Section 06 (NXPowerLite)
Section 06 (NXPowerLite)
Section 06 (NXPowerLite)
Feeder Overcurrent
Protection
Feeder Overcurrent Protection
i.e. For very high fault currents the relay will operate in
it’s minimum time; and for fault currents only slightly
above the relay pick-up current there will be a very long
operating time.
Feeder
Overcurrent
Protection
This relay then trips the breaker, and also initiates Auto-
Reclose. For about 90% of the faults this auto-reclose will
be successful, and the interruption to the customers is for
only about 0.5 seconds. If, however, the fault is
permanent, such as a broken pole or a tree on the line,
then the auto-reclose will be unsuccessful. After the
circuit breaker has autoreclosed the tripping from the
Low-Set overcurrent relay is disabled for 10 seconds. This
means that proper protection coordination will then take
place: i.e.
Feeder Overcurrent Protection
1. If the fault is in a transformer, then the fuse will
blow to isolate only the faulted transformer, and
leave the remainder of the feeder in service.
2. If the fault is on the feeder, beyond the first tap,
then the inverse timed overcurrent relay will
operate after a time delay, and the feeder will trip
a second time and “Lock Out”.
3. If the fault is close to the supply station, then the
High-Set overcurrent relay will operate and trip
the feeder a second time, with no intentional time
delay, and ‘Lock Out’.
Feeder
Overcurrent
Protection
H.S. INV. T. L.S.
R
W
H.S. INV. T. L.S.
B 30A
• Directional Supervision
• Undervoltage and Overvoltage
• Bus underirequency & Rate-of-change
• Synchronism Check
• Negative Sequence Voltage
• Auto-reclose
• Event Recording
• Oscillography, or Waveform Capture
• Fault Location
COURSE RECAP