Level Calculation
Level Calculation
Level Calculation
CALIBRATION DATA
h1 700 mm
h3 973 mm 100%
h0 0 mm
h1 b C to C
h2 273 mm
Sp.G. vapour : d3 0 0% h3
h0
Sp.G. wet leg : d2 1.067
h2
Sp.G. tank liquid : d1 0.824
Sp.G. tank leg h2: d0 1.067 L H
H L
H
CALCULATED RANGE
Note 2 : Check that the C to C value = or < transmitter Upper Range Limit / seal oil Sp. Gr.
Transmitter by Honeywell Model STD924
URL of transmitter 10198 mmH2O 1000.0 mBar
C to C max 9557 mmH2O 937 mBar Zero Elevation is -7.3%
LRL of transmitter 204 mmH2O 20 mBar
DATE : BY : REVISION :
CALIBRATION DATA
h1 1778 mm
h3 2031.8 mm 100%
h0 76.2 mm
h1 b C to C
h2 177.8 mm
Sp.G. vapour : d3 0 0% h3
h0 Purge
Sp.G. purge : d2 1.2
h2 Liquid
Sp.G. tank liquid : d1 1.1
Sp.G. tank leg h2 : d0 1.2
H L
CALCULATED RANGE
Note 2 : Check that the C to C value = or < transmitter Upper Range Limit / seal oil Sp. Gr.
Transmitter by Rosemount Model 1151DP-4
URL of transmitter 3803 mmH2O 372.9 mBar
C to C max 3169 mmH2O 311 mBar Zero Elevation is -56%
LRL of transmitter 634 mmH2O 62.2 mBar
PROJECT: CLIENT :
CALIBRATION DATA
h1 2000 mm
100%
h0 100 mm
h1 b
h2 0 mm
0%
h0
h2
Sp.G. tank liquid : d1 0.8
Sp.G. tank leg h2: d0 0.9
H L
CALCULATED RANGE
CALIBRATION DATA
h4 263 mm
h1 812 mm
Zero elevation h3 1695 mm
h0 0 mm 100%
b C to C
h2 310 mm h1 h4
Sp.G. vapour : d3 0 0% h3
h0
Sp.G. wet leg : d2 1
du 0.56 h2
Sp.G. tank upper :
Sp.G. tank leg h2: d0 1
Sp.G. tank lower: dl 1 H L
CALCULATED RANGE
Note 2 : Check that the C to C value = or < transmitter Upper Range Limit / seal oil Sp. Gr.
Transmitter by Foxboro Model 863DP-M
URL of transmitter 2549 mmH2O 250.0 mBar
C to C max 2549 mmH2O 250 mBar Zero Elevation is -31%
LRL of transmitter 133 mmH2O 13 mBar
DATE : BY : REVISION :
CALCULATED RANGE
CALIBRATION DATA
h1 1778 mm
100%
h0 508 mm
h1 b C to C
Sp.Gr. vapour : d3 0 0%
h0
Sp.Gr. sealing oil : d2 0.9
Sp.Gr. tank liquid : d1 0.8
H L
CALCULATED RANGE
Note 1 : Minus sign indicates that the zero is elevated, and that the bench calibration pressure is to be
applied to the low-pressure side of the transmitter.
Note 2 :
Sealing Oil BSO-02 BSO-19 BSO-21 BSO-22 BSO-25 Syltherm DC200 Fluorocarbon
Specific Gravity 0.93 1.11 1.068 0.949 1.87 0.934 0.934 1.85
BSO = Badotherm Sealing Oil at 25 C.
Syltherm and DC200 are trademarks of Dow Corning Corp.
Note 3 : To obtain optimum performance, position the transmitter at or below the midpoint of dimension "C to C".
Note 4 : For vacuum service, position the transmitter at or lower than the lower process connection.
Pressure at H capsule of transmitter shall not be lower than 30 mbara.
Note 5 : Check that the C to C value = or < transmitter Upper Range Limit / seal oil Sp. Gr.
Transmitter by Rosemount Model 1151DP-4
URL of transmitter 3803 mmH2O 372.9 mBar
C to C max 4225 mmH2O 414 mBar Zero Elevation is -49%
LRL of transmitter 634 mmH2O 62.2 mBar
CALIBRATION DATA
h1 3048 mm
100%
h0 500 mm
h1 b
h2 2500 mm
0% h0
Sp.Gr. sealing oil : d2 0.934
Sp.Gr. tank liquid : d1 1.2 h2
H L
CALCULATED RANGE
Note 2 :
Sealing Oil BSO-02 BSO-19 BSO-21 BSO-22 BSO-25 Syltherm800 DC200 Fluorocarbon
Specific Gravity 0.93 1.11 1.068 0.949 1.87 0.934 0.934 1.85
BSO = Badotherm Sealing Oil at 25 C.
Syltherm and DC200 are trademarks of Dow Corning Corp.
Note 3 : For vacuum service, position the transmitter at or lower than the lower process connection.
Pressure at H capsule of transmitter shall not be lower than 30 mbara.
Note 4 : Check that h2, the zero suppression of the transmitter = or < transmitter Upper Range Limit / seal oil Sp. Gr.
Transmitter by Rosemount Model 1151DP-5
URL of transmitter 19009 mmH2O 1864.0 mBar
h2 max 20352 mmH2O 1996 mBar Zero Suppression is 15.4%
LRL of transmitter 3172 mmH2O 311 mBar
CALIBRATION DATA
h1 3048 mm
100%
h2
h0 500 mm H L
h1 b
Zero elevation h2 762 mm
0%
Sp.Gr. sealing oil : d2 1.9
Sp.Gr. tank liquid : d1 1.1 h0
CALCULATED RANGE
LRV 0% 4 mA -897.8 mmH2O -88.0 mBar Zero Elevation See Note 4
URV 100% 20 mA 2455.0 mmH2O 240.7 mBar
Note 2 :
Sealing Oil BSO-02 BSO-19 BSO-21 BSO-22 BSO-25 Syltherm800 DC200 Fluorocarbon
Specific Gravity 0.93 1.11 1.068 0.949 1.87 0.934 0.934 1.85
BSO = Badotherm Sealing Oil at 25 C.
Syltherm and DC200 are trademarks of Dow Corning Corp.
Note 3 : For vacuum service, preferred position of the transmitter is at or below process connection.
Pressure at H capsule of transmitter shall not be lower than 30 mbara.
Note 4 : Check that h2, the zero elevation of the transmitter = or < transmitter Upper Range Limit / seal oil Sp. Gr.
Transmitter by Rosemount Model 1151DP-4
URL of transmitter 3803 mm 372.9 mbar
h2 max 2001 mm 196 mbar Zero Elevation is -23.6%
LRL of transmitter 3172 mmH2O 311 mBar
Chosen Transmitter is OK for the calculated zero elevation.
Calculated Span is > LRL? Yes OK If "No", select another capsule range.
Is LRV < URL ? Yes, OK If "No", check h2 value (location of transmitter).
Is URV < URL ? Yes, OK If "No", check h2 value (location of transmitter).
Note 5 : Capillary length greater than the elevation value is for installation convenience only.
For low response time and minimizing temperature effects keep the length as short as possible.
DATE : BY : REVISION :
CALCULATED RANGE
PROJECT: CLIENT :
DATE : BY : REVISION :
100%
h1
0%
Sp.G. tank upper : du 1
Sp.G. tank lower : dl 1.7
CALCULATED RANGE
DATE : BY : REVISION :
h0 254 mm 100%
b C to C
h1 h4
Sp.G. vapour : d3 0 0%
h0
Sp.G. sealing oil : d2 1.2
Sp.G. tank upper : du 0.8
CALCULATED RANGE
Note 1 : Minus sign indicates that the zero is elevated, and that the bench calibration pressure is to be
applied to the low-pressure side of the transmitter.
Note 2 :
Sealing Oil Description BSO-02 BSO-19 BSO-21 BSO-22 BSO-25 Syltherm DC200 Fluorocarbon
Specific Gravity 0.93 1.11 1.068 0.949 1.87 0.934 0.934 1.85
BSO = Badotherm Sealing Oil at 25 C.
Syltherm and DC200 are trademarks of Dow Corning Corp.
Note 3 : To obtain optimum performance, position the transmitter at or below the midpoint of dimension "C to C".
Note 4 : For vacuum service, position the transmitter at or lower than the lower process connection.
Pressure at H capsule of transmitter shall not be lower than 30 mbara.
Note 5 : Check that the C to C value = or < transmitter Upper Range Limit / seal oil Sp. Gr.
Transmitter by Foxboro Model 863DP-M
URL of transmitter 2549 mmH2O 250.0 mBar
C to C max 2125 mmH2O 208 mBar Zero Elevation is -85%
LRL of transmitter 133 mmH2O 13 mBar
Chosen Transmitter is Not OK for the vertical C to C between the Seals.
Calculated Span is > LRL? Yes OK If "No" select another another capsule range.
Is LRV < URL? Yes, OK If "No" select another another capsule range.
Note 6 : Capillary length greater than the C to C max value is for installation convenience only.
For low response time and minimizing temperature effects keep the length as short as possible.