Operating instruction
Dustproof/Waterproof LED Light Fitting
167G2 (Luxano2)
Adolf Schuch GmbH
Mainzer Str. 172 • D-67547 Worms
+49 6241 4091-0 • info@schuch.de
www.schuch.de
Series | 167G2 |
IP rating: | IP65 |
Weight | 12L..: ~1,7 kg / 15L…: ~2,0 kg |
For following information see type plate:
– Protection class
– Rated voltage
– Frequency
– symbol
– Ambient temperature
Following applies to luminaires marked :
For use in an environment where deposit of non-conductive dust on the luminaire can be expected.
Ts-45737-04
Adolf Schuch GmbH
Lichttechnische Spezialfabrik
Lighting installation with electronic control gear. Please observe:
When connecting to three-phase supplies ascertain that the neutral wire is always connected. Missing neutral conductor leads to imbalance, i.e. overloads up to 400 V, resulting in destruction of the electronic ballast.
For testing the insulation strength it is necessary to pinch off the neutral wire. In this condition the lighting until must not be used. After the insulation test correct connection of the neutral wire must be checked. Only then the installation can be used without damage to electronic ballasts. Insulation test: The test voltage has to be connected between the earth terminal and the interconnected phase and neutral terminals. Max. testvoltage 500V DC.
In supply systems 3 x 220/240 VΔ fusing disconnecting the three phases simultaneously must be provided.
The permissible ambient temperature of the luminaire must be observed. Operation outside the permissible ambient temperature will shorten the service life of the electronic components until it fails.
For maximum number of luminaires on automatic circuit breaker, see datasheet.
Caution: Disconnect supply before opening.
LEDs are sensitive to electrostatic discharge.
Please pay attention to the following recommendations during installation:
- Ground yourself shortly before touching the luminaire
- Do not touch the LED modules
- Conductive clothing should be preferred
Plastic materials can be charged to high voltages generated by friction.
Especially to note are fleece jackets, carpets, plastic films/bags…
Attention: The LED modules contained in this luminaire are not scheduled to be replaced by the user. The LED modules shall only be replaced by the manufacturer or his service agent or a similar qualified person. Repairs only by qualified personnel.
When installing LED luminaires in dirty or contaminated areas, make sure that no dirt (e.g. chemicals, sooty particles, salt or similar) gets into the luminaire during installation. The gear trays (reflector with all electrical components) of dustproof luminaires must be handled and temporarily stored in such a way that no dirt particles can be deposited or adhere to them.
Material indication
Aggressive chemicals in direct contact with the luminaire or in the form of airborne substances as well as improper cleaning agents can damage the light fitting. Do not use any alkaline or acidic solution or any solvents. Do not use any cleaning agents that are aggressive on plastics.
Replacement of ECGs in luminaires with programmed ECGs
Programmed ECGs are marked with a label showing the programming number. For a proper function of the light fitting original spare parts must be used. When placing order, please mention program number.
Energy Efficiency Label (EEL)
This luminaire contains LED Module(s) with Energy Efficiency Label:
EEL | Luminaire Type (Correlated Colour Temperature) |
B | LW / LW DIMD (840), HL / HL DIMD (840), HE VARIO (840, 850, 865), L100 (840, 850) |
C | HE VARIO (827, 830), VARIO (827, 830), L100 (827, 830, 865) |
D | VARIO (840), HE VARIO 9XX, VARIO 9XX |
This table cannot be applied for emergency luminaires.
Applicable is for luminaires with build-in NFC configurable ECGs or luminaires with build in radio system:
Hereby, Adolf Schuch GmbH declares that the present luminaire type is in compliance with Directive 2014/53/EU. The full text of EU decleration of conformity is available at the following internet address:
https://www.schuch.de/en/service/downloads
Dimensions
A | B | C | D | E | |
12L… | 1185 | 800±75 | 385±75 | 650 | 535 |
15L… | 1477 | 1092±75 | 385±75 | 930 | 547 |
Applications
167 12L…G2 =
167 15L…G2
167 12L…G2 AUS =
167 15L…G2 AUS
Scope of delivery:
167G2/DIMD/DIMC/IFS/HE Vario/T40 H50
2x
2x
2x
167G2 LW
Scope of delivery 167G2
1x
1x
2x
1x
167G2 AUS
Scope of delivery 167G2
1x
1x
1x
1x
1x
Connecting Lines
167G2/DIMD/DIMC/IFS/HE Vario/T40 H50
(2)
[2.1] Only for [C] – [E]
AUS / LW
Execution AUS /LW
1x
1x
1x
(1) (2)
(3) (4) (5)
pressure compensation AUS
Execution AUS
1x
1x
Direct Fixing
Attention!
- Mounting bolts not included. intended mounting to be made sure by installer.
Recommended screws (all with partial threads):
DIN84 M5, DIN90 ⌀ 5mm, DIN571 ⌀ 5 mm, DIN933 M5
Drill holes from inside to outside - For mounting the light fitting to a carrier rail always use the corresponding mounting material.
- Do not run the connecting cable along the ballast.
- The minimum distance between screw and protective collar must not be less than 1,5 mm.
(1)
2x
2x
(2)
Screw ⌀ 5mm not included
Fixing with Clamps
B = 15L.. 1092 +/- 75mm
12L.. 800+/- 75 mm
(3)
[3.1] Screw ⌀ 5mm not included
Vertical On-Wall fixing for Variants AUS
For vertical On-Wall fixing the plastic cable glant and breather must be orientated to the ground or to the wall.
With rear cable entry, check space for cable glant.
Options for lead in the lines
cable diameter | instillation torque counter nut | installation torque cap nut | |
Blanking Plug M20 | 8 – 15 ⌀ mm | ||
cable gland M20x1.5 | 6 – 13 ⌀ mm | 4 Nm | 3 Nm |
cable gland M25x1.5 | 9 – 17 ⌀ mm | 4 Nm | 3 Nm |
Installation
[3.3](4)
[4.1]
(5)
[5.1](6)
[6.1]Dismounting
Flat head screwdriver
ZB-Type / Change fuse
Notice: Ts-36511.02
Luminaire for operation on emergency lighting systems acc. DIN EN 60596-2-22, VDE 0711-2-22, section 22.6.3.. Replacement fuse must always be original spare part.
T 1,6A H 250V, Type 179 200
Part No.: 90294 9001
Attention!
Use only Schuch spare part!
Wiring without through wiring
DIMD
DIMD -> touch DIM
- insert a jumper
DIMC
DIMD / touch DIM / DIMC
The control lines must be designed to be mains voltage proof
For back fitting through wiring only use the Schuch extention Kit
through wiring 3 pole
- to the Reflector
(wires loosely enclosed)
Through wiring 5 pole
- to the Reflector
(wires loosely enclosed)
Loop in-loop out-wiring 5 pole
- to the Reflector
(wires loosely enclosed)
Mains cabel
Imax at through wiring
1,5 mm² Imax 8A
2,5 mm² Imax 10A