Iom Daikin Ahu DDM Fuw DDW
Iom Daikin Ahu DDM Fuw DDW
Iom Daikin Ahu DDM Fuw DDW
Please read this instruction thoroughly before using your units. Properly keep it.
The above figures are for reference only. Please refer to the object.
1
DDM1401-A1
Part No.: M08019001007
Contents
1 Safety Precautions .....................................................................................................................3
2 User Instructions........................................................................................................................6
3 General........................................................................................................................................7
3.1. Modular Air Handling Unit............................................................................................................. 7
3.2. Cabinet Fan Coil Unit..................................................................................................................... 7
4 Installation ..................................................................................................................................9
4.1. Shipment......................................................................................................................................... 9
4.2. Acceptance ..................................................................................................................................... 9
4.3. Rigging............................................................................................................................................ 9
4.4. Storage............................................................................................................................................ 9
4.5. Assembly and Installation............................................................................................................. 9
4.6. Onsite Installation........................................................................................................................ 10
4.7. Ceiling Installation ....................................................................................................................... 12
4.8. Panel Holing*................................................................................................................................ 13
4.9. Pipeline Connection and Usage of Coils................................................................................... 13
5 Wiring Connection.................................................................................................................... 15
5.1. Lighting Connection*................................................................................................................... 15
5.2. Motor Cabling............................................................................................................................... 15
5.3. Motor Line Connection................................................................................................................ 15
5.4. Electrical Heating Connection* .................................................................................................. 17
5.5. Other Connection Lines*............................................................................................................. 18
6 Debugging and Commissioning.............................................................................................. 19
6.1. Debugging .................................................................................................................................... 19
6.2. Commissioning ............................................................................................................................ 19
7 Regular Maintenance ............................................................................................................... 20
7.1. Mixing Box*................................................................................................................................... 20
7.2. Filter Section*............................................................................................................................... 20
7.3. Coil Section .................................................................................................................................. 20
7.4. Fan and Motor .............................................................................................................................. 21
7.5. Silencer Section*.......................................................................................................................... 23
7.6. Electric Heater Section* .............................................................................................................. 23
7.7. Checking Section* ....................................................................................................................... 23
7.8. Others............................................................................................................................................ 23
8 Maintenance Plan of Units (Recommend)............................................................................... 24
2
9 Trouble-shooting ...................................................................................................................... 25
10 After-sales Service Warranty ................................................................................................... 27
10.1. After-sales Service ................................................................................................................. 27
10.2. Warranty .................................................................................................................................. 27
11 Repair and Maintenance Record ............................................................................................. 28
Appendix 1: Dimensions For DDW Frameless Unit ...................................................................... 29
Appendix 2: Dimensions For DDW Frame Unit ............................................................................. 31
Appendix 3: Dimensions For FUW-H/V Unit .................................................................................. 33
Appendix 4: Dimensions For FUW-A Unit...................................................................................... 35
Bulletin illustration covers the general appearance of our products at the time of publication and we reserve
the right to make change in design and construction any time without notice.
3
1 Safety Precautions
Caution: Measures need to be followed to avoid unit damages and personal injuries.
WARNING
Installation and maintenance should be The accessory can be installed by
performed only by professionals that are professionals that are entrusted.
entrusted by the supplier. Select the optional components designed
Installation and maintenance are to be by manufacturer. Improper selection may
performed only by trained and qualified cause electric chock, fire, or other
accidents.
personnels.
CAUTION
PRECAUTIONS BEFORE INSTALLING
The cold/warm water used by the unit Do not install the unit in terrible
must meet the standard. environment.
Using unqualified water may affect the life Do not install the unit near the exhaust outlet of
and performance of the unit. In severe case, a toilet, or a hospital operating room, or near
it may cause leakage. the processing facilities of sewers, because
The requirement of water quality refers to filth, oil stain, salinity or large amount of
Chapter 4. sulfurized gas may cause the corrosion of the
components.
Do not use lubricating oil or anti-freezing Do not install the unit in a place where
solution of wrong types and version. combustible gas leakage may happens. If the
Otherwise, it may cause damage to the unit. gas leaks and gathers around the unit, there is
a risk of explosion and fire accidents.
If the unit is installed near the hospital,
telecommunication station or other similar
Configure the residual current circuit places, take proper measures to safeguard the
breaker correctly. unit. Frequency transformer, house generator,
Install the residual current circuit breaker in high frequency medical equipment and radio
accordance with electrical regulations. Error communication device may cause the
installation may cause electric shock or other air-conditioner to run abnormally or quit
accidents. working.
Civilized construction
Fan and motor must be equipped with Stack materials in specified positions on site
overload protection. Otherwise, it may and take proper measures to protect the
cause fire or other accidents. materials from moisture, rain, and snow if they
are stacked open.
Do not touch the sharp plate and heat During simultaneous operations in the same
exchange edges. room, all construction operators must respect
each other and work properly and
cooperatively.
Establish a civilized construction system. The
Ensure the drainage is smooth. construction team leader is responsible for
Improper drainage may cause poor drainage civilized construction in the working area.
so as to dampen the device.
5
CAUTION
IINSTALLATION AND PRECAUTION
Do not use power switch to start or stop Stop the unit and cut off the power
the operation of unit directly. before maintenance.
Such error operation may cause electric After shutdown, the blades may still turn for
shock or fire accident. one to three minutes. Do not force the
blades to stop by hands or other objects.
Do not change the set value of the safety Proceed with the maintenance work after
protector. the blades stop completely. The unit can be
Otherwise, it may cause fire accident or installed and maintained only by
explosion. professionals. Otherwise, it may cause
electric shock, accidental injuries and other
Do not use fuse beyond the normal accidents.
capacity.
Replacing the fuse with wire may endanger Empty the remaining water inside the
the device or cause fire accident. unit when it stops working for a long
time.
Do not short-circuit the security device to When the unit is not operating, ensure that
start the unit. the water pipe is full of antifreeze or empty
This may cause damage to the unit or fire the remaining water inside the pipe.
and explosion accident. Otherwise, the coil may be cracked to leak
water due to frost.
2 User Instructions
Check
All units should be carefully inspected for damage when received and check whether all the components are
complete. Damage or loss of parts in shipment should be reported to the dealer in written form as soon as
possible.
Precautions
Precautions in chapter one are of great importance to follow.
These precautions should be at hand for reference at any time.
7
3 General
This manual has been prepared as a guard for installing, operating and maintaining the modular air handling
unit and cabinet fan coil unit of our company. We have produced a quality product that will effectively meet
your application. However, proper installation, operation, and maintenance procedures must be followed to
realize the full capability and life of the unit.
FUW 020 A - 4 L- A A A E
4 Installation
4.1. Shipment
The units can be delivered as separate section or completely assembled (ASS). For modular air handling unit,
complete knock down shipment (CKD) is needed if the unit is big in size or there is special requirement from
customers.
4.2. Acceptance
Check if the sections, accessories and panels are intact in accordance with packing list before installation. If
there is damage or loss in shipment, please inform the seller in written form as soon as possible.
4.3. Rigging
To prevent damage to unit cabinet, a specific lifting method for offloading the units is recommended as shown
in figure 1. A rod and ropes capable of bearing the weight during hoisting are required. The spreader bars
must be in position to prevent straps or cables from rubbing the frame panel. Ensure stability and balance
when lifting the units and avoid twisting or uneven lifting. Care should be taken to prevent coil connections,
drain pan connection and accessory section from damage.
It is proposed to handle the unit by forklift when it is on flat ground (Figure 2). The forks must only be applied
under the unit base frame or wooden frame and not against the panel. In case when fork of the forklift is too
short then suitable extensions should be used.
Figure 1 Figure 2
4.4. Storage
For external storage prior to installation, the units should be more protected by tarpaulins or similar and to be
protected from dust, rain, snow, constant sun exposure and rodents. Take care of the protection film on the
surface.
Do not stack the unit.
reserve trenches and floor drains around the base to ensure condense water discharge.
e. Drain pipes and traps must be at least same diameter as the drain pan connection. Drain pan must be
level to permit condensation from coil drain freely. See figure 3 for the recommended depth and distance
of drain trap installation. Drain pan are not designed to be walked on.
>=600mm
>=W+100mm
Figure 4
11
50
0
50 0
0 50
50
0 00
10
10
00
Figure 5
f. The design of air duct should abide by local codes and regulations.
g. Ensure that the length of straight duct is at least twice the length of the air outlet. Otherwise, it may cause
pressure drop.
h. The unit should not bear the weight of external pipelines and air ducts.
i. Thermal insulation must be achieved for air ducts.
j. Flexible connection between the unit and external air ducts can avoid vibration. Ensure that the joint is
sealed and treated with proper insulation to prevent condensation on the unit surface due to air leak.
k. Install the air filter before unit commissioning. Check whether the filter element of the air filter is damaged
or contaminated.
l. Provide weather proof and shading devices when the unit is installed outdoors.
m. The transportation sections of units must be closely linked. Otherwise, it may cause air leakage or
condensation. The method of linking between each transportation section is as follows:
Figure 6 Figure 7
12
Figure 8
4.7. Ceiling Installation
Assemble the unit before ceiling operation. Ensure that the components are installed and the sections are
properly connected. The unit should be placed on an integrated channel steel for hoisting, or the unit
performance may be undermined by the inconsistent installation heights.
Roof hoisting is prohibited since the roof cannot bear the weight of the unit.
Ensure that the construction components for ceiling, the integrated channel steel and hoisting rod have
enough strength to meet the standard of operation weight. Determine the position of the hoisting rod and
adjust the fixed screw to keep the unit balanced.
Add a bumper on top to reduce vibrations (Figure 9). A spring bumper is recommended.
Figure 9
13
Figure 10
*For FUW units, there is no need for extra holes as electric wiring is led to the terminal block.
Figure 11
14
f. Install a steam trap at the outlet of steam coil to ensure smooth drainage if a steam coil is used. The
installation of steam pipe must abide by local laws and regulations to ensure that the saturated steam
enters the steam coil which prevents the coil from water hammer.
g. Allow the linkage between inlet water and fan to avoid the coil under-cooling or overheating. The coil
operates only when the fan runs.
h. The designed operation pressure of the coil is 1.6 MPa. Too high pressure will damage the coil.
i. During commission or out running of the unit in the winter, discharge the remaining water in the coil
(system) timely or adopt other methods (for example, add anti-freezing solution) to prevent the coil from crack
in low temperature (for details, refer to the maintenance and preservation of the coil).
Warning: Improper commissioning and maintenance may cause coil crack in low temperature.
j. If the ambient temperature or air inlet temperature is equal to or lower than 2°C, install preheating device
at the air inlet of a fresh air handling unit. In addition, a sealed regulating valve needs to be installed at
the new air inlet. Install anti-freezing switch beside the coil and interlock it to the sealed regulating valve
and the fan. When the unit starts, start the preheating coil or take other measures beforehand to prevent
the coil from cracking in low temperature. And when the unit is running, constantly provide the coil with
warm water with a temperature of no less than 60°C and ensure that the water flow speed inside the coil
is no less than 1 m/s.
k. Water quality requirements: Water softening treatment must be given in advance to prevent scaling in the
heat exchanger which may affect heat exchange effect. Moreover, water without softening treatment may
form scale in the pipe to increase water resistance which will affect water flow and pump work efficiency.
Reference Tendency
Item
value Corrosion Scaling
pH(25℃) 7.5~9.0 ○ ○
Conductivity (25℃) µS/cm <800 ○ ○
-
Benchmark Cl
-
mg(Cl )/L <200 ○
items SO42- mg(SO42-)/L <200 ○
Acid consumption (pH=4.8) mg(CaCO3)/L <100 ○
Full hardness mg(CaCO3)/L <200 ○
Fe mg(Fe)/L <1.0 ○ ○
2- 2-
Reference S mg(S )/L 0 ○
items NH4+ mg(NH4+)/L <1.0 ○
SiO2 mg(SiO2)/L <50 ○
Note: ○ refers to that this factor is related to the tendency of corrosion or scaling
15
5 Wiring Connection
Electric connecting should be compliant with relevant local laws and regulations. Besides, pay attention to the
following:
a. Before connecting, check whether the power supply meets the requirement of the voltage value stipulated
on the of unit nameplate;
b. Set up an independent electrical power supply, power off and overload protection device for each unit.
c. The voltage difference between any two-phrases of power supply should be smaller than 2% of the
nominal voltage.
Figure 15
Figure 13
The following figure is the schematic diagram of motor line connection of FUW series unit. Contact the factory
if the local power supply is not consistent with that shown in the diagram.
Figure 14
17
L1 L1
power supply L2 L2
380V/3N~/50Hz L3 L3
N N
customer must configure PE PE
another contactor
Q1 Q2 Qn
power supply
KM1 KM2 KMn
A B L N
2 4
TH1 TH2
3
Figure 16
a. For each group of electric heater, third-party control cabinet must be configured with another contactor,
cannot share the same contactor which is factory equipped.
b. L, N port on the terminal board TB1 must be supplied with independent 220V single-phase power.
c. Electrical heating high temperature protection and non-wind protection port A and B must be connected in
serial to the control loop of electrical heater.
d. Enable the fan before enable the electrical heater. After the fan starts and a certain air flow is reached,
pressure difference switch will close, L and N power supply loops are connected. The contactor
configured in the electrical heater connection box is connected simultaneously, and the electrical heater is
allowed to operate. However, whether the electrical heater can be powered on and starts to operate is
18
determined by the connection of the contactor in the customer’s control cabinet (the connection of
customer-configured connector is determined by the requirement of hot load capacity and electrical
heating protection A and B loops);
e. Fuse F1 and temperature control switch TH1 are installed on the top of electrical heating zone. Fuse F2
and temperature control switch TH2 are installed near the inlet of fan section. When the fan is running,
the electrical heating is powered down if the protection switches A and B are disconnected. In this case,
Users must check the equipment to ensure that no failure occurs before the electrical heater is started
again.
f. If the fan goes down and the electrical heater is not closed, the trebling protection of DPS. F1 and TH1
will cut L and N power supply loops, and disable electrical heating;
g. If the fan runs in an over-low frequency and the air flow reduces but does not reach the set point of
differential pressure switch, the air supply temperature increases until it reaches the set point of F2 or
TH2. Then, F2 and TH2 protection will cut down L and N power supply loops and disable electrical
heating.
Warning: Electrical heating high-temperature protect and no flow protect switches should be connected to the
control circuit in series. It can not be short circuit. The heating can be turned on only when the fan is work and
the fan can only stop after 3 minutes since the heating off.
*Other sections such as humidifier is available to only modular air handling units.
Warning:
All electrics must be safety grounded, and cannot be connected to neutral instead. Incorrect connection can
cause severe explosion, fire and personal injuries.
A circuit-break device with sufficient capacity must be installed near the inlet power cable. The circuit-break
device must support short-circuit protection and earth-fault protection, and the clearance between open
contacts must be at least 3 mm.
19
6.1. Debugging
a. Detect whether the installation is completed and whether internal sundries are removed;
b. For model with spring isolators, temporary transport brackets are fitted to prevent damage during
shipment. All transport brackets must be removed after installation and adjust the spring’s height
accordingly to ensure the frame is level before commissioning by turn the adjustment nut bolt clockwise
or anti-clockwise. Tighten the bolt after completing adjustment. (Figure 17);
Figure 17
c. Check whether the filter material is damaged or polluted. Install high efficiency particulate air filter after
debugging. User may prepare primary filter for debugging;
d. Check the lubrication of rotatable parts, whether the fan impeller collides with enclosure;
e. Check the tightness of belt (see Figure 20);
f. Check whether the dampers are opened as designed and the locking mechanism is locked securely;
g. Check whether the water system is clean and out of air. Before supplying water, open the vent valve first
and empty the air in the pipeline until water outputs;
h. Avoid coil freezing during the debugging in winter. Constantly supply hot water with an temperature of not
lower than 60°C to the unit coil and ensure that the water flow rate in the coil is not slower than 1 m/s.
Drain all water or add anti-freezing solution if the unit is not to be operated after debugging (for details,
refer to the maintenance and preservation of the coil).
Warning: Improper debugging and maintenance may lead the coil to crack in low temperature.
i. Detect whether the motor insulation is qualified. Measure the motor insulation value before using. Note,
discharge the wind after measurement immediately to avoid electric shock. If the insulation resistance
cannot reach the related standard, dry the wind;
j. Check the power supply voltage and the circuit connection. Inch the motor before officially launch it to
ensure that the turning of the motor and fan is correct (the turning of fan should be consistent with the
arrow direction specified on the fan).
6.2. Commissioning
The unit can be started after the above checking procedure is completed. Check whether the running current
of motor and unit sound is abnormal after the unit starts. Check the air flow, pressure of unit. Adjust the
cooling capacity and humidification amount according to different working conditions. Check whether the fan
speed exceeds the working speed stipulated on the fan nameplate.
The following conditions are not considered abnormal:
Noise: Noise is generated due to high speed air flow and the turning of fan and motor.
Vibration: High speed turning of fan and motor generates vibration.
It is normal that the noise and vibration do not exceed the value specified by relevant standard.
20
7 Regular Maintenance
Perform a good maintenance and preservation can reduce fault of running. The maintenance period of
components see Chapter 8 (Recommend).
*Apply to modular air handling units and certain DDW series units only.
*Apply to modular air handling units and certain DDW series units only.
holding a mirror in front of the discharge from the coil. If water is still being removed, the mirror will
become fogged. Continue to operate the blower until the coil is dry.
d. Bump or jar the coil slightly during the blowing operation, if possible. This will free any water, that may be
trapped and may also dislodge any dirt or scale which can trap water in the coil. Take care not to damage
the coil.
e. Allow the coil to stand for a few minutes after it is first blown out to give the moisture that adhered to the
walls of the tube a chance to accumulate. Blow it out again and if any water comes out, repeat the
blowing operation.
f. Leave drains open and all plugs out until the coil is returned to service.
The steps of washing coil with anti-freezing solution are as follows:
To wash the coil with anti-freezing solution, a centrifugal pump with motor and a running piping holding
anti-freezing solution and its container are required. The lowest temperature decides the concentration of
anti-freezing solution.
a. Shut off the water supply. Open the vents and drains provided to allow the coils to drain as complete as
possible.
b. Complete piping connections to the coil as shown in figure 3. Configure a throttling valve to the loop;
Figure 18
c. With throttling valve and drain valves closed, start the solution pump and operate until air is vented from
coil.
d. Close air vent and open throttling valve about halfway. Circulate solution about 15 minute and then check
the glycol solution strength .
e. If the solution is too weak, add anti-freeze solution to bring it up to desired strength and again circulate
through the coil for about 15 minutes.
f. When the concentration of solution returning from the coils is found satisfactory, shut down the pump and
drain anti-ffreeze from the coil.
g. The same solution can be used for flushing additional coils, providing its concentration is maintained.
rubber blanket, grease lubrication has been added to bearing and it is not required to add lubrication oil.
Fans with bearing pedestal, add lubrication oil through nipple while lubrication oil exceeds the period of
validity. The period of validity depends on grease type, rotate speed and working temperature of bearing.
Regular detect the grease when using. When the grease eliminated is black and thick, which shows the
oxidation of grease, change the lubrication oil and shorten the interval of changing.
The recommended interval is 1000~2000 h.
Note: Use only the lubricating oil with the same brand of the original one. The using of lubricating oil of
another brand may cause bearing invalidation.
d. After running for a period of time, check the service condition of absorber. Determine
whether the absorber can meet the shock absorption requirement according to practical
running condition.
e. Regularly detect the bearing of fan and motor to see whether the bearing is loose. Fix the bolt on the
bearing firmly. Detect the running condition by monitoring abnormal noises and vibrations. Stop the unit
immediately when the abnormality happens. Then, find the cause and solve the problem. Install and
replace the bearing with special tools, instead of knocking or prizing it with brute forces.
f. After running for a period of time, recheck the straightness of pulley and the tension of belt. Adjust and
replace the pulley or belt in necessity.
g. Check whether the side of V pulleys of the fan and motor are on the same plane. Ensure the straightness
of pulleys. Usually, the four-point method can be used to detect and adjust the straightness of pulley. (see
Figure 19)
Figure 19
h. When changing the V belt, use the same brand V belt of the same model and ensure that the ribbon
matches the race of pulley.
i. Detect and adjust the tension of V belt with a recognized belt tension gauge. (see Figure 20)
Measuring method: Measure the span Ls (mm) and calculate the bending ∆L: ∆L(mm) = Ls x 0.016. Extrude
the tension gauge to bend the belt until the bending reaches ∆L. Then, read the tension gauge value and
compare the value with those in the following table. Adjust the belt to a proper tension according to the
comparison result.
Figure 20
23
7.8. Others
For details about other components (such as the humidifier, transducer and heat runner), see the attached
components introductions.
9 Trouble-shooting
Common
Location Possible Causes Solutions
Failure
The impeller is eccentric.
Contact the dealer.
The gap between bearings is too large so
Contact the dealer.
that the connection is loose.
Contact the dealer.
Abnormal The impeller is loose.
Contact the dealer.
sound 1. Impeller The connection between the roller and
Contact the dealer.
bearing is loose.
Fasten the bolt.
The impeller is damaged.
Remove the
The fan fastening bolt is loose.
sundries.
Sundries exist in fan.
Pulley is not fixed on roller.
Fasten the pulley.
V belt is loose, and is adjusted in 48 hours
Adjust the V belt.
after the first running.
Adjust the V belt.
V belt is too tight.
Replace the V belt.
Improper model of V belt is used.
Replace the V belt
Lengths of V belts in a unit where multiple
2. Gearing and make sure all the
V belts are uses are different.
V belts are of the
Fan V pulley and motor V pulley are not
same length.
aligned.
Justify the V pulleys.
V belt is damaged.
Replace the V belt.
Bolts on the motor and those fastening
Fasten the bolt.
the motor cabinet are loose.
Replace the bearing.
Add lubricating oil.
The bearing fails. Fasten the bearing
There is a lack of lubricating oil. cabinet.
The bearing cabinet is loose. Perform
3. Bearing Installation is not straight. re-installation.
Sundries exist in the bearing. Remove the
The bearing is damaged. sundries.
The bearing gets rusty. Replace the bearing.
Remove the rust or
replace the bearing.
Remove the
There are sundries in the volute.
sundries.
4. Fan volute The volute is loose.
Contact the dealer.
The inlet air volute is damaged.
Contact the dealer.
Fasten the accessing
The accessing cables are loose.
cables.
Motor or relay generates hum supply noise.
5. Electrical part Contact the dealer.
Three-phase machine supplies
Supply three-phase
single-phase electricity.
electricity.
Replace the roller.
The roller is bent or deformed.
Fasten the
6. Roller The counterbalance is loose.
counterbalance.
The roller is loose.
Fasten the roller.
Air pipe is too small. Adjust the air pipe.
7. Excessive wind Static pressure is lower than design value Adjust the system.
speed in practice. Enlarge the opening of
The opening of air valve is small. the air valve.
26
Enquiry
Any question about after-sales service please contact distributor.
10.2. Warranty
A warranty application form is attached.
The dealer will give you the warranty application form after filling in necessary items.
Please keep warranty application form after checking the content.
Warranty Period
The product is warranted for one year since the date of purchase. For details, see the warranty application
form.
During the guarantee time, any services are free if presented warranty application Otherwise, you will be
charged for the costs.
28
The fault diagnosis and troubleshooting process should be described in details as possible.
For details about troubleshooting, refer to Chapter 9 “Common Failure and Solution of Unit".
Stop running the unit and cut the power when a failure is unclear. Consult the local dealers before further
processing.
Please properly keep the record.
Model: __________________________
Factory Number:___________________________
10
28.5
28.5
Q
L Q
L
F S D S
F D
N
N
F S D S
A
F D M
A M+60
M Air Vent G E
M+60
Air Vent G E
Water Outlet
40
H
Water Outlet
K
C
H
E
C
Water Inlet
E
Water Inlet
G
I
G
I
P
B 90
40 B 90
50
DDW080H 1680 1150 800 473 407 532 97 237 498 128 109 82.5 137.5 1588 660 1800 1093 DDW250H 2400 1310 1430 50 456 559 481 111 100 309 1104 143 124 110 110 137.5 2307 1290 2520 1253
DDW300H 2766 1646 1549 63 449 569 569 278 203 --- 1167 191 154 140 110 137.5 2683 1396 --- ---
DDW350H 2766 1646 1709 63 449 569 569 278 203 --- --- 185 164 150 110 137.5 2683 1556 --- ---
DDW400H 2926 1646 1869 63 500 638 638 266 200 --- --- 182 174 160 110 137.5 2843 1716 --- ---
DDW450H 2926 1646 2029 63 500 638 638 262 200 --- --- 182 174 160 110 137.5 2833 1876 --- ---
Note: Air outlets with dotted lines are for units with fan top outlet.
FI* and TI* means the fan discharge arrangement.
30
3. Single-fan Vertical Unit 4. Double-fan Vertical Unit
45 J J 45
Q
Q
L
L
40
G D F E
40
G D N D F E
Air Vent
Air Vent
Water Outlet
C
C Water Outlet
K
H
K
Water Inlet
Water Inlet
I
I
B 90
63
B 90 A Condensation Pipe R1-1/4
63
A
Condensation Pipe R1-1/4
Dimension L W H Outlet Dim Pipe Fix Dim Inlet Dim Dimension L W H Outlet Dim Pipe Fix Dim Inlet Dim
Q Q L L Q Q L L
Model A B C D E F G H I J K Model A B C D E F G N H I J K
(4R) (6R) (4R) (6R) (4R) (6R) (4R) (6R)
DDW040V 980 650 1283 333 292 149 195 498 127 181 181 82.5 137.5 888 655 DDW150V 2090 900 1673 473 407 151 167 382 736 138 194 180 110 137.5 1997 902
DDW050V 1140 650 1343 397 343 86 267 498 129 180 180 82.5 137.5 1048 649 DDW180V 2240 900 1923 430 481 107 269 342 863 137 196 182 110 137.5 2147 1035
DDW060V 1210 650 1403 397 343 93 335 561 128 179 179 82.5 137.5 1118 709 DDW200V 2320 900 1983 559 481 112 140 465 926 137 204 190 110 137.5 2227 1095
DDW080V 1320 810 1613 473 407 88 329 688 132 177 177 82.5 137.5 1228 842 DDW250V 2670 900 2043 559 481 88 267 456 976 141 193 179 110 137.5 2577 1155
DDW100V 1390 900 1853 559 481 114 259 815 129 189 189 82.5 137.5 1297 965
DDW120V 1530 900 1923 559 481 115 337 879 130 179 179 82.5 137.5 1437 1035
31
25
Q
25
L 137
L
F S D S
N
N
G
Air Vent 40 E Water Outlet
G
E Water Outlet
40
Air Vent
K
C
H
K
C
E
G
G
I
P
B 90 B 90
50
DDW030H 1050 1000 650 333 292 286 393 512 320 158 82.5 137.5 958 510 1170 950 DDW120H 1690 1170 1085 50 292 375 407 102 508 658 752 164 137 137 82.5 137.5 1598 910 1810 1120
DDW040H 1080 1100 765 398 344 235 445 557 434 164 82.5 137.5 988 590 1200 1050 DDW150H 1940 1170 1215 50 292 375 407 223 508 658 863 172 150 137 110 137.5 1850 1040 2060 1120
DDW050H 1250 1060 765 398 344 319 445 574 434 164 82.5 137.5 1158 625 1390 1010 DDW180H 2120 1310 1275 50 341 432 481 165 586 785 926 172 150 137 110 137.5 2028 1100 2240 1260
DDW060H 1320 1150 839 473 407 324 508 646 498 164 82.5 137.5 1228 660 1440 1100 DDW200H 2300 1310 1275 50 456 559 481 107 586 805 926 172 150 137 110 137.5 2207 1100 2420 1260
DDW080H 1680 1150 839 473 407 530 508 646 498 164 82.5 137.5 1588 660 1800 1100 DDW250H 2400 1310 1465 50 456 559 481 111 586 805 1104 178 150 137 110 137.5 2307 1290 2520 1260
DDW300H 2766 1646 1549 63 450 569 569 277 772 891 1167 191 152 137 110 137.5 2683 1390 --- ---
DDW350H 2766 1646 1709 63 450 569 569 277 772 891 --- 185 152 138 110 137.5 2683 1550 --- ---
DDW400H 2926 1806 1869 63 500 638 638 271 841 1046 --- 185 152 138 110 137.5 2827 1710 --- ---
Note: Air outlets with dotted lines are for units with fan top outlet.
DDW450H 2926 1806 2029 63 500 638 638 271 841 1046 --- 185 152 138 110 137.5 2827 1870 --- ---
FI* and TI* means the fan discharge arrangement.
32
3. Single-fan Vertical Unit 4. Double-fan Vertical Unit
J
137
J
LQ
40
D G E F
40
D N D G E F
Water Outlet
Water Outlet
Air Vent
Air Vent
C
H
H
K
K
Water Inlet
Water Inlet
63
63
I
I
A 90 B
A 90 B
Condensation Pipe R1-1/4
Condensation Pipe R1-1/4
1. Horizontal Unit
44 J
2. Single-fan Vertical Unit
55
F D
30
82
L
R
E
N
N
Hanging Holes 4-φ12
F S D S J
B 26 M
M-50 Air Vent Terminal Box Water Inlet Water Outlet
38
M
K
C
E
G
Terminal Box
I
35
X A 50
C
Table 1 Water Outlet
K
Water Inlet
Unit: mm
145
81
Dimension L W H Outlet Dim Pipe Fix Dim Inlet Dim Hanging Hole Dim
G T L 78 A
B 50
Model A B C D S E F G X H I T L(4R) L(6R) J K Q R M N R
Condensation Pipe R1-1/4
FUW020H 950 800 468 - 238 265 170 326 30 294 118 266 66 110 680 393 25 198 940 554
FUW030H 950 1040 468 - 302 265 313 326 30 294 118 266 66 110 920 393 25 198 1180 554 Table 2 Unit: mm
FUW040H 950 1300 468 180 235 265 244 326 40 294 118 266 66 110 1180 393 25 198 1440 554
Hanging
Dimension L W H Outlet Dim Pipe Fix Dim Inlet Dim Length
FUW050H 950 1550 468 238 301 265 244 326 40 294 118 266 66 110 1430 393 25 198 1690 554 Hole Dim
FUW060H 950 1800 468 238 301 265 367 326 40 294 118 266 66 110 1680 393 25 198 1940 554 Model A B C D E F H G L(4R) L(6R) T(4R) T(6R) J K R M N
FUW080H 1000 1800 606 242 311 343 349 407 40 392 118 303 138 138 1696 538 35 132 1940 755 FUW040V 935 585 1082 335 293 200 446 182 66 110 236 192 840 592 1055 968 520
FUW100H 1000 2180 606 242 311 343 658 407 40 392 118 303 138 138 2076 533 35 132 2320 755 FUW050V 1135 655 1320 395 341 254 546 152 66 110 326 282 1040 692 1255 1168 590
FUW120H 1050 2270 697 291 376 407 614 469 40 456 118 303 138 138 2164 612 35 132 2410 848 FUW060V 1135 655 1320 395 341 254 546 152 66 110 326 282 1040 692 1255 1168 590
FUW150H 1050 2490 723 381 474 407 580 470 40 519 118 303 138 138 2386 648 35 132 2630 848 Note: Upward table “4R” means 4 rows and “6R” means 6 rows.
Note: Upward table “4R” means 4 rows and “6R” means 6 rows.
If D value is“-”means single-fan unit which only has one outlet.
34
3. Single-fan Vertical Unit 4. Double-fan Vertical Unit
F D
102
225 S D S
105
24
24
E
E
N
N
J 1980
20 M 25 M
44
Terminal Box
Terminal Box
Water Outlet
C
C
Water Outlet
H
K
Water Inlet Water Inlet
269
269
189
176
G T L P 200 Q 200 P 482 T L P 200 Q 200
B 50 A 83 B 50 A 72
R
Condensation Pipe R1-1/4
R
Condensation Pipe R1-1/4
L L T T L L T T
Model A B C D E F H G J K R M N P Q Model A B C S D E H J K L M N P Q
(4R) (6R) (4R) (6R) (4R) (6R) (4R) (6R)
FUW080V 1350 736 1676 471 404 281 720 182 83 137 343 288 1256 873 1493 1400 675 197 500 FUW180V 2124 955 2070 476 382 406 1077 83 137 224 180 2032 1253 2247 2175 907 334 1003
FUW100V 1350 736 1676 471 404 281 720 182 83 137 343 288 1256 873 1493 1400 675 197 500 FUW200V 2124 955 2070 476 382 406 1077 83 137 224 180 2032 1253 2247 2175 907 334 1003
FUW120V 1774 956 2036 561 482 483 950 480 83 137 228 184 1680 1112 1902 1826 907 334 655 FUW250V 2476 955 2191 561 454 478 1077 83 137 224 180 2379 1253 2597 2525 907 660 701
FUW150V 1774 956 2036 561 482 483 950 480 83 137 228 184 1680 1112 1902 1826 907 334 655
Note: Upward table “4R” means 4 rows and “6R” means 6 rows.
Note: Upward table “4R” means 4 rows and “6R” means 6 rows.
35
Dimension W Inlet Dim Outlet Dim Hanging Hole Dim Dimension W Inlet Dim Outlet Dim Hanging Hole Dim
Model A B C D Model A B C D E
FUW015A 750 540 235 667 FUW030A 1220 1010 265 170 1137
FUW020A 910 700 315 827 FUW035A 1370 1160 320 210 1287
FUW025A 1070 860 395 987 FUW040A 1520 1310 330 340 1437