Sitop Pse200U: Electronic Protection of 24 V DC Load Circuits With Fast Fault Detection
Sitop Pse200U: Electronic Protection of 24 V DC Load Circuits With Fast Fault Detection
Sitop Pse200U: Electronic Protection of 24 V DC Load Circuits With Fast Fault Detection
SITOP PSE200U
Electronic protection of 24 V DC load circuits
with fast fault detection
Edition
Brochure 01/2017 siemens.com/sitop
© Siemens AG 2017
The SITOP PSE200U selectivity module distributes the SITOP PSE200U - optimized for switched-mode power
load current across several 24 V DC load circuits and supply units
monitors them reliably for overload and short-circuit
conditions. The electronics permit brief current peaks The SITOP PSE200U is specially designed to protect 24 V
caused, for example, by high inrush currents, but iso- DC individual load circuits supplied by switched-mode
late 24 V DC load circuits in the event of an extended power supplies. Individual setting of the tripping current
overload. This is ensured even on high-resistance lines allows optimum adaptation to the respective load circuit.
and in the case of "creeping" short-circuits. In such Engineering effort is minimal since the switch-off charac-
cases, miniature circuit breakers fail to trip, or trip too teristic always guarantees reliable tripping – even with
late, even if the power supply unit could deliver the high line impedances that limit the short-circuit current.
required tripping current. The SITOP PSE200U continues SITOP PSE200U reliably disconnects the faulty path as soon
to supply 24 V DC to the load circuits not affected by an as the current exceeds the set value by a small amount.
overload – a feature which avoids a possible total sys-
tem failure. The single-channel signaling version facili- Immediate switch-off increases plant availability
tates fast, channel-specific fault localization via just
one digital input at the PLC. SITOP PSE200U also has another important function: The
electronics continuously monitor the 24 V DC input volt-
Miniature circuit breakers with high current consumption age. As soon as the 24 V DC threatens to fail, the path
with a higher current than the set current is disconnected
Miniature circuit breakers are often still used for the selec- immediately. All other circuits continue to be supplied
tive protection of 24 V DC load circuits. In many cases, without interruption. Even PLCs, which can only bridge
however, when interacting with switched-mode power power failures for a few milliseconds, continue to run
supply units, they do not offer reliable protection. They without problems.
require several times the rated current in order to trip
within a few milliseconds. Because stabilized power sup-
plies limit their output current electronically when there is
a critical overload, the tripping current is not always guar- Shutdown characteristic
anteed. This can cause the 24-V supply to break in and the
PLC to go to Stop. Even if the power supply unit could sup- 100.0 sec
ply the current, immediate tripping is not necessarily
10.0 sec
assured, because with this high current requirement, the
Tripping time
5.0 sec
line resistance can no longer be neglected. It prevents the 1.0 sec
required tripping current from flowing. Therefore fast trip-
ping is only possible up to certain cable lengths and start- 0.1 sec
0.1 sec
ing from larger cable cross-sections. In addition to the line
resistance, the overall circuit design (e.g. contact resis- 0.0 sec
0% 50 % 100 % 150 %
tances at terminals) must be taken into consideration
when configuring miniature circuit breakers. Load current I/I threshold
1)
Versions with NEC Class 2: 110%
2
© Siemens AG 2017
G_KT01_XX_00122
3-color LEDs for fast on-site fault localization
Simple commissioning thanks to manual switch on/
off of load circuits using reset button 24 V DC
Outputs 1-4,
Versions
0.5...3 A/ 3...10 A/ Common signaling contact
0.5...3 A according to NEC Class 2 or single-channel signaling
3
© Siemens AG 2017
By switching on the outputs sequentially, the inrush cur- The SITOP PSE200U module with single-channel signaling
rent that the power supply has to provide is considerably requires only one digital input for signaling the switched-
reduced. This avoids the danger of a voltage dip which off output to the controller. Evaluation is carried out using
could result in disturbances within the plant. A power sup- a SIMATIC S7 or SIMOTION function block, or in the LOGO!
ply with a lower rated output current can possibly also be software, enabling simple integration into the diagnostics
used. The connection delay can be set to 0 ms (all outputs and host control or HMI systems.
simultaneously), 25 ms or 100 ms, or on a load-optimized
basis. The delay time between the outputs is identical.
Only if the setting "load-optimized" is selected, does the SITOP PSE200U with single-channel signaling:
next output not switch until the previous one is below the Cyclic signaling of channel states
set value.
OUT 1
Signal OUT 2 1 digital
output OUT 3 input
OUT 4
Output current
Current monitor
MP: 1 V = 1 A
0V
4
© Siemens AG 2017
Technical specifications New: NEC Class 2 version New: NEC Class 2 version
SITOP PSE200U with common signaling contact SITOP PSE200U with single-channel signaling
Article number 6EP1961-2BA11 6EP1961-2BA21 6EP1961-2BA31 6EP1961-2BA41
... with NEC Class 2 6EP1961-2BA51 6EP1961-2BA61
Input
Rated voltage Vin rated 24 V DC
Voltage range 22 ... 30 V DC
Input current 40 A max.
Output
Rated voltage Vout rated Typ. Uin – 0.2 V
Number of outputs 4 4 4 4
Rated current Iout rated up to +60 °C 3A 10 A 3A 10 A
per output
Setting range per output 0.5 ... 3 A 3 ... 10 A 0.5 ... 3 A 3 ... 10 A
Set time delay 0 ms, 25 ms or 100 ms (identical between outputs) or
load-optimized (as soon as the previous output is less than the set rated value)
Efficiency at Vout rated , Iout rated Typ. 99%
Protection and monitoring
Status displays Three-color LED per output: green for output connected, yellow for output manually disconnected,
red for output disconnected due to overload/short-circuit
Signal output Common signaling contact, changeover contact, Single-channel signaling: cyclic signaling for
contact rating 24 V/0.5 A channel-specific evaluation using SIMATIC S7
function block
General data
Emitted interference EN 61000-6-3, EN 55022 Class B
Noise immunity EN 61000-6-2
Ambient temperature range 0 ... +60°C (-25 to +85°C transport/storage)
Mounting DIN rail EN 60715 35 x 7.5/15
Dimensions 72 × 80 × 72 72 × 80 × 72 72 × 80 × 72 72 × 80 × 72
(width × height × depth) in mm
Weight Approx. 170 g Approx. 220 g Approx. 170 g Approx. 220 g
Accessories Device identification label 20 mm x 7 mm, 340 units. Article No. 3RT1900-1SB20
1)
6EP1961-2BA51 and 6EP1961-2BA61: GL and ABS available soon
5
© Siemens AG 2017
siemens.com/sitop