Abb Inverter Arabic
Abb Inverter Arabic
Abb Inverter Arabic
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range of product Altivar 71
Product or component type Variable speed drive
Product specific application Complex, high-power machines
Component name ATV71
Motor power kW 22 kW at 380...480 V 3 phases
Motor power hp 30 hp at 380...480 V 3 phases
Motor cable length <= 100 m Shielded cable
<= 200 m Unshielded cable
[Us] rated supply voltage 380...480 V (- 15...10 %)
Network number of phases 3 phases
Line current 42 A for 480 V 3 phases 22 kW / 30 hp
50 A for 380 V 3 phases 22 kW / 30 hp
EMC filter Integrated
Assembly style With heat sink
Variant Without remote graphic terminal
Apparent power 32.9 kVA at 380 V 3 phases 22 kW / 30 hp
Prospective line Isc <= 22 kA, 3 phases
Nominal output current 40 A at 4 kHz 460 V 3 phases 22 kW / 30 hp
48 A at 4 kHz 380 V 3 phases 22 kW / 30 hp
Maximum transient current 72 A for 60 s 3 phases 22 kW / 30 hp
79.2 A for 2 s 3 phases 22 kW / 30 hp
Output frequency 0.1...599 Hz
Nominal switching frequency 4 kHz
Switching frequency 1...16 kHz adjustable
4...16 kHz with derating factor
Asynchronous motor control profile Voltage/Frequency ratio (2 or 5 points)
Sensorless flux vector control (SFVC) (voltage or current vector)
Flux vector control (FVC) with sensor (current vector)
ENA (Energy adaptation) system for unbalanced loads
Type of polarization No impedance for Modbus
2
Discrete output type R1A, R1B, R1C configurable relay logic NO/NC, electrical durability 100000 cycles
R2A, R2B configurable relay logic NO, electrical durability 100000 cycles
Minimum switching current Configurable relay logic 3 mA at 24 V DC
Maximum switching current R1, R2 on resistive load, 5 A at 250 V AC, cos phi = 1,
R1, R2 on resistive load, 5 A at 30 V DC, cos phi = 1,
R1, R2 on inductive load, 2 A at 250 V AC, cos phi = 0.4,
R1, R2 on inductive load, 2 A at 30 V DC, cos phi = 0.4,
Discrete input number 7
Discrete input type LI6 : switch-configurable 24 V DC with level 1 PLC, impedance: 3500 Ohm
PWR : safety input 24 V DC, impedance: 1500 Ohm conforming to ISO 13849-1 level d
LI1...LI5 : programmable 24 V DC with level 1 PLC, impedance: 3500 Ohm
LI6 : switch-configurable PTC probe 0...6, impedance: 1500 Ohm
Discrete input logic LI1...LI5 positive logic (source), < 5 V (state 0), > 11 V (state 0)
LI1...LI5 negative logic (sink), > 16 V (state 0), < 10 V (state 0)
LI6 (if configured as logic input) positive logic (source), < 5 V (state 0), > 11 V (state 0)
LI6 (if configured as logic input) negative logic (sink), > 16 V (state 0), < 10 V (state 0)
Acceleration and deceleration ramps Linear adjustable separately from 0.01 to 9000 s
S, U or customized
Automatic adaptation of ramp if braking capacity exceeded, by using resistor
Braking to standstill By DC injection
Protection type Drive against exceeding limit speed
Drive against input phase loss
Drive break on the control circuit
Drive input phase breaks
Drive line supply overvoltage
Drive line supply undervoltage
Drive overcurrent between output phases and earth
Drive overheating protection
Drive overvoltages on the DC bus
Drive short-circuit between motor phases
Drive thermal protection
Motor motor phase break
Motor power removal
Motor thermal protection
Insulation resistance > 1 mOhm at 500 V DC for 1 minute to earth
Frequency resolution Analog input 0.024/50 Hz
Display unit 0.1 Hz
Communication port protocol CANopen
Modbus
Connector type 1 RJ45 for Modbus on front face
1 RJ45 for Modbus on terminal
Male SUB-D 9 on RJ45 for CANopen
Physical interface 2-wire RS 485 for Modbus
Transmission frame RTU for Modbus
Transmission rate 20 kbps, 50 kbps, 125 kbps, 250 kbps, 500 kbps, 1 Mbps for CANopen
4800 bps, 9600 bps, 19200 bps, 38.4 Kbps for Modbus on terminal
9600 bps, 19200 bps for Modbus on front face
Data format 8 bits, 1 stop, even parity for Modbus on front face
8 bits, odd even or no configurable parity for Modbus on terminal
Number of addresses 1...247 for Modbus
1...127 for CANopen
Method of access Slave for CANopen
Marking CE
Operating position Vertical +/- 10 degree
Height 420 mm
Depth 236 mm
Width 230 mm
Product weight 21 kg
Option card CC-Link communication card
Controller inside programmable card
DeviceNet communication card
Ethernet/IP communication card
Fipio communication card
I/O extension card
Interbus-S communication card
3
Interface card for encoder
Modbus Plus communication card
Modbus TCP communication card
Modbus/Uni-Telway communication card
Overhead crane card
Profibus DP communication card
Profibus DP V1 communication card
Environment
Noise level 59.9 dB conforming to 86/188/EEC
Dielectric strength 3535 V DC between earth and power terminals
5092 V DC between control and power terminals
Electromagnetic compatibility Conducted radio-frequency immunity test conforming to IEC 61000-4-6 level 3
Electrical fast transient/burst immunity test conforming to IEC 61000-4-4 level 4
Electrostatic discharge immunity test conforming to IEC 61000-4-2 level 3
Radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3 level 3
Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
1.2/50 µs - 8/20 µs surge immunity test conforming to IEC 61000-4-5 level 3
Standards EN 61800-3 environments 1 category C3
UL Type 1
EN/IEC 61800-3
IEC 60721-3-3 class 3C1
EN 55011 class A group 2
EN/IEC 61800-5-1
IEC 60721-3-3 class 3S2
EN 61800-3 environments 2 category C3
Product certifications UL
NOM 117
C-Tick
CSA
Pollution degree 2 conforming to EN/IEC 61800-5-1
3 conforming to UL 840
IP degree of protection IP20 on upper part without blanking plate on cover conforming to EN/IEC 60529
IP20 on upper part without blanking plate on cover conforming to EN/IEC 61800-5-1
IP21 conforming to EN/IEC 60529
IP21 conforming to EN/IEC 61800-5-1
IP41 on upper part conforming to EN/IEC 60529
IP41 on upper part conforming to EN/IEC 61800-5-1
IP54 on lower part conforming to EN/IEC 60529
IP54 on lower part conforming to EN/IEC 61800-5-1
Vibration resistance 1.5 mm peak to peak (f = 3...13 Hz) conforming to EN/IEC 60068-2-6
1 gn (f = 13...200 Hz) conforming to EN/IEC 60068-2-6
Shock resistance 15 gn for 11 ms conforming to EN/IEC 60068-2-27
Relative humidity 5...95 % without condensation conforming to IEC 60068-2-3
5...95 % without dripping water conforming to IEC 60068-2-3
Ambient air temperature for operation -10...50 °C without derating
Ambient air temperature for storage -25...70 °C
Operating altitude <= 1000 m without derating
1000...3000 m with current derating 1 % per 100 m
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 0946 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference contains SVHC above the threshold - Go to CaP for more details
Go to CaP for more details
Product environmental profile Available
Product environmental
Product end of life instructions Available
Contractual warranty
Warranty period 18 months
4
Product data sheet ATV71HD22N4Z
Dimensions Drawings
Dimensions in mm
a b c G H K Ø
a b c G H K Ø
Dimensions in mm
a c1 G H K Ø
a c1 G H K Ø
5
Dimensions with 2 Option Cards (1)
Dimensions in mm
a c2 G H K Ø
a c2 G H K Ø
6
Product data sheet ATV71HD22N4Z
Mounting and Clearance
Mounting Recommendations
Depending on the conditions in which the drive is to be used, its installation will require certain precautions and the use of appropriate
accessories.
Install the unit vertically:
● Avoid placing it close to heating elements
● Leave sufficient free space to ensure that the air required for cooling purposes can circulate from the bottom to the top of the unit.
Clearance
Mounting Types
Type A Mounting
Type B Mounting
Type C Mounting
By removing the protective blanking cover from the top of the drive, the degree of protection for the drive becomes IP 20.
The protective blanking cover may vary according to the drive model (refer to the user guide).
The protective blanking cover must be removed from ATV 71P•••N4Z drives when they are mounted in a dust and damp proof enclosure.
7
Product data sheet ATV71HD22N4Z
Mounting and Clearance
Ventilation
To ensure proper air circulation in the drive:
● Fit ventilation grilles.
● Ensure that there is sufficient ventilation. If there is not, install a forced ventilation unit with a filter. The openings and/or fans must provide a flow rate at least
8
Product data sheet ATV71HD22N4Z
Connections and Schema
Wiring Diagram Conforming to Standards EN 954-1 Category 1, IEC/EN 61508 Capacity SIL1, in Stopping Category
0 According to IEC/EN 60204-1
A1 ATV71 drive
KM1 Contactor
L1 DC choke
Q1 Circuit-breaker
Q2 GV2 L rated at twice the nominal primary current of T1
Q3 GB2CB05
S1, S2 XB4 B or XB5 A pushbuttons
T1 100 VA transformer 220 V secondary
(1) Line choke (three-phase); mandatory for ATV71HC11Y…HC63Y drives (except when a special transformer is used (12-pulse)).
(2) For ATV71HC40N4 drives combined with a 400 kW motor, ATV71HC50N4 and ATV71HC40Y…HC63Y, refer to the power terminal connections diag
(3) Fault relay contacts. Used for remote signalling of the drive status.
(4) Connection of the common for the logic inputs depends on the positioning of the SW1 switch. The above diagram shows the internal power supply sw
(5) There is no PO terminal on ATV71HC11Y…HC63Y drives.
(6) Optional DC choke for ATV71H•••M3, ATV71HD11M3X…HD45M3X, ATV71•075N4…•D75N4 and ATV71P•••N4Z drives. Connected in place of the
(7) Software-configurable current (0…20 mA) or voltage (0…10 V) analog input.
(8) Reference potentiometer.
All terminals are located at the bottom of the drive. Fit interference suppressors on all inductive circuits near the drive or connected on the same
circuit, such as relays, contactors, solenoid valves, fluorescent lighting, etc.
9
Product data sheet ATV71HD22N4Z
Connections and Schema
Wiring Diagram Conforming to Standards EN 954-1 Category 1, IEC/EN 61508 Capacity SIL1, in Stopping Category
0 According to IEC/EN 60204-1
A1 ATV71 drive
L1 DC choke
Q1 Circuit-breaker
Q2 Switch disconnector (Vario)
(1) Line choke (three-phase), mandatory for ATV71HC11Y…HC63Y drives (except when a special transformer is used (12-pulse)).
(2) For ATV71HC40N4 drives combined with a 400 kW motor, ATV71HC50N4 and ATV71HC40Y…HC63Y, refer to the power terminal connections diagram
(3) Fault relay contacts. Used for remote signalling of the drive status.
(4) Connection of the common for the logic inputs depends on the positioning of the SW1 switch. The above diagram shows the internal power supply switc
(5) There is no PO terminal on ATV71HC11Y…HC63Y drives.
(6) Optional DC choke for ATV71H•••M3, ATV71HD11M3X…HD45M3X, ATV71•075N4…•D75N4 and ATV71P•••N4Z drives. Connected in place of the stra
(7) Software-configurable current (0…20 mA) or voltage (0…10 V) analog input.
(8) Reference potentiometer.
All terminals are located at the bottom of the drive. Fit interference suppressors on all inductive circuits near the drive or connected on the same
circuit, such as relays, contactors, solenoid valves, fluorescent lighting, etc.
10
Product data sheet ATV71HD22N4Z
Connections and Schema
Wiring Diagram Conforming to Standards EN 954-1 Category 3, IEC/EN 61508 Capacity SIL2, in Stopping Category
0 According to IEC/EN 60204-1
A1 ATV71 drive
A2 Preventa XPS AC safety module for monitoring emergency stops and switches. One safety module can manage the “Power Removal” function for se
F1 Fuse
L1 DC choke
Q1 Circuit-breaker
S1 Emergency stop button with 2 contacts
S2 XB4 B or XB5 A pushbutton
(1) Power supply: 24 Vdc or Vac, 48 Vac, 115 Vac, 230 Vac.
(2) S2: resets XPS AC module on power-up or after an emergency stop. ESC can be used to set external starting conditions.
(3) Requests freewheel stopping of the movement and activates the “Power Removal” safety function.
(4) Line choke (three-phase), mandatory for and ATV71HC11Y…HC63Y drives (except when a special transformer is used (12-pulse)).
(5) The logic output can be used to signal that the machine is in a safe stop state.
(6) For ATV71HC40N4 drives combined with a 400 kW motor, ATV71HC50N4 and ATV71HC40Y…HC63Y, refer to the power terminal connections diag
(7) Fault relay contacts. Used for remote signalling of the drive status.
(8) Connection of the common for the logic inputs depends on the positioning of the SW1 switch. The above diagram shows the internal power supply sw
(9) Standardized coaxial cable, type RG174/U according to MIL-C17 or KX3B according to NF C 93-550, external diameter 2.54 mm /0.09 in., maximum
(10) There is no PO terminal on ATV71HC11Y…HC63Y drives.
(11) Optional DC choke for ATV71H•••M3, ATV71HD11M3X…HD45M3X, ATV71•075N4…•D75N4 and ATV71P•••N4Z drives. Connected in place of the
(12) Software-configurable current (0…20 mA) or voltage (0…10 V) analog input.
(13) Reference potentiometer.
All terminals are located at the bottom of the drive. Fit interference suppressors on all inductive circuits near the drive or connected on the same
circuit, such as relays, contactors, solenoid valves, fluorescent lighting, etc.
11
Product data sheet ATV71HD22N4Z
Connections and Schema
Wiring Diagram Conforming to Standards EN 954-1 Category 3, IEC/EN 61508 Capacity SIL2, in Stopping Category
1 According to IEC/EN 60204-1
A1 ATV71 drive
A2 (5) Preventa XPS ATE safety module for monitoring emergency stops and switches. One safety module can manage the "Power Removal” safety function f
F1 Fuse
L1 DC choke
Q1 Circuit-breaker
S1 Emergency stop button with 2 N/C contacts
S2 Run button
(1) Power supply: 24 Vdc or Vac, 115 Vac, 230 Vac.
(2) Requests controlled stopping of the movement and activates the “Power Removal” safety function.
(3) Line choke (three-phase), mandatory for ATV71HC11Y…HC63Y drives (except when a special transformer is used (12-pulse)).
(4) S2: resets XPS ATE module on power-up or after an emergency stop. ESC can be used to set external starting conditions.
(5) For stopping times requiring more than 30 seconds in category 1, use a Preventa XPS AV safety module which can provide a maximum time delay of 30
(6) The logic output can be used to signal that the machine is in a safe state.
(7) For ATV71HC40N4 drives combined with a 400 kW motor, ATV71HC50N4 and ATV71HC40Y…HC63Y, refer to the power terminal connections diagram
(8) Fault relay contacts. Used for remote signalling of the drive status.
(9) Connection of the common for the logic inputs depends on the positioning of the SW1 switch. The above diagram shows the internal power supply switc
(10) Standardized coaxial cable, type RG174/U according to MIL-C17 or KX3B according to NF C 93-550, external diameter 2.54 mm/0.09 in., maximum len
(11) Logic inputs LI1 and LI2 must be assigned to the direction of rotation: LI1 in the forward direction and LI2 in the reverse direction.
(12) There is no PO terminal on ATV71HC11Y…HC63Y drives.
(13) Optional DC choke for ATV71H•••M3, ATV71HD11M3X…HD45M3X, ATV71•075N4…•D75N4 and ATV71P•••N4Z drives. Connected in place of the stra
(14) Software-configurable current (0…20 mA) or voltage (0…10 V) analog input.
(15) Reference potentiometer.
All terminals are located at the bottom of the drive. Fit interference suppressors on all inductive circuits near the drive or connected on the same
circuit, such as relays, contactors, solenoid valves, fluorescent lighting, etc.
12
Product data sheet ATV71HD22N4Z
Performance Curves
Derating Curves
The derating curves for the drive nominal current (In) depend on the temperature, the switching frequency and the mounting type. For
intermediate temperatures (e.g. 55°C), interpolate between 2 curves.
X Switching frequency
(1) Mounting type
Above 50ºC, the drive should be fitted with a control card fan kit.
13