Nothing Special   »   [go: up one dir, main page]

MRS11 Datasheet

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

InteliLiteNT

MRS 11

Order code: IL-NT MRS 11


Controller for single gen-set applications
Datasheet
Product description
Compact gen-set controller for single gen-set
Application overview
operating in standby mode
Meets all requirements for Manual and Remote
Start (MRS) applications
Full gen-set monitoring and protection

Key features
Running hours event and performance log
Plug-in extension modules capability
WebSupervisor, AirGate and LOCATE support with
plug-in module
On-line control and monitoring over web pages with
plug-in module
Fuel theft protection
Alternative switchable configuration
Automatic and manual GCB control
Magnetic pickup input
D+ preexcitation terminal
True RMS measurement
3 phase power measurement of gen-set

| InteliLite NT Datasheet | Related HW ver: 1.6 | Related SW ver: 2.2 | Date of issue: 19.9.2017
Technical data
Power supply Binary outputs
Power supply range 8-36 V DC Number 6 non-isolated

Power supply drop-out Operating voltage 8-36 V DC


100 ms (from min. 10 V)
immunity Switching to negative supply terminal
approx. 100 mA / 8 V; 40 mA / Max current 0,5 A (2 A per group)
Power consumption
36 V
Peak power approx. 0,33 A / 8 V; 0,18 A / 36
Analog inputs
consumption (LT) V Number 3 non-isolated
Backup battery type CR 1225 Electrical range 0-2500 Ω

Estimated backup Resolution 10 bits, 4 digits


10 years
battery lifetime Precision 2% from measured value
Predefined: VDO 10Bar, VDO
Operating conditions Supported sensor Temperature, VDO Fuel level
Operating temperature -20-70 °C types User-defined: 10 points non-linear
Operating temperature (LT sensors can be defined by the user
-40-70 °C
version)
Magnetic pick-up
95% non-condensing
Operating humidity
(IEC/EN 60068-2-30) Voltage input range 2–70V
pp
Protection degree (front 4 Hz–10 kHz (min 2 V @4
IP65 Frequency input range pp
panel) Hz, 6 V @ 10 kHz)
pp
5-25 Hz, +/- 1,6 mm; 25-100 Frequency measurement
Vibration 0.2 %
Hz, a = 4 g tolerance
Shocks a 500 m/s2
max
Storage temperature -30-80 °C
D+
250 mA, during the engine start
Excitation current
Voltage measurement only
Charging fail
Measurement inputs 3 ph generator voltage 80 % of U
threshold supply

Measurement type True RMS


Display
Voltage range 480 V Ph-Ph (277 V Ph-N)
Type Built-in monochromatic
Max. measured voltage 340 V Ph-N
Resolution 128x64
Voltage accuracy 2 % from nominal voltage
Frequency range 30-70 Hz, measured from L3
Frequency accuracy 0,05 Hz

Current measurement
Measurement inputs 3ph generator current
Measurement type True RMS
Current range 5A
Max. measured current 9A
Max. allowed current 10 A continuous, 50 A/1 s
Current accuracy 2 % from nominal current

Binary inputs
Number 6 non-isolated
Input resistance 4,2 kΩ
Common pole Positive, V = 8-36 V DC
s
0 - 0,8 V close contact
Close/Open indication
2 - 36 V - V open contact
s

InteliLite NT Datasheet 2
Dimensions, terminals and mounting

Note: Dimension x depends on plug-in module.

Panel door mounting Overview of parameter x


Plug-in module Parameter x [mm]
IL-NT-AOUT8 75
IL-NT-BIO8 74
IL-NT-RS232 113
IL-NT-RS232-485 115 @ RS232 / 74 @ RS485
IL-NT-GPRS 122
IL-NT-S-USB 128
IB-Lite 108

Note: Parameter x includes reserve for connectors of plug-in modules.

Note: The controller is to be mounted onto the switchboard door. The requested cut-out size is 175x115 mm.
Use the screw holders delivered with the controller to fix the controller into the door.

InteliLite NT Datasheet 3
Available extension modules
Product Description Order code

IL-NT AOUT8 8 analog outputs packed in a unit IL-NT-AOUT8


IL-NT BIO8 8 binary inputs in a unit (HW switchable to 8 binary outputs) IL-NT-BIO8
IL-NT RS232 Communication module which provides additional RS232 interface for controller IL-NT-RS232
Communication module which provides additional RS232 and RS485 interface for
IL-NT RS232-485 IL-NT-RS232-485
controller

IL-NT GPRS Communication module with integrated GSM modem with GPRS Internet connection IL-NT-GPRS
IL-NT S-USB Communication module which provides additional USB interface for controller IL-NT-S-USB
IB-Lite Communication module which provides additional Ethernet interface for controller IB-Lite

Related products
Product Description Order code

IL-NT RD (SW) Remote Display Software for InteliLite NT IL-NT RD

Functions and protections


Description ANSI code Descritption ANSI code

Overvoltage 59 Overfrequency 81H

Undervoltage 27 Underfrequency 81L

Gas (Fuel) Level 71 Overload 32

Phase Rotation 47 Overcurrent 50+51

Current Unbalance 46 Voltage Asymmetry 47

Certificates and standards


EN 61010-1:95 +A1:97

EN 61000-6-3:2006

EN 61000-6-3:2006

EN 61000-6-1:2005

EN 61000-6-2:1999

List of standards is available on: https://webstore.iec.ch/

Manufacturer:
ComAp a.s.
Czech Republic E-mail: info@comap-control.com
Phone: +420 246 012 111 Web: www.comap-control.com

© ComAp. Features and specification are subject to change without prior notice.