Nothing Special   »   [go: up one dir, main page]

InteliSys Gas Datasheet

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

InteliSys

Gas

Order code: IS2GASXXBAB


Controller for Gas Gen-set
Datasheet Application

Product description
The InteliSys Gas is an industrial grade controller Baseload, Imp / Exp, TempByPower, Peak
for gas gen-set based CHPs and power generation shaving, Voltage and PF control (AVR bias output)
applications. Event-based and PreMortem history with customer-
Preconfigured functions, scalable and configurable selectable list of stored values; RTC; statistic
I/Os, broad communication capabilities and an values
easy-to-change software allows to adapt the Overspeed and Emergency stop detection
controller to various applications without greater
efforts. Application overview
Key features
Predefined adjustable functions for gas gen-set
Large built-in PLC interpret to suit individual needs
and design demanding applications like CHPs
SIL2 certification for selected channels
Grid codes requirements support (e.g. VDE-AR-N
4105, BDEW Richtlinien)
Support wide range of applications – from single to
multiple, from island to network parallel operation
Power management function including new mode of
effective engine run in network parallel operation
Plug&Play support of ComAp InteliVision display
family
Automatic synchronization and power control (via
speed governor or ECU)

| InteliSys Gas Datasheet | Related HW ver: 2.0 | Related SW ver: 1.0.0 | Date of issue: 15.4.2016
Technical data
Power supply Analog inputs
Power supply range 8-36 VDC Number 4 non-isolated
0.4 A / 8 VDC Switchable (Voltage,
Type
Power consumption 0.15 A / 24 VDC Resistance, Current)
0.1 A / 36 VDC Resolution 10 bits, max 4 decimals
10 years (replaceable by official Range 0-5 VDC/0-2500 Ω/0-20 mA
RTC battery
service)
Input impedance >100 kΩ/>100 kΩ/180 Ω
Fusing 2 A (without BOUT consumption)
±1 % of meas. value ±1 mV
Accuracy ±2 % of meas value ±2 Ω
Operating conditions
±1 % of meas value ±0.5 mA
Operating temperature - 40°C to + 70°C
Storage temperature - 40°C to + 80°C Analog outputs
Operating humidity 95 % w/o condensation Number 1
5 - 25 Hz, ± 1.6 mm Type Switchable (Voltage, Current)
Vibration
25-100 Hz, a = 4 g Range 0 - 10 VDC / 0 - 20 mA
Shocks a=200 m/s2 Max current/load 5 mA/500 Ω
± 0.5 % of output value ± 20 mV
Voltage measurement
Accuracy ± 0.5 % of output value ± 100
3 ph-n Gen voltage μA
Measurement inputs
3 ph-n Mains/Bus voltage
Measurement range 110 V / 277 V Magnetic pick-up
Max allowed voltage 125 % 2 Vpk-pk to 50
Voltage input range
Accuracy 1 % of 110 V / 277 V Veff

Frequency range 40-70 Hz (at accy 0.1 Hz) Frequency input range 4 Hz to 15 kHz

0.6 MΩ ph-ph Frequency measurement tolerance 0.2 %


Input impedance
0.3 MΩ ph-n
Voltage regulator output
Current measurement 5 V TTL PWM / ± 10 VDC with IG-AVRi
Type
3 ph Gen current interface
Measurement inputs
1 ph Mains current
Speed governor output
Measurement range 1A/5A
Max allowed continuous Voltage output ± 10 VDC / max.15 mA
10x Inom / 2x Inom
current Voltage output via ± 10 VDC via 10 kΩ resistor / max . 1
Accuracy 2 % of 1 A / 5 A resistor mA

Input impedance < 0.1 Ω PWM 500÷3000 Hz / 5V / max. 10mA

Binary inputs Communications


Number 16 non-isolated RS232 Direct/Modbus, non-isolated

Input resistance 4.7 kΩ RS485 Direct/Modbus, isolated

0 - 2 VDC close contact non-isolated RS485, only terminal


Close/Open indication Display port
> 4 VDC open contact connection
USB port Direct, isolated
Binary outputs LAN/Internet, Modbus TCP, SNMP,
Ethernet port
Number 16 non-isolated WebServer, AirGate

Max current 0.5 A (2 A per group) External modules


CAN1
250 kbps, max 200 m, Isolated
Switching to negative/positive supply terminal
Intercontroller and comm extensions
CAN2 250 / 50 kbps, max 200 / 1000 m,
Isolated

InteliSys Gas Datasheet 2


Dimensions, terminals and mounting

Panel door mounting DIN rail mounting Panel door mounting


(InteliVision 5) (InteliVision 8)

① InteliVision 5
② InteliSys Gas
③ DIN rail
④ InteliVision 8

InteliSys Gas Datasheet 3


Available extension modules
Product Description Order code
8 Binary inputs, 8 Binary outputs and 2 Analog outputs packed in a small unit (HW switchable to
Inteli IO8/8 I-IO8/8
IO16/0)
Inteli IO8/8 HW switchableto IO16/0 - 16 Binary inputs packed in a small unit I-IO8/8
Inteli AIN8 8 Analog inputs (R, I, V) and 1 pulse/frequency input in a small unit I-AIN8
Inteli AIN8TC 8 Thermocouple Analog inputs in a small unit I-AIN8TC
Inteli AIO9/1 9 Analog inputs (4x DC, 4x thermocouples, 1x R) in a small unit I-AIO9/1
IS-AIN8 8 Analog inputs packed in a rugged metal unit IS-AIN8
IGS-PTM 8 Binary inputs, 8 Binary outputs, 4 Analog inputs and 1 Analog output in a unit IGS-PTM
IGL-RA15 15 Binary LED output (3 colors) packed in a rugged metal unit IGL-RA15
I-AOUT8 8 Analog outputs packed in a rugged metal unit I-AOUT8
InternetBridge-NT Multiple Internet connections (PC and Modbus) to all controllers on CAN2 or RS485 IB-NT
I-LB+ Direct connection (PC) to all controllers on CAN2 or RS485 I-LB+

Related products
Product Description Order code
InteliVision 5 Color 5.6" display for monitoring and control INTELIVISION 5
InteliVision 8 Color 8" display for advanced monitoring, control & trending, USB capable INTELIVISION 8
InteliVision 12Touch Color 12" touch display for advanced monitoring, control & trending, USB capable RD1IV12TBZH
Color 17“ touchscreen display designed for complete monitoring and control of multiple
InteliVision 17Touch IV17T2
controllers or cogeneration installation.
ECON-4 Digital speed governor dedicated for speed control of gas or diesel engines. ECON-4

Functions and protections


ANSI ANSI ANSI ANSI
Description Description Description Description
code code code code
Synchronism Overcurrent
25 Excitation loss 40 51 AC reclosing 79
check (IDMT)
Earth fault current
Undervoltage 27 Current unbalance 46 51N+64 Overfrequency 81H
IDMT
Voltage asymmetry and phase
Overload 32 47 Power factor 55 Underfrequency 81L
sequence
Load shedding 32P Temperature monitoring 49T Overvoltage 59 ROCOF 81R
Reverse power 32R Generator overcurrent 50 Gas (fuel) level 71
Undercurrent 37 Earth fault current 50N+64 Vector shift 78

Certificates and standards


This product is CE compliant.

EN 60068-2-6 ed.2:2008 EN 60068-2-30, May 2000 EN 61010-1:2003

EN 60068-2-27 ed.2:2010 EN 60068-2-64

This product is tested according to:

VDE AR N 4105:2011; DIN VDE V 0124-100:2012 (CI. 5.3.3, 5.3.4, 5.3.6, 5.4.3, 5.4.5, 5.4.6, 5.5)

BDEW Medium-Voltage Guideline: 2008; FGW TR3:2013 (Clauses 4.2.2, 4.2.3, 4.2.4, 4.3.2, 4.3.3, 4.3.4., 4.5, 4.6., 4.7)

All certificates and standards are available on: https://webstore.iec.ch/

Manufacturer:
ComAp a.s. Fax: +420 266 316 647
Czech Republic E-mail: info@comap.cz
Phone: +420 246 012 111 Internet: www.comap.cz

© ComAp. Features and specification are subject to change without prior notice.