI Normal Inverse A=0.0086, B=0.0185, P=0.02, tr=0.46

ANSI Moderately Inverse A=0.0515, B=0.1140, P=0.02, tr=4.85

ANSI Long Time Extremely Inverse A=64.07, B=0.250, P=2.0, tr=30

ANSI Long Time Very Inverse A=28.55, B=0.712, P=2.0, tr=13.46

ANSI Long Time Inverse A=0.086, B=0.185, P=0.02, tr=4.6

ABB 115
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Table 159. IEC Inverse time characteristics for Sensitive directional residual overcurrent and power protection

Function Range or value Accuracy

Operating characteristic: 0.05 ≤ k ≤ 2.00 IEC 60255-151, ±5.0%


1.5 x Iset ≤ I ≤ 20 x Iset or ±160 ms whichever is
æ A ö greater
t = ç P ÷×k
ç ( I - 1) ÷
è ø
EQUATION1251-SMALL V1 EN-US

I = Imeasured/Iset

IEC Normal Inverse A=0.14, P=0.02

IEC Very inverse A=13.5, P=1.0

IEC Inverse A=0.14, P=0.02

IEC Extremely inverse A=80.0, P=2.0

IEC Short time inverse A=0.05, P=0.04

IEC Long time inverse A=120, P=1.0

Programmable characteristic k = (0.05-2.00) in steps of 0.01


Operate characteristic: A=(0.005-200.000) in steps of 0.001
B=(0.00-20.00) in steps of 0.01
æ A ö C=(0.1-10.0) in steps of 0.1
t = ç P + B÷ × k P=(0.005-3.000) in steps of 0.001
ç (I - C ) ÷
è ø TR=(0.005-100.000) in steps of 0.001
EQUATION1370-SMALL V1 EN-US CR=(0.1-10.0) in steps of 0.1
Reset characteristic: PR=(0.005-3.000) in steps of 0.001

TR
t = ×k
(I PR
- CR )
EQUATION1253-SMALL V1 EN-US

I = Imeasured/Iset

Table 160. RI and RD type inverse time characteristics for Sensitive directional residual overcurrent and power protection

Function Range or value Accuracy

RI type inverse characteristic 0.05 ≤ k ≤ 2.00 IEC 60255-151, ±5.0%


1.5 x Iset ≤ I ≤ 20 x Iset or ±160 ms whichever is
1 greater
t = ×k
0.236
0.339 -
I
EQUATION1137-SMALL V1 EN-US

I = Imeasured/Iset

RD type logarithmic inverse characteristic

æ I ö
t = 5.8 - ç 1.35 × In ÷
è k ø
EQUATION1138-SMALL V1 EN-US

I = Imeasured/Iset

116 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

GUID-2AE8C92E-5DA8-487F-927D-8E553EE29240 v2

Table 161. ANSI Inverse time characteristics for Voltage restrained time overcurrent protection

Function Range or value Accuracy

Operating characteristic: 0.05 ≤ k ≤ 999.00 ANSI/IEEE C37.112 ,


± 5.0% or ±40 ms
æ A ö whichever is greater
t =ç P + B÷×k
è (
ç I -1 ÷
ø )
EQUATION1249-SMALL V3 EN-US

Reset characteristic:

tr
t = ×k
(I 2
-1)
EQUATION1250-SMALL V1 EN-US

I = Imeasured/Iset

ANSI Extremely Inverse A=28.2, B=0.1217, P=2.0 , tr=29.1

ANSI Very inverse A=19.61, B=0.491, P=2.0 , tr=21.6

ANSI Normal Inverse A=0.0086, B=0.0185, P=0.02, tr=0.46

ANSI Moderately Inverse A=0.0515, B=0.1140, P=0.02, tr=4.85

ANSI Long Time Extremely Inverse A=64.07, B=0.250, P=2.0, tr=30

ANSI Long Time Very Inverse A=28.55, B=0.712, P=2.0, tr=13.46

ANSI Long Time Inverse A=0.086, B=0.185, P=0.02, tr=4.6

Table 162. IEC Inverse time characteristics for Voltage restrained time overcurrent protection

Function Range or value Accuracy

Operating characteristic: 0.05 ≤ k ≤ 999.00 IEC 60255-151, ±5.0%


or ±40 ms whichever is
æ A ö greater
t = ç P ÷×k
ç ( I - 1) ÷
è ø
EQUATION1251-SMALL V1 EN-US

I = Imeasured/Iset

IEC Normal Inverse A=0.14, P=0.02

IEC Very inverse A=13.5, P=1.0

IEC Inverse A=0.14, P=0.02

IEC Extremely inverse A=80.0, P=2.0

IEC Short time inverse A=0.05, P=0.04

IEC Long time inverse A=120, P=1.0

ABB 117
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

SEMOD116978-2 v10

Table 163. Inverse time characteristics for overvoltage protection

Function Range or value Accuracy

Type A curve: k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms


whichever is greater
k
t =
æU -U >ö
ç ÷
è U> ø
EQUATION1436-SMALL V1 EN-US

U> = Uset
U = Umeasured

Type B curve: k = (0.05-1.10) in steps of 0.01

k  480
t 2.0
 0.035
 U  Un  
 32   0.5 
 Un  

IECEQUATION2423 V2 EN-US

Type C curve: k = (0.05-1.10) in steps of 0.01

k × 480
t= 3.0
+ 0.035
æ U - Un > ö
ç 32 × - 0.5 ÷
è U> ø
IECEQUATION2421 V1 EN-US

Programmable curve: k = (0.05-1.10) in steps of 0.01


A = (0.005-200.000) in steps of 0.001
k×A B = (0.50-100.00) in steps of 0.01
t = +D C = (0.0-1.0) in steps of 0.1
P
æB × U -U > ö D = (0.000-60.000) in steps of 0.001
ç -C÷
è U > ø P = (0.000-3.000) in steps of 0.001
EQUATION1439-SMALL V1 EN-US

118 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Table 164. Inverse time characteristics for undervoltage protection

Function Range or value Accuracy

Type A curve: k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms


whichever is greater
k
t =
æ U < -U
ö
ç ÷
è U< ø
EQUATION1431-SMALL V1 EN-US

U< = Uset
U = Umeasured

Type B curve: k = (0.05-1.10) in steps of 0.01

k × 480
t = + 0.055
2.0
æ 32 × U < -U - 0.5 ö
ç ÷
è U < ø
EQUATION1432-SMALL V1 EN-US

U< = Uset
U = Umeasured

Programmable curve: k = (0.05-1.10) in steps of 0.01


A = (0.005-200.000) in steps of 0.001
é ù B = (0.50-100.00) in steps of 0.01
ê k×A
ú C = (0.0-1.0) in steps of 0.1
t =ê ú+D D = (0.000-60.000) in steps of 0.001
ê æ U < -U ö
P
ú P = (0.000-3.000) in steps of 0.001
êçB × -C÷ ú
ëè U < ø û
EQUATION1433-SMALL V1 EN-US

U< = Uset
U = Umeasured

ABB 119
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Table 165. Inverse time characteristics for residual overvoltage protection

Function Range or value Accuracy

Type A curve: k = (0.05-1.10) in steps of ±5.0% or ±45 ms whichever is greater


0.01
k
t =
æU -U >ö
ç ÷
è U> ø
EQUATION1436-SMALL V1 EN-US

U> = Uset
U = Umeasured

Type B curve: k = (0.05-1.10) in steps of


0.01
k ⋅ 480
t = + 0.035
2.0
 32 ⋅ U − U > − 0.5 
 
 U > 
EQUATION1437-SMALL V2 EN-US

Type C curve: k = (0.05-1.10) in steps of


0.01
k ⋅ 480
t = + 0.035
3.0
 32 ⋅ U − U > − 0.5 
 
 U > 
EQUATION1438-SMALL V2 EN-US

Programmable curve: k = (0.05-1.10) in steps of


0.01
k×A A = (0.005-200.000) in
t = +D steps of 0.001
P
æB × U - U > ö B = (0.50-100.00) in steps
ç -C÷
è U > ø of 0.01
EQUATION1439-SMALL V1 EN-US
C = (0.0-1.0) in steps of
0.1
D = (0.000-60.000) in
steps of 0.001
P = (0.000-3.000) in steps
of 0.001

120 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

25. Ordering for customized IED


GUID-43BAC6E7-5454-464E-A4B0-97D2A602785D v8

Table 166. General guidelines

Guidelines
Carefully read and follow the set of rules to ensure problem-free order management.
Please refer to the available functions table for included application functions.
PCM600 can be used to make changes and/or additions to the delivered factory configuration of the pre-configured.

Table 167. Example ordering code

To obtain the complete ordering code, please combine code from the selection tables, as given in the example below.
The selected qty of each table must be filled in, if no selection is possible the code is 0.
Example of a complete code: REC670*2.2-F00X00 - A000006000000000 - B00000000000000000000000000 - C6600666666660036221300300 - D22206020 -
E6662 - F9 - S6 - G642 - H26461114444 - K10101110 - L1100 - M614 - P11100000000000100 - B1X0 - AC - CA - B - A3X0 - CD1D1ARGN1N1XXXXXXX -
KKKXXHKKLAGXSY

Product definition - Differential protection -


REC670* 2.2 - F00 X00 - A 0 0 0 0 0 0 0 0 0 0 0 0 0 0 -

Impedance protection -
B 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 -

Current protection -
C 00 00 0 0 0 0 -

Voltage protection - Frequency protection - Multipurpose protection - General -


calculation
D 0 0 0 - E - F - S -

Secondary system supervision - Control -


G - H -

Scheme communication - Logic - Monitoring - Station communication -


K 0 0 0 - L 00 - M - P 0 0 0 0 0 0 0 0 0 0 0 0 0 -

Language - Casing - Power - HMI - Analog input - Binary input/output -


and supply
mounting
B1 - - - - - -

Station communication, remote end serial communication and time synchronization


K

Table 168. Product definition

REC670* 2.2 F00

Table 169. Product definition ordering codes

Product REC670*
Software version 2.2
Configuration alternative
Bay control REC670 F00
ACT configuration
No ACT configuration downloaded X00

Table 170. Differential protection

Position 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
A 0 0 0 0 0 0 0 0 0 0 0 0 0 0

ABB 121
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Table 171. Differential functions

Function Function Ordering no Position Available Selected Notes and rules


identification qty qty
High impedance differential protection, single phase HZPDIF 1MRK005904-HB 6 0-6

Table 172. Impedance protection

Position 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26
B 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Table 173. Current protection

Position 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
C 00 00 0 0 0 0

Table 174. Current functions

Function Function Ordering no Position Available Selected Notes and rules


identification qty qty
Instantaneous phase overcurrent protection PHPIOC 1MRK005910-AD 1 0-6
Directional phase overcurrent protection, four steps OC4PTOC 1MRK005910-BC 2 0-6
Instantaneous residual overcurrent protection EFPIOC 1MRK005910-DD 4 0-6
Directional residual overcurrent protection, four steps EF4PTOC 1MRK005910-EE 5 0-6
Four step directional negative phase sequence overcurrent NS4PTOC 1MRK005910-FB 6 0-6
protection
Sensitive directional residual overcurrent and power protection SDEPSDE 1MRK005910-GA 7 0-6
Thermal overload protection, one time constant, Celsius LCPTTR 1MRK005911-BA 8 0-6
Thermal overload protection, one time constant, Fahrenheit LFPTTR 1MRK005911-AA 9 0-6
Thermal overload protection, two time constants TRPTTR 1MRK005910-HC 10 0-6
Breaker failure protection CCRBRF 1MRK005910-LA 11 0-6
Stub protection STBPTOC 1MRK005910-NC 13 0-6
Pole discordance protection CCPDSC 1MRK005910-PA 14 0-6
Directional underpower protection GUPPDUP 1MRK005910-RA 15 0-2
Directional overpower protection GOPPDOP 1MRK005910-TA 16 0-2
Broken conductor check BRCPTOC 1MRK005910-SA 17 0-1
Capacitor bank protection CBPGAPC 1MRK005910-UB 18 0-3
Voltage restrained overcurrent protection VRPVOC 1MRK005910-XA 21 0-3

Table 175. Voltage protection

Position 1 2 3 4 5 6 7 8
D 0 0 0

Table 176. Voltage functions

Function Function Ordering no Position Available Selected Notes and rules


identification qty qty
Two step undervoltage protection UV2PTUV 1MRK005912-AA 1 0-2
Two step overvoltage protection OV2PTOV 1MRK005912-BA 2 0-2
Two step residual overvoltage protection ROV2PTOV 1MRK005912-CC 3 0-2
Voltage differential protection VDCPTOV 1MRK005912-EA 5 0-6
Loss of voltage check LOVPTUV 1MRK005912-GA 7 0-2

Table 177. Frequency protection

Position 1 2 3 4
E

122 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Table 178. Frequency functions

Function Function Ordering no Position Available Selected Notes and rules


identification qty qty
Underfrequency protection SAPTUF 1MRK005914-AC 1 0-6
Overfrequency protection SAPTOF 1MRK005914-BB 2 0-6
Rate-of-change of frequency protection SAPFRC 1MRK005914-CB 3 0-6
Frequency time accumulation protection FTAQFVR 1MRK005914-DB 4 00-12

Table 179. Multipurpose protection

Position 1
F

Table 180. Multipurpose functions

Function Function Ordering no Position Available Selected Notes and rules


identification qty qty
General current and voltage protection CVGAPC 1MRK005915-AA 1 0-9

Table 181. General calculation

Position 1
S

Table 182. General calculation functions

Function Function Ordering no Position Available Selected Notes and rules


identification qty qty
Multipurpose filter SMAIHPAC 1MRK005915-KB 1 0-6

Table 183. Secondary system supervision

Position 1 2 3
G

Table 184. Secondary system supervision functions

Function Function Ordering no Position Available Selected Notes and rules


identification qty qty
Current circuit supervision CCSSPVC 1MRK005916-AC 1 0-6
Fuse failure supervision FUFSPVC 1MRK005916-BA 2 0-4
Fuse failure supervision based on voltage difference VDSPVC 1MRK005916-CA 3 0-2

Table 185. Control

Position 1 2 3 4 5 6 7 8 9 10 11
H

ABB 123
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Table 186. Control functions

Function Function Ordering no Position Available Selected Notes and rules


identification qty Qty
Synchrocheck, energizing check and synchronizing SESRSYN 1MRK005917-AC 1 0-2 Can only be ordered
with Apparatus
control APC10/
APC15
Synchrocheck, energizing check and synchronizing SESRSYN 1MRK005917-XD 2 0-6 Can only be ordered
with Apparatus
control APC30
Autorecloser SMBRREC 1MRK005917-BC 3 0-4 Can only be ordered
with Apparatus
control APC10/
APC15
Autorecloser SMBRREC 1MRK005917-XE 4 0-6 Can only be ordered
with Apparatus
control APC30
Control functionality for a single bay, max 10 objects (1CB), APC10 1MRK005917-AZ 5 1 Only one of APC10,
including interlocking APC15 or APC30
must be ordered.
Control functionality for a single bay, max 15 objects (2CB), APC15 1MRK005917-BZ 6 1
including interlocking
Control functionality for up to 6 bays, max 30 objects (6CBs), APC30 1MRK005917-CZ 7 1
including interlocking
Automatic voltage control for tapchanger, single control TR1ATCC 1MRK005917-NC 8 0-4 Only one ATCC
may be selected.
Automatic voltage control for tapchanger, parallel control TR8ATCC 1MRK005917-PC 9 0-4
If TR1ATCC or
TR8ATCC is
ordered then one of
TCMYLTC or
TCLYLTC must be
ordered.
Tap changer control and supervision, 6 binary inputs TCMYLTC 1MRK005917-DB 10 0-4
Tap changer control and supervision, 32 binary inputs TCLYLTC 1MRK005917-EA 11 0-4

Table 187. Scheme communication

Position 1 2 3 4 5 6 7 8
K 0 0 0

Table 188. Scheme communication functions

Function Function Ordering no Position Available Selected Notes and rules


identification qty qty
Scheme communication logic with delta based blocking scheme ZCPSCH 1MRK005920-AA 1 0-1
signal transmit
Current reversal and weak-end infeed logic for distance protection ZCRWPSCH 1MRK005920-CA 3 0-1
Local acceleration logic ZCLCPSCH 1MRK005920-EA 5 0-1
Scheme communication logic for residual overcurrent protection ECPSCH 1MRK005920-FA 6 0-1
Current reversal and weak-end infeed logic for residual ECRWPSCH 1MRK005920-GA 7 0-1
overcurrent protection

Table 189. Logic

Position 1 2 3
L 00

Table 190. Logic functions

Function Function Ordering no Position Available Selected Notes and rules


identification qty qty
Configurable logic blocks Q/T 1MRK005922-MX 1 0-1
Extension logic package 1MRK005922-AZ 2 0-1

Table 191. Monitoring

Position 1 2 3
M

124 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Table 192. Monitoring functions

Function Function Ordering no Position Available Selected Notes and rules


identification qty qty
Circuit breaker condition monitoring SSCBR 1MRK005924-HA 1 00-18
Fault locator LMBRFLO 1MRK005925-XB 2 0-1
Transformer insulation loss of life monitoring LOLSPTR 1MRK005924-NB 3 0-4

Table 193. Station communication

Position 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
P 0 0 0 0 0 0 0 0 0 0 0 0 0

Table 194. Station communication functions

Function Function Ordering no Position Available Selected Notes and rules


identification qty qty
IEC 61850-9-2 Process bus communication, 8 merging units 1MRK005933-HA 1 0-1
IEC 62439-3 Parallel redundancy protocol PRP 1MRK005932-FA 2 0-1 PRP and HSR
require two SFPs
IEC 62439-3 High-availability seamless redundancy HSR 1MRK005932-NA 3 0-1
placed in pairs.
Synchrophasor report, 8 phasors 1MRK005933-DA 15 0-1

Table 195. Language selection

Language Ordering no Selection Notes and rules


First local HMI user dialogue language
HMI language, English IEC 1MRK002930-AA B1
Additional local HMI user dialogue language
No additional HMI language X0
HMI language, English US 1MRK002920-UB A12
Selected B1

Table 196. Casing selection

Casing Ordering no Selection Notes and rules


1/2 x 19" rack casing, 1 TRM 1MRK000151-VA A
3/4 x 19" rack casing, 1 TRM 1MRK000151-VB B
3/4 x 19" rack casing, 2 TRM 1MRK000151-VE C
1/1 x 19" rack casing, 1 TRM 1MRK000151-VC D
1/1 x 19" rack casing, 2 TRM 1MRK000151-VD E
Selected

Table 197. Mounting selection

Mounting details with IP40 of protection from the front Ordering no Selection Notes and rules
No mounting kit included X
19" rack mounting kit for 1/2 x 19" case or 2xRHGS6 or RHGS12 1MRK002420-BB A
19" rack mounting kit for 3/4 x 19" case or 3xRHGS6 1MRK002420-BA B
19" rack mounting kit for 1/1 x 19" case 1MRK002420-CA C
Wall mounting kit 1MRK002420-DA D Wall mounting not recommended
with communication modules with
fiber connection
Flush mounting kit 1MRK002420-PA E
Flush mounting kit + IP54 mounting seal 1MRK002420-NA F
Selected

ABB 125
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Table 198. Power supply module selection

Power supply module Ordering no Selection Notes and rules


Compression terminals 1MRK002960-GA C
Ringlug terminals 1MRK002960-HA R
Power supply module 24-60 VDC 1MRK002239-AB A
Power supply module 90-250 VDC 1MRK002239-BB B
Selected

Table 199. Human machine interface selection

Human machine hardware interface Case size Ordering no Selection Notes and rules
Medium size - graphic display, IEC keypad symbols 1/2 x 19", IEC 1MRK000028-AA B
3/4 x 19”, IEC 1MRK000028-CA
1/1 x 19”, IEC 1MRK000028-BA
Medium size - graphic display, ANSI keypad symbols 1/2 x 19", ANSI 1MRK000028-AB C
3/4 x 19”, ANSI 1MRK000028-CB
1/1 x 19”, ANSI 1MRK000028-BB
Selected

126 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Table 200. Analog system selection

Analog system Ordering no Selection Notes and rules


When more than one TRM is selected, the connector type on both TRMs must be the same (A compression or B ring lug).
Slot position (front view/rear view)

P40/X401

P41/X411
No Transformer input module included X0 X0
TRM 12I 1A, 50/60Hz, compression terminals 1MRK002247-CG A1 A1
TRM 12I 5A, 50/60Hz, compression terminals 1MRK002247-CH A2 A2
TRM 9I 1A + 3U 110/220V, 50/60Hz, compression terminals 1MRK002247-BG A3 A3
TRM 9I 5A + 3U 110/220V, 50/60Hz, compression terminals 1MRK002247-BH A4 A4
TRM 5I 1A + 4I 5A + 3U 110/220V, 50/60Hz, compression terminals 1MRK002247-BK A5 A5
TRM 6I 1A + 6U 110/220V, 50/60Hz, compression terminals 1MRK002247-AG A6 A6
TRM 6I 5A + 6U 110/220V, 50/60Hz, compression terminals 1MRK002247-AH A7 A7
TRM 6I 1A, 50/60Hz, compression terminals 1MRK002247-DG A8 A8
TRM 6I 5A, 50/60Hz, compression terminals 1MRK002247-DH A9 A9
TRM 7I 1A + 5U 110/220V, 50/60Hz, compression terminals 1MRK002247-AP A12 A12
TRM 7I 5A + 5U 110/220V, 50/60Hz, compression terminals 1MRK002247-AR A13 A13
TRM 6I 5A + 1I 1A + 5U 110/220V, 50/60Hz, compression terminals 1MRK002247-AU A14 A14
TRM 3I 5A + 4I 1A + 5U 110/220V, 50/60Hz, compression terminals 1MRK002247-AV A15 A15
TRM 3I 5A + 3I 1A + 6U 110/220V, 50/60Hz, compression terminals 1MRK002247-AE A16 A16
TRM 3IM 1A + 4IP 1A + 5U 110/220V, 50/60Hz, compression terminals 1MRK002247-EA A17 A17
TRM 3IM 5A + 4IP 5A + 5U 110/220V, 50/60Hz, compression terminals 1MRK002247-EB A18 A18
TRM 10I 1A + 2U 110/220V, 50/60Hz, compression terminals 1MRK002247-FA A19 A19
TRM 10I 5A + 2U 110/220V, 50/60Hz, compression terminals 1MRK002247-FB A20 A20
TRM 12I 1A, 50/60Hz, ring lug terminals 1MRK002247-CC B1 B1
TRM 12I 5A, 50/60Hz, ring lug terminals 1MRK002247-CD B2 B2
TRM 9I 1A + 3U 110/220V, 50/60Hz, ring lug terminals 1MRK002247-BC B3 B3
TRM 9I 5A + 3U 110/220V, 50/60Hz, ring lug terminals 1MRK002247-BD B4 B4
TRM 5I 1A + 4I 5A + 3U 110/220V, 50/60Hz, ring lug terminals 1MRK002247-BF B5 B5
TRM 6I 1A + 6U 110/220V, 50/60Hz, ring lug terminals 1MRK002247-AC B6 B6
TRM 6I 5A + 6U 110/220V, 50/60Hz, ring lug terminals 1MRK002247-AD B7 B7
TRM 6I 1A, 50/60Hz, ring lug terminals 1MRK002247-DC B8 B8
TRM 6I 5A, 50/60Hz, ring lug terminals 1MRK002247-DD B9 B9
TRM 7I 1A + 5U 110/220V, 50/60Hz, ring lug terminals 1MRK002247-AS B12 B12
TRM 7I 5A + 5U 110/220V, 50/60Hz, ring lug terminals 1MRK002247-AT B13 B13
TRM 6I 5A + 1I 1A + 5U 110/220V, 50/60Hz, ring lug terminals 1MRK002247-AX B14 B14
TRM 3I 5A + 4I 1A + 5U 110/220V, 50/60Hz, ring lug terminals 1MRK002247-AY B15 B15
TRM 3I 5A + 3I 1A + 6U 110/220V, 50/60Hz, ring lug terminals 1MRK002247-AF B16 B16
TRM 3IM 1A + 4IP 1A + 5U 110/220V, 50/60Hz, ring lug terminals 1MRK002247-EC B17 B17
TRM 3IM 5A + 4IP 5A + 5U 110/220V, 50/60Hz, ring lug terminals 1MRK002247-ED B18 B18
TRM 10I 1A + 2U 110/220V, 50/60Hz, ring lug terminals 1MRK002247-FC B19 B19
TRM 10I 5A + 2U 110/220V, 50/60Hz, ring lug terminals 1MRK002247-FD B20 B20
Selected

ABB 127
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Table 201. Maximum quantity of I/O modules, with compression terminals

When ordering I/O modules, observe the maximum quantities according to the tables below.

Note: Standard order of location for I/O modules is BIM-BOM-SOM-IOM-MIM from left to right as seen from the rear side of the IED, but
can also be freely placed.
Note: The maximum quantity of I/O modules depends on the type of connection terminals.
Case sizes BIM IOM BOM/ MIM Maximum in case
SOM
1/1 x 19” rack casing, 14 6 4 4 14 *)
one (1) TRM
1/1 x 19” rack casing, 11 6 4 4 11 *)
two (2) TRM
3/4 x 19” rack casing, 8 6 4 4 8 *)
one (1) TRM
3/4 x 19” rack casing, 5 5 4 4 5 *)
two (2) TRM
1/2 x 19” rack casing, 3 3 3 1 3
one (1) TRM
*) including a combination of maximum four modules of type BOM, SOM and MIM

Table 202. Maximum quantity of I/O modules, with ringlug terminals

Note: Only every second slot can be used.


Case sizes BIM IOM BOM/ MIM Maximum in case
SOM
1/1 x 19” rack casing, 7 6 4 4 7 **) possible locations: P3, P5, P7, P9, P11, P13, P15
one (1) TRM
1/1 x 19” rack casing, 5 5 4 4 5 **) possible locations: P3, P5, P7, P9, P11
two (2) TRM
3/4 x 19” rack casing, 4 4 4 4 4 **) possible locations: P3, P5, P7, P9
one (1) TRM
3/4 x 19” rack casing, 2 2 2 2 2, possible locations: P3, P5
two (2) TRM
1/2 x 19” rack casing, 1 1 1 1 1, possible location: P3
one (1) TRM
**) including a combination of maximum four modules of type BOM, SOM and MIM

128 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Table 203. Binary input/output module selection

Binary input/ Ordering no Selection Notes and rules


output modules
Slot position

P3/X31

P4/X41

P5/X51

P6/X61

P7/X71

P8/X81

P9/X91

P10/X101

P11/X111

P12/X121

P13/X131

P14/X141

P15/X151

P16/X161
(front view/rear
view)

1/2 case with 1 █ █ █ These black marks


TRM indicate the maximum
number of modules per
3/4 case with 1 █ █ █ █ █ █ █ █
casing type and the
TRM
slots that can be
3/4 case with 2 █ █ █ █ █ occupied.
TRM
1/1 case with 1 █ █ █ █ █ █ █ █ █ █ █ █ █ █
TRM
1/1 case with 2 █ █ █ █ █ █ █ █ █ █ █
TRM
Compression 1MRK002960-KA C
terminals
Ringlug terminals 1MRK002960-LA R Only every second slot
can be used; see Table
202
No board in slot X X X X X X X X X X X X X X
Binary output 1MRK000614-AB A A A A A A A A A A A A A A
module 24 output
relays (BOM)
BIM 16 inputs, 1MRK000508-DD B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1
RL24, 24-30VDC,
50mA
BIM 16 inputs, 1MRK000508-AD C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1
RL48, 48-60VDC,
50mA
BIM 16 inputs, 1MRK000508-BD D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1
RL110,
110-125VDC,
50mA
BIM 16 inputs, 1MRK000508-CD E1 E1 E1 E1 E1 E1 E1 E1 E1 E1 E1 E1 E1 E1
RL220,
220-250VDC,
50mA
BIM 16 inputs, 1MRK000508-CE E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2
RL220,
220-250VDC,
120mA
BIM 16 inputs, 1MRK000508-HA F F F F F F F F F F F F F F
RL24, 24-30VDC,
50mA, enhanced
pulse counting
BIM 16 inputs, 1MRK000508-EA G G G G G G G G G G G G G G
RL48, 48-60VDC,
50mA, enhanced
pulse counting
BIM 16 inputs, 1MRK000508-FA H H H H H H H H H H H H H H
RL110,
110-125VDC,
50mA, enhanced
pulse counting
BIM 16 inputs, 1MRK000508-GA K K K K K K K K K K K K K K
RL220,
220-250VDC,
50mA, enhanced
pulse counting
IOM 8 inputs, 1MRK000173-GD L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1
10+2 outputs,
RL24, 24-30VDC,
50mA
IOM 8 inputs, 1MRK000173-AE M1 M1 M1 M1 M1 M1 M1 M1 M1 M1 M1 M1 M1 M1
10+2 outputs,
RL48, 48-60VDC,
50mA

ABB 129
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Table 203. Binary input/output module selection, continued


Binary input/ Ordering no Selection Notes and rules
output modules
IOM 8 inputs, 1MRK000173-BE N1 N1 N1 N1 N1 N1 N1 N1 N1 N1 N1 N1 N1 N1
10+2 outputs,
RL110,
110-125VDC,
50mA
IOM 8 inputs, 1MRK000173-CE P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1
10+2 outputs,
RL220,
220-250VDC,
50mA
IOM 8 inputs 1MRK000173-CF P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2
10+2 outputs,
RL220,
220-250VDC,
110mA
IOM with MOV 8 1MRK000173-GC U U U U U U U U U U U U U U
inputs, 10+2
outputs, RL24,
24-30VDC, 50mA
IOM with MOV 8 1MRK000173-AD V V V V V V V V V V V V V V
inputs, 10+2
outputs, RL48,
48-60VDC, 50mA
IOM with MOV 8 1MRK000173-BD W W W W W W W W W W W W W W
inputs, 10+2
outputs, RL110,
110-125VDC,
50mA
IOM with MOV 8 1MRK000173-CD Y Y Y Y Y Y Y Y Y Y Y Y Y Y
inputs, 10+2
outputs, RL220,
220-250VDC,
50mA
mA input module 1MRK000284-AB R R R R R R R R R R R R R R
MIM 6 channels
SOM Static 1MRK002614-BA T1 T1 T1 T1 T1 T1 T1 T1 T1 T1 T1 T1 T1 SOM must not be
output module, placed in the following
12 outputs; 6 positions: 1/2 case slot
standard relays P5, 3/4 case 1 TRM slot
+ 6 static outputs, P10, 3/4 case 2 TRM
48-60VDC slot P7, 1/1 case 2 TRM
slot P13.
SOM Static 1MRK002614-CA T2 T2 T2 T2 T2 T2 T2 T2 T2 T2 T2 T2 T2
output module,
12 outputs; 6
standard relays
+ 6 static outputs,
110-250VDC
Selected

130 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Table 204. Station communication, remote end serial communication and time synchronization selection

Station communication, remote end Ordering no Selection Notes and rules


serial communication and time
synchronization
Slot position (front view/rear view) The maximum number

P30:1/X301

P30:2/X302

P30:3/X303

P30:4/X304

P30:5/X305

P30:6/X306

P30:6:1/X3061

P30:6:2/X3062

P31:1/X311

P31:2/X312

P31:3/X313

P32:2/X322

P32:3/X323

LDCM mode
and type of LDCM
modules supported
depend on the total
amount of I/O and
communication modules
in the IED.
Available slots in 1/2, 3/4 and 1/1 █ █ █ █ █ █ █ █ █ █ █ █
case with 1 TRM
Available slots in 3/4 and 1/1 case █ █ █ █ █ █ █ █ █ █ █ █ █ █
with 2 TRM
No communication board included X X X X X X X X X X X X
Ethernet SFP, optical LC connector 1MRK005500-AA K K K K K K Ethernet SFP is basic in
P30:1. P30:6:1 and
Ethernet SFP, RJ45 connector 1MRK005500-BA P P P P P P
P30:6:2 require the
Optical Ethernet module
in P30:6.
Optical Ethernet module 1MRK002266-EA H
Serial SPA/LON/DNP/IEC 1MRK001608-AB L
60870-5-103 plastic interface
Serial SPA/LON/DNP/IEC 1MRK001608-BB M
60870-5-103 plastic/glass interface
Serial SPA/LON/DNP/IEC 1MRK001608-CB N
60870-5-103 glass interface
Galvanic RS485 communication 1MRK002309-AA G G G
module
Optical short range LDCM 1MRK002122-AB A A A A A A Max 2 LDCMs can be
ordered. Always place
Optical medium range LDCM, 1310 1MRK002311-AA B B B B B B
LDCM modules on the
nm
same board to support
Optical long range LDCM, 1550 nm 1MRK002311-BA C C C C C C redundant
communication: in P30:5
and P30:6, P31:2 and
P31:3 or P32:2 and
P32:3.
Line data communication, default — X Default if no LDCM is
64kbps mode selected
Allow line data communication in 1MRK007002-AA Y
2Mbps mode
GPS time module 1MRK002282-AB S S S S
IRIG-B time synchronization module 1MRK002305-AA F F F F
Selected

ABB 131
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

26. Ordering for pre-configured IED


GUID-25AF8847-411F-4F1D-91ED-0ED71C5AA8A1 v13

Guidelines
Carefully read and follow the set of rules to ensure problem-free order management.
Please refer to the available functions table for included application functions.
PCM600 can be used to make changes and/or additions to the delivered factory configuration of the pre-configured.

To obtain the complete ordering code, please combine code from the tables, as given in the example below.
Example code: REC670 *2.2-A30X00- A02H02-B1A3-AC-CA-B-A3X0-CDAB1RGN1N1XXXXXXX-KKKXXHKKLAGXSY. Using the code of each position #1-11
specified as REC670*1-2 2-3 3-4 4-5 6-7 7-8-9 9 9-10 10 10 10 10 10 10 10-11 11 11 11 11 11 11 11 11 11 11
# 1 - 2 - 3 - 4 - 5 6 - 7 - 8 - 9 -
REC670* 2.2 - - - - - - - -

10 - 11
-

Position
SOFTWARE #1 Notes and rules
Version number
Version no. 2.2
Selection for position #1

Configuration alternatives Ordering no #2 Notes and rules


Single breaker 1MRK004004-AG A30
Double breaker 1MRK004004-BG B30
1 1/2 breaker diameter 1MRK004004-CG C30
Single breaker, with PMU 1MRK004004-EG D30
ACT configuration
ABB standard configuration X00
Selection for
position #2

132 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Software options Ordering no #3 Notes and rules


No option X00 All fields in the ordering form do
not need to be filled in.
High impedance differential protection - 3 blocks 1MRK004001-AB A02 A02 only in A30/B30/D30, A07
only in C30
High impedance differential protection - 6 blocks 1MRK004001-AG A07
Stub protection 1MRK004001-VG B25 B25 only in B30/C30
1MRK004001-VK B27 B27 only in A30/D30
Sensitive directional residual overcurrent and power protection 1MRK004001-CT C16
Directional power and voltage restrained overcurrent protection 1MRK004001-VL C35
Current and breaker failure protection - 1 circuit breaker 1MRK004001-US C51 Only one type of Current and
breaker failure protection can be
Current and breaker failure protection - 2 circuit breakers 1MRK004001-UT C52
ordered.
Current and breaker failure protection - 1 1/2 circuit breaker 1MRK004001-UU C53 C51 only in A30/D30; C52 only in
B30; C53 only in C30
Voltage protection - 2 buses 1MRK004001-DB D02
Frequency protection - station 1MRK004001-EA E01
General current and voltage protection 1MRK004001-FA F01
Fuse failure supervision based on voltage difference 1MRK004001-HC G03
Autorecloser, 1 circuit breaker 1MRK004001-GD H04 Only one type of Autorecloser
can be ordered.
Autorecloser, 2 circuit breakers 1MRK004001-GE H05
H04 only in A30/D30, H05 only in
Autorecloser, 3 circuit breakers 1MRK004001-GF H06 B30, H06 only in C30
Voltage control, single transformer 1MRK004001-GL H11 H11 and H15 only in
A30/B30/D30
Voltage control, parallel transformers 1MRK004001-GM H15
H16 and H18 only in C30
Voltage control, single transformer, 2 control blocks 1MRK004001-GN H16 Only one type of voltage control
Voltage control, parallel transformers, 2 control blocks 1MRK004001-GP H18 can be ordered.

Scheme communication 1MRK004001-KC K01


Transformer insulation loss of life monitoring 1MRK004001-KM M21
IEC 62439-3 Parallel redundancy protocol 1MRK004001-PP P23 Options P23 and P24 require two
SFPs placed in pairs.
IEC 62439-3 High-availability seamless redundancy 1MRK004001-PR P24
IEC 61850-9-2 Process Bus communication, 8 merging units 1MRK004001-PT P30
Synchrophasor report, 8 phasors 1MRK004001-PV P32 P32 only in A30/B30/C30
Selection for
position #3

Language Ordering no #4 Notes and rules


First local HMI user dialogue language
HMI language, English IEC 1MRK002930-AA B1
Additional local HMI user dialogue language
No additional HMI language X0
HMI language, English US 1MRK002920-UB A12
Selection for B1
position #4

Casing Ordering no #5 Notes and rules


1/2 x 19" rack casing, 1 TRM 1MRK000151-VA A Only for A30/B30/D30
3/4 x 19" rack casing, 1 TRM 1MRK000151-VB B
3/4 x 19" rack casing, 2 TRM 1MRK000151-VE C
1/1 x 19" rack casing, 1 TRM 1MRK000151-VC D Only for A30/B30/D30
1/1 x 19" rack casing, 2 TRM 1MRK000151-VD E
Selection for
position #5

ABB 133
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Mounting details with IP40 of protection from the front Ordering no #6 Notes and rules
No mounting kit included X
19" rack mounting kit for 1/2 x 19" case or 2xRHGS6 or RHGS12 1MRK002420-BB A Only for A30/B30/D30
19" rack mounting kit for 3/4 x 19" case or 3xRGHS6 1MRK002420-BA B
19" rack mounting kit for 1/1 x 19" case 1MRK002420-CA C
Wall mounting kit 1MRK002420-DA D Wall mounting not recommended
with communication modules with
fiber connection
Flush mounting kit 1MRK002420-PA E
Flush mounting kit + IP54 mounting seal 1MRK002420-NA F
Selection for
position #6

Power supply modules Ordering no #7 Notes and rules


Compression terminals 1MRK002960-GA C
Ringlug terminals 1MRK002960-HA R
Power supply module, 24-60 VDC 1MRK002239-AB A
Power supply module, 90-250 VDC 1MRK002239-BB B
Selection for
position #7

Human machine hardware interface Case size Ordering no #8 Notes and rules
Medium size - graphic display, IEC keypad symbols 1/2 x 19", IEC 1MRK000028-AA B Only valid for A30/B30/D30
3/4 x 19”, IEC 1MRK000028-CA
1/1 x 19”, IEC 1MRK000028-BA
Medium size - graphic display, ANSI keypad symbols 1/2 x 19", ANSI 1MRK000028-AB C Only valid for A30/B30/D30
3/4 x 19”, ANSI 1MRK000028-CB
1/1 x 19”, ANSI 1MRK000028-BB
Selection for
position #8

Analog system Ordering no #9 Notes and rules


When more than one TRM is selected, the connector type on both TRMs must be the same (A compression or B ring lug).
Slot position (front view/rear view)
P40/X401

P41/X411

No Transformer input module included X0 X0 Only valid if IEC 61850-9-2


Process bus communication is
selected.
TRM 9I 1A + 3U 110/220V, 50/60Hz, compression terminals 1MRK002247-BG A3 Only for A30/B30/D30
TRM 9I 5A + 3U 110/220V, 50/60Hz, compression terminals 1MRK002247-BH A4
TRM 5I 1A + 4I 5A + 3U 110/220V, 50/60Hz, compression terminals 1MRK002247-BK A5
TRM 6I 1A + 6U 110/220V, 50/60Hz, compression terminals 1MRK002247-AG A6 A6 A second TRM is optional for
A30/B30/D30 and required for
TRM 6I 5A + 6U 110/220V, 50/60Hz, compression terminals 1MRK002247-AH A7 A7
C30.
TRM 6I 1A, 50/60Hz, compression terminals 1MRK002247-DG A8 Only for A30/B30/D30
TRM 6I 5A, 50/60Hz, compression terminals 1MRK002247-DH A9
TRM 7I 1A + 5U 110/220V, 50/60Hz, compression terminals 1MRK002247-AP A12
TRM 7I 5A + 5U 110/220V, 50/60Hz, compression terminals 1MRK002247-AR A13
TRM 9I 1A + 3U 110/220V, 50/60Hz, ring lug terminals 1MRK002247-BC B3
TRM 9I 5A + 3U 110/220V, 50/60Hz, ring lug terminals 1MRK002247-BD B4
TRM 5I 1A + 4I 5A + 3U 110/220V, 50/60Hz, ring lug terminals 1MRK002247-BF B5
TRM 6I 1A + 6U 110/220V, 50/60Hz, ring lug terminals 1MRK002247-AC B6 B6 A second TRM is optional for
A30/B30/D30 and required for
TRM 6I 5A + 6U 110/220V, 50/60Hz, ring lug terminals 1MRK002247-AD B7 B7
C30.
TRM 6I 1A, 50/60Hz, ring lug terminals 1MRK002247-DC B8 Only for A30/B30/D30
TRM 6I 5A, 50/60Hz, ring lug terminals 1MRK002247-DD B9
TRM 7I 1A + 5U 110/220V, 50/60Hz, ring lug terminals 1MRK002247-AS B12
TRM 7I 5A + 5U 110/220V, 50/60Hz, ring lug terminals 1MRK002247-AT B13
Selection for
position #9

134 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Binary input/output Ordering no #10 Notes and rules


module and mA
input module
For pulse counting, for example kWh metering, the BIM with enhanced pulse counting capabilities must be used.
Note: 1 BIM required in position P3 and 1 BOM required in position P4. Products B30 and C30 require an extra BIM in position P5.
Slot position (front

P3/X31

P4/X41

P5/X51

P6/X61

P7/X71

P8/X81

P9/X91

P10/X101

P11/X111

P12/X121

P13/X131

P14/X141

P15/X151

P16/X161
view/rear view)

1/2 case with 1 TRM █ █ █ These black marks


indicate the maximum
3/4 case with 1 TRM █ █ █ █ █ █ █ █
number of modules per
3/4 case with 2 TRM █ █ █ █ █ casing type and the
1/1 case with 1 TRM █ █ █ █ █ █ █ █ █ █ █ █ █ █ slots that can be
occupied.
1/1 case with 2 TRM █ █ █ █ █ █ █ █ █ █ █
Compression 1MRK002960-KA C
terminals
No board in slot X X X X X X X X X X X X
Binary output 1MRK000614-AB A A A A A A A A A A A A A Maximum 4 (BOM+SOM
module 24 output +MIM) boards. P5 not in
relays (BOM) B30/C30.
BIM 16 inputs, 1MRK000508-DD B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1
RL24, 24-30VDC,
50mA
BIM 16 inputs, 1MRK000508-AD C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1
RL48, 48-60VDC,
50mA
BIM 16 inputs, 1MRK000508-BD D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1
RL110,
110-125VDC,
50mA
BIM 16 inputs, 1MRK000508-CD E1 E1 E1 E1 E1 E1 E1 E1 E1 E1 E1 E1 E1
RL220,
220-250VDC,
50mA
BIM 16 inputs, 1MRK000508-CE E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2
RL220,
220-250VDC,
120mA
BIM 16 inputs, 1MRK000508-HA F F F F F F F F F F F F P5 not in B30/C30
RL24, 24-30VDC,
50mA, enhanced
pulse counting
BIM 16 inputs, 1MRK000508-EA G G G G G G G G G G G G
RL48, 48-60VDC,
50mA, enhanced
pulse counting
BIM 16 inputs, 1MRK000508-FA H H H H H H H H H H H H
RL110,
110-125VDC,
50mA, enhanced
pulse counting
BIM 16 inputs, 1MRK000508-GA K K K K K K K K K K K K
RL220,
220-250VDC,
50mA, enhanced
pulse counting
IOM 8 inputs, 10+2 1MRK000173-GD L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1
outputs, RL24,
24-30VDC, 50mA
IOM 8 inputs, 10+2 1MRK000173-AE M1 M1 M1 M1 M1 M1 M1 M1 M1 M1 M1 M1
outputs, RL48,
48-60VDC, 50mA
IOM 8 inputs, 10+2 1MRK000173-BE N1 N1 N1 N1 N1 N1 N1 N1 N1 N1 N1 N1
outputs, RL110,
110-125VDC,
50mA
IOM 8 inputs, 10+2 1MRK000173-CE P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1
outputs, RL220,
220-250VDC,
50mA

ABB 135
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Binary input/output Ordering no #10 Notes and rules


module and mA
input module
For pulse counting, for example kWh metering, the BIM with enhanced pulse counting capabilities must be used.
Note: 1 BIM required in position P3 and 1 BOM required in position P4. Products B30 and C30 require an extra BIM in position P5.
IOM 8 inputs 10+2 1MRK000173-CF P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2
outputs, RL220,
220-250VDC,
110mA
IOM with MOV 8 1MRK000173-GC U U U U U U U U U U U U
inputs, 10+2
outputs, RL24,
24-30VDC, 50mA
IOM with MOV 8 1MRK000173-AD V V V V V V V V V V V V
inputs, 10+2
outputs, RL48,
48-60VDC, 50mA
IOM with MOV 8 1MRK000173-BD W W W W W W W W W W W W
inputs, 10+2
outputs, RL110,
110-125VDC,
50mA
IOM with MOV 8 1MRK000173-CD Y Y Y Y Y Y Y Y Y Y Y Y
inputs, 10+2
outputs, RL220,
220-250VDC,
50mA
mA input module 1MRK000284-AB R R R R R R R R R R R R Maximum 1 MIM in 1/2
MIM 6 channels case
P5 not in B30/C30
SOM Static output 1MRK002614-BA T1 T1 T1 T1 T1 T1 T1 T1 T1 T1 T1 SOM must not to be
module, 12 placed in the position
outputs; 6 standard nearest to NUM: 1/2
relays + 6 static case slot P5, 3/4 case 1
outputs, 48-60VDC TRM slot P10, 3/4 case
2 TRM slot P7, 1/1 case
SOM Static output 1MRK002614-CA T2 T2 T2 T2 T2 T2 T2 T2 T2 T2 T2
2 TRM slot P13.
module, 12
P5 not in B30/C30
outputs; 6 standard
relays + 6 static
outputs,
110-250VDC
Selection for C
position #10

136 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

Station communication, remote end Ordering no #11 Notes and rules


serial communication and time
synchronization
Slot position (front view/rear view) The maximum number

P30:1/X301

P30:2/X302

P30:3/X303

P30:4/X304

P30:5/X305

P30:6/X306

P30:6:1/X3061

P30:6:2/X3062

P31:1/X311

P31:2/X312

P31:3/X313

P32:2/X322

P32:3/X323

LDCM mode
and type of LDCM
modules supported
depend on the total
amount of I/O and
communication modules
in the IED.
Available slots in 1/2 and 3/4 case █ █ █ █ █ █ █ █ █ █ █ █
with 1 TRM
Available slots in 3/4 and 1/1 case █ █ █ █ █ █ █ █ █ █ █ █ █ █
with 2 TRM
No communication board included X X X X X X X X X X X X
Ethernet SFP, optical LC connector 1MRK005500-AA K K K K K K Ethernet SFP is basic in
P30:1. P30:6:1 and
Ethernet SFP, RJ45 connector 1MRK005500-BA p p p p p p
P30:6:2 require Optical
Ethernet module in
P30:6.
Optical Ethernet module 1MRK002266-EA H
Serial SPA/LON/DNP/IEC 1MRK001608-AB L
60870-5-103 plastic interface
Serial SPA/LON/DNP/IEC 1MRK001608-BB M
60870-5-103 plastic/glass interface
Serial SPA/LON/DNP/IEC 1MRK001608-CB N
60870-5-103 glass interface
Galvanic RS485 communication 1MRK002309-AA G G G
module
Optical short range LDCM 1MRK002122-AB A A A A A A Max 2 LDCMs can be
ordered. Always place
Optical medium range, LDCM 1310 1MRK002311-AA B B B B B B
LDCM modules on the
nm
same board to support
redundant
communication: in P30:5
and P30:6, P31:2 and
P31:3 or P32:2 and
P32:3.
Line data communication, default — X Default if no LDCM is
64kbps mode selected
Allow line data communication in 1MRK007002-AA Y
2Mbps mode
GPS time module 1MRK002282-AB S S S S
IRIG-B time synchronization module 1MRK002305-AA F F F F
Selection for
position #11

ABB 137
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

27. Ordering for Accessories

Accessories
IP15151-1 v1
GPS antenna and mounting details
M12374-3 v5

GPS antenna, including mounting kits Quantity: 1MRK 001 640-AA

Cable for antenna, 20 m (Appx. 65 ft) Quantity: 1MRK 001 665-AA

Cable for antenna, 40 m (Appx. 131 ft) Quantity: 1MRK 001 665-BA

Interface converter (for remote end data communication)


M16668-3 v9

External interface converter from C37.94 (64kbps) to G703 Quantity: 1 2


1MRK 002 245-AA

External interface converter from C37.94 (64kbps/2Mbps) to G703.E1 Quantity: 1 2


1MRK 002 245-BA

Test switch Multi-breaker/Single or Three Phase trip with internal neutral


SEMOD111888-5 v12
The test system COMBITEST intended for use with the IEDs on current circuits (ordering number RK926 315-BE).
is described in 1MRK 512 001-BEN and 1MRK 001024-CA.
Please refer to the website: www.abb.com/protection-control Multi-breaker/Single or Three Phase trip with external neutral
for detailed information. on current circuit (ordering number RK926 315-BV).

Due to the high flexibility of our product and the wide variety The normally open "In test mode" contact 29-30 on the RTXP
of applications possible the test switches needs to be test switches should be connected to the input of the test
selected for each specific application. function block to allow activation of functions individually
during testing.
Select your suitable test switch base on the available
contacts arrangements shown in the reference Test switches type RTXP 24 is ordered separately. Please
documentation. refer to Section Related documents for references to
corresponding documents.
However our proposals for suitable variants are;
RHGS 6 Case or RHGS 12 Case with mounted RTXP 24 and
Single breaker/Single or Three Phase trip with internal neutral the on/off switch for dc-supply are ordered separately. Please
on current circuits (ordering number RK926 315-AK). refer to Section Related documents for references to
corresponding documents.
Single breaker/Single or Three Phase trip with external neutral
on current circuits (ordering number RK926 315-AC).
Protection cover
M15040-3 v6

Protective cover for rear side of RHGS6, 6U, 1/4 x 19” Quantity: 1MRK 002 420-AE

Protective cover for rear side of terminal, 6U, 1/2 x 19” Quantity: 1MRK 002 420-TA

Protective cover for rear side of terminal, 6U, 3/4 x 19” Quantity: 1MRK 002 420-SA

Protective cover for rear side of terminal, 6U, 1/1 x 19” Quantity: 1MRK 002 420-RA

138 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

External resistor unit


SEMOD120228-4 v8

High impedance resistor unit with resistor and voltage dependent resistor 20-100V, 1ph Quantity: 1 2 3
RK 795 101-MA

High impedance resistor unit with resistor and voltage dependent resistor 20-100V, 3ph Quantity: RK 795 101-MB

High impedance resistor unit with resistor and voltage dependent resistor 100-400V, 1ph Quantity: 1 2 3
RK 795 101-CB

High impedance resistor unit with resistor and voltage dependent resistor 100-400V, 3ph Quantity: RK 795 101-DC

Combiflex
IP15161-1 v1

Key switch for settings SEMOD130356-4 v6

Key switch for lock-out of settings via LHMI Quantity: 1MRK 000 611-A

Note: To connect the key switch, leads with 10 A Combiflex socket on one end must be used.
SEMOD130267-5 v7

Mounting kit Ordering number


Side-by-side mounting kit Quantity 1MRK 002 420-Z

Configuration and monitoring tools


M15042-3 v4 IP15162-1 v2

Front connection cable between LHMI and PC Quantity: 1MRK 001 665-CA

SEMOD131414-4 v3

LED Label special paper A4, 1 pc Quantity: 1MRK 002 038-CA

LED Label special paper Letter, 1 pc Quantity: 1MRK 002 038-DA

Manuals
M15161-3 v14

Note: One (1) IED Connect USB flash drive containing user documentation (Operation manual, Technical
manual, Installation manual, Commissioning manual, Application manual and Getting started guide),
Connectivity packages and LED label template is always included for each IED.

Rule: Specify additional quantity of IED Connect USB flash drive requested. Quantity: 1MRK 002 290-AE

ABB 139
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

User documentation
Rule: Specify the number of printed manuals requested
Application manual IEC Quantity: 1MRK 511 401-UEN

ANSI Quantity: 1MRK 511 401-UUS

Technical manual IEC Quantity: 1MRK 511 402-UEN

ANSI Quantity: 1MRK 511 402-UUS

Commissioning manual IEC Quantity: 1MRK 511 403-UEN

ANSI Quantity: 1MRK 511 403-UUS

Communication protocol manual, IEC 61850 Edition 1 IEC Quantity: 1MRK 511 392-UEN

Communication protocol manual, IEC 61850 Edition 2 IEC Quantity: 1MRK 511 393-UEN

Communication protocol manual, IEC 60870-5-103 IEC Quantity: 1MRK 511 394-UEN

Communication protocol manual, LON IEC Quantity: 1MRK 511 395-UEN

Communication protocol manual, SPA IEC Quantity: 1MRK 511 396-UEN

Communication protocol manual, DNP ANSI Quantity: 1MRK 511 391-UUS

Point list manual, DNP ANSI Quantity 1MRK 511 397-UUS

Operation manual IEC Quantity: 1MRK 500 127-UEN

ANSI Quantity: 1MRK 500 127-UUS

Installation manual IEC Quantity: 1MRK 514 026-UEN

ANSI Quantity: 1MRK 514 026-UUS

Engineering manual IEC Quantity: 1MRK 511 398-UEN

140 ABB
1MRK 511 404-BEN B
Bay control REC670 2.2
Product version: 2.2

ANSI Quantity: 1MRK 511 398-UUS

Cyber security deployment guideline IEC Quantity: 1MRK 511 399-UEN

Application guide, Communication set-up IEC Quantity: 1MRK 505 382-UEN

Reference information
M2175-3 v4

For our reference and statistics we would be pleased to be provided with the following application data:

Country: End user:

Station name: Voltage level: kV

Related documents
GUID-94E8A5CA-BE1B-45AF-81E7-5A41D34EE112 v6 670 series manuals Document numbers

Documents related to REC670 Document numbers Operation manual IEC:1MRK 500 127-UEN
ANSI:1MRK 500 127-UUS
Application manual IEC:1MRK 511 401-UEN
ANSI:1MRK 511 401-UUS Engineering manual IEC:1MRK 511 398-UEN
ANSI:1MRK 511 398-UUS
Commissioning manual IEC:1MRK 511 403-UEN
ANSI:1MRK 511 403-UUS Installation manual IEC:1MRK 514 026-UEN
ANSI:1MRK 514 026-UUS
Product guide 1MRK 511 404-BEN
Communication protocol manual, 1MRK 511 391-UUS
Technical manual IEC:1MRK 511 402-UEN DNP3
ANSI:1MRK 511 402-UUS
Communication protocol manual, 1MRK 511 394-UEN
Type test certificate IEC:1MRK 511 404-TEN IEC 60870-5-103
ANSI:1MRK 511 404-TUS
Communication protocol manual, 1MRK 511 392-UEN
IEC 61850 Edition 1

Communication protocol manual, 1MRK 511 393-UEN


IEC 61850 Edition 2

Communication protocol manual, 1MRK 511 395-UEN


LON

Communication protocol manual, 1MRK 511 396-UEN


SPA

Point list manual, DNP3 1MRK 511 397-UUS

Accessories guide IEC:1MRK 514 012-BEN


ANSI:1MRK 514 012-BUS

Cyber security deployment 1MRK 511 399-UEN


guideline

Connection and Installation 1MRK 513 003-BEN


components

Test system, COMBITEST 1MRK 512 001-BEN

Application guide, 1MRK 505 382-UEN


Communication set-up

ABB 141
142

ABB AB
Grid Automation Products
721 59 Västerås, Sweden
Phone: +46 (0) 21 32 50 00

abb.com/protection-control
1MRK 511 404-BEN

© Copyright 2017 ABB. All rights reserved.