Nature">
Grupo 3 Proyecto 6
Grupo 3 Proyecto 6
Grupo 3 Proyecto 6
INSTALACIONES ELECTRICAS I
INTEGRANTES:
ÍNDICE ............................................................................................................... 2
INTRODUCCIÓN ................................................................................................................ 3
MARCO TEÓRICO .............................................................................................................. 4
NORMAS USADAS.............................................................................................................. 4
MÉTODO DE CÁLCULO ................................................................................................... 5
CAPÍTULO 2: MEMORIA DESCRIPTIVA......................................................... 7
ANÁLISIS FASORIAL.......................................................................................................... 9
CÁLCULO DE LA POTENCIA CONTRATADA ...................................................................... 10
CÁLCULO DEL GRUPO ELECTRÓGENO ............................................................................ 11
CÁLCULO DE CONDUCTORES E ITM: .............................................................................. 12
DIMENSIONAMIENTO DE CABLES:.................................................................................. 12
CCM01............................................................................................................................. 13
CCM02............................................................................................................................. 13
CALCULO DE LA CORRIENTE DE CORTOCIRCUITO ......................................................... 15
SISTEMAS DE MEDICIÓN EN BAJA Y MEDIANA TENSIÓN ............................................... 19
DISEÑO DE ITM DE BAJA TENSION ................................................................................ 20
SELECCIÓN DE LOS BANCOS CONDENSADORES ............................................................ 20
COMPENSACIÓN AUTOMATIZADA .............................................................................. 23
CALCULO DEL SISTEMA DE ATERRAMIENTO ............................................................. 24
CAPÍTULO 4: ESPECIFICACIONES TÉCNICAS DE EQUIPOS Y MATERIALES 27
PLANOS ............................................................................................................. 46
CAPÍTULO 1:
INTRODUCCIÓN
NORMAS USADAS
𝐼𝑘 = 𝐼𝑛𝑜𝑚 ∗ 1,1
𝐼𝑛𝑜𝑚
𝑅𝑇 =
𝐼𝑛 (𝐼𝑇𝑀 )
5 ⋅ 𝐼𝑛𝑜𝑚
𝑅𝑀 =
𝐼𝑛 (𝐼𝑇𝑀)
1,2 ⋅ 𝐼𝑝 ⋅ 𝐼𝑛𝑜𝑚
𝑅𝑀 =
𝐼𝑛 (𝐼𝑇𝑀)
𝑃
𝐼𝑛𝑜𝑚 =
√3 ⋅ 𝑉𝑛 ⋅ 𝐹𝑝 ⋅ 𝐸𝐹
0,0309 ⋅ 𝐿 ⋅ 𝐼𝑛𝑜𝑚 ⋅ 𝐹𝑃
𝐷𝑣(𝐼𝑛𝑜𝑚) =
𝑉𝑛 ⋅ 𝑆𝑐𝑢 (𝑚𝑚)
0,0309 ⋅ 𝐿 ⋅ 𝐼𝑎𝑟𝑟 ⋅ 𝐹𝑃
𝐷𝑣(𝐼𝑎𝑟𝑟) =
𝑉𝑛 ⋅ 𝑆𝑐𝑢 (𝑚𝑚)
Potencia de Compensación:
𝑄𝑐 = 𝑃 ∗ (𝑡𝑎𝑛𝑔 (𝜃𝑖 ) − tan(𝜃𝑓)
MEMORIA DESCRIPTIVA
LONGI TIPO
ITE DESCRIPCION ARRAN
DESCRIPCION DE LAS CRGAS T CARG
M GENERAL .
(m) A
C. COMPUTO 35 KW, FP = 0.79
AIRE ACONDICIONADO. 68 KW, FP =
0.88
AREA
C1 TENSIÓN ESTABILIZADA 55 KW, FP = 115 m
ADMINISTRATIVA XXXX
0.87
ALUM. TOMACORRIENTE 48 KW, FP =
0.75
C2 SERV. AUXILIARES 115 KW, FP = 0.83 45 m
CRITICA
Y-
C3
ZONA MOLIENDA 250 HP, 04 POLOS 289 m Delta
25HP, 08 POLOS
30 HP, 04 POLOS
10 HP, 06 POLOS
15 HP, 02 POLOS
C4 CCMO1 165 m ADC II
20 HP, 02 POLOS
30 HP, 08 POLOS
20 HP, 02 POLOS
40 HP, 08 POLOS
C5 ENVASADO LIQUIDOS 145 KW, 0.91 156 m ADC I
C6 ENVASADO SOLIDOS 250 KW, 0.82 174 m ADC I
60 HP, 02 POLOS V.V.
NO CRÍTICA
75 HP, 04 POLOS V.V.
100 HP, 08 POLOS V.V.
C7 CCMO2 198 m
150 HP, 06 POLOS S.S.
50 HP, 04 POLOS S.S.
125 HP, 06 POLOS S.S.
CAPÍTULO 3:
CÁLCULOS JUSTIFICATIVOS
ANÁLISIS FASORIAL
CCM01
ITEM
HP POL KW EF FP VOL AMP a AMP a
1 25 8 21.7 86% 0.80 400 39.13 -36.87
2 30 4 25.4 88% 0.90 400 40.79 -25.84
3 10 6 8.9 84% 0.80 400 16.02 -36.87
4 15 2 13.2 85% 0.90 400 21.11 -25.84
279.66 -32.21
5 20 2 17.8 84% 0.90 400 28.49 -25.84
6 30 8 25.7 87% 0.80 400 46.41 -36.87
7 20 2 17.8 84% 0.90 400 28.49 -25.84
8 40 8 33.5 89% 0.80 400 60.49 -36.87
1236
CÁLCULO
FACTOR DE SIMULTANEIDAD
POTENCIA
0.55
POTENCIA DEL TRANSFORMADOR CALCULADO (KW) 850
POTENCIA DEL TRANSFORMADOR COMERCIAL (KW) 900
TENSION NOMINAL (KV) 10
TARIFA MT4
DIMENSIONAMIENTO DE CABLES:
C1 AREA ADMINISTRATIVA 3 - 1x240 mm2 tipo N2XH triple + 1x25 mm2 NH-80 + Diam 105 mm PVC - SAP
C2 SERV. AUXILIARES 3 - 1x70 mm2 tipo N2XH triple + 1x25 mm2 NH-80 + Diam 65 mm PVC - SAP
C3 ZONA MOLIENDA 3 - 1x300 mm2 tipo N2XH triple) + 1x25 mm2 NH-80 + Diam 105 mm PVC - SAP
C4 CCMO1 3 - 1x150 mm2 tipo N2XH triple) + 1x25 mm2 NH-80 + Diam 80 mm PVC - SAP
C5 ENVASADO LÍQUIDOS 3 - 1x120 mm2 tipo N2XH triple) + 1x25 mm2 NH-80 + Diam 80 mm PVC - SAP
C6 ENVASADO SÓLIDOS 3 - 1x300 mm2 tipo N2XH triple) + 1x60 mm2 NH-80 + Diam 105 mm PVC - SAP
C7 CCM02 2(3 - 1x400 mm2 tipo N2XH triple) + 1x50 mm2 NH-80 + 2(Diam 115 mm PVC - SAP)
GRUPO ELECTROG 4(3 - 1x300 mm2 tipo N2XH triple) + 1x70 mm2 NH-80 + 4(Diam 105 mm PVC - SAP)
CONCESIONARIO 7(3 - 1x400 mm2 tipo N2XH triple) + 1x70 mm2 NH-80 + 7(Diam 115 mm PVC - SAP)
ITEM DESCRIPCIÓN CONFIGURACIÓN DEL CABLE
C1 AIRE ACONDICIONADO 3 - 1x25 mm2 tipo N2XH triple + 1x10 mm2 NH-80 + Diam 35 mm PVC - SAP
C2 C. COMPUTO 3 - 1x50 mm2 tipo N2XH triple + 1x16 mm2 NH-80 + Diam 35 mm PVC - SAP
C3 TENSION ESTABILIZADA 3 - 1x35 mm2 tipo N2XH triple + 1x10 mm2 NH-80 + Diam 40 mm PVC - SAP
C4 ALUM Y TOMAC 3 - 1x35 mm2 tipo N2XH triple + 1x10 mm2 NH-80 + Diam 40 mm PVC - SAP
CCM01
CCM01
1 3 - 1x16 mm2 tipo N2XH triple + 1x10 mm2 NH-80 + Diam 35 mm PVC - SAP
2 3 - 1x25 mm2 tipo N2XH triple + 1x10 mm2 NH-80 + Diam 35 mm PVC - SAP
3 3 - 1x16 mm2 tipo N2XH triple + 1x10 mm2 NH-80 + Diam 35 mm PVC - SAP
4 3 - 1x16 mm2 tipo N2XH triple + 1x10 mm2 NH-80 + Diam 35 mm PVC - SAP
5 3 - 1x16 mm2 tipo N2XH triple + 1x10 mm2 NH-80 + Diam 35 mm PVC - SAP
6 3 - 1x16 mm2 tipo N2XH triple + 1x10 mm2 NH-80 + Diam 35 mm PVC - SAP
7 3 - 1x16 mm2 tipo N2XH triple + 1x10 mm2 NH-80 + Diam 35 mm PVC - SAP
8 3 - 1x25 mm2 tipo N2XH triple + 1x10 mm2 NH-80 + Diam 35 mm PVC - SAP
CCM02
1 3 - 1x50 mm2 tipo N2XH triple + 1x16 mm2 NH-80 + Diam 55 mm PVC - SAP
2 3 - 1x70 mm2 tipo N2XH triple + 1x16 mm2 NH-80 + Diam 65 mm PVC - SAP
3 3 - 1x70 mm2 tipo N2XH triple + 1x16 mm2 NH-80 + Diam 65 mm PVC - SAP
CCM02
4 3 - 1x50 mm2 tipo N2XH triple + 1x16 mm2 NH-80 + Diam 55 mm PVC - SAP
5 3 - 1x70 mm2 tipo N2XH triple + 1x16 mm2 NH-80 + Diam 65 mm PVC - SAP
6 3 - 1x70 mm2 tipo N2XH triple + 1x16 mm2 NH-80 + Diam 65 mm PVC - SAP
CALCULO DE LA CORRIENTE DE CORTOCIRCUITO
ICC EN A:
ICC EN B:
ICC EN C:
◦ 𝑍𝑇 = 14.4213| 81.5617°
ICC EN C (MT):
RT XT Z ꝋ
ZT (MMT) 1.4421275 + 14.3489875 = 14.4213 84.2608295 Ω
R X Z ꝋ
Zc (MT) 2.3834 + 16.0659 = 16.2417 81.5617031
ICC A 11.5 KA
ICC B 6.8 KA
ICC C 46.6 KA
SISTEMAS DE MEDICIÓN EN BAJA Y MEDIANA
TENSIÓN
PUNTO A - TRAFOMIX
TC TT
Burden 10 VA Burden 10 VA
Clase de Presición 0.2S Clase de Presición 0.2S
Ip 4000 A Vp 22.9 KV
Is 5A Vs 5A
RT 800 RT 47.7
Punto B y C
TC TT
Burden 10 VA Burden 10 VA
Clase de Presición 0.2S Clase de Presición 0.2S
Ip 3500 A Vp 400 V
Is 5A Vs 5A
RT 700 RT 80
Punto D y E
TC TT
Burden 10 VA Burden 10 VA
Clase de Presición 0.2S Clase de Presición 0.2S
Ip 1600 A Vp 400 V
Is 5A Vs 5A
RT 320 RT 80
DISEÑO DE ITM DE BAJA TENSION
ITM PC
Pinst FP T Inom Idis Icom RT RM
ITM DESCRIPCION DE CARGAS KW V A A A ORIG ORIG
ITM 01 ITM CELDA DE MEDICIÓN 1544.9 0.85 400 2623 3148 3500 0.75 3.7
ITM 02 ITM TTA - 1 1544.9 0.85 400 2623 3148 3500 0.75 3.7
ITM 03 ITM TABLERO GENERAL NORMAL 1544.9 0.85 400 2623 3148 3500 0.75 3.7
ITM 04 ITM TTA - 2 687.7 0.8 400 1241 1489 1600 0.78 3.9
ITM 05 ITM GRUPO ELECTRÓGENO 687.7 0.8 400 1241 1489 1600 0.78 3.9
ITM 06 ITM TTA - 3 687.7 0.8 400 1241 1489 1600 0.78 3.9
ITM 07 ITM TABLERO GENERAL EMERGENCIA 687.7 0.8 400 1241 1489 1600 0.78 3.9
CABLE
PARAMETROS ELECTRICOS BANCOS
N2XH
Qcal Qreal IN ITMt ITMc Idcable Scable Capac
PASOS
KVAR KVAR A A A CARGAS mm^2 A(ducto)
1 30 20.83 30.07 39.09 50 42 6 68
2 30 20.83 30.07 39.09 50 42 6 68
3 30 20.83 30.07 39.09 50 42 6 68
4 30 20.83 30.07 39.09 50 42 6 68
5 30 20.83 30.07 39.09 50 42 6 68
6 30 20.83 30.07 39.09 50 42 6 68
7 30 20.83 30.07 39.09 50 42 6 68
8 30 20.83 30.07 39.09 50 42 6 68
9 10 6.94 10.02 13.03 16 14 6 68
10 10 6.94 10.02 13.03 16 14 6 68
11 RESERVA
12 RESERVA
TOTAL 260 181 261 339 400 365 120 380
BANCO CONDENSADORES AUTOMATIZADO CARGAS NO CRITICAS 400V 60Hz
PARAMETROS ELECTRICOS CABLE N2XH ITM
DESCRIPCION
Pinst QC Inom Idis Scu Cap Idis Icom
GENERAL FPin FPfi φi φf QT
KW KVAR A A mm^2 A A A
BARRA PRINCIPAL 686 0.87 0.985 29.54 9.94 268 271 387 542 300 600 705 800
AJUSTE DE BANCOS 268 X 1.440 = 386 390 X 0.694 = 271 RT 0.5
ELECCION DE BANCOS 30 30 30 30 30 60 60 30 30 30 30 390 RM 2.4
3-1x 300 mm^2 TIPO N2XH TRIPLE + 1x25 mm^2 NH-80 + PVC SAP DIAM 105 mm
PASOS
KVAR KVAR A A A A mm^2 A(ducto)
1 30 20.83 30.07 39 40 42.10 6 68
2 30 20.83 30.07 39 40 42.10 6 68
3 30 20.83 30.07 39 40 42.10 6 68
4 30 20.83 30.07 39 40 42.10 6 68
5 30 20.83 30.07 39 40 42.10 6 68
6 60 41.67 60.14 78 80 84.20 10 95
7 60 41.67 60.14 78 80 84.20 10 95
8 30 20.83 30.07 39 40 42.10 6 68
9 30 20.83 30.07 39 40 42.10 6 68
10 30 20.83 30.07 39 40 42.10 6 68
11 30 20.83 30.07 39 40 42.10 6 68
12 RESERVA
TOTAL 390 270.83 390.91 508.19 630 547.28 300 600
COMPENSACIÓN AUTOMATIZADA
CALCULO DEL SISTEMA DE ATERRAMIENTO
RESISTIVIDADES MEDIAS DE TERRENOS TÍPICOS, DEL TOMO UTLILIZACIÓN DE CÓDIGO NACIONAL DE ELÉCTRICIDAD
r = L / Ln (4L/d)
Donde:
δ = Coeficiente de reducción
r = Radio semiesférico equivalente en m.
X = Distancia entre varillas de cobre (jabalinas)
L = Longitud de la varilla
d = Diámetro de la varilla
R1 = Resistencia de una sola varilla (valor obtenido anteriormente)
Los cálculos se ha realizado bajo las siguientes consideraciones:
δ = Coeficiente de reducción
X = 6.00 m
L = 2.4 m
d = 0.020 m
R1 = 677.99
R4 = 250.4 Con cuatro pozos
El tratamiento de la materiales impreganantes a utilizarse en los pozos
de tierra será mezclado con tierra de cultivo, que según
recomendaciones de los fabricantes, el porcentaje de reducción de
resistencia es:
1 Dosis de 5Kgms. ........ 80-85%.
2 Dosis de 5Kgms. ........ 85-90%.
3 Dosis de 5Kgms. ........ 90-95%.
4 Dosis de 5 Kgms …….. 95-98%.
El valor de la resistencia del sistema de puesta a tierra para 08 pozo
es 85.865 ohmios. Es importante que todas las conexiones al sistema
de tierra sean con cables de 35 mm² como mínimo y en las conexiones
se utilicen soldadura exotérmica (Cadweld o similar) en donde sea
posible y accesorios y conectores de cobre de buena calidad en el resto
de instalaciones. Los resultados de finales se indican en el cuadro
adjunto.
TABLA DE RESULTADOS EN EL CÁLCULO DEL SISTEMA DE ATERRAMIENTO
Objetivo
Esta especificación técnica tiene por objeto establecer los requisitos generales
que deben cumplir el suministro, fabricación, inspección, pruebas y puestas en
servicio de Celdas de Media Tensión, para ser instaladas en Subestaciones de
sus Empresas Distribuidoras. El suministro debe incluir el equipamiento
completo de las Celdas de Media Tensión, con todos los componentes y
accesorios necesarios para su instalación, puesta en servicio y operación. Para
los propósitos de esta especificación, se entenderá como Celdas de Media
Tensión, al conjunto de cubículos de celdas tipo METALENCLOSED, en las cuales
se ubican equipos de maniobra (interruptores de potencia extraíbles,
seccionadores, etc), medida (transformadores de corriente y de tensión, etc),
protección y control; montados en uno o más compartimientos insertos en una
estructura metálica externa, y que cumple la función de recibir y distribuir la
energía eléctrica.
La norma IEC 60298 define que las celdas de MT para uso eléctrico deben
ser METALENCLOSED (es decir metálicas), pero dentro de esta
clasificación pueden ser compartimentadas o sin compartimentar. Las
celdas con cuatro compartimientos (Baja Tensión, Cables, aparato de
maniobra, y conducto de barras) se denominan METALCLAD.
Pruebas y certificaciones
Desde el punto de vista de costos no hay razón para que el vacío sea más
caro que el SF6, pues son menos piezas y tiempos de fabricación. De aparecer
así es solo por motivos comerciales.
Requerimiento de calidad
Condiciones ambientales
Celdas.
IEC 60694: Estipulaciones comunes para las normas de equipos de alta tensión.
SUBESTACIÓN G ITM 05
3X1600A
ELÉCTRICA 7(3 - 1x400 mm2 tipo N2XH triple) + 1x70 mm2 NH-80/T
1600/5 A
MEDIDOR
MM MULTIFUNCIÓN
(Ver Detalles) If= 2A
SCHNEIDER
PM5560
RED DE 3500/5 A MEDIDOR
MULTIFUNCIÓN
0.2S
MM SCHNEIDER
CONCESIONARIA If= 2A 0.2S
PM5560 4(3 - 1x300 mm2 tipo N2XH triple) + 1x70 mm2 NH-80/T
TABLERO DE
TRANSFERENCIA
ITM 02 ITM 06
DSE8760
3X3500A
3X1600A
AUTOMÁTICA - TTA
TABLERO
AUTOSOPORTADO
IP-54
3X1600A
AUTOSOPORTADO ITM 03
3X3500A
If= 2A
IP-54 AUTOSOPORTADO
IP-54
MD = 1236 KW
1M
2N
4M
2M
3M
1N
3X1600A
3X400A
3X1000A
3X400A
3X400A
3X630A
3X400A
3X400A
BARRA 380V/60HZ
3X800A
2E
1E
3X400A
3X630A
TIERRA DE PROTECCIÓN DE BAJA TENSIÓN
CONDENSADORES 02
TABLERO DE BANCO DE
TRANSFORMADOR
400 KVA, 3ɸ 400/380 PT - BT
BANCO DE CONDENSADORES 01
PT - BT
CCMO2
CCMO1
MOLIENDA
ENVASADO LÍQUIDOS
ENVASADO SÓLIDOS
PT - NEUTRO
PT - NEUTRO
ZONA
PT - BT
AREA ADMINISTRATIVA
SERV. AUXILIARES
TABLERO DE
TDE - AA
PROFESOR: PROYECTO:
DIAGRAMA UNIFILAR
HUBER MURILLO
CURSO
:
INSTALACIONES ELECTRICOS 1
GRUPO:
.
-
3
CAD: ESCALA:
1/50
FECHA:
26/09/2020
1
TABLERO
AUTOMATIZADO 01
TABLERO DE BANCO
DE CONDENSADORES
AUTOSOPORTADO IP-54
30 KVAR
3x50 A C-2
IP-54
MATJA 02
K
BANCO Nº1
400V/60HZ
400V/60HZ
3X40A 3 - 1x16 mm2 tipo N2XH triple + 1x10 mm2 NH-80/T GM
3x18 A C-3
TABLERO DE
MATJA 03
K
30 KVAR
DESTRIBUCIÓN CCM01
BANCO Nº2
3 - 1x16 mm2 tipo N2XH triple + 1x10 mm2 NH-80/T GM
3x32 A C-5
MATJA 05
K
3X40A
3 - 1x16 mm2 tipo N2XH triple + 1x10 mm2 NH-80/T
GM
3x50 A C-6
MATJA 06
K
30 KVAR
3 - 1x16 mm2 tipo N2XH triple + 1x10 mm2 NH-80/T
GM
3x32A C-7
K
MATJA 07
3X40A
3 - 1x25 mm2 tipo N2XH triple + 1x10 mm2 NH-80/T
GM
3x65 A C-8
MATJA 08
K
3X400A
30 KVAR
BANCO Nº3 BANCO Nº4
3X40A
3X630A
A TIERRA
30 KVAR
3X80A
TGE
BARRA DE PUESTA
60 KVAR
BANCO Nº5 BANCO Nº6
TGN
3X40A
30 KVAR
BANCO Nº11
TABLERO
3 - 1x50 mm2 tipo N2XH triple + 1x16 mm2 NH-80/T 3x100 A C-1
AUTOMATIZADO 02
MATJA 01 V.V.
TABLERO DE BANCO
DE CONDENSADORES
AUTOSOPORTADO IP-54
IP-54
3x125 A C-2
TABLERO DE
MATJA 02 V.V.
TABLERO ADOSADO
DESTRIBUCIÓN CCM02
3X50A
2( 3 - 1x150 mm2 tipo N2XH triple) + 1x25 mm2 NH-80/T 3x400 A C-4
S.S.
400V/60Hz
MATJA 04
30 KVAR
BANCO Nº1
3X50A
3 - 1x70 mm2 tipo N2XH triple + 1x16 mm2 NH-80/T
3x80 A C-5
MATJA 05 S.S.
30 KVAR
BANCO Nº2
3X50A
3x200 A C-6
MATJA 06
30 KVAR
S.S.
3X16A
3X400A
3X1000A
10 KVAR
3X16A
A TIERRA
10 KVAR
BANCO Nº3 BANCO Nº4 BANCO Nº5
TGE
TGN
BARRA DE PUESTA
.
GRUPO:
-
DIBUJANTE:
3 - 1x120 mm2 tipo N2XH triple
PROYECTISTAS:
3
HUBER MURILLO
3X50A
CAD:
30 KVAR
BANCO Nº11
MD = 370 KW
PLANO:
ESCALA:
PROYECTO:
1/50
ELECTRICO
FECHA:
3 - 1x6 mm2 tipo N2XH triple
26/01/2021
LAMINA:
2
INSTALACIONES ELECTRICOS 1
CELDA DE CELDA DE
CELDA DE PROTECCIÓN CELDA DE MEDICIÓN
REMONTE TRANSFORMACIÓN
If= 2A
RED DE
CONCESIONARIA
MEDIDOR
MM MULTIFUNCIÓN
SCHNEIDER
PM5560
2000 KVA 3500/5 A
22.9 KV/400 V
Dyn5
03
50N 50
TC
M
-PU 51N 51
-PU
Bornera
de tierra
Bornera
de tierra
PROFESOR: PROYECTO:
ELECTRICO
GRUPO:
.
ESCOBAR MENDOZA YORK AXEL
-
3
CAD: ESCALA:
1/50
FECHA:
26/09/2020
3
TGE
3X400A
TDE-AA
BARRA 380V/60HZ
C1
C4
3X125A
3X125A
3X160A
1
1
2
2
3X100A
0
0
C3
C2
3X125A
3X160A
BARRA NEUTRO
BARRA DE PUESTA
A TIERRA
3 - 1x50 mm2 tipo N2XH triple + 1x16 mm2 NH-80/T
UPS ESTABILIZADOR
PROFESOR: PROYECTO:
ACONDICIONADO
TOMACORRIENTE
CENTRO DE
COMPUTO
PT-BT
TENSIÓN
ALUMBRADO
AIRE
CURSO
:
BT-NEUTRO INSTALACIONES ELECTRICOS 1
ELECTRICO
GRUPO:
.
ESCOBAR MENDOZA YORK AXEL
-
3
CAD: ESCALA:
1/50
FECHA:
26/09/2020
4