Diesel Generators

M. Nageswar Rao,
Sr.Mgr.(EMD),
NTPC-Simhadri

Date: 08.06.2016

Contents
Need for DG sets
Principle & Operation
DG set parts
DG sets starting
Auto start
Remote start
Local Starting
Voltage/speed bias
Protections & Alarms
2

Need for DG sets


DG sets are the backbone of the emergency supply

equipment of the power plant.


Safe isolation/ shutdown of the Unit in case of
AC failure

Grid failure
11kV unit bus fault
DC failure
Unit 220V dc failure.
Switchyard 220V dc failure
Station C&I 24V dc failure (Stage#2)

Emergency equipment (EOP, DC SOP, DC JOP, DC scanner

air fans) will start with battery back up.


For long time operation, DG sets to be started to charge
Emergency bus.
3

Principle &
Operation

DG sets Working Principle


Diesel engine is the prime mover, which

drives an alternator to produce electrical


energy.

chemical

DIESEL
DIESEL
ENGINE
ENGINE

mechanical

ALTERNATOR
ALTERNATOR

electrical

LOAD
LOAD

DG set system

Parts of DG set
Diesel Engine
Alternator
PCC (power command)
Local control Panel
Battery & Battery charger
Day tank
Radiator
Stack

Pros & Cons


Advantages

Disadvantages

Low operating costs


Easily available in the

market
Portable
Least inflammable
Maintenance is easy

Sound (However, one can

even buy silent


generators)
Produces higher smoke
8

DG set Rating
Prime Power Rating
(PRP)

Stand by Power
Rating (ESP)

Applicable for supplying in lieu of commercially installations served


electric power
purchased power.
by a reliable utility
source.
Power availability at
variable load for

unlimited number of
hours.

the duration of
power outage

Overload capacity at
intermittent periods.

10%

Nil

DG sets in NTPCSimhadri

10

DG sets in Simhadri
Stage#1

Stage#2

11

DG sets in SMPP
Stage#1

Stage#2

DG set Supplier

Powerica

Jaksons

Prime Power
Rating

415V, 1500kVA,

415V, 1250kVA,

Diesel Engine

Cummins

Alternator

Stamford-New Age,
U.K.

Stamford, India

Control

PLC based

Microprocessor based
Power Command

Enclosure

Open type

Accoustic enclosure

Diesel Engine specs


Stage#1
Make
Model

Stage#2
Cummins

KTA-50-G8

KTA-50-G3

No. of cylinders

16 Vee

Aspiration

Turbocharged-Aftercooled

Method of cooling of Engine &


lubrication oil

Displacement

Radiator cooled, Water cooled


50.3 ltrs (3067 cub.inch)

Output - Prime

1735 bhp (1294


kWm)

1470 bhp (1097


kWm)

Fuel consumption @100%


load

301.7 ltr/hr

251.8 ltr/hr

Oil consumption @100% load

0.35 ltr/hr

0.3 ltr/hr

Governor / Class

Electronic / A1

Lubricating oil system capacity

177 ltrs

Coolant capacity (engine +


radiator)

510 ltrs

440 ltrs

Alternator specs
Rating
Voltage, p.f.
Stator current

Stage#1

Stage#2

1500 kVA

1250 kVA

3-ph ,415V, 0.8 pf lag


2086 A

1739 A

Rated overload capacity

110% for 1 Hr. in every 12 Hrs Operation.

Stator winding

2/3 pitch, Double Layer Lap

Class of insulation

Class H

Temperature rise over 50 degC at rated


current

Class H

Make

Stamford-New Age, U.K.

Stamford, India

Frame size / Model No.

HC-74G

PI-734C2
0.5%

Voltage regulation
Winding

Alternator standard
Enclosure
Max. permissible unbalance electrical
loading

Star 12 winding

Star- 6 winding

IS 4722, IEC 60034-1

IP 22

IP 23

25% unbalance in electrical loading is allowed provided


none of the phases exceeds the rated current

Bearing

DE (BALL. 6228 C3)


NDE(BALL. 6319 C3)

Weight

4022 kg

Parts of DG set

15

DG set parts

16

Diesel Engine
In the diesel engine, air is

drawn into the cylinder and


is compressed to a high
ratio (14:1 to 25:1).
During this compression,
the air is heated to a
temperature of 700900C.
A metered quantity of
diesel fuel is then injected
into the cylinder, which
ignites spontaneously
because of the high
temperature. Hence, the
diesel engine is also known
as compression ignition (CI)

17

Alternator
Synchronous

generator
brushless with
rotating magnetic
field

18

Alternator naming

19

Exciter
Alternator is separately excited by the

PMG.
This is a shaft mounted, high frequency,
pilot exciter which provides a constant
supply of clean power via the Automatic
Voltage Regulator (AVR) to the main
exciter.
The main exciter output is fed to the
main rotor, through a full wave bridge
rectifier, protected by surge
suppression.

Stage
#1

Stage#2

Type

Brushless

Ratin
g

10.3 kVA, 3.6A,


0.8pf

20

Genset control
AVR Control

PCC control

21

ECP
The ECP controls the engine

speed at the set reference


speed (for e.g. 1500 RPM)
from No load to full load
(Isochronous operation).

22

AVR- MX321
3 phase rms sensed with a voltage regulation of 0.5% rms

(see the note on regulation).


The UFRO circuit has adjustable slope and dwell for
controlled recovery from step loads.
An over voltage protection circuit will shutdown the output
device of the AVR, it can also trip an optional excitation
circuit breaker if required.
Generator mounted current transformer to provide
quadrature droop characteristics for load sharing during
parallel operation.
Provision is also made for the connection of the STAMFORD
power factor controller, for embedded applications, and a
remote voltage trimmer.
23

PCC
PCC is a

microprocessor
based generator
set
monitoring,
metering, and
control system

designed to mount
directly on the
generator set.
24

Turbo charger

25

After cooler
Large capacity

integral aftercoolers
are supplied with
cooling water
separate from the
engine jacket.
This provides cooler,
denser intake air for
more complete
combustion and
reduced engine
stresses for longer

26

Radiator
A two pump, two

loop system must be


employed; i.e.
the engine jacket is

cooled by one
radiator or heat
exchanger and
the aftercoolers are
cooled by a separate
radiator or heat
exchanger.
27

Fuel filter
Dual spin on paper

element fuel filters


with standard water
separator

28

Fuel supply control


Fuel pump
Actuator
Fuel shut off valve

29

Lub-oil filter
Lub oil filter

Super bypass lub-oil


filter

30

Starter motor

31

Battery charging
alternator

32

Air filter

33

Lub-oil priming pump

34

Alternator terminals
Phase side
Neutral side

35

DG set starting

36

DG set starting
Remote starting

37

DG starting (St#1)
EMCC normally fed from USS Section#1.
In case of failure of incoming supply from 1DA/2DA bus,
on sensing of under voltage, tie breaker gets opened
Main DG takes auto-start & DG incomer auto-closes.
If Main DG fails to start, start S/B DG manually.

38

DG starting (St#2)
Both the sections of EMCC are fed from USS respective sections.
Main DG is on Sec#1 and S/B DG is on Sec#2
In case of failure of incoming supply from USS bus (1 section),
Bus coupler comes in auto.
In case of both sections fail

Auto start command goes to both Main DG & S/B DG.


After 13 seconds, Incomer of Main DG auto-closes.
In case of failure of Main DG comes in service in auto, Stand by DG set has to be started manually and board
has to be charged from ECP.
Bus coupler will close in auto on charging of any DG breaker.

39

Synch scheme

40

DG set starting in case of


both AC & DC failure of
UES
As per COS-Elec IOM,

2013, it was decided


to provide a self
powered (from VT
supply) Static U/V
relay (Minilec) with
the same setting that
of U/V relay in the VT
panel of UES may be
mounted with a
parallel contact for
DG set starting

41

DG set starting
Local starting

42

Starting of St#1DG sets


Electronic Instrument Panel
Local Control Panel
Remote command

43

St#1 DG Local start


Start the switch in Electronic
Control Panel

Keep Local/Remote switch in


Local
Press the Start Push button in
Local control Panel

44

St#2 DG Local start


Keep Local/Remote switch in
Local
Press the Local Start Push
button in Local control Panel

Keep O/Manual/Auto Switch in


Manual position
Press the Manual Run/Stop
button

45

Bias Voltage &


Speed

46

Bias- Stage#1 DG
Voltage bias through Motorized POT
Speed bias through Solid state POT

47

Bias- Stage#2 DG
Voltage/Speed bias through Digital POT
Aux 101 card enables PCC to accept
Voltage bias &
Speed bias

48

Aux. supplies

1-ph 415V ac supply (from UES),

Stage#1

which further steps down to 220V ac


Stage#2
to feed
Priming pump
Heaters (space heaters, lube oil
heater, water heater)
Lighting (canopy lights, panel
lamps, plug & socket)
Power source
24V dc battery charger to further
feed

1-ph 415V ac supply (from

UES),
24v dc (from DCDB), to feed
PLC

24V batteries
Engine protections (5kA, 6kA, 7kA)
Power command controls

220v dc (from DCDB), to feed


All protections
Annunciation panel

49

Protections & Alarms


Stage#1

Stage#2

Alarms

Protections

Alarms

Protections

Differential 87

Earth fault 51N

Over current

Overvoltage

Under voltage
High water temp.

Low lube oil pressure

Neutral displacement

Removed

Removed

Over speed
Under/Over frequency
Winding/ Bearing temp. high
Fuel oil level very low

50

Thank you all

51

Step timing control (STC) injectors


Premium STC injectors with ceremic
components have more durability and provide
high injection pressure for better fuel economy.
STCs variable fuel injection timing
Improves startability
Reduces part load fuel consumption, and
Minimizes white smoke at idle during cold start up.

Outer Base Circle (OBC). Injector