Control Module
Intelligent/Addressable Devices
General
The FCM-1 Addressable Control Module
provides Notifier intelligent fire alarm
control panels a circuit for Notification
Appliances (horns, strobes, speakers, etc.)
Addressability allows the FCM-1 to be
activated, either manually or through panel
programming, on a select (zone or area of
coverage) basis.
Features
• Built-in type identification automatically
identifies these devices to the control
panel. CLIP loops). It responds to regular polls
• Internal circuitry and relay powered from the control panel and reports its type
directly by two-wire SLC loop. The FCM-1 and status, including the
module requires power (for horns, open/normal/short status of its
strobes, etc.), or audio (for speakers). Notification Appliance Circuit (NAC). The
• Integral LED “blinks” green each time a LED blinks with each poll received. On
communication is received from the command, it activates its internal relay. The
control panel and turns on in steady red FCM-1 supervises notification or control
when activated. circuits.
• LED blink may be deselected globally
(affects all devices). Upon code command from the panel, the
• High noise immunity (EMF/RFI). FCM-1 will disconnect the supervision and
• The FCM-1 may be used to switch connect the external power supply in the
24-volt NAC power, audio (up to 70.7 proper polarity across the load device. The
Vrms). disconnection of the supervision provides
• Wide viewing angle of LED. a positive indication to the panel that the
• Direct-dial entry of address 01– 159 for control relay actually turned ON. The
FlashScan loops, 01 – 99 for CLIP mode external power supply is always relay
loops. isolated from the communication loop so
• Compatible with FlashScan® and CLIP that a trouble condition on the external
protocol systems power supply will never interfere with the
rest of the system.
Applications
The FCM-1 is used to switch 24 VDC Rotary switches set a unique address for
audible/visual power or high-level audio each module. The address may be set
(speakers). before or after mounting. The built-in
Operation TYPE CODE (not settable) will identify the
module to the control panel, so as to
Each FCM-1 uses one of 159 possible differentiate between a module and a
module addresses on a SLC loop (99 on sensor address.
Ordering Information
FG-05-024 FCM-1 Single intelligent control (monitored output) module