Load Sharing: Sharing of Load When Two Alternators Are in Parallel
Load Sharing: Sharing of Load When Two Alternators Are in Parallel
Load Sharing: Sharing of Load When Two Alternators Are in Parallel
When several alternators are required to run in parallel, it probably happens that
their rated outputs differ. In such cases it is usual to divide the total load between
them in such a way that each alternator takes the load in the same proportion of its
rated load in total rated outputs. The total load is not divided equally.
Alternatively, it may be desired to run one large alternator permanently on full
load, the fluctuations in load being borne by one or more of the others. If the
alternators are sharing the load equally the power triangles are as shown in Fig
From the circuit we have V = E1 - I1Z1 = E2 - I2Z2 and hence, I1 = E1 - V/Z1 and
I2 = E2 - V/Z2
And the circulating current or synchronizing current Is = (E1 - E2) / (Z1 + Z2)
Since their induced emfs are the same, there is no resultant emf acting around the
local circuit formed by their two armature windings, so that the synchronizing
current, Is, is zero. Since the armature resistance is neglected, the vector difference
between E1 = E2 and V is equal to, I1Xs1 I2Xs2 , this vector leading the current I by
900, where XS1 and XS2 are the synchronous reactances of the two alternators
respectively.
Now consider the effect of reducing the excitation of the second alternator. E2 is
therefore reduced as shown in Figure. This reduces the terminal voltage slightly, so
let the excitation of the first alternator be increased so as to bring the terminal
voltage back to its original value. Since the two alternator inputs are unchanged
and losses are neglected, the two kW outputs are the same as before. The current I2
is changed due to the change in E2, but the active components of both I1 and I2
remain unaltered. It can be observed that there is a small change in the load angles
of the two alternators, this angle being slightly increased in the case of the weakly
excited alternator and slightly decreased in the case of the strongly excited
alternator. It can also be observed that I1 + I2 = I, the total load current.
Parallel Operation of Alternators
2. The speed of the incoming machine must be such that its frequency
(= PN/60) equals bus-bar frequency.
3. The phase of the alternator voltage must be identical with the phase of the
bus-bar voltage. 4. The phase angle between identical phases must be zero.
It means that the switch must be closed at (or very near) the instant the two
voltages have correct phase relationship.
Condition (1) is indicated by a voltmeter, conditions (2), (3) and (4) are indicated
by synchronizing lamps or a synchronoscope.
Lamp L1 is connected between R and R′, L2 between Y and B′ (not Y and Y′)
and L3 between B and Y′ (and not B and B′) as shown in Fig:
Two set of star vectors will rotate at unequal speeds if the frequencies of the two
are different. If the incoming alternator is running faster, then voltage
star R′ Y′ B′ appear to rotate anticlockwise with respect to the bus-bar voltage
star RYB at a speed corresponding to the difference between their frequencies.
With reference to Fig: 2.6, it is seen that voltage across L1 is RR′ to be increasing
from zero, and that across L2 isYB′ which is decreasing, having just passed through
its maximum, and that across L3 BY′ which is increasing and approaching its
maximum. Hence the lamps will light up one after the other in the order 2, 3,
1,2,3,1 or 1, 2, 3. If the incoming alternator is running slower, then the sequence of
light up will be 1, 3, 2. Synchronization is done at the moment the uncrossed
lamp L1 is in the middle of the dark period and other two lamps are equally bright.
Hence this method of synchronization is known as two bright one dark lamp
method.
Salient - pole type rotor means a low and moderate speed rotor having large
diameter and small axial length with projected poles coming out of the rotor frame
the outer surface of which almost follows the inner cylindrical surface of the stator
frame.
The value of voltage regulation obtained by EMF method is always more than the
actual value, therefore it is called Pessimistic method.
Compared to the EMF method, MMF method, involves more number of complex
calculation steps. Further the OCC is referred twice and SCC is referred once while
predetermining the voltage regulation for each load condition. Reference of OCC
takes care of saturation effect. As this method require more effort, the final result is
very close to the actual value. Hence this method is called optimistic method.
Cylindrical Rotor
1 . Small diameter and long axial length, length
2. Used for high - speed turboalternators
3. No projecting poles
4. Does not need damper windings.
5. Windage loss is less
8. What are the methods by using zero p.f. lagging curve can be obtained?
Zero power factor characteristic of an alternator gives the variation of terminal
voltage with field current, when the alternator is delivering its full rated current to
a zero power factor (lagging) load. This characteristic is obtained by running the
machine at synchronous speed and connecting a purely inductive
3phase load to its terminals. The load is varied in steps and at each step the field
current is adjusted, so that the armature current is equal to its rated value.
9. What are squirrel-cage windings of alternators? How and why are they
used?
10. Write down the equation for frequency of emf induced in an Altenator.
F = (PN)/120 Hz,
Where
P- Number of poles
N-Speed in rpm
11. What are the advantages of salient pole type construction used
forSynchronous machines?
Advantages of salient-pole type construction are : They allow better ventilation
The pole faces are so shaped that the radial air gap length increases from the pole
center to the pole tips so that the flux distribution in the air-gap is sinusoidal in
shape which will help the machine to generate sinusoidal emf
Due to the variable reluctance the machine develops additional reluctance power
which is independent of excitation
Alternators can be classified into the following two types according to its rotor
construction
Smooth cylindrical type alternator
Salient pole alternator
13.Why is short pitch winding preferred over full-pitch winding ?
Advantages
Waveform of the emf can be approximately made to a sine wave and distorting
harmonics can be reduced or totally eliminated.
Conductor material , copper , is saved in the back and front end connections due to
less coil-span.
Fractional slot winding with fractional number of lots/phase can be used which in
turn reduces the tooth ripples.
Apart from the constant loss incurred in Alternators is the copper loss, occurring in
the 3 -phase winding which depends on I2 R, the square of the current delivered by
the generator.
Most of the Alternators are manufactured with large power rating ,hundreds of kW
or MW, and also with large voltage rating upto 33kV. For Alternators of such
power and voltage ratings conducting load test is not possible. Hence other indirect
methods of testing are used and the performance like voltage regulation then can
be predetermined at any desired load currents and power factors.
17. Name the various methods for predetermining the voltage regulation of 3-
phase Alternator.
The following are the three methods which are used to predetermine the voltage
regulation of smooth cylindrical type Alternators
Synchronous impedance / EMF method Ampere-turn / MMF method
Potier / ZPF method
18. What are the advantages and disadvantages of estimating the voltage
regulation of an Alternator by EMF method?
Simple no load tests (for obtaining OCC and SCC) are to be conducted
Calculation procedure is much simpler
Disadvantages:
The value of voltage regulation obtained by this method is always higher than the
actual value
19. What are the test data required for predetermining the voltage regulation
of an Alternator by MMF method?
Data required for MMF method are :
The terminal voltage magnitude of the incoming Alternator must be made equal to
the existing Alternator or the bus-bar voltage magnitude.
The phase sequence of the incoming Alternator voltage must be similar to the bus-
bar voltage. The frequency of the incoming Alternator voltage must be the same as
the bus-bar voltage.
23.List the factors that affect the load sharing in parallel operating
generators?
The total active and reactive power delivered to the load, connected across the
common bus-bars, are shared among Synchronous generators, operating in parallel,
based on the following three factors
Prime-mover characteristic/input
24.Why almost all large size Synchronous machines are constructed with
rotating field system type?
The following are the principal advantages of the rotating field system type
construction of Synchronous machines:
The relatively small amount of power, about 2%, required for field system via slip-
rings and brushes. For the same air gap dimensions, which is normally decided by
the kVA rating, more space is available in the stator part of the machine for
providing more insulation to the system of conductors, especially for machines
rated for 11kV or above. Insulation to stationary system of conductors is not
subjected to mechanical stresses due to centrifugal action.
Steam turbines are found to operate at fairly good efficiency only at high speeds.
The hig h speed operation of rotors tends to increase mechanical losses and so the
rotors should have a smooth external surface. Hence, smooth cylindrical type
rotors with less diamete rand large axial length are used for Synchronous
generators driven by steam turbines with either 2 or4 poles.
As the speed of operation is low for hydro turbines used in Hydro-electric plants,
salient pole type Synchronous generators are used. These allow better ventilatio
nandalso have other advantages over smooth cylindrical type rotor.
Mechanical degree is the unit for accounting the angle between two points based
on their mechanical or physical placement. Electrical degree is used to account the
angle between two points in rotating electrical machines. Since all electrical
machines operate with the help of magnetic
fields,theelectricaldegreeisaccountedwithreferencetothemagneticfield.180 electrical
degree is accounted as the angle between adjacent North and South poles.
When coil-sides belonging to each phase are housedor distributed in more than
ones lot under each pole regi on then the winding is called distributed winding. A
full pitch coil has width of coil other wise called coil-span as 180º-angle between
adjacent slots in electrical degree and x=1,2,3…
29.Definewinding factor.
ThewindingfactorKdisdefinedastheratioofphasoradditionofemfinducedinallthe
coilsbelonging toeach phasewinding to theirarithmeticaddition.
VariationsinterminalvoltageinAlternatorsonloadconditionareduetothefollowing
three causes:
□ Voltage variation due to the resistance of the winding, R
□ Voltage variation due to the leakage reactance of the
winding, Xt
In complex form Zs = (R + jXs )In polar form Zs = |Zs| <Where |Zs|= ¥_52 + X2 s)
The phase angle introduced between the induced emf phasor, E and terminal
voltage phasor , U during the load condition of an Alternator is called load angle.
35.Why is the stator core of Alternator laminated?
The correctness of the phase sequence can be checked by looking at the three sets
of lamps connected across the3-pole of the synchronizing witch. If the lamps grow
bright and darkinunisonitisan indication of the correctness of the phase sequence.
If on the other hand, they become bright and dark one after the other, connections
to any two machine terminals have to be interchanged after shutting down the
machine.
38.Whataretheadvantagesanddisadvantagesofthreedarklampsmethodofsynchr
onizing?
Advantages:
□ The synchronous switch using lamps is inexpensive
Disadvantages:
□ The rate of flickering of the lamps only indicates the frequency difference
between the bus-barand the incoming Alternator. The frequency of the in coming
Alternator in relation to the bus-bar frequency is not available.
41.List the factors that affect the load sharing in parallel operating
generators?
The total active and reactive power delivered to the load, connected across the
common bus-bars, are shared among Synchronous generators, operating in parallel,
based on the following three factors
□ Prime-mover characteristic/input
□ Excitation level and
□ Percentage synchronous impedance and its R/X ratio
42. How does the change in prime mover input affect the load sharing?
The decrease in excitation in one generator causes the reactive power shared byitto
decrease and a corresponding increase in reactive-power shared by other
generators. The change inactive-power sharing is less appreciable. There will be a
slight decrease in terminal voltage magnitude also.
The following steps are to be taken before disconnecting one Alternator from
parallel operation
The prime-mover input of the outgoing generator has to be decreased and that of
other generators has to be increased and by this the entire active-power delivered
by the outgoing generator is transferred to other generators.
The source or supply lines with non-variable voltage and frequency are called
infinite bus-bars. The source lines are said to have zero source impedance and
infinite rotational inertia.
46.How does increase in excitation of the Alternator connected to infinite bus-
bars affect this operation?
Angle is positive during generator operation and negative during motor operation.
48.An Alternator is found to have its terminal voltage on load condition more
than that on no load. What is the nature of the load connected?
The nature of the load is of leading power factor ,load consisting of resistance and
capacitive reactance.