Electromagnetic compatibility
EMC emitted interference
Inputs/ Outputs
Product function
● Parameterizable inputs Yes
● Parameterizable outputs Yes
Number of inputs 4
● for thermistor connection 1
Number of digital inputs
● with a common reference potential 4
Digital input version
● Type 1 acc. to IEC 61131 Yes
Input voltage at digital input at DC rated value 24 V
Number of outputs 3
Number of outputs as contact-affected switching 3
element
Number of semiconductor outputs 0
Wire length for digital signals maximum 300 m
Wire length for thermistor connection
● with conductor cross-section = 0.5 mm² 50 m
maximum
● with conductor cross-section = 1.5 mm² 150 m
maximum
● with conductor cross-section = 2.5 mm² 250 m
maximum
Communication/ Protocol
● Protocol is supported PROFIBUS DP protocol Yes
● Protocol is supported PROFINET IO protocol No
● Protocol is supported PROFIsafe protocol Yes
● Protocol is supported Modbus RTU No
● Protocol is supported EtherNet/IP No
Connections/Terminals
Product function
● removable terminal for auxiliary and control Yes
circuit
Type of electrical connection
● for auxiliary and control current circuit screw-type terminals
Type of connectable conductor cross-sections
● solid 1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²)
● finely stranded with core end processing 1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
● at AWG conductors solid 1x (20 ... 12), 2x (20 ... 14)
● at AWG conductors stranded 1x (20 ... 14), 2x (20 ... 16)
Tightening torque
● with screw-type terminals 0.8 ... 1.2 N·m
Tightening torque [lbf·in]
● with screw-type terminals 7 ... 10.3 lbf·in
Ambient conditions
Installation altitude at height above sea level
● 1 maximum 2 000 m
● 2 maximum 3 000 m
● 3 maximum 4 000 m; No protective separation at 40 °C
Ambient temperature
● during operation -25 ... +60 °C
● during storage -40 ... +80 °C
● during transport -40 ... +80 °C
Environmental category
● during operation acc. to IEC 60721 3K6 (no formation of ice, no condensation, relative humidity 10 ...
95%), 3C3 (no salt mist), 3S2 (sand must not get into the
devices), 3M6
● during storage acc. to IEC 60721 1K6 (no condensation, relative humidity 10 ... 95%), 1C2 (no salt
mist), 1S2 (sand must not get into the devices), 1M4
● during transport acc. to IEC 60721 2K2, 2C1, 2S1, 2M2
Relative humidity
● during operation 5 ... 95 %
Contact rating of auxiliary contacts according to UL B300 / R300
Short-circuit protection
Design of short-circuit protection
● per output Fuse links: gG 6 A, quick-response 10 A (IEC 60947-5-1),
miniature circuit-breaker C char.: 1.6 A (IEC 60947-5-1) or 6 A
(I_K < 500 A)
Galvanic isolation
Design of the electrical isolation Protective separation in accordance with IEC 60947-1 for all
circuits
Certificates/approvals
other
PROFINET- PROFIsafe-
Certification Certification
Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
http://www.siemens.com/industrial-controls/catalogs
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3UF7010-1AU00-0
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3UF7010-1AU00-0
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3UF7010-1AU00-0
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3UF7010-1AU00-0&lang=en
45 119
52.1
111.2
OUT 3
IN2
24V
IN1
IN3
IN4
A1
10
9
6
-K
Sys
DEVICE
Sys
BUS Logic
GEN. FAULT
PROFIBUS DP
SIMOCODE PRO
PROFIBUS DP
A2
T1
T2
B
A
OUT1
OUT2
OUT3
SPE