Saes J 200
Saes J 200
Saes J 200
1 Scope............................................................. 2
2 Conflicts and Deviations................................. 2
3 References..................................................... 2
4 Modifications to PIP PCCPR001,
Pressure Measurement Design Criteria......... 3
1 Scope
This standard prescribes the minimum mandatory requirements governing the design
and installation of pressure and differential pressure (D/P) instruments.
The requirements of this standard are in addition to and supplement the requirements of
the Process Industry Practice PIP PCCPR001, "Pressure Measurement Criteria"
referenced in Section 3 of this standard.
2.1 Any conflicts between this Standard and other applicable Saudi Aramco
Engineering Standards (SAESs), Materials System Specifications (SAMSSs),
Standard Drawings (SASDs), or industry standards, codes, and forms shall be
resolved in writing by the Company or Buyer Representative through the
Manager, Process & Control Systems Department of Saudi Aramco, Dhahran.
2.2 Direct all requests to deviate from this standard in writing to the Company or
Buyer Representative, who shall follow internal company procedure SAEP-302
and forward such requests to the Manager, Process & Control Systems
Department of Saudi Aramco, Dhahran.
3 References
The selection of material and equipment, and the design, construction, maintenance, and
repair of equipment and facilities covered by this standard shall comply with the latest
edition of the references listed below, unless otherwise noted.
Page 2 of 6
Document Responsibility: Instrumentation SAES-J-200
Issue Date: 8 October 2008
Next Planned Update: 18 May 2013 Pressure
The following paragraph numbers refer to PIP PCCPR001 (April 2007), which is a part
of this standard. The text in each paragraph is an addition, exception, modification, or
deletion to the requirements of PIP PCCPR001 as noted. Paragraph numbers not
appearing in PIP PCCPR001 are new paragraphs to be inserted.
Page 3 of 6
Document Responsibility: Instrumentation SAES-J-200
Issue Date: 8 October 2008
Next Planned Update: 18 May 2013 Pressure
4.1.12 (Additional Paragraph) All instruments and their accessories shall meet the
relevant requirements of SAES-J-003 pertaining to ambient conditions.
Locally mounted instruments and their accessories shall meet the relevant
electrical area classification requirements of SAES-B-068.
4.2.2 (Addition) Add the word "Process" before the word "pressure".
4.2.3 (Modification Exception) Pressure gauges shall have safety glass. Plastic
lenses (acrylic or polycarbonate) can only be used if they are the standard
window material for gauges supplied as part of a package unit. Lenses,
when used, are to be compatible with the surrounding process and ambient
environments.
4.2.7 (Addition) Add the following sentence at the end of the paragraph: "siphons
shall also be used for process fluids with a temperature over 250°C (480°F)
when the gauge is above the tap connection."
4.2.8 (Additional Paragraph) Standard ranges shall be selected such that the
normal operating pressure falls between 30% and 70% of the scale range.
4.3.6 (Additional Paragraph) Electric switch contacts shall be snap acting, single-
pole, double-throw (SPDT) as a minimum. The contact rating shall be
sufficient to operate solenoids, relays, or other devices as specified in the
data sheet without the need for additional or interposing relays.
Hermetically sealed switch contacts are preferable.
Page 4 of 6
Document Responsibility: Instrumentation SAES-J-200
Issue Date: 8 October 2008
Next Planned Update: 18 May 2013 Pressure
4.7.1 All pulsation dampeners (or snubbers), siphons, diaphragm seals and similar
accessories shall be shown on P&IDs.
4.7.2 Snubber design shall allow easy disassembly to facilitate cleaning. Snubbers
shall not be used on switches in critical (e.g., ESD) service. Pulsation
dampeners using a restriction orifice or a moving piston are acceptable.
Capillary tube-type snubbers are not acceptable.
4.7.3 Gauge savers protecting instruments against pressures that are very high
compared to the operating range may be used, except on switches in critical
(e.g., ESD) service.
5.1 Branch connection up to and including the first block (root) valve shall meet
the applicable Saudi Aramco piping codes. If more than one instrument are
sharing a common root valve, means to isolate each instrument
independently shall be provided.
Commentary Note:
The device manifold is acceptable to provide the required isolation at the end-
use device in clean/non-plugging services when multiple devices share a
common root valve connection.
5.3 For low-pressure service, e.g., furnace draft, the instrument is to be mounted
at the same elevation or above the pressure tap.
5.4 All pressure instrument installations shall be equipped with vent/drain valves.
5.5 For additional details of typical pressure instrument installations refer to the
referenced Saudi Aramco Library Drawings and PIP PCIPR000, PCIDP000,
PCIPR100, and PCIDP100.
Page 5 of 6
Document Responsibility: Instrumentation SAES-J-200
Issue Date: 8 October 2008
Next Planned Update: 18 May 2013 Pressure
NEMA Type 1 or IEC IP 22. For outdoor installation NEMA Type 4 or IEC
IP 65 enclosures are required as a minimum.
Revision Summary
18 May 2008 Revised the "Next Planned Update". Reaffirmed the contents of the document and reissued
with minor changes.
8 October 2008 Editorial revisions to update the committee membership.
Page 6 of 6