SAES B 055 Plant Layout
SAES B 055 Plant Layout
SAES B 055 Plant Layout
1 Scope............................................................. 2
2 Conflicts and Deviations................................ 2
3 References..................................................... 2
4 Definitions...................................................... 3
5 Design Considerations................................... 5
6 Instructions for Use of
Spacing Charts and Tables.................... 6
7 Miscellaneous Onsite
Spacing Requirements........................... 7
8 Introduction to Offsite
Spacing Chart – Figure 2..................... 10
9 Miscellaneous Offsite
Spacing Requirements......................... 10
1 Scope
This Standard provides minimum spacing requirements for equipment and structures in
the design and layout of new plants and expansions or modifications of existing plants.
Exception:
Where this Standard is in conflict with specialized requirements for offshore platforms,
covered in SAES-B-009; for piers, wharves, sea islands, in SAES-B-060; bulk plants/air
fueling operations in SAES-B-070, and buildings in SAES-M-100, those Standards shall
govern.
2.1 Any conflicts between this Standard and other applicable Saudi Aramco
Engineering Standards (SAESs), Saudi Aramco Materials System Specifications
(SAMSSs), Saudi Aramco Standard Drawings (SASDs), or industry standards,
codes, and forms shall be resolved in writing by the Company or Buyer
Representative through the Manager, Loss Prevention Department of Saudi
Aramco, Dhahran.
2.2 Direct all requests to deviate from this Standard in writing to the Company or
Buyer Representative, who shall follow internal company procedure SAEP-302
and forward such requests to the Manager, Loss Prevention Department of Saudi
Aramco, Dhahran.
3 References
The selection of material and equipment, and the design, construction, maintenance, and
repair of equipment and facilities covered by the Standard shall comply with the latest
edition of the references listed below, unless otherwise noted.
Page 2 of 34
Document Responsibility: Loss Prevention Standards Committee SAES-B-055
Issue Date: 25 March 2012
Next Planned Update: 25 March 2017 Plant Layout
4 Definitions
Accessway: An accessway is a level paved area that allows access for mobile
maintenance or fire fighting vehicles to equipment. An accessway will often have a
dead-end since it is not intended for continued travel through a unit. Accessways are
restricted to use only by emergency vehicles, for maintenance, or for the delivery of
operations or maintenance supplies.
Combustible Liquid: A liquid that has a flash point greater than 54°C (130°F).
Examples are fluids such as diesel, C7+ feed stocks, bunker fuel, and sulfur.
Page 3 of 34
Document Responsibility: Loss Prevention Standards Committee SAES-B-055
Issue Date: 25 March 2012
Next Planned Update: 25 March 2017 Plant Layout
Flammable Liquid: A liquid that has a flash point equal to or less than 54°C (130°F).
Examples would be fluids such as stabilized crude, gasoline, Jet A-1, Jet JP-4, Jet JP-8,
C6 and lighter feed and blending stocks, and methanol. For purposes of this Standard, a
combustible liquid stored or processed at a temperature equal to or higher than 8°C
(15°F) below its flashpoint shall be considered to be a flammable liquid.
Flashing Liquid: A flammable liquid with a true vapor pressure greater than 90 kPa(abs)
(13 psia) at 54°C (130°F). Examples are fluids such as "gassy" crude oil, C5 feed
streams, and other products which due to their high vapor pressure cannot be stored in
atmospheric storage tanks, not including refrigerated liquids and not including fluids
with vapor pressures exceeding 67 kPa (ga) (10 psig).
High-Flash Stocks: High-flash Stocks are fluids having a flash point over 54°C
(130°F), stored at temperatures more than 8°C below the flash point. Also see
Combustible Liquid.
Low-flash Stocks: Low-flash stocks are fluids with a true vapor pressure less than
90 kPa(abs) (13 psia) and a flash point under 54°C (130°F). This may also characterize
any other fluids that are stored at temperatures above the fluids flash point or within
8°C of the fluid's flash point.
Main Overhead Powerlines: Powerlines that carry a power load in excess of 69 kV.
Main Office Building: An office building that contains offices for 25 or more people
who perform engineering or administrative activities not directly supporting day-to-day
operations of a plant.
Major Highway: A major highway (for the purposes of use in Section 9.4 in this
standard) is a public primary or secondary roadway as designated by the Ministry of
Transport. A primary road connects urban areas of 100,000 persons or more, connects
multiple regions, and serves international connections and is generally a limited access
highway. A secondary road may or may not have controlled-access, connects urban
areas of 50,000 persons or more, connects 2 regions, and may or may not serve
international connections.
Major Offsite Pipeways: Piping that interconnects plants or that connects plants and
storage facilities.
Off-site spacing: Spacing between units. Also spacing between a unit and certain types
of equipment that are not normally inside a process unit such as flares or LPG storage
vessels.
On-site Spacing: Spacing between equipment within the same process unit or utility
unit.
Page 4 of 34
Document Responsibility: Loss Prevention Standards Committee SAES-B-055
Issue Date: 25 March 2012
Next Planned Update: 25 March 2017 Plant Layout
Perimeter Fence: The fence which completely surrounds an area designated by Saudi
Aramco for a distinct function (plant area, light industrial part, camp, or other function).
Plant Piping: Pressure piping system, within an identified plant-area. Plant piping
design and spacing is covered in SAES-L-310.
Plant Utility Service: The supply of steam, water, air, nitrogen or inert gas within a
processing plant.
Plot-Limit: The plot-limit is a boundary, within the plant area, which surrounds a
single unit or function. The plot-limit may be physical such as a wall, the edge of a road
or pipe-way, chains, posts or a boundary indicated on an approved plot plan.
5 Design Considerations
5.1 General
Plant layouts for new construction shall provide for a maximum of safety and
exposure protection from the spread of fire, with ease of operation and
maintenance consistent with economical design.
5.2 Requirements for future expansion shall be identified by the Facilities Planning
Department and reasonable allowances made on the plot plan drawings.
The basic objectives of the Spacing Design criteria given in this Standard are as
follows:
Page 5 of 34
Document Responsibility: Loss Prevention Standards Committee SAES-B-055
Issue Date: 25 March 2012
Next Planned Update: 25 March 2017 Plant Layout
5.3.5 To separate continuous ignition sources from equipment that may have
a higher potential to be a source of release of flammable materials.
The minimum required spacing distances given in this Standard will provide
spacing similar to other plants when compared with facilities similar in nature
elsewhere in the world. They are minimums which will satisfy the above
objectives but do not account for situations such as potential vapor cloud
explosions or flare stack dispersion. There will be instances when special
considerations will provide cause to deviate from these recommended spacings.
The required minimum spacing distances for buildings and equipment are
presented in the Onsite Spacing Chart (Figure 1) and the Offsite Spacing Chart
(Figure 2).
Page 6 of 34
Document Responsibility: Loss Prevention Standards Committee SAES-B-055
Issue Date: 25 March 2012
Next Planned Update: 25 March 2017 Plant Layout
For each facility covered in the charts, the basic spacing is given. This basic
spacing is the required distance to be maintained between a given facility and
other general processing equipment, building or support facility unless a
deviation is indicated in the body of the chart. (See paragraph 6.3 for spacing
between two facilities). This distance is required to minimize the likelihood of a
specific facility becoming involved in fires originating on other equipment, or
vice versa. This basic spacing is not normally required between items of
equipment in similar services, such as a pump and its spare, or pumps and
compressors and their individual drivers.
It is essential that the onsite and offsite charts be used in conjunction with the
spacing guides provided in the Appendix of this standard. These guides are
intended to supplement their respective charts with the following information:
Gas expansion turbines and hydraulic turbines shall be treated in their spacing
similar to compressor or pumps handling flammable fluids.
7.1 Introduction
The onsite Spacing Chart in Figure 1 provides spacing distances for the typical
on-site equipment. However, it is impractical to include all spacing requirements
Page 7 of 34
Document Responsibility: Loss Prevention Standards Committee SAES-B-055
Issue Date: 25 March 2012
Next Planned Update: 25 March 2017 Plant Layout
in Figure 1. For this reason, spacings are established in this section for
additional items of equipment where fire prevention or safety spacing is
considered to be important. This includes personnel safety items, as well as
equipment involved in hydrocarbon releases or providing a source of ignition for
such releases.
Air intakes are required for a number of items of equipment that are located in
or near plants. Included are internal combustion engines and turbines, air
compressors, inert gas generators, forced draft furnaces, buildings (including
substations) containing unclassified electrical equipment, and boilers.
These equipment items represent an internal source of ignition for any
flammable vapors that might have been pulled in with the air, and the potential
for internal explosion. For this reason, the locations of air intakes in relation to
adjacent equipment must be carefully selected.
7.3 Facility layout and spacing for offshore GOSPs shall meet SAES-B-009.
7.4.1 Analyzer and Operator shelters may be located within the plot-limits of
a plant.
7.4.2 The shelters shall be located with free access of no less than 3 m on all
sides. For details, see SAES-B-014 and SAES-J-502.
7.5.2 The exhaust stack for combustion gas turbines and internal combustion
engines shall discharge above the turbine or engine at a level outside
the classified electrical area.
Page 8 of 34
Document Responsibility: Loss Prevention Standards Committee SAES-B-055
Issue Date: 25 March 2012
Next Planned Update: 25 March 2017 Plant Layout
Portable gas cylinders are used in some plant areas. Vulnerability to fire
exposure shall be considered in selecting their location within the plant. The
following shall apply:
7.9 Windsocks shall be installed at plant facilities handling flammable gases, volatile
liquids or toxic materials. These areas include, but are not limited to, GOSPs, gas
processing and compression plants, chlorination facilities, bulk plants, production
or injection wellsites in populated areas, permanent outdoor storage areas for
portable gas cylinders, and near gas flare systems. Windsocks shall be mounted
where they can be clearly seen from most ground level points within the plant
boundary. Mounting shall be on the tops of structures or on a pole. More than one
windsock may be required at a plant site. Windsocks shall also be installed at
heliports. Windsocks at heliports shall be lighted if required for night flights by
the Chief Pilot. Windsocks are not required along pipelines except in hydrocarbon
pump stations and major manifolding and scraping stations.
Page 9 of 34
Document Responsibility: Loss Prevention Standards Committee SAES-B-055
Issue Date: 25 March 2012
Next Planned Update: 25 March 2017 Plant Layout
8.1 The Offsite Chart in Figure 2 provides spacing distances for the typical facilities
being used by Saudi Aramco. These recommended figures will satisfy the
objectives listed in Section 5.3. The provisions of Section 5.5 shall apply if
reductions are needed.
All facilities within the plot-limits shall be located a minimum of 300 meters
from major roadways or railroad lines.
Spacing for the auxiliary platforms associated directly with a GOSP is covered
under SAES-B-009. Other offshore platforms are normally unmanned and
support no process, separating or storage facilities. Examples are water injection
platforms and platforms supporting piping manifolds only. Such platforms shall
normally be placed at least 45 m from any platform containing oil and gas
separation, processing, handling or storage facilities.
Spacing between overhead electrical grid transmission lines and pipelines shall
be in accordance with SAES-B-064.
The following minimum basic spacing for electric transmission lines shall be
kept from:
a) Flares and burn pits - 150 m horizontal.
b) Major highways (as defined in Section 4) - 30 m horizontal.
c) All items - 9 m vertical.
Page 10 of 34
Document Responsibility: Loss Prevention Standards Committee SAES-B-055
Issue Date: 25 March 2012
Next Planned Update: 25 March 2017 Plant Layout
9.5.2 All buildings, major equipment areas, and areas reserved for future
plant expansions shall be accessible to allow for installation of large
vessels or oversized heavy equipment.
9.5.3 The number of pipe racks and overhead powerlines crossing roads
shall be minimized as much as possible in the layout of a plant area.
Overhead obstruction warning signs and tell-tales shall be installed on
each approach to pipe racks and powerlines.
9.5.4 Vehicle barriers shall be provided for exposed piping near grade for
primary and secondary roads.
9.5.5 Placement and protection of fire hydrants and monitors shall be such
that firefighter access to the fire hydrant and monitor is not hindered.
9.5.7 The minimum vertical clearance (measured from the highest point of
the road grade) of overhead powerline conductors at in-plant road
crossings shall meet SAES-P-107.
9.5.8 Three types of roads are normally associated with oil processing plants,
refineries, and similar facilities.
a) Primary roads are generally for vehicular traffic outside a plant
but they may also be used inside large plants such as Ras Tanura
Refinery. Primary roads are used to allow unrestricted traffic to
travel more easily and safely between plants or through an
industrial area such as a light industrial park.
b) Secondary roads are roads which are inside the plant and
normally carry general traffic with no restrictions.
c) Accessways are usually within the plant plot-limits and restricted
to maintenance or emergency vehicles or to the delivery of
operational supplies after permission is secured from the plant
Page 11 of 34
Document Responsibility: Loss Prevention Standards Committee SAES-B-055
Issue Date: 25 March 2012
Next Planned Update: 25 March 2017 Plant Layout
Page 12 of 34
Document Responsibility: Loss Prevention Standards Committee SAES-B-055
Issue Date: 25 March 2012
Next Planned Update: 25 March 2017 Plant Layout
Where residential housing facilities, under Saudi Aramco's control are within a
distance of 1.5 km of a hydrocarbon processing plant area perimeter fence the
facilities shall be located upwind or crosswind of the prevailing wind direction.
The prevailing wind direction applicable to a particular location shall be
determined after consultation with the Environmental Protection Department,
Environmental Unit. However, in no case shall such housing be located closer
than 500 m of a hydrocarbon processing plant area perimeter fence.
9.7.1 The use of tanks and vessels made of thermoplastic resins is prohibited.
Revision Summary
35 March 2012 Revised the "Next Planned Update." Reaffirmed the content of the document, and reissued
with minor revision.
Page 13 of 34
Document Responsibility: Loss Prevention Standards Committee SAES-B-055
Issue Date: 25 March 2012
Next Planned Update: 25 March 2017 Plant Layout
A1.1 Scope
A1.2.1 Facilities Location Guidelines: Within plant plot limits, the locations of major
facilities such as control houses, furnaces, compressors, electrical substations,
etc., shall be determined in accordance with the spacing standards, with
consideration given to proximity of adjoining facilities, location of roadways,
prevailing wind direction, site topography, and similar factors.
A1.2.2 Accessways in Layout-General: The overall layout of the process area shall
be designed with accessways for firefighting, maintenance, and turnaround
isolation. The typical rectangular block pattern is recommended for large
plants and major complexes. This block layout will provide for at least two
approaches to all major process units. All-weather roads shall be provided in
all instances.
Page 14 of 34
Document Responsibility: Loss Prevention Standards Committee SAES-B-055
Issue Date: 25 March 2012
Next Planned Update: 25 March 2017 Plant Layout
A1.2.4.2 Other equipment shall not be installed directly over any of the
following:
a) Pumps or compressors handling flammable materials.
b) Air-cooled heat exchangers.
c) Heat exchangers or drums containing flammable materials at
temperatures above 315°C, or above the known auto ignition
temperatures, if lower.
The notation "From A-1, B-1", etc., found in the spacing discussions of various items,
refers to the spacing between the equipment with those reference letters in Figure 1 and
the particular item being discussed.
Page 15 of 34
Document Responsibility: Loss Prevention Standards Committee SAES-B-055
Issue Date: 25 March 2012
Next Planned Update: 25 March 2017 Plant Layout
E-1 Emergency Valves for Shut Off, Snuffing Steam, Water Sprays, Isolation, etc.
Page 16 of 34
Document Responsibility: Loss Prevention Standards Committee SAES-B-055
Issue Date: 25 March 2012
Next Planned Update: 25 March 2017 Plant Layout
Page 17 of 34
Document Responsibility: Loss Prevention Standards Committee SAES-B-055
Issue Date: 25 March 2012
Next Planned Update: 25 March 2017 Plant Layout
General: Equipment associated with the compressors, such as air cooled heat
exchangers, knockout drums, etc., may be located in the compressor area and
need not comply with the 7.5 m spacing to non-associated equipment, provided
they do not restrict access for firefighting and maintenance. However, in such
instances, fireproofing shall be in accordance with SAES-B-006. Access to
compressors for firefighting purposes must be maintained on at least two sides
of the installation. Compressors handling inert gases or air may be spaced closer
to each other than is shown for gas compressors. Air intakes for air compressors
must be located in a safe area as discussed in Section 7.2 of this standard.
Steam or electric motor-driven gas compressors with less than 150 kW drivers
may be treated as pumps for spacing and location purposes.
Spacing Distance, m. Remarks
Basic 7.5 Spacing provides a degree of protection to expensive
compressor equipment from fires or explosions
involving adjacent equipment, and vice-versa.
G-1 10 As an exception, spacing does not apply to the driver
for the particular compressor being driven. Spacing is
based on the driver being a possible ignition source.
H-1 3 Provides access for operation and maintenance, and
allows increased fire fighting access between units.
Two compressors may be grouped in the same risk
area, 7.5 m spacing would be required for fire fighting
access on at least two sides in this case.
Page 18 of 34
Document Responsibility: Loss Prevention Standards Committee SAES-B-055
Issue Date: 25 March 2012
Next Planned Update: 25 March 2017 Plant Layout
General: Flammable liquid pumps shall not be placed beneath other equipment
such as towers, drums, air-cooled heat exchangers or pipeways, in order to avoid
fire involvement of such equipment. They shall be located clear of overhead
obstructions in order that they may be reached by mobile equipment for
maintenance operations.
Spacing Distance, m. Remarks
Basic 5 Since these flammable liquids are above their
autoignition temperatures, they will ignite on release.
Added spacing is provided between pumps, with their
higher fire potential, and adjacent high valued
equipment. Additional access is also provided for
fire fighting purposes.
From F-1 7.5 Furnaces do not represent a primary ignition source.
Spacing based on minimizing damage if a release
occurs, with a subsequent fire on either piece of
equipment.
From I-1 1.5 Spacing allowable for pumps in the same service only.
If in different services, even if both are operating at
temperatures above 315°C, the basic spacing
requirement of 5 m must be met.
General: Flammable liquid pumps present a higher fire potential so they should
be located away from ignition sources.
Spacing Distance, m. Remarks
Basic 3 Spacing minimizes damage in case of fire, by providing
clear access for fire fighting. Spacing less than I-1
since pumps operating below autoignition temperature
of hydrocarbon do not represent as great of a fire risk
as those operating above autoignition temperature.
Page 19 of 34
Document Responsibility: Loss Prevention Standards Committee SAES-B-055
Issue Date: 25 March 2012
Next Planned Update: 25 March 2017 Plant Layout
General: Due to the extensive heat transfer surface and type of metals used for
those surfaces, air-cooled heat exchanger bundles are highly vulnerable to damage
within a few minutes under fire exposure. Air cooled heat exchangers shall be
located on the opposite side of the plant, away from furnaces, to avoid ignition in
case of air cooled heat exchanger leakage. They shall not be located over
equipment listed in A1.2.4.2, which may have a relatively higher fire potential.
Location over major pipeways with equipment on both sides shall be carefully
considered. This is based on limited firefighting access, and the maintenance
difficulties that are introduced. When layout dictates that they be located above
major pipeways, then the following requirements shall be applied:
a) Adequate headroom of at least 3 m shall be provided between the lowest
part of the air-cooled heat exchanger and the top of the pipe rack.
b) Flanges and valves shall be minimized in all hydrocarbon lines below the
air-cooled heat exchanger.
c) The horizontal spacing requirements as given in Figure 1 from both the
air-cooled heat exchanger and the pipeway shall be met.
d) Access shall be provided for mobile equipment used in the removal or
replacement of the air-cooled heat exchanger units.
e) Supports for the air-cooled heat exchanger and pipeway shall be
fireproofed if so required by SAES-B-006.
Spacing Distance, m. Remarks
Basic 3 Spacing to minimize fire exposure to air-cooled heat
exchangers, since they are more vulnerable to fire
damage than shell and tube exchangers.
From M-1, R-1, - This equipment can be located beneath air cooled
S-1, T-1 heat exchangers, subject to general requirements.
M-1 Drums
Spacing Distance, m. Remarks
Basic 1.5 Spacing is primarily to provide access for operating
and maintenance; it also allows some access for
fire fighting.
Page 20 of 34
Document Responsibility: Loss Prevention Standards Committee SAES-B-055
Issue Date: 25 March 2012
Next Planned Update: 25 March 2017 Plant Layout
General: The spacing requirements for this item apply to any exchanger
Page 21 of 34
Document Responsibility: Loss Prevention Standards Committee SAES-B-055
Issue Date: 25 March 2012
Next Planned Update: 25 March 2017 Plant Layout
General: Spacing is less since any flammable materials released will generally
be below their autoignition temperatures.
Spacing Distance, m. Remarks
Basic 1.5 Primarily provides access for operation and
maintenance.
From R-1 1 For exchangers in similar service.
Page 22 of 34
Document Responsibility: Loss Prevention Standards Committee SAES-B-055
Issue Date: 25 March 2012
Next Planned Update: 25 March 2017 Plant Layout
General: Offsite locations for this type of vessel shall be used if not otherwise
dictated by process reasons. The inventory of onsite pressure storage shall be
held to a minimum. The location of such vessels should be at the unit boundary,
at a minimum of 15 m from furnaces and other sources of ignition.
This category covers refrigeration or other accumulator vessels of over
40 m³ normal capacity, containing pentane or lighter flammable liquids.
Spacing Distance, m. Remarks
Basic 25 Spacing is to minimize exposure to other plant
equipment from a potential source of prolonged,
severe fire. It also minimizes ignition potential in case
of light hydrocarbon release from this equipment.
From U-1 1.5 x Dia. Provides spacing between vessels for fire fighting
operation, and maintenance access.
These spacings are based on blowdown or water disengaging drums that are
vented to a flare system.
Spacing Distance, m. Remarks
Basic 7.5 This equipment should be located in a separate unit
area in order to avoid its involvement in plant fires.
The notation "From A-2, B-2", etc., found in the spacing discussions of various items,
refers to the spacing between the equipment with those reference letters in Figure 2 and
the particular item being discussed.
Page 23 of 34
Document Responsibility: Loss Prevention Standards Committee SAES-B-055
Issue Date: 25 March 2012
Next Planned Update: 25 March 2017 Plant Layout
General: This involves those pumps whose loss would significantly reduce the
capability of delivering crude or products to major pipelines or marine tanker
terminals.
Spacing Distance, m. Remarks
Basic 45 Spacing allows access for fire fighting and will
minimize damage to pumps in case of fire or explosion
in other equipment.
General: Piping which interconnects plants, or plants and storage vessels, must
be routed such that it will not remain in service through plant areas that are shut
down for turnaround. Pipeways must be outside the dikes protecting any product
or crude oil storage vessels.
Page 24 of 34
Document Responsibility: Loss Prevention Standards Committee SAES-B-055
Issue Date: 25 March 2012
Next Planned Update: 25 March 2017 Plant Layout
General: Liquefied Petroleum Gas (LPG) loading racks for road tank trucks
shall be consolidated at one location at the periphery of the main plant facilities.
This location shall be near an access gate (other than main gate), so that traffic
through the plant is minimized and high-risk areas are avoided. Refer to
SAES-B-070 for further details.
Tank truck loading racks must be provided with adequate space and roadways
for safe truck driving and parking, as well as safe access to and from loading
racks and weight-scales where included.
Spacing Distance, m. Remarks
Basic 60 This spacing allows for dispersion of vapors that may
be released at the rack when making or breaking
connections, or in case of a loading arm failure.
Damage to other equipment in case of a fire at the rack
is also minimized, and vice-versa.
General: This category includes storage vessels (spheres and spheroids, bullets,
dome roof tanks, horizontal storage tanks, etc.) that store fluids with a true vapor
pressure higher than 90 kPa (abs). Releases from this equipment can result in
large vapor clouds. Also, fires associated with such storage are difficult to
handle and constitute a high risk of vessel failure with sudden release of the
entire vessel contents. These vessels shall be located down slope and downwind
from plant areas or other critical facilities or residential areas. There shall be no
other equipment inside the diked areas of these vessels, excepting associated
Page 25 of 34
Document Responsibility: Loss Prevention Standards Committee SAES-B-055
Issue Date: 25 March 2012
Next Planned Update: 25 March 2017 Plant Layout
piping. The vessel shell shall be at least 15 m inside the dike wall, with the
associated equipment, i.e. pumps, at least 7.5 m from outside the dike.
Spacing Distance, m. Remarks
Basic 60 This spacing provides separation from major plant
facilities such as processing areas and buildings.
Protection is also provided for the pressure storage
vessels in case of fire or explosion at other facilities.
From H-2, I-2 60 This distance may be reduced I-2 depending upon the
size of the storage vessel. Refer to SAES-B-005.
From J-2 30 Reduced spacing allowed due to nature of stocks in
atmospheric storage tanks. Refer to SAES-B-005.
General: Low-flash stocks are fluids with true vapor pressure less than
90 kPa(abs) and a flash point under 54°C and any other fluid that may be stored
at temperatures above or within 8°C of its flash point. These normally will be
floating roof tanks. Tanks shall be placed down slope from plants or other
critical facilities or residential areas.
The spacing between the tank shell and the dike shall meet SAES-B-005.
Except for associated piping, there shall not be any equipment within the diked
area of these tanks.
Spacing Distance, m. Remarks
Basic 60 Spacing is based on large tanks and is reasonable to
permit containment of a tank fire and keep it from
involving other facilities. It will also protect the tanks in
case of fires and explosion at other facilities. This is a
maximum spacing, it may be reduced. Refer to
SAES-B-005.
Page 26 of 34
Document Responsibility: Loss Prevention Standards Committee SAES-B-055
Issue Date: 25 March 2012
Next Planned Update: 25 March 2017 Plant Layout
General: High-flash Stocks are fluids having a flash point over 54°C, stored at
temperatures more than 8°C below the flash point. Tanks shall be located
down-slope and down-wind from process areas or other critical facilities or
populated areas. Area within dike of storage vessel must be free of all
equipment other than associated piping. The spacing between the tank shell
and the dike shall meet SAES-B-005.
Spacing Distance, m. Remarks
Basic 30 High-flash stocks as defined represent a reduced fire
hazard, therefore, a reduced spacing is called for as
compared to the low-flash stocks. This spacing
primarily provides for avoiding damage to this tankage
from fire or explosion in adjacent facilities. Spacing
may vary with size of tank. Refer to SAES-B-005.
General: These facilities are critical to the continued operation of the plant or
refinery. They represent constant sources of ignition for any hydrocarbon
releases from plant process areas. They shall, therefore, be placed away from
process areas as far as possible, consistent with operating demands.
Spacing Distance, m. Remarks
Basic 45 Spacing provides protection for these critical facilities
from possible fire or explosion in equipment handling
hydrocarbons. Steam generators which supply less than
25% of the total steam demand for a refinery or other
multiplant facility, or which supply steam only to a
particular plant within that facility, may be located nearer
operating equipment with spacing as for furnaces.
From N-2 30 Reduced spacing allowed since boiler and generating
stations constitute only a minor risk to these type
facilities. Conversely, N-2 facilities do not represent a
hazard to boilers or generating facilities.
From P-2 45 Spacing may be reduced to 30 m if the adjoining
property has only buildings or other facilities affording
little risk to the boiler plant/generating facilities.
Page 27 of 34
Document Responsibility: Loss Prevention Standards Committee SAES-B-055
Issue Date: 25 March 2012
Next Planned Update: 25 March 2017 Plant Layout
General: These are normally high voltage power lines and they shall be routed
away from process areas and tank farms. These power lines are critical to
operations and should be protected from fires or explosions in other facilities, as
these could cause a failure of the main electrical supply.
Spacing Distance, m. Remarks
Basic 60 Minimum spacing to provide protection from fires or
explosions in operating equipment or tankage.
From D-2 - Personnel should be protected from electric shocks per
SAES-B-064.
General: These pumps may well represent the difference between minor
damage by fire or explosion and the loss of an entire process unit or plant or
Page 28 of 34
Document Responsibility: Loss Prevention Standards Committee SAES-B-055
Issue Date: 25 March 2012
Next Planned Update: 25 March 2017 Plant Layout
tankage area.
Spacing Distance, m. Remarks
Basic 45 This spacing is to prevent the main fire pumps from
becoming involved in a fire or explosion occurring in
major plant hydrocarbon handling equipment.
Special purpose fire pumps, such as those for
special risk protection systems, may be spaced
closer to facilities not being protected by this system.
From Q-2 15 Reduced spacing permitted since exposure to fire
pumps can be controlled.
Page 29 of 34
Document Responsibility: Loss Prevention Standards Committee SAES-B-055
Issue Date: 25 March 2012
Next Planned Update: 25 March 2017 Plant Layout
General: The design basis for spacing has to take into account the amount of
heat liberated at the flare and the amount of heat that can be tolerated by
personnel and equipment for various situations. The spacings given in Figure 2
are basic minimums; the actual spacings used shall be those resulting from
design calculation on the particular flare under consideration. Refer to
SAES-F-007 for details.
General: These spacings are bare minimums. They are primarily intended to
reduce the effects of smoke on personnel and equipment in nearby facilities and
on residential or public areas. The radiant heat effects on personnel and equipment
must be included in spacing calculations, as required by SAES-F-007.
Page 30 of 34
Document Responsibility: Loss Prevention Standards Committee SAES-B-055
Issue Date: 25 March 2012
Next Planned Update: 25 March 2017 Plant Layout
General: For wells, see SAES-B-062 for details on how to calculate the
minimum required spacing.
Page 31 of 34
Document Responsibility: Loss Prevention Standards Committee SAES-B-055
Issue Date: 25 March 2012
Next Planned Update: 25 March 2017 Plant Layout
General: Residential areas should be kept free of hazards due to oil and gas
handling installations. See paragraph 9.6.
Spacing Distance, m. Remarks
Basic 500 Under normal weather conditions, this minimum
spacing from a hydrocarbon processing plant area
perimeter fence provides a residential area or main
office building with a significant reduction in risk from
hazards from oil and gas handling installations.
From D-2 - Standard SAES-B-064 applies.
From U-2 - Standard SAES-B-062 applies.
Page 32 of 34
Document Responsibility: Loss Prevention Standards Committee SAES-B-055
Issue Date: 25 March 2012
Next Planned Update: 25 March 2017 Plant Layout
Exchangers Operating
Emergency Valves for
Shutoff, Isolation, etc.
(internally insulated)
o
Disengaging Drums
o
Satellite Instrument
Gas Compressors
o
conjunction with the Onsite Spacing
Control Buildings
Onsite Pipeways
Critical Electrical
Cooling Towers
above 315 C
Flammables
Switchracks
Guide for Figure 1. BASIC SPACING
o
FACILITY
Buildings
Materials
Vessels
Boilers
315 C
Drums
(far left-hand column) is the distance to
o
be maintained if not indicated in the
chart.
o
5 Pumps above 315 C I-1 30 15 15 7.5 7.5 7.5 7.5 7.5 1.5 5 15 5 5 5 7.5 5 5 5 5 5 25 7.5 5 I-1
3 Pumps Handling Flammable Materials J-1 30 15 15 7.5 7.5 15 10 7.5 5 1 15 3 3 3 7.5 5 5 3 3 1.5 25 7.5 A J-1
1.5 Drums M-1 30 15 15 7.5 7.5 15 10 7.5 5 3 15 B 1.5 1.5 7.5 5 5 1.5 B 1.5 25 7.5 A M-1
3 Towers and Columns N-1 30 15 15 7.5 7.5 15 10 7.5 5 3 15 3 1.5 3 7.5 5 5 1.5 B 3 25 7.5 A N-1
1.5 Exchangers Operating below 315 oC R-1 30 15 15 7.5 7.5 15 10 7.5 5 3 15 B 1.5 1.5 7.5 5 5 1 B 1.5 25 7.5 A R-1
Page 33 of 34
Document Responsibility: Loss Prevention Standards Committee SAES-B-055
Issue Date: 25 March 2012
Next Planned Update: 25 March 2017 Plant Layout
Refrigerated Storage
Generating Facilities
Chemical Storage
conjunction with the Offsite Spacing
Skimming Ponds
Office Buildings
Oil / Gas Wells
Process Areas
Property Lines
Flash Stocks
Flash Stocks
Guide for Figure 2. BASIC SPACING
Firehouses
FACILITY
Centers
Pumps
(far left-hand column) is the distance to
be maintained if not indicated in the
chart.
7.5 Major Offsite Pipeways D-2 7.5 7.5 7.5 Y 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 W 15 7.5 7.5 15 7.5 15 15 100 500 D-2
150 Burn Pits and Ground Flares T-2 150 150 150 15 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 X V Y T-2
Page 34 of 34