Millennium PDF
Millennium PDF
Millennium PDF
ED. A
ED. W
ED. M
UV
MILLENNIUM
GENERAL DESCRIPTION
SERIE ED…
UNITS WITH DIRECT EXPANSION COIL
The precision air conditioning units series ED with direct expansion coil have been designed for
use in technology centers, computer processing centers, in telecom applications and in all those
environments requiring special thermo-hygrometric conditions.
• The units have been specially designed to use R22 refrigerant or the ecological gas R407C
(version K).
• The units are available in different configuration depending on air intake and discharge:
U: air intake from the front, upflow air discharge
V: air intake from the bottom upflow air discharge
B: air intake from behind, upflow air discharge
D: air intake from the top, downflow air discharge
• Available versions are also:
ED...A indoor unit and outdoor remote condenser
ED...W indoor unit with installed watercooled condenser
ED...M indoor unit and outdoor condensing group
Provided with:
• Housing in steel structural and panels, finely painted with epoxy powders and sound insulated
by means of polyurethane panels installed in the internal part of the unit.
• 1 or 2 Scroll compressors (for models 451D, 601D, 581, 651, 721, 821 the compressors are
Bristol compressors) with thermal protection, installed on rubber dampers, with crankcase
heater where necessary (for ED…M version the compressors are installed on the condensing
unit)
• Centrifugal fans directly coupled to the low rpm motor.
• Direct expansion cooling coil in copper pipes and aluminium fins.
• Drip tray for condensing in alluminium.
• Regenerable air filters-Standard F4 efficiency.
• Components of the cooling circuit:
Thermostatic valve with external equalizer, sight glass, dehydrating filter, safety device, high
and low pressure switch, liquid receiver, check valve on liquid line, solenoid valve.
For the ED…W version a weld brazed plate condenser is installed on the unit
• CE compliant electrical panel fitted with magnetothermal main switch, automatic switches,
remote switches, overload protection, low tension auxiliary circuits, terminal board.
• EMIPRO microprocessor operating the management and alarm system of the unit.
Data in this catalogue are not binding and subject to variation without prior notice
SERIE UV…
UNITS WITH CHILLED WATER COIL
The precision air conditioning units series UV with chilled water coil have been designed for use
in technology centers, computer processing centers, in telecom applications and in all those
environments requiring special thermo-hygrometric conditions.
• The units are available in different versions depending on air intake and discharge:
U: air intake from the front, upflow air discharge
V: air intake from the bottom upflow air discharge
B: air intake from behind, upflow air discharge
D: air intake from the top, downflow air discharge
Provided with:
• Housing in steel structural and panels, finely painted with epoxy powders and sound
insulated by means of polyurethane panels installed in the internal part of the unit.
• Centrifugal fans directly coupled to the low rpm motor.
• Chilled water coil in copper pipes and aluminium fins.
• Three-way modulating valve electronically controlled.
• Drip tray for condensing in alluminium.
• Regenerable air filters-Standard F4 efficiency.
• CE compliant electrical panel fitted with magnetothermal main switch, automatic
switches, remote switches, overload protection, low tension auxiliary circuits, terminal
board.
• EMIPRO microprocessor operating the management and alarm system of the unit.
OPTIONS DESCRIPTION
MILLENNIUM E 07/02
PRECISION AIR CONDITIONING UNITS - DIRECT EXPANSION - R22 - R407C - Versions U,V,B
MODEL ED.A 221 241 251 291 301 341 321 361 451 351 431 531
Size M1 M1 M1 M1 M1 M1 M2 M2 M2 M3 M3 M3
Cooling capacity 1) R 22
Total (27°C-50%) kW 22,0 24,0 25,3 29,0 31,7 35,7 32,1 36,3 45,9 36,0 43,9 51,4
Sensible (27°C-50%) kW 18,3 19,9 21,0 24,0 26,3 29,6 26,7 30,1 38,1 29,9 36,4 42,7
Total (24°C-50%) kW 20,2 22,0 23,2 26,6 29,1 32,7 29,5 33,3 42,1 33,0 40,3 47,2
Sensible (24°C-50%) kW 18,4 19,8 21,4 23,6 26,5 30,1 28,6 29,9 37,9 31,7 36,3 42,5
Total (22°C-50%) kW 19,4 21,2 22,3 25,5 27,9 31,5 28,4 32,0 40,5 31,8 38,7 45,4
Sensible (22°C-50%) kW 18,1 19,7 20,8 23,8 26,0 29,3 26,4 29,7 37,7 29,6 36,0 42,2
Nominal absorbed power. 3) kW 4,5 5,0 5,6 6,4 6,8 7,8 6,8 7,6 10,0 7,6 10,4 11,7
Nominal absorbed current. 3) A 8,0 9,8 11,1 11,8 13,0 15,0 12,9 14,7 19,6 14,7 19,8 21,8
Cooling capacity 2) R 407 C
Total (27°C-50%) kW 21,2 23,1 24,4 27,9 30,5 34,3 30,9 34,9 44,2 34,7 42,3 49,5
Sensible (27°C-50%) kW 17,6 19,2 20,2 23,1 25,3 28,5 25,7 29,0 36,7 28,8 35,1 41,1
Total (24°C-50%) kW 19,4 21,2 22,3 25,6 28,0 31,5 28,4 32,0 40,5 31,8 38,8 45,4
Sensible (24°C-50%) kW 17,7 19,3 20,3 23,3 25,4 28,7 27,5 29,1 36,9 30,5 35,3 41,3
Total (22°C-50%) kW 18,7 20,4 21,5 24,6 26,9 30,3 27,3 30,8 39,0 30,6 37,3 43,7
Sensible (22°C-50%) kW 17,4 19,0 20,0 22,9 25,0 28,2 25,4 28,6 36,3 28,4 34,7 40,6
Nominal absorbed power. 3) kW 4,7 5,2 5,8 6,6 7,0 8,1 7,0 7,9 10,4 7,9 10,8 12,2
Nominal absorbed current. 3) A 8,3 10,2 11,5 12,3 13,5 15,6 13,4 15,3 20,4 15,3 20,5 22,7
SCROLL Compressors
Standard number n.° 1 1 1 1 1 1 1 1 1 1 1 1
Optional number n.° nd nd nd 2 nd 2 nd 2 2 2 2 2
Capacity steps(1 compr.) n.° 1 1 1 1 1 1 1 1 1 1 1 1
Capacity steps (2 compr.) n.° nd nd nd 2 nd 2 nd 2 2 2 2 2
Hot gas by - pass 4) n.° 1 1 1 1 1 1 1 1 1 1 1 1
Max absorbed current. A 11,4 13 17 20 17,9 19,2 20 29 26 29 35 35
Inrush current 5) A 63 86 83 53 105 114 111 111 96 111 149 149
Centrifugal fans
Number n.° 2 2 2 2 2 2 2 2 2 2 2 2
Air flow rate l/s 1480 1480 1480 1480 1700 1700 2222 2222 2222 2722 2722 2722
Air flow rate mc/h 5328 5328 5328 5328 6120 6120 7999 7999 7999 9799 9799 9799
Ext avaible pressure 10) Pa 75 75 75 60 70 70 165 165 150 70 65 40
Higher avaible pressure 1M Pa 200 200 200 185 155 155 185 185 170 135 130 105
Higher avaible pressure 2M Pa 245 245 245 230 250 250 235 235 220 240 235 210
Higher avaible pressure 3M Pa 265 265 265 250 300 300 335 335 320 290 285 260
Higher avaible pressure 4M Pa 355 355 355 340 360 360 375 375 360 340 335 310
Higher avaible pressure 5M Pa 405 405 405 390 nd nd nd nd nd 460 455 430
Max absorbed power. 9) W 891 891 891 891 1518 1518 2468 2468 2468 2178 2178 2178
Max absorbed current.9) A 5,4 5,4 5,4 5,4 9,2 9,2 5 5 5 13,2 13,2 13,2
Humidifier
Max steam prodution kg/h 5 5 5 5 5 5 5 5 5 13 13 13
Max absorbed power kW 3,7 3,7 3,7 3,7 3,7 3,7 3,7 3,7 3,7 9,4 9,4 9,4
Max absorbed current A 9,7 9,7 9,7 9,7 9,7 9,7 9,7 9,7 9,7 24,7 24,7 24,7
Electric heater
Capacity kW 9 9 9 9 9 9 9 9 9 13,5 13,5 13,5
Steps n.° 3 3 3 3 3 3 3 3 3 3 3 3
Absorbed current A 13,3 13,3 13,3 13,3 13,3 13,3 13,3 13,3 13,3 19,9 19,9 19,9
Warm water coil 6)
Capacity kW 15 15 15 15 15 15 19 19 19 22 22 22
Water flow rate l/s 0,24 0,24 0,24 0,24 0,24 0,24 0,3 0,3 0,3 0,4 0,4 0,4
Pressure drop (coil + valve) kPa 48 48 48 48 48 48 27 27 27 57 57 57
Hot gas coil
Capacity kW 11 11 11 11 11 11 17 17 17 17 17 17
Sound pressure level 7)
Version U, B dB(A) 51 51 52 52 53 53 61 62 62 61 61 61
Version V dB(A) 48 48 48 48 49 49 58 58 58 57 57 57
Dimensions - Weight
Length mm 1230 1230 1230 1230 1230 1230 1530 1530 1530 1730 1730 1730
Width mm 665 665 665 665 665 665 665 665 665 815 815 815
Height mm 1975 1975 1975 1975 1975 1975 1975 1975 1975 1995 1995 1995
Weight kg 280 285 290 295 300 305 325 331 340 360 365 378
Power supply 400V-50Hz-3F+T+N
Remote consenser stand. 8) CR 26 26 29 35 35 45 45 45 52 45 48 58
Silenced remote condenser. 8) CRS 24 28 28 34 34 41 41 41 56 41 56 56
Ultrasilenc. remote condenser 8) CRU 25 33 33 33 44 44 44 44 50 44 50 67
MILLENNIUM E 07/02
PRECISION AIR CONDITIONING UNITS - DIRECT EXPANSION - R22 - R407C - Versions U,V,B
MODEL ED.A 172 192 202 232 272 342 302 362 442
Size L3 L3 M1 M1 M1 M1 M2 M2 M2
Cooling capacity 1) R 22
Total (27°C-50%) kW 17,1 19,1 21,1 23,8 27,1 34,6 31,3 37,1 45,9
Sensible (27°C-50%) kW 14,0 15,7 17,3 19,5 22,2 28,4 25,7 30,4 37,6
Total (24°C-50%) kW 15,7 17,5 19,3 21,8 24,8 31,8 28,7 34,0 42,1
Sensible (24°C-50%) kW 14,1 16,0 18,2 20,1 22,4 28,6 28,2 30,6 37,9
Total (22°C-50%) kW 15,1 16,9 18,6 21,0 23,9 30,5 27,6 32,7 40,5
Sensible (22°C-50%) kW 13,9 15,6 17,2 19,4 22,1 28,2 25,6 30,3 37,5
Nominal absorbed power. 3) kW 3,6 4,3 4,3 5 6,2 7,6 6,3 7,6 9,8
Nominal absorbed current. 3) A 6,8 8 8,1 9,2 12,02 15 11,6 15,2 19,6
Cooling capacity 2) R 407 C
Total (27°C-50%) kW 16,4 18,4 20,3 22,9 26,0 33,3 30,1 35,7 44,1
Sensible (27°C-50%) kW 13,5 15,1 16,6 18,7 21,3 27,3 24,7 29,2 36,2
Total (24°C-50%) kW 15,1 16,9 18,6 21,0 23,9 30,5 27,6 32,7 40,5
Sensible (24°C-50%) kW 13,6 15,2 16,7 18,9 21,5 27,5 27,1 29,4 36,9
Total (22°C-50%) kW 14,5 16,2 17,9 20,2 23,0 29,4 26,6 31,5 38,9
Sensible (22°C-50%) kW 13,4 15,0 16,5 18,7 21,2 27,2 24,6 29,1 36,0
Nominal absorbed power. 3) kW 3,7 4,5 4,5 5,2 6,4 7,9 6,5 7,9 10,2
Nominal absorbed current. 3) A 7,1 8,3 8,4 9,6 12,5 15,6 12,1 15,8 20,4
SCROLL Compressors
standard number n.° 2 2 2 2 2 2 2 2 2
Standard choking n.° G2
Max absorbed current. A 10 12 10 12 16 20 20 20 26
Inrush current A 29 36 36 42 48 60 46 60 91
CENTRIFUGAL fans
Number n.° 1 1 2 2 2 2 2 2 2
Air flow rate l/s 890 890 1480 1480 1480 1700 2222 2222 2222
Air flow rate mc/h 3204 3204 5328 5328 5328 6120 7999 7999 7999
Ext avaible pressure std 7) Pa 70 70 75 75 75 70 165 165 150
Higher avaible pressure 1M Pa 120 120 200 200 200 155 185 185 170
Higher avaible pressure 2M Pa 200 200 245 245 245 250 235 235 220
Higher avaible pressure 3M Pa 290 290 265 265 265 300 335 335 320
Higher avaible pressure 4M Pa 353 353 355 355 355 360 375 375 360
Higher avaible pressure 5M Pa 420 420 405 405 405 nd nd nd nd
Max absorbed power. 8) W 627 627 891 891 891 1518 2468 2468 2468
Max absorbed current.8) A 3,8 3,8 5,4 5,4 5,4 9,2 5 5 5
Humidifier
Max steam prodution kg/h 5 5 5 5 5 5 5 5 5
Max absorbed power kW 3,7 3,7 3,7 3,7 3,7 3,7 3,7 3,7 3,7
Max absorbed current A 9,7 9,7 9,7 9,7 9,7 9,7 9,7 9,7 9,7
Electric heater
Capacity kW 6 6 9 9 9 9 9 9 9
Steps n.° 1 1 3 3 3 3 3 3 3
Absorbed current A 13,3 13,3 13,3 13,3 13,3 13,3 13,3 13,3 13,3
Warm water coil 4)
Capacity kW 11 11 15 15 15 15 19 19 19
Water flow rate l/s 0,18 0,18 0,24 0,24 0,24 0,24 0,3 0,3 0,3
Pressure drop (coil + valve) kPa 21 21 48 48 48 48 27 27 27
Hot gas coil
Capacity kW 9 9 11 11 11 11 17 17 17
Sound pressure level 5)
Version U, B dB(A) 51 51 52 52 52 52 59 59 59
Version V dB(A) 49 49 50 50 50 50 57 57 57
Dimensions - Weight
Length mm 940 940 1230 1230 1230 1230 1530 1530 1530
Width mm 565 565 665 665 665 665 665 665 665
Height mm 1800 1800 1975 1975 1975 1975 1975 1975 1975
Weight kg 290 300 320 330 335 340 360 368 375
Power supply 400V-50Hz-3F+T+N
Remote consenser stand. 6) CR 2*CR11 2*CR11 2*CR14 2*CR14 2*CR18 2*CR18 2*CR18 2*CR18 2*CR26
Silenced remote condenser. 6) CRS 2*CRS10 2*CRS10 2*CRS13 2*CRS13 2*CRS21 2*CRS21 2*CRS21 2*CRS21 2*CRS28
Ultrasilenced remote condenser. 6) CRU 2*CRU9 2*CRU12 2*CRU17 2*CRU17 2*CRU17 2*CRU19 2*CRU19 2*CRU19 2*CRU33
MODEL ED.A 412 452 492 482 532 572 602 542 622 682 842 762 892 1002 1102
Size M3 M3 M3 M4 M4 M4 M4 M5 M5 M5 M5 M6 M6 M6 M6
Cooling capacity 1) R 22
Total (27°C-50%) kW 42,4 45,3 50,3 49,7 53,4 58,5 61,2 54,5 62,4 69,7 85,5 77,5 91,1 102 110
Sensible (27°C-50%) kW 34,8 37,2 41,2 40,7 43,8 48,0 50,2 44,7 51,2 57,1 70,1 63,5 74,7 83,5 90,1
Total (24°C-50%) kW 38,9 41,6 46,1 45,6 49,0 53,7 56,2 50,0 57,2 63,9 78,4 71,1 83,6 93,4 101
Sensible (24°C-50%) kW 35,4 37,4 41,5 41,0 44,1 48,3 50,5 49,0 52,1 57,5 70,6 67,5 75,2 84,1 91,7
Total (22°C-50%) kW 37,4 40,0 44,3 43,8 47,1 51,6 54,0 48,1 55,0 61,5 75,4 68,3 80,4 89,8 96,9
Sensible (22°C-50%) kW 34,6 37,0 41,0 40,5 43,6 47,7 50,0 44,5 50,9 56,9 69,7 63,2 74,3 83,1 89,6
Nominal absorbed power. 3) kW 8,8 10,3 11,2 10,0 11,8 13,2 14,2 11,2 13,2 15,0 20,0 15,6 20,1 23,4 24,0
Nominal absorbed current. 3) A 16,1 19,4 22,0 19,6 23,0 25,8 26,0 22,8 25,8 27,8 39,4 29,6 39,4 43,6 41,8
Cooling capacity 2) R 407 C
Total (27°C-50%) kW 40,7 43,6 48,3 47,8 51,4 56,3 58,9 52,4 60,0 67,0 82,2 74,5 87,6 97,9 106
Sensible (27°C-50%) kW 33,4 35,7 39,6 39,2 42,1 46,1 48,3 43,0 49,2 54,9 67,4 61,1 71,8 80,3 86,6
Total (24°C-50%) kW 37,4 40,0 44,3 43,8 47,1 51,6 54,0 48,1 55,0 61,5 75,4 68,3 80,4 89,8 96,9
Sensible (24°C-50%) kW 33,6 36,0 39,9 39,4 42,4 46,5 48,6 47,1 50,1 55,3 67,9 64,9 72,3 80,8 87,2
Total (22°C-50%) kW 35,9 38,4 42,6 42,1 45,3 49,6 51,9 46,2 52,9 59,1 72,5 65,7 77,3 86,4 93,2
Sensible (22°C-50%) kW 33,3 35,6 39,4 39,0 41,9 45,9 48,0 42,8 49,0 54,7 67,1 60,8 71,5 79,9 86,2
Nominal absorbed power. 3) kW 9,1 10,7 11,6 10,4 12,2 13,7 14,7 11,6 13,7 15,6 20,8 16,2 20,9 24,3 24,9
Nominal absorbed current. 3) A 16,7 20,2 22,9 20,4 23,9 26,8 27,0 23,7 26,8 28,9 41,0 30,8 41,0 45,3 43,5
SCROLL Compressors
standard number n.° 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
Standard choking n.° G2
Max absorbed current. A 23 34 34 26 38 40 50 29 40 50 70 40 70 70 56
Inrush current A 67 79 90 91 90 117 109 92 117 110 160 117 160 162 172
CENTRIFUGAL fans
Number n.° 2 2 2 2 2 2 2 3 3 3 3 4 4 4 4
Air flow rate l/s 2722 2722 2722 2920 2920 2920 2920 3950 3950 4170 4170 5277 5277 5277 6670
Air flow rate mc/h 9799 9799 9799 10512 10512 10512 10512 14220 14220 15012 15012 18997 18997 18997 24012
Ext avaible pressure std 7) Pa 70 65 40 65 65 65 65 55 55 70 70 55 55 50 75
Higher avaible pressure 1M Pa 135 130 105 110 110 110 110 95 95 215 215 95 95 90 220
Higher avaible pressure 2M Pa 240 235 210 250 250 250 250 260 260 290 290 260 260 255 290
Higher avaible pressure 3M Pa 290 285 260 335 335 335 335 320 320 405 405 330 330 325 nd
Higher avaible pressure 4M Pa 340 335 310 450 450 450 450 410 410 nd nd 410 410 405 nd
Higher avaible pressure 5M Pa 460 455 430 nd nd nd nd nd nd nd nd nd nd nd nd
Max absorbed power. 8) W 2178 2178 2178 2244 2244 2244 2244 3366 3366 6664 6664 4488 4488 4488 10662
Max absorbed current.8) A 13,2 13,2 13,2 13,6 13,6 13,6 13,6 20,4 20,4 13,5 13,5 27,2 27,2 27,2 21,6
Humidifier
Max steam prodution kg/h 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13
Max absorbed power kW 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4
Max absorbed current A 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7
Electric heater
Capacity kW 13,5 13,5 13,5 13,5 13,5 13,5 13,5 18 18 18 18 18 18 18 18
Steps n.° 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3
Absorbed current A 19,9 19,9 19,9 19,9 19,9 19,9 19,9 26,6 26,6 26,6 26,6 26,6 26,6 26,6 26,6
Warm water coil 4)
Capacity kW 22 22 22 24 24 24 24 25 25 25 25 35 35 35 35
Water flow rate l/s 0,35 0,35 0,35 0,38 0,38 0,38 0,38 0,41 0,41 0,41 0,41 0,6 0,6 0,6 0,6
Pressure drop (coil + valve) kPa 57 57 57 47 47 47 47 25 25 25 25 46 46 46 46
Hot gas coil
Capacity kW 17 17 17 18 18 18 18 17 17 17 17 21 21 21 21
Sound pressure level 5)
Version U, B dB(A) 61 61 61 59 59 59 59 62 62 62 62 64 64 64 65
Version V dB(A) 58 58 58 57 57 57 57 59 59 59 59 60 60 60 61
Dimensions - Weight
Length mm 1730 1730 1730 1990 1990 1990 1990 2390 2390 2390 2390 2950 2950 2950 2950
Width mm 815 815 815 815 815 815 815 815 815 815 815 815 815 815 815
Height mm 1995 1995 1995 1995 1995 1995 1995 1995 1995 1995 1995 1995 1995 1995 1995
Weight kg 400 410 425 450 460 475 490 515 520 530 540 565 580 595 610
Power supply 400V-50Hz-3F+T+N
Remote consenser stand. 6) CR 2*CR26 2*CR26 2*CR29 2*CR 26 2*CR35 2*CR35 2*CR35 2*CR35 2*CR35 2*CR45 2*CR52 2*CR52 2*CR52 2*CR58 2*CR58
Silenced remote condenser. 6) CRS 2*CRS24 2*CRS28 2*CRS28 2*CRS28 2*CRS34 2*CRS34 2*CRS34 2*CRS34 2*CRS34 2*CRS41 2*CRS56 2*CRS56 2*CRS56 2*CRS56 2*CRS66
Ultrasilen. remote condenser 6) CRU 2*CRU22 2*CRU33 2*CRU33 2*CRU33 2*CRU33 2*CRU44 2*CRU44 2*CRU33 2*CRU44 2*CRU44 2*CRU50 2*CRU50 2*CRU50 2*CRU67 2*CRU67
MILLENNIUM E 07/02
PRECISION AIR CONDITIONING UNITS - DIRECT EXPANSION - R22 - R407C - Versions D
MILLENNIUM E 07/02
PRECISION AIR CONDITIONING UNITS - DIRECT EXPANSION - R22 - R407C - Versions D
MODEL ED.A 221 241 251 291 301 341 321 361 451 351 431 531
Size M1 M1 M1 M1 M1 M1 M2 M2 M2 M3 M3 M3
Cooling capacity 1) R 22
Total (27°C-50%) kW 22,0 24,0 25,3 29,0 31,7 35,7 32,1 36,3 45,9 36,0 43,9 51,4
Sensible (27°C-50%) kW 18,3 19,9 21,0 24,0 26,3 29,6 26,7 30,1 38,1 29,9 36,4 42,7
Total (24°C-50%) kW 20,2 22,0 23,2 26,6 29,1 32,7 29,5 33,3 42,1 33,0 40,3 47,2
Sensible (24°C-50%) kW 18,4 19,8 21,4 23,6 26,5 30,1 28,6 29,9 37,9 31,7 36,3 42,5
Total (22°C-50%) kW 19,4 21,2 22,3 25,5 27,9 31,5 28,4 32,0 40,5 31,8 38,7 45,4
Sensible (22°C-50%) kW 18,1 19,7 20,8 23,8 26,0 29,3 26,4 29,7 37,7 29,6 36,0 42,2
Nominal absorbed power. 3) kW 4,5 5,0 5,6 6,4 6,8 7,8 6,8 7,6 10,0 7,6 10,4 11,7
Nominal absorbed current. 3) A 8,0 9,8 11,1 11,8 13,0 15,0 12,9 14,7 19,6 14,7 19,8 21,8
Cooling capacity 2) R 407 C
Total (27°C-50%) kW 21,2 23,1 24,4 27,9 30,5 34,3 30,9 34,9 44,2 34,7 42,3 49,5
Sensible (27°C-50%) kW 17,6 19,2 20,2 23,1 25,3 28,5 25,7 29,0 36,7 28,8 35,1 41,1
Total (24°C-50%) kW 19,4 21,2 22,3 25,6 28,0 31,5 28,4 32,0 40,5 31,8 38,8 45,4
Sensible (24°C-50%) kW 17,7 19,3 20,3 23,3 25,4 28,7 27,5 29,1 36,9 30,5 35,3 41,3
Total (22°C-50%) kW 18,7 20,4 21,5 24,6 26,9 30,3 27,3 30,8 39,0 30,6 37,3 43,7
Sensible (22°C-50%) kW 17,4 19,0 20,0 22,9 25,0 28,2 25,4 28,6 36,3 28,4 34,7 40,6
Nominal absorbed power. 3) kW 4,7 5,2 5,8 6,6 7,0 8,1 7,0 7,9 10,4 7,9 10,8 12,2
Nominal absorbed current. 3) A 8,3 10,2 11,5 12,3 13,5 15,6 13,4 15,3 20,4 15,3 20,5 22,7
SCROLL Compressors SCROLL Hermetic SCROLL
Standard number n.° 1 1 1 1 1 1 1 1 1 1 1 1
Capacity steps n.° 1 1 1 1 1 1 1 1 1 1 1 1
Hot gas by-pass 4) n.° 1 1 1 1 1 1 1 1 1 1 1 1
Max absorbed current. A 11 13 17 20 18 19 20 29 26 29 35 35
Inrush current 5) A 63 86 83 53 105 114 111 111 96 111 149 149
Centrifugal fans
Number n.° 1 1 1 1 1 1 2 2 2 2 2 2
Air flow rate l/s 1480 1480 1480 1480 1700 1700 2222 2222 2222 2722 2722 2722
Air flow rate mc/h 5328 5328 5328 5328 6120 6120 7999 7999 7999 9799 9799 9799
Ext avaible pressure 10) Pa 80 80 80 60 60 60 50 50 35 60 55 30
Higher avaible pressure 1M Pa 210 210 210 190 90 90 95 95 80 125 120 95
Higher avaible pressure 2M Pa 242 242 242 220 255 255 195 195 180 230 225 200
Higher avaible pressure 3M Pa 400 400 400 380 310 310 235 235 220 280 275 250
Higher avaible pressure 4M Pa nd nd nd nd nd nd nd nd nd 330 325 300
Higher avaible pressure 5M Pa nd nd nd nd nd nd nd nd nd 450 445 420
Max absorbed power. 9) W 2123 2123 2123 2123 2764 2764 2145 2145 2145 2178 2178 2178
Max absorbed current.9) A 4,3 4,3 4,3 4,3 5,6 5,6 13 13 13 13,2 13,2 13,2
Humidifier
Max steam prodution kg/h 5 5 5 5 5 5 5 5 5 13 13 13
Max absorbed power kW 3,7 3,7 3,7 3,7 3,7 3,7 3,7 3,7 3,7 9,4 9,4 9,4
Max absorbed current A 9,7 9,7 9,7 9,7 9,7 9,7 9,7 9,7 9,7 24,7 24,7 24,7
Electric heater
Capacity kW 9 9 9 9 9 9 9 9 9 13,5 13,5 13,5
Steps n.° 3 3 3 3 3 3 3 3 3 3 3 3
Absorbed current A 13,3 13,3 13,3 13,3 13,3 13,3 13,3 13,3 13,3 19,9 19,9 19,9
Warm water coil 6)
Capacity kW 15 15 15 15 15 15 19 19 19 22 22 22
Water flow rate l/s 0,24 0,24 0,24 0,24 0,24 0,24 0,3 0,3 0,3 0,4 0,4 0,4
Pressure drop (coil + valve) kPa 48 48 48 48 48 48 27 27 27 57 57 57
Hot gas coil
Capacity kW 11 11 11 11 11 11 17 17 17 17 17 17
Sound pressure level 7)
Version D dB(A) 58 58 58 58 56 56 58 58 58 57 57 57
Dimensions - Weight
Length mm 1230 1230 1230 1230 1230 1230 1530 1530 1530 1730 1730 1730
Width mm 665 665 665 665 665 665 665 665 665 815 815 815
Height mm 1975 1975 1975 1975 1975 1975 1975 1975 1975 1995 1995 1995
Weight kg 255 258 292 297 297 305 325 331 351 360 390 415
Power supply 400V-50Hz-3F+T+N
Remote consenser stand. 8) CR 26 26 29 35 35 45 45 45 52 45 48 58
Silenced remote condenser. 8) CRS 24 28 28 34 34 41 41 41 56 41 56 56
Ultrasilenced remote condenser 8) CRU 25 33 33 33 44 44 44 44 50 44 50 67
MILLLENNIUM E 07/02
PRECISION AIR CONDITIONING UNITS - DIRECT EXPANSION - R22 - R407C - Versions D
MILLENNIUM E 07/02
PRECISION AIR CONDITIONING UNITS - DIRECT EXPANSION - R22 - R407C - Versions D
MODEL ED.A 172 192 202 232 272 342 302 362 442
Size L3 L3 M1 M1 M1 M1 M2 M2 M2
Cooling capacity 1) R 22
Total (27°C-50%) kW 17,1 19,1 21,1 23,8 27,1 34,6 31,3 37,1 45,9
Sensible (27°C-50%) kW 14,0 15,7 17,3 19,5 22,2 28,4 25,7 30,4 37,6
Total (24°C-50%) kW 15,7 17,5 19,3 21,8 24,8 31,8 28,7 34,0 42,1
Sensible (24°C-50%) kW 14,1 16,0 18,2 20,1 22,4 28,6 28,2 30,6 37,9
Total (22°C-50%) kW 15,1 16,9 18,6 21,0 23,9 30,5 27,6 32,7 40,5
Sensible (22°C-50%) kW 13,9 15,6 17,2 19,4 22,1 28,2 25,6 30,3 37,5
Nominal absorbed power. 3) kW 3,6 4,3 4,3 5,0 6,2 7,6 6,3 7,6 9,8
Nominal absorbed current. 3) A 6,8 8,0 8,1 9,2 12,0 15,0 11,6 15,2 19,6
Cooling capacity 2) R 407 C
Total (27°C-50%) kW 16,4 18,4 20,3 22,9 26,0 33,3 30,1 35,7 44,1
Sensible (27°C-50%) kW 13,5 15,1 16,6 18,7 21,3 27,3 24,7 29,2 36,2
Total (24°C-50%) kW 15,1 16,9 18,6 21,0 23,9 30,5 27,6 32,7 40,5
Sensible (24°C-50%) kW 13,6 15,2 16,7 18,9 21,5 27,5 27,1 29,4 36,9
Total (22°C-50%) kW 14,5 16,2 17,9 20,2 23,0 29,4 26,6 31,5 38,9
Sensible (22°C-50%) kW 13,4 15,0 16,5 18,7 21,2 27,2 24,6 29,1 36,0
Nominal absorbed power. 3) kW 3,7 4,5 4,5 5,2 6,4 7,9 6,5 7,9 10,2
Nominal absorbed current. 3) A 7,1 8,3 8,4 9,6 12,5 15,6 12,1 15,8 20,4
SCROLL Compressors
standard number n.° 2 2 2 2 2 2 2 2 2
Standard choking n.° G2
Max absorbed current. A 10 12 10 12 16 20 20 20 26
Inrush current 5) A 29 36 36 42 48 60 46 60 91
CENTRIFUGAL fans
Number n.° 1 1 1 1 1 1 2 2 2
Air flow rate l/s 890 890 1480 1480 1480 1700 2222 2222 2222
Air flow rate mc/h 3204 3204 5328 5328 5328 6120 7999 7999 7999
Ext avaible pressure std 7) Pa 90 90 80 80 80 60 50 50 35
Higher avaible pressure 1M Pa 170 170 210 210 210 90 95 95 80
Higher avaible pressure 2M Pa 260 260 242 242 242 255 195 195 180
Higher avaible pressure 3M Pa 320 320 400 400 400 310 235 235 220
Higher avaible pressure 4M Pa 390 390 nd nd nd nd 275 275 260
Higher avaible pressure 5M Pa 457 457 nd nd nd nd nd nd nd
Max absorbed power. 8) W 627 627 2123 2123 2123 2764 2468 2468 2468
Max absorbed current.8) A 3,8 3,8 4,3 4,3 4,3 5,6 5 5 5
Humidifier
Max steam prodution kg/h 5 5 5 5 5 5 5 5 5
Max absorbed power kW 3,7 3,7 3,7 3,7 3,7 3,7 3,7 3,7 3,7
Max absorbed current A 9,7 9,7 9,7 9,7 9,7 9,7 9,7 9,7 9,7
Electric heater
Capacity kW 6 6 9 9 9 9 9 9 9
Steps n.° 1 1 3 3 3 3 3 3 3
Absorbed current A 13,3 13,3 13,3 13,3 13,3 13,3 13,3 13,3 13,3
Warm water coil 4)
Capacity kW 11 11 15 15 15 15 19 19 19
Water flow rate l/s 0,18 0,18 0,24 0,24 0,24 0,24 0,3 0,3 0,3
Pressure drop (coil + valve) kPa 21 21 48 48 48 48 27 27 27
Hot gas coil
Capacity kW 9 9 11 11 11 11 17 17 17
Sound pressure level 5)
Version D dB(A) 49 49 60 60 60 57 57 57 57
Dimensions - Weight
Length mm 940 940 1230 1230 1230 1230 1530 1530 1530
Width mm 565 565 665 665 665 665 665 665 665
Height mm 1800 1800 1975 1975 1975 1975 1975 1975 1975
Weight kg 290 300 320 330 335 340 360 368 375
Power supply 400V-50Hz-3F+T+N
Remote consenser stand. 6) CR 2*CR11 2*CR11 2*CR14 2*CR14 2*CR18 2*CR18 2*CR18 2*CR18 2*CR26
Silenced remote condenser. 6) CRS 2*CRS10 2*CRS10 2*CRS13 2*CRS13 2*CRS21 2*CRS21 2*CRS21 2*CRS21 2*CRS28
Ultrasilenced remote condenser 8) CRU 2*CRU9 2*CRU12 2*CRU17 2*CRU17 2*CRU17 2*CRU19 2*CRU19 2*CRU19 2*CRU33
MILLENNIUM E 07/02
PRECISION AIR CONDITIONING UNITS - DIRECT EXPANSION - R22 - R407C - Versions D
MODEL ED.A 412 452 492 482 532 572 602 542 622 682 842 762 892 1002 1102
Size M3 M3 M3 M4 M4 M4 M4 M5 M5 M5 M5 M6 M6 M6 M6
Cooling capacity 1) R 22
Total (27°C-50%) kW 42,4 45,3 50,3 49,7 53,4 58,5 61,2 54,5 62,4 69,7 85,5 77,5 91,1 102 110
Sensible (27°C-50%) kW 34,8 37,2 41,2 40,7 43,8 48,0 50,2 44,7 51,2 57,1 70,1 63,5 74,7 83,5 90,1
Total (24°C-50%) kW 38,9 41,6 46,1 45,6 49,0 53,7 56,2 50,0 57,2 63,9 78,4 71,1 83,6 93,4 101
Sensible (24°C-50%) kW 35,4 37,4 41,5 41,0 44,1 48,3 50,5 49,0 52,1 57,5 70,6 67,5 75,2 84,1 91,7
Total (22°C-50%) kW 37,4 40,0 44,3 43,8 47,1 51,6 54,0 48,1 55,0 61,5 75,4 68,3 80,4 89,8 96,9
Sensible (22°C-50%) kW 34,6 37,0 41,0 40,5 43,6 47,7 50,0 44,5 50,9 56,9 69,7 63,2 74,3 83,1 89,6
Nominal absorbed power. 3) kW 8,8 10,3 11,2 10,0 11,8 13,2 14,2 11,2 13,2 15,0 20,0 15,6 20,1 23,4 24,0
Nominal absorbed current. 3) A 16,1 19,4 22,0 19,6 23,0 25,8 26,0 22,8 25,8 27,8 39,4 29,6 39,4 43,6 41,8
Cooling capacity 2) R 407 C
Total (27°C-50%) kW 40,7 43,6 48,3 47,8 51,4 56,3 58,9 52,4 60,0 67,0 82,2 74,5 87,6 97,9 106
Sensible (27°C-50%) kW 33,4 35,7 39,6 39,2 42,1 46,1 48,3 43,0 49,2 54,9 67,4 61,1 71,8 80,3 86,6
Total (24°C-50%) kW 37,4 40,0 44,3 43,8 47,1 51,6 54,0 48,1 55,0 61,5 75,4 68,3 80,4 89,8 96,9
Sensible (24°C-50%) kW 33,6 36,0 39,9 39,4 42,4 46,5 48,6 47,1 50,1 55,3 67,9 64,9 72,3 80,8 87,2
Total (22°C-50%) kW 35,9 38,4 42,6 42,1 45,3 49,6 51,9 46,2 52,9 59,1 72,5 65,7 77,3 86,4 93,2
Sensible (22°C-50%) kW 33,3 35,6 39,4 39,0 41,9 45,9 48,0 42,8 49,0 54,7 67,1 60,8 71,5 79,9 86,2
Nominal absorbed power. 3) kW 9,1 10,7 11,6 10,4 12,2 13,7 14,7 11,6 13,7 15,6 20,8 16,2 20,9 24,3 24,9
Nominal absorbed current. 3) A 16,7 20,2 22,9 20,4 23,9 26,8 27,0 23,7 26,8 28,9 41,0 30,8 41,0 45,3 43,5
SCROLL Compressors
standard number n.° 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
Standard choking n.° G2
Max absorbed current. A 23 34 34 26 38 40 50 29 40 50 70 40 70 70 56
Inrush current 5) A 67 79 90 91 90 117 109 92 117 110 160 117 160 162 172
CENTRIFUGAL fans
Number n.° 2 2 2 2 2 2 2 3 3 3 3 4 4 4 4
Air flow rate l/s 2722 2722 2722 2920 2920 2920 2920 3950 3950 4170 4170 5277 5277 5277 6670
Air flow rate mc/h 9799 9799 9799 10512 10512 10512 10512 14220 14220 15012 15012 18997 18997 18997 24012
Ext avaible pressure std 7) Pa 60 55 30 40 40 40 40 45 45 45 45 40 40 35 35
Higher avaible pressure 1M Pa 125 120 95 90 90 90 90 85 85 195 195 80 80 75 180
Higher avaible pressure 2M Pa 230 225 200 230 230 230 230 250 250 265 265 245 245 240 250
Higher avaible pressure 3M Pa 280 275 250 315 315 315 315 310 310 380 380 315 315 310 nd
Higher avaible pressure 4M Pa 330 325 300 430 430 430 430 400 400 nd nd 395 395 390 nd
Higher avaible pressure 5M Pa 450 445 420 nd nd nd nd nd nd nd nd nd nd nd nd
Max absorbed power. 8) W 2178 2178 2178 2244 2244 2244 2244 3366 3366 6664 6664 4488 4488 4488 10662
Max absorbed current.8) A 13,2 13,2 13,2 13,6 13,6 13,6 13,6 20,4 20,4 13,5 13,5 27,2 27,2 27,2 21,6
Humidifier
Max steam prodution kg/h 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13
Max absorbed power kW 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4
Max absorbed current A 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7
Electric heater
Capacity kW 13,5 13,5 13,5 13,5 13,5 13,5 13,5 18 18 18 18 18 18 18 18
Steps n.° 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3
Absorbed current A 19,9 19,9 19,9 19,9 19,9 19,9 19,9 26,6 26,6 26,6 26,6 26,6 26,6 26,6 26,6
Warm water coil 4)
Capacity kW 22 22 22 24 24 24 24 25 25 25 25 35 35 35 35
Water flow rate l/s 0,35 0,35 0,35 0,38 0,38 0,38 0,38 0,41 0,41 0,41 0,41 0,6 0,6 0,6 0,6
Pressure drop (coil + valve) kPa 57 57 57 47 47 47 47 25 25 25 25 46 46 46 46
Hot gas coil
Capacity kW 17 17 17 18 18 18 18 17 17 17 17 21 21 21 21
Sound pressure level 5)
Version D dB(A) 58 58 58 57 57 57 57 59 59 59 59 60 60 60 61
Dimensions - Weight
Length mm 1730 1730 1730 1990 1990 1990 1990 2390 2390 2390 2390 2950 2950 2950 2950
Width mm 815 815 815 815 815 815 815 815 815 815 815 815 815 815 815
Height mm 1995 1995 1995 1995 1995 1995 1995 1995 1995 1995 1995 1995 1995 1995 1995
Weight kg 400 410 425 450 460 475 490 515 520 530 540 565 580 595 610
Power supply 400V-50Hz-3F+T+N
Remote consenser stand. 6) CR 2*CR26 2*CR26 2*CR29 2*CR 26 2*CR35 2*CR35 2*CR35 2*CR35 2*CR35 2*CR45 2*CR52 2*CR52 2*CR52 2*CR58 2*CR58
Silenced remote condenser. 6) CRS 2*CRS24 2*CRS28 2*CRS28 2*CRS28 2*CRS34 2*CRS34 2*CRS34 2*CRS34 2*CRS34 2*CRS41 2*CRS56 2*CRS56 2*CRS56 2*CRS56 2*CRS66
Ultrasilenced remote condenser 6 CRU 2*CRU22 2*CRU33 2*CRU33 2*CRU33 2*CRU33 2*CRU44 2*CRU44 2*CRU33 2*CRU44 2*CRU44 2*CRU50 2*CRU50 2*CRU50 2*CRU67 2*CRU67
MILLENNIUM E 07/02
PRECISION AIR CONDITIONING UNITS - DIRECT EXPANSION - R22 - R407C - Versions U,V,B
MILLENNIUM E 07/02
PRECISION AIR CONDITIONING UNITS - DIRECT EXPANSION - R22 - R407C - Versions U,V,B
MODEL ED…W 221 241 251 291 301 341 321 361 451 351 431 531
Size M1 M1 M1 M1 M1 M1 M2 M2 M2 M3 M3 M3
Cooling capacity 1) R 22
Total (27°C-50%) kW 22,7 24,8 26,1 29,9 32,6 36,8 33,1 37,4 47,3 37,1 45,3 53,0
Sensible (27°C-50%) kW 18,4 20,1 21,1 24,2 26,4 29,8 26,8 30,3 38,3 30,1 36,7 43,0
Total (24°C-50%) kW 21,4 23,4 24,6 28,2 30,8 34,7 31,3 35,3 44,6 35,0 42,7 50,0
Sensible (24°C-50%) kW 18,4 20,1 21,2 24,2 26,5 29,8 26,9 30,3 38,4 30,1 36,7 43,0
Total (22°C-50%) kW 20,4 22,2 23,4 26,8 29,3 33,0 29,8 33,6 42,5 33,4 40,7 47,6
Sensible (22°C-50%) kW 19,0 20,7 21,8 24,9 27,3 30,7 27,7 31,2 39,5 31,0 37,8 44,3
Nominal absorbed power. 2) kW 4,0 4,4 5,0 5,6 6,0 6,9 6,0 6,8 8,8 6,8 9,2 10,4
Nominal absorbed current. 2) A 7,1 8,7 9,8 10,4 11,5 13,3 11,4 13,0 17,3 13,0 17,5 19,3
Cooling capacity 1) R 407 C
Total (27°C-50%) kW 21,8 23,8 25,1 28,7 31,4 35,4 31,9 36,0 45,5 35,7 43,6 51,0
Sensible (27°C-50%) kW 17,9 19,5 20,6 23,6 25,8 29,0 26,1 29,5 37,4 29,3 35,7 41,9
Total (24°C-50%) kW 20,6 22,5 23,7 27,1 29,6 33,4 30,1 33,9 43,0 33,7 41,1 48,1
Sensible (24°C-50%) kW 17,7 19,3 20,4 23,3 25,5 28,7 25,9 29,2 37,0 29,0 35,3 41,4
Total (22°C-50%) kW 19,6 21,4 22,6 25,8 28,2 31,8 28,6 32,3 40,9 32,1 39,1 45,9
Sensible (22°C-50%) kW 18,1 19,7 20,8 23,7 26,0 29,3 26,4 29,7 37,7 29,5 36,0 42,2
Nominal absorbed power. 2) kW 4,1 4,6 5,1 5,8 6,2 7,2 6,2 7,0 9,2 7,0 9,6 10,8
Nominal absorbed current. 2) A 7,4 9,0 10,2 10,9 12,0 13,8 11,9 13,6 18,0 13,6 18,2 20,1
SCROLL Compressors
Standard number n.° 1 1 1 1 1 1 1 1 1 1 1 1
Optional number n.° nd nd nd 2 2 2 2 2 2 2 2 2
Capacity steps(1 compr.) n.° 1 1 1 1 1 1 1 1 1 1 1 1
Capacity steps (2 compr.) n.° nd nd nd 2 2 2 2 2 2 2 2 2
Hot gas by - pass 3) n.° 1 1 1 1 1 1 1 1 1 1 1 1
Max absorbed current. A 11,4 13 17 20 17,9 19,2 20 29 26 29 35 35
Inrush current 3) A 63 86 83 53 105 114 111 111 96 111 149 149
Water flow rate at condenser l/s 1,21 1,33 1,41 1,61 1,76 1,99 1,78 2,01 2,56 2,00 2,48 2,89
Pressure drop kPa 10 48 55 45 51 47 51 47 59 47 59 60
Centrifugal fans
Number n.° 2 2 2 2 2 2 2 2 2 2 2 2
Air flow rate l/s 1480 1480 1480 1480 1700 1700 2222 2222 2222 2722 2722 2722
Air flow rate mc/h 5328 5328 5328 5328 6120 6120 7999 7999 7999 9799 9799 9799
Ext avaible pressure 6) Pa 75 75 75 60 70 70 165 165 150 70 65 40
Higher avaible pressure 1M Pa 200 200 200 185 155 155 185 185 170 135 130 105
Higher avaible pressure 2M Pa 245 245 245 230 250 250 235 235 220 240 235 210
Higher avaible pressure 3M Pa 265 265 265 250 300 300 335 335 320 290 285 260
Higher avaible pressure 4M Pa 355 355 355 340 360 360 375 375 360 340 335 310
Higher avaible pressure 5M Pa 405 405 405 390 nd nd nd nd nd 460 455 430
Max absorbed power. 7) W 891 891 891 891 1518 1518 2468 2468 2468 2178 2178 2178
Max absorbed current.7) A 5,4 5,4 5,4 5,4 9,2 9,2 5 5 5 13,2 13,2 13,2
Humidifier
Max steam prodution kg/h 5 5 5 5 5 5 5 5 5 13 13 13
Max absorbed power kW 3,7 3,7 3,7 3,7 3,7 3,7 3,7 3,7 3,7 9,4 9,4 9,4
Max absorbed current A 9,7 9,7 9,7 9,7 9,7 9,7 9,7 9,7 9,7 24,7 24,7 24,7
Electric heater
Capacity kW 9 9 9 9 9 9 9 9 9 13,5 13,5 13,5
Steps n.° 3 3 3 3 3 3 3 3 3 3 3 3
Absorbed current A 13,3 13,3 13,3 13,3 13,3 13,3 13,3 13,3 13,3 19,9 19,9 19,9
Warm water coil 4)
Capacity kW 15 15 15 15 15 15 19 19 19 22 22 22
Water flow rate l/s 0,24 0,24 0,24 0,24 0,24 0,24 0,3 0,3 0,3 0,4 0,4 0,4
Pressure drop (coil + valve) kPa 35 35 35 35 35 35 11 11 11 37 37 37
Hot gas coil
Capacity kW 11 11 11 11 11 11 17 17 17 17 17 17
Sound pressure level 5)
Version U, B dB(A) 51 51 52 52 53 53 61 62 62 61 61 61
Version V dB(A) 48 48 48 48 49 49 58 58 58 57 57 57
Dimensions - Weight
Length mm 1230 1230 1230 1230 1230 1230 1530 1530 1530 1730 1730 1730
Width mm 665 665 665 665 665 665 665 665 665 815 815 815
Height mm 1975 1975 1975 1975 1975 1975 1975 1975 1975 1995 1995 1995
Weight kg 310 318 326 333 338 346 348 367 378 396 403 431
Power supply 400V-50Hz-3F+T+N
MILLENNIUM E 07/02
PRECISION AIR CONDITIONING UNITS - DIRECT EXPANSION - R22 - R407C - Versions U,V,B
MILLENNIUM E 07/02
PRECISION AIR CONDITIONING UNITS - DIRECT EXPANSION - R22 - R407C - Versions U,V,B
MODEL ED.W 172 192 202 232 272 342 302 362 442
Size L3 L3 M1 M1 M1 M1 M2 M2 M2
Cooling capacity 1) R 22
Total (27°C-50%) kW 17,6 19,7 21,7 24,5 27,9 35,7 32,3 38,2 47,3
Sensible (27°C-50%) kW 14,3 16,0 17,6 19,9 22,6 28,9 26,1 31,0 38,3
Total (24°C-50%) kW 16,6 18,6 20,5 23,1 26,3 33,7 30,5 36,1 44,6
Sensible (24°C-50%) kW 14,3 16,0 17,6 19,9 22,6 28,9 26,2 31,0 38,4
Total (22°C-50%) kW 15,8 17,7 19,5 22,0 25,1 32,1 29,0 34,3 42,5
Sensible (22°C-50%) kW 14,7 16,5 18,1 20,5 23,3 29,8 27,0 31,9 39,5
Nominal absorbed power. 2) kW 3,2 3,8 3,8 4,4 5,5 6,7 5,6 6,7 8,7
Nominal absorbed current. 2) A 6,0 7,1 7,2 8,1 10,6 13,3 10,3 13,5 17,3
Cooling capacity 1) R 407 C
Total (27°C-50%) kW 16,9 18,9 20,9 23,6 26,8 34,3 31,0 36,8 45,5
Sensible (27°C-50%) kW 13,9 15,5 17,1 19,3 22,0 28,1 25,5 30,1 37,3
Total (24°C-50%) kW 16,0 17,9 19,7 22,2 25,3 32,4 29,3 34,7 42,9
Sensible (24°C-50%) kW 13,7 15,4 16,9 19,1 21,8 27,8 25,2 29,8 36,9
Total (22°C-50%) kW 15,2 17,0 18,8 21,2 24,1 30,8 27,9 33,0 40,9
Sensible (22°C-50%) kW 14,0 15,7 17,3 19,5 22,2 28,4 25,7 30,4 37,6
Nominal absorbed power. 2) kW 3,3 3,9 3,9 4,6 5,7 7,0 5,8 7,0 9,0
Nominal absorbed current. 2) A 6,3 7,4 7,5 8,5 11,1 13,8 10,7 14,0 18,0
SCROLL Compressors
Standard number n.° 2 2 2 2 2 2 2 2 2
Capacity steps (2 compr) n.° G2
Max absorbed current. A 10 12 10 12 16 20 20 20 26
Inrush current A 29 36 36 42 48 60 46 60 91
Water flow rate at condenser l/s 0,95 1,07 1,16 1,32 1,52 1,93 1,72 2,04 2,55
Pressure drop kPa 44 38 38 8 8 8 8 8 48
Centrifugal fans
Number n.° 1 1 2 2 2 2 2 2 2
Air flow rate l/s 890 890 1480 1480 1480 1700 2222 2222 2222
Air flow rate mc/h 3204 3204 5328 5328 5328 6120 7999 7999 7999
Ext avaible pressure 5) Pa 70 70 75 75 75 70 165 165 150
Higher avaible pressure 1M Pa 120 120 200 200 200 155 185 185 170
Higher avaible pressure 2M Pa 200 200 245 245 245 250 235 235 220
Higher avaible pressure 3M Pa 290 290 265 265 265 300 335 335 320
Higher avaible pressure 4M Pa 353 353 355 355 355 360 375 375 360
Higher avaible pressure 5M Pa 420 420 405 405 405 nd nd nd nd
Max absorbed power. 6) W 627 627 891 891 891 1518 2468 2468 2468
Max absorbed current.6) A 3,8 3,8 5,4 5,4 5,4 9,2 5 5 5
Humidifier
Max steam prodution kg/h 5 5 5 5 5 5 5 5 5
Max absorbed power kW 3,7 3,7 3,7 3,7 3,7 3,7 3,7 3,7 3,7
Max absorbed current A 9,7 9,7 9,7 9,7 9,7 9,7 9,7 9,7 9,7
Electric heater
Capacity kW 6 6 9 9 9 9 9 9 9
Steps n.° 1 1 3 3 3 3 3 3 3
Absorbed current A 13,3 13,3 13,3 13,3 13,3 13,3 13,3 13,3 13,3
Warm water coil 3)
Capacity kW 11 11 15 15 15 15 19 19 19
Water flow rate l/s 0,18 0,18 0,24 0,24 0,24 0,24 0,3 0,3 0,3
Pressure drop (coil + valve) kPa 4 4 35 35 35 35 11 11 11
Hot gas coil
Capacity kW 9 9 11 11 11 11 17 17 17
Sound pressure level 4)
Version V,U dB(A) 51 51 52 52 52 52 59 59 59
Version B dB(A) 49 49 50 50 50 50 57 57 57
Dimensions - Weight
Length mm 940 940 1230 1230 1230 1230 1530 1530 1530
Width mm 565 565 665 665 665 665 665 665 665
Height mm 1800 1800 1975 1975 1975 1975 1975 1975 1975
Weight kg 299 310 331 343 350 358 375 386 397
Power supply 400V-50Hz-3F+T+N
MILLENNIUM E 07/02
PRECISION AIR CONDITIONING UNITS - DIRECT EXPANSION - R22 - R407C - Versions U,V,B
MODEL ED.W 412 452 492 482 532 572 602 542 622 682 842 762 892 1002 1102
Size M3 M3 M3 M4 M4 M4 M4 M5 M5 M5 M5 M6 M6 M6 M6
Cooling capacity 1) R 22
Total (27°C-50%) kW 43,7 46,7 51,8 51,2 55,1 60,3 63,1 56,2 64,3 71,8 88,1 79,8 93,9 105,0 113,2
Sensible (27°C-50%) kW 35,4 37,8 42,0 41,5 44,6 48,9 51,1 45,5 52,1 58,2 71,4 64,7 76,1 85,0 91,7
Total (24°C-50%) kW 41,2 44,1 48,9 48,3 52,0 56,9 59,5 53,0 60,7 67,8 83,1 75,3 88,6 99,0 106,8
Sensible (24°C-50%) kW 35,4 37,9 42,0 41,5 44,7 48,9 51,2 45,6 52,2 58,3 71,5 64,8 76,2 85,2 91,9
Total (22°C-50%) kW 39,3 42,0 46,6 46,0 49,5 54,2 56,7 50,5 57,8 64,5 79,2 71,7 84,4 94,3 101,7
Sensible (22°C-50%) kW 36,5 39,0 43,3 42,8 46,0 50,4 52,7 46,9 53,7 60,0 73,6 66,7 78,5 87,7 94,6
Nominal absorbed power. 2) kW 7,8 9,1 9,9 8,8 10,4 11,7 12,6 9,9 11,7 13,3 17,7 13,8 17,8 20,7 21,2
Nominal absorbed current. 2) A 14,2 17,2 19,5 17,3 20,4 22,8 23,0 20,2 22,8 24,6 34,9 26,2 34,9 38,6 37,0
Cooling capacity 1) R 407 C
Total (27°C-50%) kW 42,0 44,9 49,8 49,2 53,0 58,0 60,7 54,0 61,8 69,1 84,7 76,8 90,3 101 109
Sensible (27°C-50%) kW 34,4 36,8 40,9 40,4 43,4 47,6 49,8 44,3 50,7 56,6 69,5 63,0 74,1 82,8 89,3
Total (24°C-50%) kW 39,6 42,4 47,0 46,5 50,0 54,7 57,2 51,0 58,3 65,2 79,9 72,4 85,2 95,2 103
Sensible (24°C-50%) kW 34,1 36,4 40,4 39,9 43,0 47,0 49,2 43,8 50,2 56,0 68,7 62,3 73,3 81,9 88,3
Total (22°C-50%) kW 37,7 40,4 44,8 44,2 47,6 52,1 54,5 48,5 55,6 62,1 76,1 69,0 81,1 90,7 97,8
Sensible (22°C-50%) kW 34,7 37,1 41,2 40,7 43,8 47,9 50,2 44,7 51,1 57,1 70,0 63,5 74,7 83,4 90,0
Nominal absorbed power. 2) kW 8,1 9,5 10,3 9,2 10,8 12,1 13,0 10,3 12,1 13,8 18,4 14,3 18,5 21,5 22,0
Nominal absorbed current. 2) A 14,8 17,9 20,2 18,0 21,2 23,7 23,9 21,0 23,7 25,6 36,3 27,2 36,3 40,1 38,5
SCROLL Compressors
Standard number n.° 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
Capacity steps (2 comprer) n.° G2
Max absorbed current. A 23 34 34 26 38 40 50 29 40 50 70 40 70 70 56
Inrush current A 67 79 90 91 90 117 109 92 117 110 160 117 160 162 172
Water flow rate at condenser l/s 2,34 2,54 2,81 2,73 2,98 3,28 3,44 3,01 3,46 3,87 4,82 4,26 5,08 5,72 6,12
Pressure drop kPa 10 48 55 48 55 52 48 55 52 48 58 48 58 60 60
Centrifugal fans
Number n.° 2 2 2 2 2 2 2 3 3 3 3 4 4 4 4
Air flow rate l/s 2722 2722 2722 2920 2920 2920 2920 3950 3950 4170 4170 5280 5280 5280 6670
Air flow rate mc/h 9799 9799 9799 10512 10512 10512 10512 14220 14220 15012 15012 19008 19008 19008 24012
Ext avaible pressure 5) Pa 70 65 40 65 65 65 65 55 55 70 70 55 55 50 75
Higher avaible pressure 1M Pa 135 130 105 110 110 110 110 95 95 215 215 95 95 90 220
Higher avaible pressure 2M Pa 240 235 210 250 250 250 250 260 260 290 290 260 260 255 290
Higher avaible pressure 3M Pa 290 285 260 335 335 335 335 320 320 405 405 330 330 325 nd
Higher avaible pressure 4M Pa 340 335 310 450 450 450 450 410 410 nd nd 410 410 405 nd
Higher avaible pressure 5M Pa 460 455 430 nd nd nd nd nd nd nd nd nd nd nd nd
Max absorbed power. 6) W 2178 2178 2178 2244 2244 2244 2244 3366 3366 6664 6664 4488 4488 4488 10662
Max absorbed current.6) A 13,2 13,2 13,2 13,6 13,6 13,6 13,6 20,4 20,4 13,5 13,5 27,2 27,2 27,2 21,6
Humidifier
Max steam prodution kg/h 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13
Max absorbed power kW 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4
Max absorbed current A 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7
Electric heater
Capacity kW 13,5 13,5 13,5 13,5 13,5 13,5 13,5 18 18 18 18 18 18 18 18
Steps n.° 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3
Absorbed current A 19,9 19,9 19,9 19,9 19,9 19,9 19,9 26,6 26,6 26,6 26,6 26,6 26,6 26,6 26,6
Warm water coil 3)
Capacity kW 22 22 22 24 24 24 24 25 25 25 25 35 35 35 35
Water flow rate l/s 0,35 0,35 0,35 0,38 0,38 0,38 0,38 0,41 0,41 0,41 0,41 0,6 0,6 0,6 0,6
Pressure drop (coil + valve) kPa 37 37 37 17 17 17 17 10 10 10 10 21 21 21 21
Hot gas coil
Capacity kW 17 17 17 18 18 18 18 17 17 17 17 21 21 21 21
Sound pressure level 4)
Version V,U dB(A) 61 61 61 59 59 59 59 62 62 62 62 64 64 64 65
Version B dB(A) 58 58 58 57 57 57 57 59 59 59 59 60 60 60 61
Dimensions - Weight
Length mm 1730 1730 1730 1990 1990 1990 1990 2390 2390 2390 2390 2950 2950 2950 2950
Width mm 815 815 815 815 815 815 815 815 815 815 815 815 815 815 815
Height mm 1995 1995 1995 1995 1995 1995 1995 1995 1995 1995 1995 1995 1995 1995 1995
Weight kg 417 432 447 472 482 502 517 537 547 561 576 596 616 631 646
Power supply 400V-50Hz-3F+T+N
MILLENNIUM E 07/02
PRECISION AIR CONDITIONING UNITS - DIRECT EXPANSION - R22 - R407C - Versions D
MILLENNIUM E 07/02
PRECISION AIR CONDITIONING UNITS - DIRECT EXPANSION - R22 - R407C - Versions D
MODEL ED.W 221 241 251 291 301 341 321 361 451 351 431 531
Size M1 M1 M1 M1 M1 M1 M2 M2 M2 M3 M3 M3
Cooling capacity 1) R 22
Total (27°C-50%) kW 22,7 24,8 26,1 29,9 32,6 36,8 33,1 37,4 47,3 37,1 45,3 53,0
Sensible (27°C-50%) kW 18,4 20,1 21,1 24,2 26,4 29,8 26,8 30,3 38,3 30,1 36,7 43,0
Total (24°C-50%) kW 21,4 23,4 24,6 28,2 30,8 34,7 31,3 35,3 44,6 35,0 42,7 50,0
Sensible (24°C-50%) kW 18,4 20,1 21,2 24,2 26,5 29,8 26,9 30,3 38,4 30,1 36,7 43,0
Total (22°C-50%) kW 20,4 22,2 23,4 26,8 29,3 33,0 29,8 33,6 42,5 33,4 40,7 47,6
Sensible (22°C-50%) kW 19,0 20,7 21,8 24,9 27,3 30,7 27,7 31,2 39,5 31,0 37,8 44,3
Nominal absorbed power. 2) kW 4,0 4,4 5,0 5,6 6,0 6,9 6,0 6,8 8,8 6,8 9,2 10,4
Nominal absorbed current. 2) A 7,1 8,7 9,8 10,4 11,5 13,3 11,4 13,0 17,3 13,0 17,5 19,3
Cooling capacity 1) R 407 C
Total (27°C-50%) kW 21,8 23,8 25,1 28,7 31,4 35,4 31,9 36,0 45,5 35,7 43,6 51,0
Sensible (27°C-50%) kW 17,9 19,5 20,6 23,6 25,8 29,0 26,1 29,5 37,4 29,3 35,7 41,9
Total (24°C-50%) kW 20,6 22,5 23,7 27,1 29,6 33,4 30,1 33,9 43,0 33,7 41,1 48,1
Sensible (24°C-50%) kW 17,7 19,3 20,4 23,3 25,5 28,7 25,9 29,2 37,0 29,0 35,3 41,4
Total (22°C-50%) kW 19,6 21,4 22,6 25,8 28,2 31,8 28,6 32,3 40,9 32,1 39,1 45,9
Sensible (22°C-50%) kW 18,1 19,7 20,8 23,7 26,0 29,3 26,4 29,7 37,7 29,5 36,0 42,2
Nominal absorbed power. 2) kW 4,1 4,6 5,1 5,8 6,2 7,2 6,2 7,0 9,2 7,0 9,6 10,8
Nominal absorbed current. 2) A 7,4 9,0 10,2 10,9 12,0 13,8 11,9 13,6 18,0 13,6 18,2 20,1
SCROLL Compressors
Standard number n.° 1 1 1 1 1 1 1 1 1 1 1 1
Capacity steps n.° 1 1 1 1 1 1 1 1 1 1 1 1
Hot gas by - pass 3) n.° 1 1 1 1 1 1 1 1 1 1 1 1
Max absorbed current. A 11,4 13 17 20 17,9 19,2 20 29 26 29 35 35
Inrush current A 63 86 83 53 105 114 111 111 96 111 149 149
Water flow rate at condenser l/s 1,21 1,33 1,41 1,61 1,76 1,99 1,78 2,01 2,56 2,00 2,48 2,89
Pressure drop kPa 10 48 55 45 51 47 51 47 59 47 59 60
Centrifugal fans
Number n.° 1 1 1 1 1 1 2 2 2 2 2 2
Air flow rate l/s 1480 1480 1480 1480 1700 1700 2222 2222 2222 2722 2722 2722
Air flow rate mc/h 5328 5328 5328 5328 6120 6120 7999 7999 7999 9799 9799 9799
Ext avaible pressure 6) Pa 80 80 80 60 60 60 50 50 35 60 55 30
Higher avaible pressure 1M Pa 210 210 210 190 90 90 95 95 80 125 120 95
Higher avaible pressure 2M Pa 242 242 242 220 255 255 195 195 180 230 225 200
Higher avaible pressure 3M Pa 400 400 400 380 310 310 235 235 220 280 275 250
Higher avaible pressure 4M Pa nd nd nd nd nd nd nd nd nd 330 325 300
Higher avaible pressure 5M Pa nd nd nd nd nd nd nd nd nd 450 445 420
Max absorbed power. 7) W 2123 2123 2123 2123 2764 2764 2145 2145 2145 2178 2178 2178
Max absorbed current.7) A 4,3 4,3 4,3 4,3 5,6 5,6 13 13 13 13,2 13,2 13,2
Humidifier
Max steam prodution kg/h 5 5 5 5 5 5 5 5 5 13 13 13
Max absorbed power kW 3,7 3,7 3,7 3,7 3,7 3,7 3,7 3,7 3,7 9,4 9,4 9,4
Max absorbed current A 9,7 9,7 9,7 9,7 9,7 9,7 9,7 9,7 9,7 24,7 24,7 24,7
Electric heater
Capacity kW 9 9 9 9 9 9 9 9 9 13,5 13,5 13,5
Steps n.° 3 3 3 3 3 3 3 3 3 3 3 3
Absorbed current A 13,3 13,3 13,3 13,3 13,3 13,3 13,3 13,3 13,3 19,9 19,9 19,9
Warm water coil 4)
Capacity kW 15 15 15 15 15 15 19 19 19 22 22 22
Water flow rate l/s 0,24 0,24 0,24 0,24 0,24 0,24 0,3 0,3 0,3 0,4 0,4 0,4
Pressure drop (coil + valve) kPa 48 48 48 48 48 48 27 27 27 57 57 57
Hot gas coil
Capacity kW 11 11 11 11 11 11 17 17 17 17 17 17
Sound pressure level 5)
Version D dB(A) 58 58 58 58 56 56 58 58 58 57 57 57
Dimensions - Weight
Length mm 1230 1230 1230 1230 1230 1230 1530 1530 1530 1730 1730 1730
Width mm 665 665 665 665 665 665 665 665 665 815 815 815
Height mm 1975 1975 1975 1975 1975 1975 1975 1975 1975 1995 1995 1995
Weight kg 310 318 326 333 338 346 348 367 378 396 403 431
Power supply 400V-50Hz-3F+T+N
MILLENNIUM E 07/02
PRECISION AIR CONDITIONING UNITS - DIRECT EXPANSION - R22 - R407C - Versions D
MILLENNIUM E 07/02
PRECISION AIR CONDITIONING UNITS - DIRECT EXPANSION - R22 - R407C - Versions D
MODEL ED.W 172 192 202 232 272 342 302 362 442
Size L3 L3 M1 M1 M1 M1 M2 M2 M2
Cooling capacity 1) R 22
Total (27°C-50%) kW 17,6 19,7 21,7 24,5 27,9 35,7 32,3 38,2 47,3
Sensible (27°C-50%) kW 13,4 15,0 16,5 18,6 21,2 27,1 24,5 29,1 36,0
Total (24°C-50%) kW 16,6 18,6 20,5 23,1 26,3 33,7 30,5 36,1 44,6
Sensible (24°C-50%) kW 14,9 16,7 18,4 20,8 23,7 30,3 27,4 32,5 40,2
Total (22°C-50%) kW 15,8 17,7 19,5 22,0 25,1 32,1 29,0 34,3 42,5
Sensible (22°C-50%) kW 13,1 14,7 16,2 18,3 20,8 26,6 24,1 28,5 35,3
Nominal absorbed power. 2) kW 3,2 3,8 3,8 4,4 5,5 6,7 5,6 6,7 8,7
Nominal absorbed current. 2) A 6,0 7,1 7,2 8,1 10,6 13,3 10,3 13,5 17,3
Cooling capacity 2) R 407 C
Total (27°C-50%) kW 16,9 18,9 20,9 23,6 26,8 34,3 31,0 36,8 45,5
Sensible (27°C-50%) kW 14,0 15,7 17,3 19,5 22,2 28,4 25,7 30,4 37,7
Total (24°C-50%) kW 16,0 17,9 19,7 22,2 25,3 32,4 29,3 34,7 42,9
Sensible (24°C-50%) kW 13,8 15,5 17,1 19,3 22,0 28,1 25,4 30,1 37,2
Total (22°C-50%) kW 15,2 17,0 18,8 21,2 24,1 30,8 27,9 33,0 40,9
Sensible (22°C-50%) kW 14,3 16,0 17,6 19,9 22,6 28,9 26,2 31,0 38,4
Nominal absorbed power. 2) kW 3,3 3,9 3,9 4,6 5,7 7,0 5,8 7,0 9,0
Nominal absorbed current. 2) A 6,3 7,4 7,5 8,5 11,1 13,8 10,7 14,0 18,0
SCROLL Compressors
Standard number n.° 2 2 2 2 2 2 2 2 2
Capacity steps (2 compress.) n.° G2
Max absorbed current. A 10 12 10 12 16 20 20 20 26
Inrush current A 29 36 36 42 48 60 46 60 91
Water flow rate at condenser l/s 0,95 1,07 1,16 1,32 1,52 1,93 1,72 2,04 2,55
Pressure drop kPa 44 38 38 8 8 8 8 8 48
Centrifugal fans
Number n.° 1 1 1 1 1 1 2 2 2
Air flow rate l/s 890 890 1480 1480 1480 1700 2222 2222 2222
Air flow rate mc/h 3204 3204 5328 5328 5328 6120 7999 7999 7999
Ext avaible pressure 5) Pa 90 90 80 80 80 60 50 50 35
Higher avaible pressure 1M Pa 170 170 210 210 210 90 95 95 80
Higher avaible pressure 2M Pa 260 260 242 242 242 255 195 195 180
Higher avaible pressure 3M Pa 320 320 400 400 400 310 235 235 220
Higher avaible pressure 4M Pa 390 390 nd nd nd nd 275 275 260
Higher avaible pressure 5M Pa 457 457 nd nd nd nd nd nd nd
Max absorbed power. 6) W 627 627 2123 2123 2123 2764 2468 2468 2468
Max absorbed current.6) A 3,8 3,8 4,3 4,3 4,3 5,6 5 5 5
Humidifier
Max steam prodution kg/h 5 5 5 5 5 5 5 5 5
Max absorbed power kW 3,7 3,7 3,7 3,7 3,7 3,7 3,7 3,7 3,7
Max absorbed current A 9,7 9,7 9,7 9,7 9,7 9,7 9,7 9,7 9,7
Electric heater
Capacity kW 6 6 9 9 9 9 9 9 9
Steps n.° 1 1 3 3 3 3 3 3 3
Absorbed current A 13,3 13,3 13,3 13,3 13,3 13,3 13,3 13,3 13,3
Warm water coil 3)
Capacity kW 11 11 15 15 15 15 19 19 19
Water flow rate l/s 0,18 0,18 0,24 0,24 0,24 0,24 0,3 0,3 0,3
Pressure drop (coil + valve) kPa 21 21 48 48 48 48 27 27 27
Hot gas coil
Capacity kW 9 9 11 11 11 11 17 17 17
Sound pressure level 4)
Version D db(A) 49 49 60 60 60 57 57 57 57
Dimensions - Weight
Length mm 940 940 1230 1230 1230 1230 1530 1530 1530
Width mm 565 565 665 665 665 665 665 665 665
Height mm 1800 1800 1975 1975 1975 1975 1975 1975 1975
Weight kg 299 310 331 343 350 358 375 386 397
Power supply 400V-50Hz-3F+T+N
MILLENNIUM E 07/02
PRECISION AIR CONDITIONING UNITS - DIRECT EXPANSION - R22 - R407C - Versions D
MODEL ED.W 412 452 492 482 532 572 602 542 622 682 842 762 892 1002 1102
Size M3 M3 M3 M4 M4 M4 M4 M5 M5 M5 M5 M6 M6 M6 M6
Cooling capacity 1) R 22
Total (27°C-50%) kW 43,7 46,7 51,8 51,2 55,1 60,3 63,1 56,2 64,3 71,8 88,1 79,8 93,9 105,0 113,2
Sensible (27°C-50%) kW 33,2 35,5 39,4 38,9 41,9 45,8 48,0 42,7 48,9 54,6 67,0 60,7 71,4 79,8 86,0
Total (24°C-50%) kW 41,2 44,1 48,9 48,3 52,0 56,9 59,5 53,0 60,7 67,8 83,1 75,3 88,6 99,0 106,8
Sensible (24°C-50%) kW 37,1 39,7 44,0 43,5 46,8 51,2 53,6 47,7 54,6 61,0 74,8 67,8 79,7 89,1 96,1
Total (22°C-50%) kW 39,3 42,0 46,6 46,0 49,5 54,2 56,7 50,5 57,8 64,5 79,2 71,7 84,4 94,3 101,7
Sensible (22°C-50%) kW 32,6 34,8 38,6 38,2 41,1 45,0 47,1 41,9 48,0 53,6 65,7 59,5 70,0 78,3 84,4
Nominal absorbed power. 2) kW 7,8 9,1 9,9 8,8 10,4 11,7 12,6 9,9 11,7 13,3 17,7 13,8 17,8 20,7 21,2
Nominal absorbed current. 2) A 14,2 17,2 19,5 17,3 20,4 22,8 23,0 20,2 22,8 24,6 34,9 26,2 34,9 38,6 37,0
Cooling capacity 1) R 407 C
Total (27°C-50%) kW 42,0 44,9 49,8 49,2 53,0 58,0 60,7 54,0 61,8 69,1 84,7 76,8 90,3 101 109
Sensible (27°C-50%) kW 34,8 37,2 41,3 40,8 43,9 48,0 50,2 44,7 51,2 57,2 70,1 63,6 74,8 83,6 90,1
Total (24°C-50%) kW 39,6 42,4 47,0 46,5 50,0 54,7 57,2 51,0 58,3 65,2 79,9 72,4 85,2 95,2 103
Sensible (24°C-50%) kW 34,4 36,7 40,8 40,3 43,3 47,4 49,6 44,2 50,6 56,5 69,3 62,8 73,9 82,6 89,0
Total (22°C-50%) kW 37,7 40,4 44,8 44,2 47,6 52,1 54,5 48,5 55,6 62,1 76,1 69,0 81,1 90,7 97,8
Sensible (22°C-50%) kW 35,4 37,9 42,0 41,5 44,6 48,9 51,1 45,5 52,1 58,2 71,4 64,7 76,1 85,1 91,7
Nominal absorbed power. 2) kW 8,1 9,5 10,3 9,2 10,8 12,1 13,0 10,3 12,1 13,8 18,4 14,3 18,5 21,5 22,0
Nominal absorbed current. 2) A 14,8 17,9 20,2 18,0 21,2 23,7 23,9 21,0 23,7 25,6 36,3 27,2 36,3 40,1 38,5
SCROLL Compressors
Standard number n.° 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
Capacity steps (2 comprer) n.° G2
Max absorbed current. A 23 34 34 26 38 40 50 29 40 50 70 40 70 70 56
Inrush current A 67 79 90 91 90 117 109 92 117 110 160 117 160 162 172
Water flow rate at condenser l/s 2,34 2,54 2,81 2,73 2,98 3,28 3,44 3,01 3,46 3,87 4,82 4,26 5,08 5,72 6,12
Pressure drop kPa 10 48 55 48 55 52 48 55 52 48 58 48 58 60 60
Centrifugal fans
Number n.° 2 2 2 2 2 2 2 3 3 3 3 4 4 4 4
Air flow rate l/s 2722 2722 2722 2920 2920 2920 2920 3950 3950 4170 4170 5277 5277 5277 6670
Air flow rate mc/h 9799 9799 9799 10512 10512 10512 10512 14220 14220 15012 15012 18997 18997 18997 24012
Ext avaible pressure 5) Pa 60 55 30 40 40 40 40 45 45 45 45 40 40 35 35
Higher avaible pressure 1M Pa 125 120 95 90 90 90 90 85 85 195 195 80 80 75 180
Higher avaible pressure 2M Pa 230 225 200 230 230 230 230 250 250 265 265 245 245 240 250
Higher avaible pressure 3M Pa 280 275 250 315 315 315 315 310 310 380 380 315 315 310 nd
Higher avaible pressure 4M Pa 330 325 300 430 430 430 430 400 400 nd nd 395 395 390 nd
Higher avaible pressure 5M Pa 450 445 420 nd nd nd nd nd nd nd nd nd nd nd nd
Max absorbed power. 6) W 2178 2178 2178 2244 2244 2244 2244 3366 3366 6664 6664 4488 4488 4488 10662
Max absorbed current.6) A 13,2 13,2 13,2 13,6 13,6 13,6 13,6 20,4 20,4 13,5 13,5 27,2 27,2 27,2 21,6
Humidifier
Max steam prodution kg/h 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13
Max absorbed power kW 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4
Max absorbed current A 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7
Electric heater
Capacity kW 13,5 13,5 13,5 13,5 13,5 13,5 13,5 18 18 18 18 18 18 18 18
Steps n.° 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3
Absorbed current A 19,9 19,9 19,9 19,9 19,9 19,9 19,9 26,6 26,6 26,6 26,6 26,6 26,6 26,6 26,6
Warm water coil 3)
Capacity kW 22 22 22 24 24 24 24 25 25 25 25 35 35 35 35
Water flow rate l/s 0,35 0,35 0,35 0,38 0,38 0,38 0,38 0,41 0,41 0,41 0,41 0,6 0,6 0,6 0,6
Pressure drop (coil + valve) kPa 57 57 57 47 47 47 47 25 25 25 25 46 46 46 46
Hot gas coil
Capacity kW 17 17 17 18 18 18 18 17 17 17 17 21 21 21 21
Sound pressure level 4)
Version D db(A) 58 58 58 57 57 57 57 59 59 59 59 60 60 60 61
Dimensions - Weight
Length mm 1730 1730 1730 1990 1990 1990 1990 2390 2390 2390 2390 2950 2950 2950 2950
Width mm 815 815 815 815 815 815 815 815 815 815 815 815 815 815 815
Height mm 1995 1995 1995 1995 1995 1995 1995 1995 1995 1995 1995 1995 1995 1995 1995
Weight kg 417 432 447 472 482 502 517 537 547 561 576 596 616 631 646
Power supply 400V-50Hz-3F+T+N
MILLENNIUM E 07/02
PRECISION AIR CONDITIONING UNITS - DIRECT EXPANSION - R22 - R407C - Versions U,V,B
MODEL ED...M 61 81 91 101 121 141 151 171 201
Size L1 L1 L1 L2 L2 L2 L3 L3 L3
Cooling capacity 1) R 22
Total (27°C-50%) kW 6,6 8,3 9,4 10,4 11,8 13,8 14,7 17,3 20,2
Sensible (27°C-50%) kW 5,5 6,9 7,8 8,6 9,8 11,4 12,2 14,4 16,8
Total (24°C-50%) kW 6,0 7,6 8,7 9,6 10,8 12,6 13,5 15,9 18,6
Sensible (24°C-50%) kW 5,4 6,9 8,0 8,6 9,7 11,2 12,2 14,5 16,5
Total (22°C-50%) kW 5,8 7,3 8,3 9,2 10,4 12,2 12,9 15,3 17,9
Sensible (22°C-50%) kW 5,4 6,8 7,7 8,5 9,7 11,3 12,0 14,2 16,6
Cooling capacity 2) R 407C
Total (27°C-50%) kW 6,3 8,0 9,1 10,0 11,3 13,2 14,1 16,6 19,5
Sensible (27°C-50%) kW 5,3 6,6 7,5 8,3 9,4 11,0 11,7 13,8 16,1
Total (24°C-50%) kW 5,8 7,3 8,3 9,2 10,4 12,2 12,9 15,3 17,9
Sensible (24°C-50%) kW 5,3 6,7 7,7 8,4 9,5 11,1 11,8 13,9 16,2
Total (22°C-50%) kW 5,6 7,0 8,0 8,8 10,0 11,7 12,4 14,7 17,2
Sensible (22°C-50%) kW 5,2 6,5 7,4 8,2 9,3 10,9 11,6 13,7 16,0
Centrifugal fans
Number n.° 1 1 1 1 1 1 1 1 1
Air flow rate l/s 360 445 445 625 625 625 750 890 890
Air flow rate mc/h 1296 1602 1602 2250 2250 2250 2700 3204 3204
Ext avaible pressure 7) Pa 75 90 90 90 90 85 45 70 70
Higher avaible pressure 1M Pa 145 145 145 120 120 115 87 120 120
Higher avaible pressure 2M Pa 200 270 270 180 180 175 125 200 200
Higher avaible pressure 3M Pa 260 345 345 240 240 235 295 290 290
Higher avaible pressure 4M Pa 410 405 405 380 380 375 340 353 353
Higher avaible pressure 5M Pa 560 455 455 nd nd nd 440 420 420
Max absorbed power. 8) W 446 446 446 446 446 446 495 627 627
Max absorbed current.8) A 2,7 2,7 2,7 2,7 2,7 2,7 3 3,8 3,8
Humidifier
Max steam prodution kg/h 3 3 3 5 5 5 5 5 5
Max absorbed power kW 2,1 2,1 2,1 3,7 3,7 3,7 3,7 3,7 3,7
Max absorbed current A 6 6 6 10 10 10 10 10 10
Electric heater
Capacity kW 3 3 3 3 3 3 6 6 6
Steps n.° 1 1 1 1 1 1 2 2 2
Absorbed current A 7,8 7,8 7,8 7,8 7,8 7,8 13,3 13,3 13,3
Warm water coil 4)
Capacity kW 5 5 5 7 7 7 11 11 11
Water flow rate l/s 0,08 0,08 0,08 0,15 0,15 0,15 0,18 0,18 0,18
Pressure drop (coil + valve) kPa 23 23 23 23 23 23 21 21 21
Hot gas coil
Capacity kW 4 4 4 6 6 6 9 9 9
Sound pressure level 5)
Version U,B dB(A) 44 49 49 46 46 46 47 49 49
Version V dB(A) 42 47 47 44 44 44 45 46 46
Dimensions - Weight
Length mm 490 490 490 640 640 640 940 940 940
Width mm 565 565 565 565 565 565 565 565 565
Height mm 1800 1800 1800 1800 1800 1800 1800 1800 1800
Weight kg 175 180 182 200 210 230 250 254 260
Power supply 400V-50Hz-3F+T+N
Remote condensing units 6) MCR 51 71 81 81 91 121 121 141 171
Nominal absorbed power. 3) kW 1,5 1,8 2,2 2,3 2,53 3,2 3,12 3,81 4,5
R407C R22
Nominal absorbed current. 3) A 2,8 3,4 4,0 4,5 4,7 5,9 6,0 7,5 8,0
Nominal absorbed power. 3) kW 1,6 1,9 2,3 2,4 2,6 3,3 3,2 4,0 4,7
Nominal absorbed current. 3) A 2,9 3,6 4,2 4,7 4,9 6,1 6,3 7,8 8,3
Standard number n.° 1 1 1 1 1 1 1 1 1
Capacity steps n.° 1 1 1 1 1 1 1 1 1
Max absorbed current. A 4 5 6 6 7 8 8 10 11
Inrush current A 20 27 34 34 39 43 44 56 63
MILLENNIUM E 07/02
PRECISION AIR CONDITIONING UNITS - DIRECT EXPANSION - R 22-R 407C - Versions U, V, B
MODEL ED.M 221 241 251 291 301 341 321 361 451 351 431 531
Size M1 M1 M1 M1 M1 M1 M2 M2 M2 M3 M3 M3
Cooling capacity 1) R 22
Total (27°C-50%) kW 22,0 24,0 25,3 29,0 31,7 35,7 32,1 36,3 45,9 36,0 43,9 51,4
Sensible (27°C-50%) kW 18,3 19,9 21,0 24,0 26,3 29,6 26,7 30,1 38,1 29,9 36,4 42,7
Total (24°C-50%) kW 20,2 22,0 23,2 26,6 29,1 32,7 29,5 33,3 42,1 33,0 40,3 47,2
Sensible (24°C-50%) kW 18,4 19,8 21,4 23,6 26,5 30,1 28,6 29,9 37,9 31,7 36,3 42,5
Total (22°C-50%) kW 19,4 21,2 22,3 25,5 27,9 31,5 28,4 32,0 40,5 31,8 38,7 45,4
Sensible (22°C-50%) kW 18,1 19,7 20,8 23,8 26,0 29,3 26,4 29,7 37,7 29,6 36,0 42,2
Cooling capacity 2) R407C
Totale (27°C-50%) kW 21,2 23,1 24,4 27,9 30,5 34,3 30,9 34,9 44,2 34,7 42,3 49,5
Sensible (27°C-50%) kW 17,6 19,2 20,2 23,1 25,3 28,5 25,7 29,0 36,7 28,8 35,1 41,1
Totale (24°C-50%) kW 19,4 21,2 22,3 25,6 28,0 31,5 28,4 32,0 40,5 31,8 38,8 45,4
Sensible (24°C-50%) kW 17,7 19,3 20,3 23,3 25,4 28,7 27,5 29,1 36,9 30,5 35,3 41,3
Totale (22°C-50%) kW 18,7 20,4 21,5 24,6 26,9 30,3 27,3 30,8 39,0 30,6 37,3 43,7
Sensible (22°C-50%) kW 17,4 19,0 20,0 22,9 25,0 28,2 25,4 28,6 36,3 28,4 34,7 40,6
Centrifugal fans
Number n.° 2 2 2 2 2 2 2 2 2 2 2 2
Air flow rate l/s 1480 1480 1480 1480 1700 1700 2222 2222 2222 2722 2722 2722
Air flow rate mc/h 5328 5328 5328 5328 6120 6120 7999 7999 7999 9799 9799 9799
Ext avaible pressure 7) Pa 75 75 75 60 70 70 165 165 150 70 65 40
Higher avaible pressure 1M Pa 200 200 200 185 155 155 185 185 170 135 130 105
Higher avaible pressure 2M Pa 245 245 245 230 250 250 235 235 220 240 235 210
Higher avaible pressure 3M Pa 265 265 265 250 300 300 335 335 320 290 285 260
Higher avaible pressure 4M Pa 355 355 355 340 360 360 375 375 360 340 335 310
Higher avaible pressure 5M Pa 405 405 405 390 nd nd nd nd nd 460 455 430
Max absorbed power. 8) W 891 891 891 891 1518 1518 2468 2468 2468 2178 2178 2178
Max absorbed current.8) A 5,4 5,4 5,4 5,4 9,2 9,2 5 5 5 13,2 13,2 13,2
Humidifier
Max steam prodution kg/h 5 5 5 5 5 5 5 5 5 13 13 13
Max absorbed power kW 3,7 3,7 3,7 3,7 3,7 3,7 3,7 3,7 3,7 9,4 9,4 9,4
Max absorbed current A 9,7 9,7 9,7 9,7 9,7 9,7 9,7 9,7 9,7 24,7 24,7 24,7
Electric heater
Capacity kW 9 9 9 9 9 9 9 9 9 13,5 13,5 13,5
Steps n.° 3 3 3 3 3 3 3 3 3 3 3 3
Absorbed current A 13,3 13,3 13,3 13,3 13,3 13,3 13,3 13,3 13,3 19,9 19,9 19,9
Warm water coil 4)
Capacity kW 15 15 15 15 15 15 19 19 19 22 22 22
Water flow rate l/s 0,24 0,24 0,24 0,24 0,24 0,24 0,3 0,3 0,3 0,4 0,4 0,4
Pressure drop (coil + valve) kPa 48 48 48 48 48 48 27 27 27 57 57 57
Hot gas coil
Capacity kW 11 11 11 11 11 11 17 17 17 17 17 17
Sound pressure level 5)
Version U,B dB(A) 49 49 50 50 51 51 59 60 60 59 59 59
Version V dB(A) 46 46 46 46 47 47 56 56 56 55 55 55
Dimensions - Weight
Length mm 1230 1230 1230 1230 1230 1230 1530 1530 1530 1730 1730 1730
Width mm 665 665 665 665 665 665 665 665 665 815 815 815
Height mm 1975 1975 1975 1975 1975 1975 1975 1975 1975 1995 1995 1995
Weight kg 280 285 290 295 300 305 325 331 340 360 365 378
Power supply 400V-50Hz-3F+T+N
Remote condensing units 6) MCR 171 191 201 211 241 281 241 281 361 281 361 421
Nominal absorbed power. 3) kW 4,5 5,0 5,6 6,4 6,8 7,8 6,8 7,6 10,0 7,6 10,4 11,7
R407C R22
Nominal absorbed current. 3) A 8,0 9,8 11,1 11,8 13,0 15,0 12,9 14,7 19,6 14,7 19,8 21,8
Nominal absorbed power. 3) kW 4,7 5,2 5,8 6,6 7,0 8,1 7,0 7,9 10,4 7,9 10,8 12,2
Nominal absorbed current. 3) A 8,3 10,2 11,5 12,3 13,5 15,6 13,4 15,3 20,4 15,3 20,5 22,7
Standard number n.° 1 1 1 1 1 1 1 1 1 1 1 1
Capacity steps n.° 1 1 1 1 1 1 1 1 1 1 1 1
Max absorbed current. A 11,4 13 17 20 17,9 19,2 20 29 26 29 35 35
Inrush current A 63 86 83 53 105 114 111 111 96 111 149 149
MODEL ED.M 172 192 202 232 272 342 302 362 442
Size L3 L3 M1 M1 M1 M1 M2 M2 M2
Cooling capacity 1) R 22
Total (27°C-50%) kW 17,1 19,1 21,1 23,8 27,1 34,6 31,3 37,1 45,9
Sensible (27°C-50%) kW 14,0 15,7 17,3 19,5 22,2 28,4 25,7 30,4 37,6
Total (24°C-50%) kW 15,7 17,5 19,3 21,8 24,8 31,8 28,7 34,0 42,1
Sensible (24°C-50%) kW 14,1 16,0 18,2 20,1 22,4 28,6 28,2 30,6 37,9
Total (22°C-50%) kW 15,1 16,9 18,6 21,0 23,9 30,5 27,6 32,7 40,5
Sensible (22°C-50%) kW 13,9 15,6 17,2 19,4 22,1 28,2 25,6 30,3 37,5
Cooling capacity 2) R407C
Total (27°C-50%) kW 16,4 18,4 20,3 22,9 26,0 33,3 30,1 35,7 44,1
Sensible (27°C-50%) kW 13,5 15,1 16,6 18,7 21,3 27,3 24,7 29,2 36,2
Total (24°C-50%) kW 15,1 16,9 18,6 21,0 23,9 30,5 27,6 32,7 40,5
Sensible (24°C-50%) kW 13,4 15,2 17,5 18,9 21,5 27,5 27,1 29,4 36,9
Total (22°C-50%) kW 14,5 16,2 17,9 20,2 23,0 29,4 26,6 31,5 38,9
Sensible (22°C-50%) kW 13,4 15,0 16,5 18,7 21,2 27,2 24,6 29,1 36,0
Centrifugal fans
Number n.° 1 1 2 2 2 2 2 2 2
Air flow rate l/s 890 890 1480 1480 1480 1700 2222 2222 2222
Air flow rate mc/h 3204 3204 5328 5328 5328 6120 7999 7999 7999
Ext avaible pressure 7) Pa 70 70 75 75 75 70 165 165 150
Higher avaible pressure 1M Pa 120 120 200 200 200 155 185 185 170
Higher avaible pressure 2M Pa 200 200 245 245 245 250 235 235 220
Higher avaible pressure 3M Pa 290 290 265 265 265 300 335 335 320
Higher avaible pressure 4M Pa 353 353 355 355 355 360 375 375 360
Higher avaible pressure 5M Pa 420 420 405 405 405 nd nd nd nd
Max absorbed power. 8) W 627 627 891 891 891 1518 2468 2468 2468
Max absorbed current.8) A 3,8 3,8 5,4 5,4 5,4 9,2 5 5 5
Humidifier
Max steam prodution kg/h 5 5 5 5 5 5 5 5 5
Max absorbed power kW 3,7 3,7 3,7 3,7 3,7 3,7 3,7 3,7 3,7
Max absorbed current A 9,7 9,7 9,7 9,7 9,7 9,7 9,7 9,7 9,7
Electric heater
Capacity kW 6 6 9 9 9 9 9 9 9
Steps n.° 1 1 3 3 3 3 3 3 3
Absorbed current A 13,3 13,3 13,3 13,3 13,3 13,3 13,3 13,3 13,3
Warm water coil 4)
Capacity kW 11 11 15 15 15 15 19 19 19
Water flow rate l/s 0,18 0,18 0,24 0,24 0,24 0,24 0,3 0,3 0,3
Pressure drop (coil + valve) kPa 21 21 48 48 48 48 27 27 27
Hot gas coil
Capacity kW 9 9 11 11 11 11 17 17 17
Sound pressure level 5)
Version U,B dB(A) 49 49 50 50 50 50 57 57 57
Version V dB(A) 47 47 48 48 48 48 55 55 55
Dimensions - Weight
Length mm 940 940 1230 1230 1230 1230 1530 1530 1530
Width mm 565 565 665 665 665 665 665 665 665
Height mm 1800 1800 1975 1975 1975 1975 1975 1975 1975
Weight kg 290 300 320 330 335 340 360 368 375
Power supply 400V-50Hz-3F+T+N
Remote condensing units 6) MCR 2*71 2*81 2*81 2*91 2*121 2*141 2*121 2*141 2*191
Nominal absorbed power. 3) kW 3,6 4,3 4,3 5,0 6,2 7,6 6,3 7,6 9,8
R407C R22
Nominal absorbed current. 3) A 6,8 8,0 8,1 9,2 12,0 15,0 11,6 15,2 19,6
Nominal absorbed power. 3) kW 3,7 4,5 4,5 5,2 6,4 7,9 6,5 7,9 10,2
Nominal absorbed current. 3) A 7,1 8,3 8,4 9,6 12,5 15,6 12,1 15,8 20,4
Standard number n.° 2 2 2 2 2 2 2 2 2
Capacity steps n.° G2
Max absorbed current. A 10 12 10 12 16 20 20 20 26
Inrush current A 29 36 36 42 48 60 46 60 91
MILLENNIUM E 07/02
PRECISION AIR CONDITIONING UNITS - DIRECT EXPANSION - R22 - R407C - Versions U,V,B
MODEL ED.M 412 452 492 482 532 572 602 542 622 682 842 762 892 1002 1102
Size M3 M3 M3 M4 M4 M4 M4 M5 M5 M5 M5 M6 M6 M6 M6
Cooling capacity 1) R 22
Total (27°C-50%) kW 42,4 45,3 50,3 49,7 53,4 58,5 61,2 54,5 62,4 69,7 85,5 77,5 91,1 102 110
Sensible (27°C-50%) kW 34,8 37,2 41,2 40,7 43,8 48,0 50,2 44,7 51,2 57,1 70,1 63,5 74,7 83,5 90,1
Total (24°C-50%) kW 38,9 41,6 46,1 45,6 49,0 53,7 56,2 50,0 57,2 63,9 78,4 71,1 83,6 93,4 101
Sensible (24°C-50%) kW 35,4 37,4 41,5 41,0 44,1 48,3 50,5 49,0 52,1 57,5 70,6 67,5 75,2 84,1 91,7
Total (22°C-50%) kW 37,4 40,0 44,3 43,8 47,1 51,6 54,0 48,1 55,0 61,5 75,4 68,3 80,4 89,8 96,9
Sensible (22°C-50%) kW 34,6 37,0 41,0 40,5 43,6 47,7 50,0 44,5 50,9 56,9 69,7 63,2 74,3 83,1 89,6
Sensible (27°C-50%) kW 33,4 35,7 39,6 39,2 42,1 46,1 48,3 43,0 49,2 54,9 67,4 61,1 71,8 80,3 86,6
Totale (24°C-50%) kW 37,4 40,0 44,3 43,8 47,1 51,6 54,0 48,1 55,0 61,5 75,4 68,3 80,4 89,8 96,9
Sensible (24°C-50%) kW 33,6 36,0 39,9 39,4 42,4 46,5 48,6 47,1 50,1 55,3 67,9 64,9 72,3 80,8 87,2
Totale (22°C-50%) kW 35,9 38,4 42,6 42,1 45,3 49,6 51,9 46,2 52,9 59,1 72,5 65,7 77,3 86,4 93,2
Sensible (22°C-50%) kW 33,3 35,6 39,4 39,0 41,9 45,9 48,0 42,8 49,0 54,7 67,1 60,8 71,5 79,9 86,2
Centrifugal fans
Number n.° 2 2 2 2 2 2 2 3 3 3 3 4 4 4 4
Air flow rate l/s 2722 2722 2722 2920 2920 2920 2920 3950 3950 4170 4170 5277 5277 5277 6670
Air flow rate mc/h 9799 9799 9799 10512 10512 10512 10512 14220 14220 15012 15012 18997 18997 18997 24012
Higher avaible pressure 1M Pa 135 130 105 110 110 110 110 95 95 215 215 95 95 90 220
Higher avaible pressure 2M Pa 240 235 210 250 250 250 250 260 260 290 290 260 260 255 290
Higher avaible pressure 3M Pa 290 285 260 335 335 335 335 320 320 405 405 330 330 325 nd
Higher avaible pressure 4M Pa 340 335 310 450 450 450 450 410 410 nd nd 410 410 405 nd
Max absorbed power. 8) W 2178 2178 2178 2244 2244 2244 2244 3366 3366 6664 6664 4488 4488 4488 10662
Max absorbed current.8) A 13,2 13,2 13,2 13,6 13,6 13,6 13,6 20,4 20,4 13,5 13,5 27,2 27,2 27,2 21,6
Humidifier
Max absorbed power kW 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4
Max absorbed current A 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7
Electric heater
Steps n.° 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3
Absorbed current A 19,9 19,9 19,9 19,9 19,9 19,9 19,9 26,6 26,6 26,6 26,6 26,6 26,6 26,6 26,6
Capacity kW 22 22 22 24 24 24 24 25 25 25 25 35 35 35 35
Water flow rate l/s 0,35 0,35 0,35 0,38 0,38 0,38 0,38 0,41 0,41 0,41 0,41 0,6 0,6 0,6 0,6
Capacity kW 17 17 17 18 18 18 18 17 17 17 17 21 21 21 21
Version V dB(A) 56 56 56 55 55 55 55 57 57 57 57 58 58 58 59
Dimensions - Weight
Length mm 1730 1730 1730 1990 1990 1990 1990 2390 2390 2390 2390 2950 2950 2950 2950
Width mm 815 815 815 815 815 815 815 815 815 815 815 815 815 815 815
Height mm 1995 1995 1995 1995 1995 1995 1995 1995 1995 1995 1995 1995 1995 1995 1995
Weight kg 400 410 425 450 460 475 490 515 520 530 540 565 580 595 610
Remote condensing units 6) MCR 2*171 2*191 2*201 2*191 2*201 2*241 2*241 2*201 2*241 2*281 2*361 2*281 2*361 2*421 2*421
Nominal absorbed power. 3) kW 8,8 10,3 11,2 10 11,8 13,2 14,2 11,2 13,2 15 20 15,6 20,1 23,4 24
R22
Nominal absorbed current. 3) A 16,1 19,4 22 19,6 23 25,8 26 22,8 25,8 27,8 39,4 29,6 39,4 43,6 41,8
R407C
Nominal absorbed power. 3) kW 9,1 10,7 11,6 10,4 12,2 13,7 14,7 11,6 13,7 15,6 20,8 16,2 20,9 24,3 24,9
Nominal absorbed current. 3) A 16,7 20,2 22,9 20,4 23,9 26,8 27,0 23,7 26,8 28,9 41,0 30,8 41,0 45,3 43,5
Inrush current A 67 79 90 91 90 117 109 92 117 110 160 117 160 162 172
MILLENNIUM E 07/02
PRECISION AIR CONDITIONING UNITS - DIRECT EXPANSION - R22 - R407C - Versions D
Nominal absorbed current. 3) A 2,8 3,4 4,0 4,5 4,7 5,9 6,0 7,5 8,0
Nominal absorbed power. 3) kW 1,6 1,9 2,3 2,4 2,6 3,3 3,2 4,0 4,7
Nominal absorbed current. 3) A 2,9 3,6 4,2 4,7 4,9 6,1 6,3 7,8 8,3
Standard number n.° 1 1 1 1 1 1 1 1 1
Capacity steps n.° 1 1 1 1 1 1 1 1 1
Max absorbed current. A 4 5 6 6 7 8 8 10 11
Inrush current A 20 27 34 34 39 43 44 56 63
MILLENNIUM E 07/02
PRECISION AIR CONDITIONING UNITS - DIRECT EXPANSION - R 22-R 407C - Version D
MODEL ED.M 221 241 251 291 301 341 321 361 451 351 431 531
Size M1 M1 M1 M1 M1 M1 M2 M2 M2 M3 M3 M3
Cooling capacity 1) R 22
Total (27°C-50%) kW 22,0 24,0 25,3 29,0 31,7 35,7 32,1 36,3 45,9 36,0 43,9 51,4
Sensible (27°C-50%) kW 18,3 19,9 21,0 24,0 26,3 29,6 26,7 30,1 38,1 29,9 36,4 42,7
Total (24°C-50%) kW 20,2 22,0 23,2 26,6 29,1 32,7 29,5 33,3 42,1 33,0 40,3 47,2
Sensible (24°C-50%) kW 18,4 19,8 21,4 23,6 26,5 30,1 28,6 29,9 37,9 31,7 36,3 42,5
Total (22°C-50%) kW 19,4 21,2 22,3 25,5 27,9 31,5 28,4 32,0 40,5 31,8 38,7 45,4
Sensible (22°C-50%) kW 18,1 19,7 20,8 23,8 26,0 29,3 26,4 29,7 37,7 29,6 36,0 42,2
Cooling capacity 2) R407C
Totale (27°C-50%) kW 21,2 23,1 24,4 27,9 30,5 34,3 30,9 34,9 44,2 34,7 42,3 49,5
Sensible (27°C-50%) kW 17,6 19,2 20,2 23,1 25,3 28,5 25,7 29,0 36,7 28,8 35,1 41,1
Totale (24°C-50%) kW 19,4 21,2 22,3 25,6 28,0 31,5 28,4 32,0 40,5 31,8 38,8 45,4
Sensible (24°C-50%) kW 17,7 19,3 20,3 23,3 25,4 28,7 27,5 29,1 36,9 30,5 35,3 41,3
Totale (22°C-50%) kW 18,7 20,4 21,5 24,6 26,9 30,3 27,3 30,8 39,0 30,6 37,3 43,7
Sensible (22°C-50%) kW 17,4 19,0 20,0 22,9 25,0 28,2 25,4 28,6 36,3 28,4 34,7 40,6
Centrifugal fans
Number n.° 1 1 1 1 1 1 2 2 2 2 2 2
Air flow rate l/s 1480 1480 1480 1480 1700 1700 2222 2222 2222 2722 2722 2722
Air flow rate mc/h 5328 5328 5328 5328 6120 6120 7999 7999 7999 9799 9799 9799
Ext avaible pressure 7) Pa 80 80 80 60 60 60 50 50 35 60 55 30
Higher avaible pressure 1M Pa 210 210 210 190 90 90 95 95 80 125 120 95
Higher avaible pressure 2M Pa 242 242 242 220 255 255 195 195 180 230 225 200
Higher avaible pressure 3M Pa 400 400 400 380 310 310 235 235 220 280 275 250
Higher avaible pressure 4M Pa nd nd nd nd nd nd nd nd nd 330 325 300
Higher avaible pressure 5M Pa nd nd nd nd nd nd nd nd nd 450 445 420
Max absorbed power. 8) W 2123 2123 2123 2123 2764 2764 2145 2145 2145 2178 2178 2178
Max absorbed current.8) A 4,3 4,3 4,3 4,3 5,6 5,6 13 13 13 13,2 13,2 13,2
Humidifier
Max steam prodution kg/h 5 5 5 5 5 5 5 5 5 13 13 13
Max absorbed power kW 3,7 3,7 3,7 3,7 3,7 3,7 3,7 3,7 3,7 9,4 9,4 9,4
Max absorbed current A 9,7 9,7 9,7 9,7 9,7 9,7 9,7 9,7 9,7 24,7 24,7 24,7
Electric heater
Capacity kW 9 9 9 9 9 9 9 9 9 13,5 13,5 13,5
Steps n.° 3 3 3 3 3 3 3 3 3 3 3 3
Absorbed current A 13,3 13,3 13,3 13,3 13,3 13,3 13,3 13,3 13,3 19,9 19,9 19,9
Warm water coil 4)
Capacity kW 15 15 15 15 15 15 19 19 19 22 22 22
Water flow rate l/s 0,24 0,24 0,24 0,24 0,24 0,24 0,3 0,3 0,3 0,4 0,4 0,4
Pressure drop (coil + valve) kPa 48 48 48 48 48 48 27 27 27 57 57 57
Hot gas coil
Capacity kW 11 11 11 11 11 11 17 17 17 17 17 17
Sound pressure level 5)
Version D dB(A) 56 56 56 56 54 54 56 56 56 55 55 55
Dimensions - Weight
Length mm 1230 1230 1230 1230 1230 1230 1530 1530 1530 1730 1730 1730
Width mm 665 665 665 665 665 665 665 665 665 815 815 815
Height mm 1975 1975 1975 1975 1975 1975 1975 1975 1975 1995 1995 1995
Weight kg 255 258 292 297 297 305 325 331 351 360 390 415
Power supply 400V-50Hz-3F+T+N
Remote condensing units 6) MCR 171 191 201 211 241 281 241 281 361 281 361 421
Nominal absorbed power. 3) kW 4,5 5,0 5,6 6,4 6,8 7,8 6,8 7,6 10,0 7,6 10,4 11,7
R22
Nominal absorbed current. 3) A 8,0 9,8 11,1 11,8 13,0 15,0 12,9 14,7 19,6 14,7 19,8 21,8
Nominal absorbed power. 3) kW 4,7 5,2 5,8 6,6 7,0 8,1 7,0 7,9 10,4 7,9 10,8 12,2
R407C
Nominal absorbed current. 3) A 8,3 10,2 11,5 12,3 13,5 15,6 13,4 15,3 20,4 15,3 20,5 22,7
Standard number n.° 1 1 1 1 1 1 1 1 1 1 1 1
Capacity steps n.° 1 1 1 1 1 1 1 1 1 1 1 1
Max absorbed current. A 11,4 13 17 20 17,9 19,2 20 29 26 29 35 35
Inrush current A 63 86 83 53 105 114 111 111 96 111 149 149
MILLENNIUM E 07/02
PRECISION AIR CONDITIONING UNITS - DIRECT EXPANSION - R 22-R 407C - Version D
MILLENNIUM E 07/02
PRECISION AIR CONDITIONING UNITS - DIRECT EXPANSION - R22 - R407C - Versions D
MODEL ED.M 172 192 202 232 272 342 302 362 442
Size L3 L3 M1 M1 M1 M1 M2 M2 M2
Cooling capacity 1) R 22
Total (27°C-50%) kW 17,1 19,1 21,1 23,8 27,1 34,6 31,3 37,1 45,9
Sensible (27°C-50%) kW 14,0 15,7 17,3 19,5 22,2 28,4 25,7 30,4 37,6
Total (24°C-50%) kW 15,7 17,5 19,3 21,8 24,8 31,8 28,7 34,0 42,1
Sensible (24°C-50%) kW 14,1 16,0 18,2 20,1 22,4 28,6 28,2 30,6 37,9
Total (22°C-50%) kW 15,1 16,9 18,6 21,0 23,9 30,5 27,6 32,7 40,5
Sensible (22°C-50%) kW 13,9 15,6 17,2 19,4 22,1 28,2 25,6 30,3 37,5
Cooling capacity 2) R407C
Total (27°C-50%) kW 16,4 18,4 20,3 22,9 26,0 33,3 30,1 35,7 44,1
Sensible (27°C-50%) kW 13,5 15,1 16,6 18,7 21,3 27,3 24,7 29,2 36,2
Total (24°C-50%) kW 15,1 16,9 18,6 21,0 23,9 30,5 27,6 32,7 40,5
Sensible (24°C-50%) kW 13,4 15,2 17,5 18,9 21,5 27,5 27,1 29,4 36,9
Total (22°C-50%) kW 14,5 16,2 17,9 20,2 23,0 29,4 26,6 31,5 38,9
Sensible (22°C-50%) kW 13,4 15,0 16,5 18,7 21,2 27,2 24,6 29,1 36,0
Centrifugal fans
Number n.° 1 1 1 1 1 1 2 2 2
Air flow rate l/s 890 890 1480 1480 1480 1700 2222 2222 2222
Air flow rate mc/h 3204 3204 5328 5328 5328 6120 7999 7999 7999
Ext avaible pressure 7) Pa 90 90 80 80 80 60 50 50 35
Higher avaible pressure 1M Pa 170 170 210 210 210 90 95 95 80
Higher avaible pressure 2M Pa 260 260 242 242 242 255 195 195 180
Higher avaible pressure 3M Pa 320 320 400 400 400 310 235 235 220
Higher avaible pressure 4M Pa 390 390 nd nd nd nd 275 275 260
Higher avaible pressure 5M Pa 457 457 nd nd nd nd nd nd nd
Max absorbed power. 8) W 627 627 2123 2123 2123 2764 2468 2468 2468
Max absorbed current.8) A 3,8 3,8 4,3 4,3 4,3 5,6 5 5 5
Humidifier
Max steam prodution kg/h 5 5 5 5 5 5 5 5 5
Max absorbed power kW 3,7 3,7 3,7 3,7 3,7 3,7 3,7 3,7 3,7
Max absorbed current A 9,7 9,7 9,7 9,7 9,7 9,7 9,7 9,7 9,7
Electric heater
Capacity kW 6 6 9 9 9 9 9 9 9
Steps n.° 1 1 3 3 3 3 3 3 3
Absorbed current A 13,3 13,3 13,3 13,3 13,3 13,3 13,3 13,3 13,3
Warm water coil 4)
Capacity kW 11 11 15 15 15 15 19 19 19
Water flow rate l/s 0,18 0,18 0,24 0,24 0,24 0,24 0,3 0,3 0,3
Pressure drop (coil + valve) kPa 21 21 48 48 48 48 27 27 27
Hot gas coil
Capacity kW 9 9 11 11 11 11 17 17 17
Sound pressure level 5)
Version D dB(A) 47 47 58 58 58 55 55 55 55
Dimensions - Weight
Length mm 940 940 1230 1230 1230 1230 1530 1530 1530
Width mm 565 565 665 665 665 665 665 665 665
Height mm 1800 1800 1975 1975 1975 1975 1975 1975 1975
Weight kg 290 300 320 330 335 340 360 368 375
Power supply 400V-50Hz-3F+T+N
Remote condensing units 6) MCR 2*71 2*81 2*81 2*91 2*121 2*141 2*121 2*141 2*191
Nominal absorbed power. 3) kW 3,6 4,3 4,3 5 6,2 7,6 6,3 7,6 9,8
R22
Nominal absorbed current. 3) A 6,8 8 8,1 9,2 12,02 15 11,6 15,2 19,6
Nominal absorbed power. 3) kW 3,7 4,5 4,5 5,2 6,4 7,9 6,5 7,9 10,2
R407C
Nominal absorbed current. 3) A 7,1 8,3 8,4 9,6 12,5 15,6 12,1 15,8 20,4
Standard number n.° 2 2 2 2 2 2 2 2 2
Capacity steps n.° G2
Max absorbed current. A 10 12 10 12 16 20 20 20 26
Inrush current A 29 36 36 42 48 60 46 60 91
MILLENNIUM E 07/02
PRECISION AIR CONDITIONING UNITS - DIRECT EXPANSION - R22 - R407C - Version D
MODEL ED.M 412 452 492 482 532 572 602 542 622 682 842 762 892 1002 1102
Size M3 M3 M3 M4 M4 M4 M4 M5 M5 M5 M5 M6 M6 M6 M6
Cooling capacity 1) R 22
Total (27°C-50%) kW 42,4 45,3 50,3 49,7 53,4 58,5 61,2 54,5 62,4 69,7 85,5 77,5 91,1 102 110
Sensible (27°C-50%) kW 34,8 37,2 41,2 40,7 43,8 48,0 50,2 44,7 51,2 57,1 70,1 63,5 74,7 83,5 90,1
Total (24°C-50%) kW 38,9 41,6 46,1 45,6 49,0 53,7 56,2 50,0 57,2 63,9 78,4 71,1 83,6 93,4 101
Sensible (24°C-50%) kW 35,4 37,4 41,5 41,0 44,1 48,3 50,5 49,0 52,1 57,5 70,6 67,5 75,2 84,1 91,7
Total (22°C-50%) kW 37,4 40,0 44,3 43,8 47,1 51,6 54,0 48,1 55,0 61,5 75,4 68,3 80,4 89,8 96,9
Sensible (22°C-50%) kW 34,6 37,0 41,0 40,5 43,6 47,7 50,0 44,5 50,9 56,9 69,7 63,2 74,3 83,1 89,6
Totale (27°C-50%) kW 40,7 43,6 48,3 47,8 51,4 56,3 58,9 52,4 60,0 67,0 82,2 74,5 87,6 97,9 106
Sensible (27°C-50%) kW 33,4 35,7 39,6 39,2 42,1 46,1 48,3 43,0 49,2 54,9 67,4 61,1 71,8 80,3 86,6
Totale (24°C-50%) kW 37,4 40,0 44,3 43,8 47,1 51,6 54,0 48,1 55,0 61,5 75,4 68,3 80,4 89,8 96,9
Sensible (24°C-50%) kW 33,6 36,0 39,9 39,4 42,4 46,5 48,6 47,1 50,1 55,3 67,9 64,9 72,3 80,8 87,2
Totale (22°C-50%) kW 35,9 38,4 42,6 42,1 45,3 49,6 51,9 46,2 52,9 59,1 72,5 65,7 77,3 86,4 93,2
Sensible (22°C-50%) kW 33,3 35,6 39,4 39,0 41,9 45,9 48,0 42,8 49,0 54,7 67,1 60,8 71,5 79,9 86,2
Centrifugal fans
Number n.° 2 2 2 2 2 2 2 3 3 3 3 4 4 4 4
Air flow rate l/s 2722 2722 2722 2920 2920 2920 2920 3950 3950 4170 4170 5280 5280 5280 6670
Air flow rate mc/h 9799 9799 9799 10512 10512 10512 10512 14220 14220 15012 15012 19008 19008 19008 24012
Higher avaible pressure 2M Pa 230 225 200 230 230 230 230 250 250 265 265 245 245 240 250
Higher avaible pressure 3M Pa 280 275 250 315 315 315 315 310 310 380 380 315 315 310 nd
Higher avaible pressure 4M Pa 330 325 300 430 430 430 430 400 400 nd nd 395 395 390 nd
Max absorbed power. 8) W 2178 2178 2178 2244 2244 2244 2244 3366 3366 6664 6664 4488 4488 4488 10662
Max absorbed current.8) A 13,2 13,2 13,2 13,6 13,6 13,6 13,6 20,4 20,4 13,5 13,5 27,2 27,2 27,2 21,6
Humidifier
Max absorbed power kW 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4 9,4
Max absorbed current A 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7
Electric heater
Steps n.° 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3
Absorbed current A 19,9 19,9 19,9 19,9 19,9 19,9 19,9 26,6 26,6 26,6 26,6 26,6 26,6 26,6 26,6
Warm water coil 4)
Capacity kW 22 22 22 24 24 24 24 25 25 25 25 35 35 35 35
Water flow rate l/s 0,35 0,35 0,35 0,38 0,38 0,38 0,38 0,41 0,41 0,41 0,41 0,6 0,6 0,6 0,6
Capacity kW 17 17 17 18 18 18 18 17 17 17 17 21 21 21 21
Sound pressure level 5)
Version D dB(A) 56 56 56 55 55 55 55 57 57 57 57 58 58 58 59
Dimensions - Weight
Length mm 1730 1730 1730 1990 1990 1990 1990 2390 2390 2390 2390 2950 2950 2950 2950
Width mm 815 815 815 815 815 815 815 815 815 815 815 815 815 815 815
Height mm 1995 1995 1995 1995 1995 1995 1995 1995 1995 1995 1995 1995 1995 1995 1995
Weight kg 400 410 425 450 460 475 490 515 520 530 540 565 580 595 610
Power supply 400V-50Hz-3F+T+N
Remote condensing units 6 MCR 2*171 2*191 2*201 2*191 2*201 2*241 2*241 2*201 2*241 2*281 2*361 2*281 2*361 2*421 2*421
Nominal absorbed power. kW 8,8 10,3 11,2 10,0 11,8 13,2 14,2 11,2 13,2 15,0 20,0 15,6 20,1 23,4 24,0
R407C R22
Nominal absorbed current. A 16,1 19,4 22,0 19,6 23,0 25,8 26,0 22,8 25,8 27,8 39,4 29,6 39,4 43,6 41,8
Nominal absorbed power. kW 9,1 10,7 11,6 10,4 12,2 13,7 14,7 11,6 13,7 15,6 20,8 16,2 20,9 24,3 24,9
Nominal absorbed current. A 16,7 20,2 22,9 20,4 23,9 26,8 27,0 23,7 26,8 28,9 41,0 30,8 41,0 45,3 43,5
Standard number n.° 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
MILLENNIUM E 07/02
PRECISION AIR CONDITIONING UNITS - DIRECT EXPANSION
MODEL ED.A
Correction factor for total cooling capacity depending on the room temperature
22 °C 23 °C 24 °C 25 °C 26 °C 27 °C
0,96 0,98 1 1,03 1,06 1,09
MODEL ED.M
Correction factor for total cooling capacity depending on the room temperature
22 °C 23 °C 24 °C 25 °C 26 °C 27 °C
0,96 0,98 1 1,03 1,06 1,09
135 135 130
MODEL ED.W
Correction factor for total cooling capacity depending on the room temperature
22 °C 23 °C 195 190 26 °C 27 °C
0,96 0,98 1 1,03 1,06 1,09
CORRECTION FACTOR FOR COOLING CAPACITY DEPENDING ON THE CONDENSER WATER TEMPERATURE
Attention! These coefficients are valid only for 24 - 27 °C room temperature. For room temperature of 22°C it isn't possible to apply these
coefficients. Please contact our sales department
MODEL UV
MILLENNIUM E 07/02
UV…
UNITS FOR
CHILLED WATER OPERATION
UV - PRECISION AIR CONDITIONING UNITS - CHILLED WATER - Version U, V, B
MODEL UV 60 80 120 170 190 240 280 320 380 470 550 640 740 800 870 1000
Size L1 L1 L2 L3 M1 M1 M1 M2 M2 M3 M4 M5 M5 M6 M6 M6
Cooling capacity 1)
Total (27°C-50%) kW 8,8 11,2 18,9 25,2 27,1 35,2 41,3 45,1 54,5 68,7 80,7 94,3 109 117 129 154
Sensible (27°C-50%) kW 6,6 8,4 14,2 18,9 20,3 26,4 31,0 33,9 40,8 51,5 60,5 70,7 81,7 87,8 96,9 120,4
Water flow rate l/s 0,42 0,54 0,91 1,20 1,29 1,68 1,97 2,16 2,60 3,28 3,85 4,50 5,20 5,59 6,17 7,38
Total (24°C-50%) kW 5,9 7,6 12,8 17,0 18,3 23,8 27,9 30,5 36,8 46,4 54,5 63,7 73,6 79,1 87,3 104
Sensible (24°C-50%) kW 5,3 6,8 11,5 15,3 17,4 21,4 25,1 27,5 33,1 41,8 49,1 57,3 66,2 72,8 81,2 93,9
Water flow rate l/s 0,28 0,36 0,61 0,81 0,87 1,14 1,33 1,46 1,76 2,22 2,60 3,04 3,52 3,78 4,17 4,98
Total (22°C-50%) kW 4,6 5,8 9,8 13,1 14,1 18,3 21,5 23,5 28,3 35,7 41,9 49,0 56,6 60,8 67,2 80,2
Sensible (22°C-50%) kW 4,5 5,8 9,8 12,9 13,9 18,3 21,2 23,5 28,0 35,7 40,7 49,0 56,0 60,2 66,5 79,4
Water flow rate l/s 0,22 0,28 0,47 0,62 0,67 0,87 1,03 1,12 1,35 1,71 2,00 2,34 2,70 2,91 3,21 3,83
Pressure drop 3) kPa 58 74 58 59 63 52 61 51 84 48 67 44 42 79 95 57
Cooling capacity 2)
Total (27°C-50%) kW 6,0 7,7 12,7 17,3 19,8 24,6 27,6 32,2 37,7 48,0 55,3 67,7 76,0 85,1 94,6 110
Sensible (27°C-50%) kW 5,1 6,5 10,8 14,7 16,9 20,9 23,5 27,4 32,0 40,8 47,0 57,6 64,6 72,4 80,4 93,1
Water flow rate l/s 0,29 0,37 0,60 0,83 0,95 1,18 1,32 1,54 1,80 2,29 2,64 3,24 3,63 4,07 4,52 5,23
Total (24°C-50%) kW 4,1 5,2 8,6 11,7 13,4 16,7 18,7 21,8 25,5 32,4 37,4 45,8 51,4 57,5 63,9 74,0
Sensible (24°C-50%) kW 4,1 5,2 8,6 11,7 13,4 16,7 18,7 21,8 25,5 32,4 37,4 45,8 51,4 57,5 63,9 74,0
Water flow rate l/s 0,19 0,25 0,41 0,56 0,64 0,80 0,89 1,04 1,22 1,55 1,78 2,19 2,45 2,75 3,05 3,54
Total (22°C-50%) kW 3,2 4,2 6,8 9,4 10,7 13,3 14,9 17,4 20,4 25,9 29,9 36,6 41,1 46,0 51,1 59,2
Sensible (22°C-50%) kW 3,2 4,2 6,8 9,4 10,7 13,3 14,9 17,4 20,4 25,9 29,9 36,6 41,1 46,0 51,1 59,2
Water flow rate l/s 0,16 0,20 0,33 0,45 0,51 0,64 0,71 0,83 0,97 1,24 1,43 1,75 1,96 2,20 2,44 2,83
Pressure drop 3) kPa 30 38 30 30 32 26 31 26 43 25 34 22 21 40 48 29
Centrifugal fans
Number n.° 1 1 1 1 2 2 2 2 2 2 2 3 3 4 4 4
Air flow rate l/s 335 335 330 972 1700 1556 1500 2083 2083 2772 3000 4583 4375 5970 6950 6670
Air flow rate mc/h 1206 1206 1188 3499 6120 5602 5400 7499 7499 9979 10800 16499 15750 21492 25020 24012
Ext avaible pressure 6) Pa 85 65 50 40 45 70 75 65 55 100 65 85 90 85 110 130
Higher avaible pressure 1M Pa 110 125 70 100 70 90 95 160 150 170 125 110 150 240 260 275
Higher avaible pressure 2M Pa 180 220 165 140 150 185 195 210 200 275 255 210 230 290 335 345
Higher avaible pressure 3M Pa 230 250 225 150 210 230 240 230 220 325 325 285 300 410 nd nd
Higher avaible pressure 4M Pa 275 265 320 310 350 355 355 270 260 375 485 435 440 440 nd nd
Higher avaible pressure 5M Pa 590 315 340 410 410 nd nd 395 385 495 nd nd nd nd nd nd
Max absorbed power. 7) W 446 446 446 908 891 1254 1254 2244 2244 2178 2244 6664 6664 8885 10662 10662
Max absorbed current.7) A 2,7 2,7 2,7 5,5 5,4 7,6 7,6 13,6 13,6 13,2 13,6 13,5 13,5 18 21,6 21,6
Humidifier
Max steam prodution kg/h 5 5 5 5 5 5 5 5 5 13 13 13 13 13 13 13
Max absorbed power kW 3,7 3,7 3,7 3,7 3,7 3,7 3,7 3,7 3,7 9,4 9,4 9,4 9,4 9,4 9,4 9,4
Max absorbed current A 9,7 9,7 9,7 9,7 9,7 9,7 9,7 9,7 9,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7
Electric heater
Capacity kW 3 3 3 6 9 9 9 9 9 13,5 13,5 18 18 18 18 18
Steps n.° 1 1 1 2 3 3 3 3 3 3 3 3 3 3 3 3
Absorbed current A 7,8 7,8 7,8 13,3 13,3 13,3 13,3 13,3 13,3 19,9 19,9 26,6 26,6 26,6 26,6 26,6
Warm water coil 4)
Capacity kW 5 5 7 11 15 15 15 19 19 22 24 25 25 35 35 35
Water flow rate l/s 0,08 0,08 0,15 0,18 0,24 0,24 0,24 0,30 0,30 0,40 0,40 0,41 0,41 0,57 0,57 0,57
Pressure drop (coil + valve) kPa 23 23 17 25 52 52 52 38 38 61 67 28 28 44 44 44
Sound pressure level 5)
Version U,B dB(A) 46 46 47 51 52 52 51 59 59 60 61 61 61 62 66 65
Version V dB(A) 45 45 46 48 49 49 48 56 56 57 58 58 58 59 63 62
Dimensions - Weight
Length mm 490 490 640 940 1230 1230 1230 1530 1530 1730 1990 2390 2390 2950 2950 2950
Width mm 565 565 565 565 665 665 665 665 665 815 815 815 815 815 815 815
Height mm 1800 1800 1800 1800 1975 1975 1975 1975 1975 1995 1995 1995 1995 1995 1995 1995
Weight kg 155 160 190 198 221 230 241 267 274 290 310 325 332 346 370 384
Power supply 400V-50Hz-3F+T+N
MILLENNIUM E 07/02
UV - PRECISION AIR CONDITIONING UNITS - CHILLED WATER - Version D
MODEL UV 60 80 120 170 190 240 280 320 380 470 550 640 740 800 870 1000
Size L1 L1 L2 L3 M1 M1 M1 M2 M2 M3 M4 M5 M5 M6 M6 M6
Cooling capacity 1)
Total (27°C-50%) kW 8,6 12,0 16,9 25,8 27,1 35,2 41,3 45,1 54,5 68,7 80,7 94,3 109 117 129 154
Sensible (27°C-50%) kW 6,5 9,0 12,7 19,3 20,3 26,4 31,0 33,9 40,8 51,5 60,5 70,7 81,7 87,8 96,9 116
Water flow rate l/s 0,41 0,58 0,81 1,23 1,29 1,68 1,97 2,16 2,60 3,28 3,85 4,50 5,20 5,59 6,17 7,38
Total (24°C-50%) kW 5,8 8,1 11,4 17,4 18,3 23,8 27,9 30,5 36,8 46,4 54,5 63,7 73,6 79,1 87,3 104
Sensible (24°C-50%) kW 5,2 7,3 10,3 15,7 17,4 21,4 25,1 27,5 33,1 41,8 49,1 57,3 66,2 72,8 81,2 93,9
Water flow rate l/s 0,28 0,39 0,54 0,83 0,87 1,14 1,33 1,46 1,76 2,22 2,60 3,04 3,52 3,78 4,17 4,98
Total (22°C-50%) kW 4,5 6,3 8,8 13,4 14,1 18,3 21,5 23,5 28,3 35,7 41,9 49,0 56,6 60,8 67,2 80,2
Sensible (22°C-50%) kW 4,4 6,2 8,8 13,3 13,9 18,3 21,2 23,5 28,0 35,7 40,7 49,0 56,0 60,2 66,5 79,4
Water flow rate l/s 0,21 0,30 0,42 0,64 0,67 0,87 1,03 1,12 1,35 1,71 2,00 2,34 2,70 2,91 3,21 3,83
Pressure drop 3) kPa 58 70 64 69 63 52 61 51 84 48 67 44 42 79 95 57
Cooling capacity 2)
Total (27°C-50%) kW 6,0 8,3 11,5 17,3 19,8 24,6 27,6 32,2 37,7 48,0 55,3 67,7 76,0 85,1 94,6 110
Sensible (27°C-50%) kW 5,4 7,4 10,3 15,6 17,8 22,2 24,9 29,0 33,9 43,2 49,8 61,0 68,4 76,6 85,1 98,6
Water flow rate l/s 0,29 0,39 0,55 0,83 0,95 1,18 1,32 1,54 1,80 2,29 2,64 3,24 3,63 4,07 4,52 5,23
Total (24°C-50%) kW 4,1 5,6 7,7 11,7 13,4 16,7 18,7 21,8 25,5 32,4 37,4 45,8 51,4 57,5 63,9 74,0
Sensible (24°C-50%) kW 4,1 5,6 7,7 11,7 13,4 16,7 18,7 21,8 25,5 32,4 37,4 45,8 51,4 57,5 63,9 74,0
Water flow rate l/s 0,19 0,27 0,37 0,56 0,64 0,80 0,89 1,04 1,22 1,55 1,78 2,19 2,45 2,75 3,05 3,54
Total (22°C-50%) kW 3,2 4,5 6,2 9,4 10,7 13,3 14,9 17,4 20,4 25,9 29,9 36,6 41,1 46,0 51,1 59,2
Sensible (22°C-50%) kW 2,9 4,0 5,6 8,4 9,6 12,0 13,4 15,7 18,3 23,3 26,9 32,9 37,0 41,4 46,0 53,3
Water flow rate l/s 0,16 0,21 0,30 0,45 0,51 0,64 0,71 0,83 0,97 1,24 1,43 1,75 1,96 2,20 2,44 2,83
Pressure drop 3) kPa 30 36 33 35 32 26 31 26 43 25 34 22 21 40 48 29
Centrifugal fans
Number n.° 1 1 1 1 2 2 2 2 2 2 2 3 3 4 4 4
Air flow rate l/s 388 445 625 890 1700 1556 1500 2083 2083 2772 3000 4583 4375 5970 6950 6670
Air flow rate mc/h 1396,8 1602 2250 3204 6120 5602 5400 7499 7499 9979 10800 16499 15750 21492 25020 24012
Ext avaible pressure 6) Pa 50 45 45 70 80 115 120 75 60 60 30 45 50 40 55 75
Higher avaible pressure 1M Pa 90 105 70 125 135 155 165 95 80 130 90 70 110 195 205 220
Higher avaible pressure 2M Pa 140 220 175 155 270 280 280 135 120 235 220 170 190 245 280 290
Higher avaible pressure 3M Pa 200 230 250 205 335 335 330 260 245 285 290 245 260 365 nd nd
Higher avaible pressure 4M Pa 270 245 260 335 nd nd nd nd nd 335 450 395 400 395 nd nd
Higher avaible pressure 5M Pa 570 295 330 425 nd nd nd nd nd 445 nd nd nd nd nd nd
Max absorbed power. 7) W 446 446 446 908 1518 1518 1518 2277 2277 2178 2244 6664 6664 8885 10662 10662
Max absorbed current.7) A 2,7 2,7 2,7 5,5 9,2 9,2 9,2 13,8 13,8 13,2 13,6 13,5 13,5 18 21,6 21,6
Humidifier
Max steam prodution kg/h 5 5 5 5 5 5 5 5 5 13 13 13 13 13 13 13
Max absorbed power kW 3,7 3,7 3,7 3,7 3,7 3,7 3,7 3,7 3,7 9,4 9,4 9,4 9,4 9,4 9,4 9,4
Max absorbed current A 9,7 9,7 9,7 9,7 9,7 9,7 9,7 9,7 9,7 24,7 24,7 24,7 24,7 24,7 24,7 24,7
Electric heater
Capacity kW 3 3 3 6 9 9 9 9 9 13,5 13,5 18 18 18 18 18
Steps n.° 1 1 1 2 3 3 3 3 3 3 3 3 3 3 3 3
Absorbed current A 7,8 7,8 7,8 13,3 13,3 13,3 13,3 13,3 13,3 19,9 19,9 26,6 26,6 26,6 26,6 26,6
Warm water coil 4)
Capacity kW 5 5 7 11 15 15 15 19 19 22 24 25 25 35 35 35
Water flow rate l/s 0,08 0,08 0,15 0,18 0,24 0,24 0,24 0,3 0,3 0,4 0,4 0,41 0,41 0,57 0,57 0,57
Pressure drop (coil + valve) kPa 23 23 17 25 52 52 52 38 38 61 67 28 28 44 44 44
Sound pressure level 5)
Version D dB(A) 45 45 46 48 56 54 53 58 58 57 58 58 58 59 63 62
Dimensions - Weight
Length mm 490 490 640 940 1230 1230 1230 1530 1530 1730 1990 2390 2390 2950 2950 2950
Width mm 565 565 565 565 665 665 665 665 665 815 815 815 815 815 815 815
Height mm 1800 1800 1800 1800 1975 1975 1975 1975 1975 1995 1995 1995 1995 1995 1995 1995
Weight kg 155 160 190 198 221 230 241 267 274 290 310 325 332 346 370 384
Power supply 400V-50Hz-3F+T+N
MILLENNIUM E 07/02
TECHNICAL DATA FOR FANS
FOR MODELS ED…A - ED…M - ED…W - ONE CIRCUIT VERSION U - V - B
61 81 91 101 121 141 151 171 201 221 241 251 291 301
Number n 1 1 1 1 1 1 1 1 1 2 2 2 2 2
Higher available pressure std 1) Pa 75 90 90 90 90 85 45 70 70 75 75 75 60 70
Power supply V 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph
Name - plate input power W 245 245 245 280 280 280 350 350 350 280 280 280 280 550
Max. absorbed current A 2,7 2,7 2,7 2,7 2,7 2,7 3,0 3,8 3,8 5,4 5,4 5,4 5,4 9,2
Max. absorbed power W 446 446 446 446 446 446 495 627 627 891 891 891 891 1518
Higher available pressure 1M 1) Pa 145 145 145 120 120 115 87 120 120 200 200 200 185 155
Power supply V 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph
Name - plate input power W 300 350 350 420 420 420 350 550 550 550 550 550 550 550
Max absorbed current A 2,3 3,1 3,1 3,4 3,4 3,4 3,8 4,6 4,6 9,2 9,2 9,2 9,2 13,6
Max. absorbed power W 380 512 512 561 561 561 627 759 759 1518 1518 1518 1518 2244
Increase of dB(A) 2) dB(A) 3 0 0 4 4 4 0 6 6 7 7 7 7 0
Higher available pressure 2M 1) Pa 200 270 270 180 180 175 125 200 200 245 245 245 230 250
Power supply V 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph
Name - plate input power W 350 350 350 420 420 420 350 550 550 550 550 550 550 550
Max absorbed current A 3,1 3,1 3,1 3,4 3,4 3,4 3,8 4,6 4,6 13,6 13,6 13,6 13,6 11,8
Max. absorbed power W 512 512 512 561 561 561 627 759 759 2244 2244 2244 2244 1947
Increase of dB(A) 2) dB(A) 7 0 0 5 5 5 0 3 3 6 6 6 6 0
Higher available pressure 3M 1) Pa 260 345 345 240 240 235 295 290 290 265 265 265 250 300
Power supply V 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph
Name - plate input power W 350 373 373 550 550 550 550 550 550 550 550 550 550 550
Max absorbed current A 3,1 4,1 4,1 4,6 4,6 4,6 4,6 5,9 5,9 9,2 9,2 9,2 9,2 13
Max. absorbed power W 512 677 677 759 759 759 759 974 974 1518 1518 1518 1518 2145
Increase of dB(A) 2) dB(A) 7 1 1 7 7 7 2 5 5 5 5 5 5 0
Higher available pressure 4M 1) Pa 410 405 405 380 380 375 340 353 353 355 355 355 340 360
Power supply V 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 380V 3Ph
Name - plate input power W 550 550 550 550 550 550 550 550 550 550 550 550 550 1500
Max absorbed current A 5,5 5,5 5,5 5,9 5,9 5,9 5,7 6,5 6,5 11,8 11,8 11,8 11,8 11,2
Max. absorbed power W 908 908 908 974 974 974 941 1073 1073 1947 1947 1947 1947 5529
Increase of dB(A) 2) dB(A) 8 9 9 8 8 8 4 6 6 6 6 6 6 4
Higher available pressure 5M 1) Pa 560 455 455 nd nd nd 440 420 420 405 405 405 390 nd
Power supply V 220V 1Ph 220V 1Ph 220V 1Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph
Name - plate input power W 550 550 550 1500 1500 1500 1500 1500 1500 1500
Max absorbed current A 5,5 5,5 5,5 5,6 5,6 5,6 11,2 11,2 11,2 11,2
Max. absorbed power W 908 908 908 2764 2764 2764 5529 5529 5529 5529
Increase of dB(A) 2) dB(A) 16 9 9 8 9 9 10 10 10 10
341 321 361 451 351 431 531 471 521 601 581 651 721 821
Number n 2 2 2 2 2 2 2 2 2 2 3 3 3 3
Higher available pressure std 1) Pa 70 165 165 150 70 65 40 65 65 60 55 55 70 70
Power supply V 220V 1Ph 380V 3Ph 380V 3Ph 380V 3Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 380V 3Ph 380V 3Ph
Name - plate input power W 550 550 550 550 736 736 736 736 736 736 736 736 1100 1100
Max. absorbed current A 9,2 5 5 5 13,2 13,2 13,2 13,6 13,6 13,6 20,4 20,4 13,5 13,5
Max. absorbed power W 1518 2468 2468 2468 2178 2178 2178 2244 2244 2244 3366 3366 6664 6664
Higher available pressure 1M 1) Pa 155 185 185 170 135 130 105 110 110 110 95 95 215 215
Power supply V 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph
Name - plate input power W 550 550 550 550 1100 1100 1100 1100 1100 1100 1100 1100 1500 1500
Max. absorbed current A 13,6 13 13 13 8,6 8,6 8,6 9 9 9 13,5 13,5 16,8 16,8
Max. absorbed power W 2244 2145 2145 2145 4245 4245 4245 4443 4443 4443 6664 6664 8293 8293
Increase of dB(A) 2) dB(A) 0 0 0 0 1 1 1 1 1 1 0 0 6 6
Higher available pressure 2M 1) Pa 250 235 235 220 240 235 210 250 250 250 260 260 290 290
Power supply V 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph
Name - plate input power W 550 600 600 600 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500
Max. absorbed current A 11,8 16,4 16,4 16,4 9,4 9,4 9,4 11,2 11,2 11,2 16,8 16,8 16,2 16,2
Max. absorbed power W 1947 2706 2706 2706 4640 4640 4640 5529 5529 5529 8293 8293 7997 7997
Increase of dB(A) 2) dB(A) 0 0 0 0 8 8 8 6 6 6 5 5 3 3
Higher available pressure 3M 1) Pa 300 335 335 320 290 285 260 335 335 335 320 320 405 405
Power supply V 220V 1Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph
Name - plate input power W 550 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500
Max. absorbed current A 13 9,4 9,4 9,4 11,2 11,2 11,2 10,6 10,6 10,6 16,2 16,2 16,2 16,2
Max. absorbed power W 2145 4640 4640 4640 5529 5529 5529 5232 5232 5232 7997 7997 7997 7997
Increase of dB(A) 2) dB(A) 0 4 4 4 4 4 4 3 3 3 3 3 4 4
Higher available pressure 4M 1) Pa 360 375 375 360 340 335 310 450 450 450 410 410 nd nd
Power supply V 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph
Name - plate input power W 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500
Max. absorbed current A 11,2 11,2 11,2 11,2 10 10 10 10,6 10,6 10,6 16,2 16,2
Max. absorbed power W 5529 5529 5529 5529 4936 4936 4936 5232 5232 5232 7997 7997
Increase of dB(A) 2) dB(A) 4 1 1 1 3 3 3 4 4 4 4 4
Higher available pressure 5M 1) Pa nd nd nd nd 460 455 430 nd nd nd nd nd nd nd
Power supply V 380V 3Ph 380V 3Ph 380V 3Ph
Name - plate input power W 1500 1500 1500
Max. absorbed current A 10 10 10
Max. absorbed power W 4936 4936 4936
Increase of dB(A) 2) dB(A) 5 5 5
MILLENNIUM E 07/02
TECHNICAL DATA FOR FANS
FOR MODELS ED…A - ED…M - ED…W - ONE CIRCUIT VERSION D
61 81 91 101 121 141 151 171 201 221 241 251 291 301
Number n 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Higher available pressure std 1) Pa 65 55 55 45 45 40 65 90 90 80 80 80 60 60
Power supply V 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph
Name - plate input power W 245 350 350 280 280 280 350 550 550 1100 1100 1100 1100 1500
Max. absorbed current A 2,7 3,1 3,1 2,7 2,7 2,7 3,8 4,6 4,6 4,3 4,3 4,3 4,3 5,6
Max. absorbed power W 446 512 512 446 446 446 627 759 759 2123 2123 2123 2123 2764
Higher available pressure 1M 1) Pa 120 180 180 75 75 70 105 170 170 210 210 210 190 90
Power supply V 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph
Name - plate input power W 300 350 350 420 420 420 350 550 550 1500 1500 1500 1500 1500
Max absorbed current A 2,3 3,1 3,1 3,4 3,4 3,4 3,8 4,6 4,6 5,6 5,6 5,6 5,6 5,4
Max. absorbed power W 380 512 512 561 561 561 627 759 759 2764 2764 2764 2764 2666
Increase of dB(A) 2) dB(A) 3 0 0 4 4 4 1 0 0 4 4 4 4 0
Higher available pressure 2M 1) Pa 180 255 255 135 135 130 280 260 260 242 242 242 220 255
Power supply V 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph
Name - plate input power W 350 373 373 420 420 420 550 550 550 1500 1500 1500 1500 1500
Max absorbed current A 3,1 4,1 4,1 3,4 3,4 3,4 4,6 5,9 5,9 5,0 5,0 5,0 5,0 5,0
Max. absorbed power W 512 677 677 561 561 561 911 1168 1168 2468 2468 2468 2468 2468
Increase of dB(A) 2) dB(A) 7 0 0 5 5 5 5 0 0 1 1 1 1 0
Higher available pressure 3M 1) Pa 330 315 315 195 195 190 320 320 320 400 400 400 380 310
Power supply V 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph
Name - plate input power W 350 550 550 550 550 550 550 550 550 1500 1500 1500 1500 1500
Max absorbed current A 3,1 5,5 5,5 4,6 4,6 4,6 5,7 6,5 6,5 5,0 5,0 5,0 5,0 5,4
Max. absorbed power W 512 908 908 759 759 759 941 1073 1073 2468 2468 2468 2468 2666
Increase of dB(A) 2) dB(A) 7 1 1 7 7 7 7 0 0 3 3 3 3 0
Higher available pressure 4M 1) Pa 480 365 365 335 335 330 410 390 390 nd nd nd nd nd
Power supply V 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 380V 3Ph 380V 3Ph 380V 3Ph
Name - plate input power W 550 550 550 550 550 550 1500 1500 1500
Max absorbed current A 5,5 5,5 5,5 5,9 5,9 5,9 5,6 5,6 5,6
Max. absorbed power W 908 908 908 974 974 974 2764 2764 2764
Increase of dB(A) 2) dB(A) 8 9 9 8 8 8 11 3 3
Higher available pressure 5M 1) Pa 630 nd nd nd nd nd nd nd nd nd nd nd nd nd
Power supply V 220V 1Ph
Name - plate input power W 550
Max absorbed current A 5,5
Max. absorbed power W 908
Increase of dB(A) 2) dB(A) 16
341 321 361 451 351 431 531 471 521 601 581 651 721 821
Number n 1 2 2 2 2 2 2 2 2 2 3 3 3 3
Higher available pressure std 1) Pa 60 50 50 35 60 55 30 40 40 40 45 45 45 45
Power supply V 380V 3Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 380V 3Ph 380V 3Ph
Name - plate input power W 1500 550 550 550 736 736 736 736 736 736 736 736 1100 1100
Max. absorbed current A 5,6 13 13 13 13,2 13,2 13,2 13,6 13,6 13,6 20,4 20,4 13,5 13,5
Max. absorbed power W 2764 2145 2145 2145 2178 2178 2178 2244 2244 2244 3366 3366 6664 6664
Higher available pressure 1M 1) Pa 90 95 95 80 125 120 95 90 90 90 85 85 195 195
Power supply V 380V 3Ph 220V 1Ph 220V 1Ph 220V 1Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph
Name - plate input power W 1500 600 600 600 1100 1100 1100 1100 1100 1100 1100 1100 1500 1500
Max. absorbed current A 5,4 16,4 16,4 16,4 8,6 8,6 8,6 9 9 9 13,5 13,5 16,8 16,8
Max. absorbed power W 2666 2706 2706 2706 4245 4245 4245 4443 4443 4443 6664 6664 8293 8293
Increase of dB(A) 2) dB(A) -6 -1 -1 -1 1 1 1 1 1 1 0 0 6 6
Higher available pressure 2M 1) Pa 255 195 195 180 230 225 200 230 230 230 250 250 265 265
Power supply V 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph
Name - plate input power W 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500
Max. absorbed current A 5,0 9,4 9,4 9,4 9,4 9,4 9,4 11,2 11,2 11,2 16,8 16,8 16,2 16,2
Max. absorbed power W 2468 4640 4640 4640 4640 4640 4640 5529 5529 5529 8293 8293 7997 7997
Increase of dB(A) 2) dB(A) -1 6 6 6 8 8 8 6 6 6 5 5 3 3
Higher available pressure 3M 1) Pa 310 235 235 220 280 275 250 315 315 315 310 310 380 380
Power supply V 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph
Name - plate input power W 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500
Max. absorbed current A 5,4 11,2 11,2 11,2 11,2 11,2 11,2 10,8 10,8 10,8 16,2 16,2 16,2 16,2
Max. absorbed power W 2666 5529 5529 5529 5529 5529 5529 5331 5331 5331 7997 7997 7997 7997
Increase of dB(A) 2) dB(A) -4 3 3 3 4 4 4 3 3 3 3 3 4 4
Higher available pressure 4M 1) Pa nd nd nd nd 330 325 300 430 430 430 400 400 nd nd
Power supply V 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph
Name - plate input power W 1500 1500 1500 1500 1500 1500 1500 1500
Max. absorbed current A 10 10 10 10,8 10,8 10,8 16,2 16,2
Max. absorbed power W 4936 4936 4936 5331 5331 5331 7997 7997
Increase of dB(A) 2) dB(A) 3 3 3 4 4 4 4 4
Higher available pressure 5M 1) Pa nd nd nd nd 450 445 420 nd nd nd nd nd nd nd
Power supply V 380V 3Ph 380V 3Ph 380V 3Ph
Name - plate input power W 1500 1500 1500
Max. absorbed current A 10 10 10
Max. absorbed power W 4936 4936 4936
Increase of dB(A) 2) dB(A) 5 5 5
MILLENNIUM E 07/02
TECHNICAL DATA FOR FANS
FOR MODELS ED…A - ED…M - ED…W - TWO CIRCUITS VERSIONS U - V - B
172 192 202 232 272 342 302 362 442 412 452 492
Number n 1 1 2 2 2 2 2 2 2 2 2 2
Higher available pressure std 1) Pa 70 70 75 75 75 70 165 165 150 70 65 40
Power supply V 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 380V 3Ph 380V 3Ph 380V 3Ph 220V 1Ph 220V 1Ph 220V 1Ph
Name - plate input power W 350 350 280 280 280 550 550 550 550 736 736 736
Max. absorbed current A 3,8 3,8 5,4 5,4 5,4 9,2 5,0 5,0 5,0 13,2 13,2 13,2
Max. absorbed power W 627 627 891 891 891 1518 2468 2468 2468 2178 2178 2178
Higher available pressure 1M 1) Pa 120 120 200 200 200 155 185 185 170 135 130 105
Power supply V 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 380V 3Ph 380V 3Ph 380V 3Ph
Name - plate input power W 550 550 550 550 550 550 550 550 550 1100 1100 1100
Max absorbed current A 4,6 4,6 9,2 9,2 9,2 13,6 13 13 13 8,6 8,6 8,6
Max. absorbed power W 759 759 1518 1518 1518 2244 2145 2145 2145 4245 4245 4245
Increase of dB(A) 2) dB(A) 6 6 7 7 7 0 0 0 0 0 0 0
Higher available pressure 2M 1) Pa 200 200 245 245 245 250 235 235 220 240 235 210
Power supply V 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 380V 3Ph 380V 3Ph 380V 3Ph
Name - plate input power W 550 550 550 550 550 550 600 600 600 1500 1500 1500
Max absorbed current A 4,6 4,6 13,6 13,6 13,6 11,8 16,4 16,4 16,4 9,4 9,4 9,4
Max. absorbed power W 759 759 2244 2244 2244 1947 2706 2706 2706 4640 4640 4640
Increase of dB(A) 2) dB(A) 3 3 6 6 6 0 0 0 0 8 8 8
Higher available pressure 3M 1) Pa 290 290 265 265 265 300 335 335 320 290 285 260
Power supply V 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph
Name - plate input power W 550 550 550 550 550 550 1500 1500 1500 1500 1500 1500
Max absorbed current A 5,9 5,9 9,2 9,2 9,2 13 9,4 9,4 9,4 11,2 11,2 11,2
Max. absorbed power W 974 974 1518 1518 1518 2145 4640 4640 4640 5529 5529 5529
Increase of dB(A) 2) dB(A) 5 5 5 5 5 0 4 4 4 4 4 4
Higher available pressure 4M 1) Pa 353 353 355 355 355 360 375 375 360 340 335 310
Power supply V 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph
Name - plate input power W 550 550 550 550 550 1500 1500 1500 1500 1500 1500 1500
Max absorbed current A 6,5 6,5 11,8 11,8 11,8 11,2 11,2 11,2 11,2 10 10 10
Max. absorbed power W 1073 1073 1947 1947 1947 5529 5529 5529 5529 4936 4936 4936
Increase of dB(A) 2) dB(A) 6 6 6 6 6 0 1 1 1 3 3 3
Higher available pressure 5M 1) Pa 420 420 405 405 405 nd nd nd nd 460 455 430
Power supply V 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph
Name - plate input power W 1500 1500 1500 1500 1500 1500 1500 1500
Max absorbed current A 5,6 5,6 11,2 11,2 11,2 10 10 10
Max. absorbed power W 2764 2764 5529 5529 5529 4936 4936 4936
Increase of dB(A) 2) dB(A) 9 9 10 10 10 5 5 5
482 532 572 602 542 622 682 842 762 892 1002 1102
Number n 2 2 2 2 3 3 3 3 4 4 4 4
Higher available pressure std 1) Pa 65 65 65 65 55 55 70 70 55 55 50 75
Power supply V 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 380V 3Ph 380V 3Ph 220V 1Ph 220V 1Ph 220V 1Ph 380V 3Ph
Name - plate input power W 736 736 736 736 736 736 1100 1100 736 736 736 1500
Max. absorbed current A 13,6 13,6 13,6 13,6 20,4 20,4 13,5 13,5 27,2 27,2 27,2 21,6
Max. absorbed power W 2244 2244 2244 2244 3366 3366 6664 6664 4488 4488 4488 10662
Higher available pressure 1M 1) Pa 110 110 110 110 95 95 215 215 95 95 90 220
Power supply V 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph
Name - plate input power W 1100 1100 1100 1100 1100 1100 1500 1500 1100 1100 1100 1500
Max absorbed current A 9 9 9 9 13,5 13,5 16,8 16,8 18 18 18 20
Max. absorbed power W 4443 4443 4443 4443 6664 6664 8293 8293 8885 8885 8885 9872
Increase of dB(A) 2) dB(A) 0 0 0 0 1 1 6 6 0 0 0 4
Higher available pressure 2M 1) Pa 250 250 250 250 260 260 290 290 260 260 255 290
Power supply V 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph
Name - plate input power W 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500
Max absorbed current A 11,2 11,2 11,2 11,2 16,8 16,8 16,2 16,2 22,4 22,4 22,4 21,6
Max. absorbed power W 5529 5529 5529 5529 8293 8293 7997 7997 11057 11057 11057 10662
Increase of dB(A) 2) dB(A) 6 6 6 6 5 5 3 6 6 6 6 2
Higher available pressure 3M 1) Pa 335 335 335 335 320 320 405 405 330 330 325 nd
Power supply V 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph
Name - plate input power W 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500
Max absorbed current A 10,8 10,8 10,8 10,8 16,2 16,2 16,2 16,2 21,6 21,6 21,6
Max. absorbed power W 5331 5331 5331 5331 7997 7997 7997 7997 10662 10662 10662
Increase of dB(A) 2) dB(A) 3 3 3 3 6 6 4 4 4 4 4
Higher available pressure 4M 1) Pa 450 450 450 450 410 410 nd nd 410 410 405 nd
Power supply V 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph
Name - plate input power W 1500 1500 1500 1500 1500 1500 1500 1500 1500
Max absorbed current A 10,8 10,8 10,8 10,8 16,2 16,2 21,6 21,6 21,6
Max. absorbed power W 5331 5331 5331 5331 7997 7997 10662 10662 10662
Increase of dB(A) 2) dB(A) 4 4 4 4 4 4 5 5 5
Higher available pressure 5M 1) Pa nd nd nd nd nd nd nd nd nd nd nd nd
Power supply V
Name - plate input power W
Max absorbed current A
Max. absorbed power W
Increase of dB(A) 2) dB(A)
MILLENNIUM E 07/02
TECHNICAL DATA FOR FANS
FOR MODELS ED…A - ED…M - ED…W - TWO CIRCUITS VERSIONS D
172 192 202 232 272 342 302 362 442 412 452 492
Number n 1 1 1 1 1 1 2 2 2 2 2 2
Higher available pressure std 1) Pa 90 90 80 80 80 60 50 50 35 60 55 30
Tensione di alimentazione V 220V 1Ph 220V 1Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 220V 1Ph 220V 1Ph 220V 1Ph
Potenza di targa per motore W 350 350 1100 1100 1100 1500 550 550 550 736 736 736
Corrente assorbita max. A 3,8 3,8 4,3 4,3 4,3 5,6 5,0 5,0 5,0 13,2 13,2 13,2
Potenza assorbita max. W 627 627 2123 2123 2123 2764 2468 2468 2468 2178 2178 2178
Prevalenza disponibile 1M 1) Pa 170 170 210 210 210 90 95 95 80 125 120 95
Tensione di alimentazione V 220V 1Ph 220V 1Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 220V 1Ph 220V 1Ph 220V 1Ph 380V 3Ph 380V 3Ph 380V 3Ph
Potenza di targa per motore W 550 550 1500 1500 1500 1500 550 550 550 1100 1100 1100
Corrente assorbita max. A 4,6 4,6 5,6 5,6 5,6 5,4 13 13 13 8,6 8,6 8,6
Potenza assorbita max. W 759 759 2764 2764 2764 2666 2145 2145 2145 4245 4245 4245
Incremento di dB(A) 2) dB(A) 6 6 4 4 4 6 0 0 0 0 0 0
Prevalenza disponibile 2M 1) Pa 260 260 242 242 242 255 195 195 180 230 225 200
Tensione di alimentazione V 220V 1Ph 220V 1Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 220V 1Ph 220V 1Ph 220V 1Ph 380V 3Ph 380V 3Ph 380V 3Ph
Potenza di targa per motore W 550 550 1500 1500 1500 1500 600 600 600 1500 1500 1500
Corrente assorbita max. A 4,6 4,6 5 5 5 5 16,4 16,4 16,4 9,4 9,4 9,4
Potenza assorbita max. W 759 759 2468 2468 2468 2468 2706 2706 2706 4640 4640 4640
Incremento di dB(A) 2) dB(A) 3 3 1 1 1 0 0 0 0 8 8 8
Prevalenza disponibile 3M 1) Pa 320 320 400 400 400 310 235 235 220 280 275 250
Tensione di alimentazione V 220V 1Ph 220V 1Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph
Potenza di targa per motore W 550 550 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500
Corrente assorbita max. A 5,9 5,9 5 5 5 5,4 9,4 9,4 9,4 11,2 11,2 11,2
Potenza assorbita max. W 974 974 2468 2468 2468 2666 4640 4640 4640 5529 5529 5529
Incremento di dB(A) 2) dB(A) 5 5 3 3 3 4 4 4 4 4 4 4
Prevalenza disponibile 4M 1) Pa 390 390 nd nd nd nd 275 275 260 330 325 300
Tensione di alimentazione V 220V 1Ph 220V 1Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph
Potenza di targa per motore W 1500 1500 1500 1500 1500 1500 1500 1500
Corrente assorbita max. A 6,5 6,5 11,2 11,2 11,2 10 10 10
Potenza assorbita max. W 1073 1073 5529 5529 5529 4936 4936 4936
Incremento di dB(A) 2) dB(A) 6 6 1 1 1 3 3 3
Prevalenza disponibile 5M 1) Pa 457 457 nd nd nd nd nd nd nd 450 445 420
Tensione di alimentazione V 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph
Potenza di targa per motore W 1500 1500 1500 1500 1500
Corrente assorbita max. A 5,6 5,6 10 10 10
Potenza assorbita max. W 2764 2764 4936 4936 4936
Incremento di dB(A) 2) dB(A) 9 9 5 5 5
482 532 572 602 542 622 682 842 762 892 1002 1102
N° ventilatori n 2 2 2 2 3 3 3 3 4 4 4 4
Prevalenza disponibile std 1) Pa 40 40 40 40 45 45 45 45 40 40 35 35
Tensione di alimentazione V 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 380V 3Ph 380V 3Ph 220V 1Ph 220V 1Ph 220V 1Ph 380V 3Ph
Potenza di targa per motore W 736 736 736 736 736 736 1100 1100 736 736 736 1500
Corrente assorbita max. A 13,6 13,6 13,6 13,6 20,4 20,4 13,5 13,5 27,2 27,2 27,2 21,6
Potenza assorbita max. W 2244 2244 2244 2244 3366 3366 6664 6664 4488 4488 4488 10662
Prevalenza disponibile 1M 1) Pa 90 90 90 90 85 85 195 195 80 80 75 180
Tensione di alimentazione V 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph
Potenza di targa per motore W 1100 1100 1100 1100 1100 1100 1500 1500 1100 1100 1100 1500
Corrente assorbita max. A 9 9 9 9 13,5 13,5 16,8 16,8 18 18 18 20
Potenza assorbita max. W 4443 4443 4443 4443 6664 6664 8293 8293 8885 8885 8885 9872
Incremento di dB(A) 2) dB(A) 0 0 0 0 1 1 6 6 0 0 0 4
Prevalenza disponibile 2M 1) Pa 230 230 230 230 250 250 265 265 245 245 240 250
Tensione di alimentazione V 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph
Potenza di targa per motore W 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500
Corrente assorbita max. A 11,2 11,2 11,2 11,2 16,8 16,8 16,2 16,2 22,4 22,4 22,4 21,6
Potenza assorbita max. W 5529 5529 5529 5529 8293 8293 7997 7997 11057 11057 11057 10662
Incremento di dB(A) 2) dB(A) 6 6 6 6 5 5 3 6 6 6 6 2
Prevalenza disponibile 3M 1) Pa 315 315 315 315 310 310 380 380 315 315 310 nd
Tensione di alimentazione V 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph
Potenza di targa per motore W 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500
Corrente assorbita max. A 10,8 10,8 10,8 10,8 16,2 16,2 16,2 16,2 21,6 21,6 21,6
Potenza assorbita max. W 5331 5331 5331 5331 7997 7997 7997 7997 10662 10662 10662
Incremento di dB(A) 2) dB(A) 3 3 3 3 6 6 4 4 4 4 4
Prevalenza disponibile 4M 1) Pa 430 430 430 430 400 400 nd nd 395 395 390 nd
Tensione di alimentazione V 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph
Potenza di targa per motore W 1500 1500 1500 1500 1500 1500 1500 1500 1500
Corrente assorbita max. A 10,8 10,8 10,8 10,8 16,2 16,2 21,6 21,6 21,6
Potenza assorbita max. W 5331 5331 5331 5331 7997 7997 10662 10662 10662
Incremento di dB(A) 2) dB(A) 4 4 4 4 4 4 5 5 5
Prevalenza disponibile 5M 1) Pa nd nd nd nd nd nd nd nd nd nd nd nd
Tensione di alimentazione V
Potenza di targa per motore W
Corrente assorbita max. A
Potenza assorbita max. W
Incremento di dB(A) 2) dB(A)
MILLENNIUM E 07/02
TECHNICAL DATA FOR FANS
FOR MODELS UV - VERSIONS U - V - B
60 80 120 170 190 240 280 320 380 470 550 640 740 800 870 1000
Number n 1 1 1 1 2 2 2 2 2 2 2 3 3 4 4 4
Higher available pressure std 1) Pa 85 65 50 40 45 70 75 65 55 100 65 85 90 85 110 130
Power supply V 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph
Name - plate input power W 245 245 280 500 280 350 350 550 550 736 736 1100 1100 1100 1500 1500
Max. absorbed current A 2,7 2,7 2,7 5,5 5,4 7,6 7,6 13,6 13,6 13,2 13,6 13,5 13,5 18,0 21,6 21,6
Max. absorbed power W 446 446 446 908 891 1254 1254 2244 2244 2178 2244 6664 6664 8885 10662 10662
Higher available pressure 1M 1) Pa 110 125 70 100 70 90 95 160 150 170 125 110 150 240 260 275
Power supply V 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph
Name - plate input power W 300 350 350 550 350 550 550 600 600 1100 1100 1500 1500 1500 1500 1500
Max. absorbed current A 2,3 3,1 3,8 6,8 7,6 9,2 9,2 12,8 12,8 8,6 9 14,1 14,1 20 20 20
Max. absorbed power W 380 512 627 1122 1254 1518 1518 2112 2112 4245 4443 6960 6960 9872 9872 9872
Increase of dB(A) 2) dB(A) 5 2 2 0 1 5 5 1 1 1 1 11 11 5 5 4
Higher available pressure 2M 1) Pa 180 220 165 140 150 185 195 210 200 275 255 210 230 290 335 345
Power supply V 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph
Name - plate input power W 350 300 550 550 550 550 550 550 550 1500 1500 1500 1500 1500 1500 1500
Max. absorbed current A 3,1 2,6 4,6 6,8 9,2 13,6 13,6 13,8 13,8 9,4 11,2 16,8 16,8 21,6 21,6 21,6
Max. absorbed power W 512 515 759 1122 1518 2244 2244 2277 2277 4640 5529 8293 8293 10662 10662 10662
Increase of dB(A) 2) dB(A) 7 3 6 0 7 5 5 2 2 7 7 5 5 3 2 2
Higher available pressure 3M 1) Pa 230 250 225 150 210 230 240 230 220 325 325 285 300 410 nd nd
Power supply V 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph
Name - plate input power W 350 350 550 550 550 550 550 550 550 1500 1500 1500 1500 1500
Max. absorbed current A 3,1 3,1 6,8 5,9 13,6 13 13 5 5 11,2 10,8 16,2 16,2 20
Max. absorbed power W 512 512 1122 974 2244 2145 2145 2468 2468 5529 5331 7997 7997 9872
Increase of dB(A) 2) dB(A) 7 4 8 -1 7 6 7 1 1 4 4 2 2 6
Higher available pressure 4M 1) Pa 275 265 320 310 350 355 355 270 260 375 485 435 440 440 nd nd
Power supply V 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 380V 3Ph 380V 3Ph 220V 1Ph 220V 1Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph
Name - plate input power W 550 420 550 550 550 1500 1500 550 550 1500 1500 1500 1500 1500
Max. absorbed current A 5,5 3,6 5,9 6,9 13 11,2 11,2 13 13 10 10,8 16,2 16,2 21,6
Max. absorbed power W 908 594 974 1139 2145 5529 5529 2145 2145 4936 5331 7997 7997 10662
Increase of dB(A) 2) dB(A) 8 5 8 1 7 11 11 0 0 3 5 4 3 4
Higher available pressure 5M 1) Pa 590 315 340 410 410 395 385 495 nd nd nd nd nd nd
Power supply V 220V 1Ph 220V 1Ph 220V 1Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph
Name - plate input power W 550 373 550 1500 1500 1500 1500 1500
Max. absorbed current A 5,5 4,1 6,5 5,6 11,2 11,2 11,2 10
Max. absorbed power W 907,5 676,5 1072,5 2764 5529 5529 5529 4936
Increase of dB(A) 2) dB(A) 16 12 8 1 11 3 3 5
MILLENNIUM E 07/02
TECHNICAL DATA FOR FANS
FOR MODELS UV - VERSION D
60 80 120 170 190 240 280 320 380 470 550 640 740 800 870 1000
Number n 1 1 1 1 2 2 2 2 2 2 2 3 3 4 4 4
Higher available pressure std 1) Pa 50 45 45 70 80 115 120 75 60 60 30 45 50 40 55 75
Power supply V 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph
Name - plate input power W 245 245 280 500 550 550 550 550 550 736 736 1100 1100 1100 1500 1500
Max. absorbed current A 2,7 2,7 2,7 5,5 9,2 9,2 9,2 13,8 13,8 13,2 13,6 13,5 13,5 18,0 22 22
Max. absorbed power W 446 446 446 908 1518 1518 1518 2277 2277 2178 2244 6664 6664 8885 10662 10662
Higher available pressure 1M 1) Pa 90 105 70 125 135 155 165 95 80 130 90 70 110 195 205 220
Power supply V 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph
Name - plate input power W 300 350 350 550 550 550 550 550 550 1100 1100 1500 1500 1500 1500 1500
Max. absorbed current A 2,3 3,1 3,8 6,8 13,6 13,6 13,6 5 5 8,6 9 14,1 14,1 15 20 20
Max. absorbed power W 380 512 627 1122 2244 2244 2244 2468 2468 4245 4443 6960 6960 7404 9872 9872
Increase of dB(A) 2) dB(A) 5 2 2 0 0 0 0 0 0 1 1 11 11 5 5 4
Higher available pressure 2M 1) Pa 140 220 175 155 270 280 280 135 120 235 220 170 190 245 280 290
Power supply V 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph
Name - plate input power W 350 300 550 550 550 550 550 550 550 1500 1500 1500 1500 1500 1500 1500
Max. absorbed current A 3,1 2,6 4,6 6,8 13 13 13 13 13 9,4 11,2 16,8 16,8 21,6 21,6 21,6
Max. absorbed power W 512 429 759 1122 2145 2145 2145 2145 2145 4640 5529 8293 8293 10662 10662 10662
Increase of dB(A) 2) dB(A) 7 3 6 0 0 2 2 0 0 7 7 5 5 3 2 2
Higher available pressure 3M 1) Pa 200 230 250 205 335 335 330 260 245 285 290 245 260 365 nd nd
Power supply V 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph
Name - plate input power W 350 350 550 550 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500
Max. absorbed current A 3,1 3,1 6,8 5,9 11,2 11,2 11,2 11,2 11,2 11,2 10,8 16,2 16,2 20
Max. absorbed power W 512 512 1122 974 5529 5529 5529 5529 5529 5529 5331 7997 7997 9872
Increase of dB(A) 2) dB(A) 7 4 8 0 4 6 6 1 1 4 4 2 2 6
Higher available pressure 4M 1) Pa 270 245 260 335 335 450 395 400 395 nd nd
Power supply V 220V 1Ph 220V 1Ph 220V 1Ph 220V 1Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph 380V 3Ph
Name - plate input power W 550 420 550 550 1500 1500 1500 1500 1500
Max. absorbed current A 5,5 3,6 5,9 6,9 10 10,8 16,2 16,2 21,6
Max. absorbed power W 908 594 974 1139 4936 5331 7997 7997 10662
Increase of dB(A) 2) dB(A) 8 5 8 1 3 5 4 3 4
Higher available pressure 5M 1) Pa 570 295 330 425 445 nd nd nd nd nd nd
Power supply V 220V 1Ph 220V 1Ph 220V 1Ph 380V 3Ph 380V 3Ph
Name - plate input power W 550 373 550 1500 1500
Max. absorbed current A 5,5 4,1 6,5 5,6 10
Max. absorbed power W 907,5 676,5 1072,5 2764 4936
Increase of dB(A) 2) dB(A) 16 12 8 1 5
MILLENNIUM E 07/02
PRESSURE DROP
FOR MODELS ED A/W/M - ONE CIRCUIT VERSIONS U -V -B
MODELS ED A/W/M 61 81 91 101 121 141 151 171 201 221 241 251 291 301
Pressure drop BC UVB Pa 11 13 13 10 10 10 8 9 9 12 12 12 12 14
F5 (50) UVB Pa 15 40 40 30 30 30 9 25 25 25 25 25 15 40
F5 (100) UVB Pa / / / / / / / / / 0 0 0 0 2
F6 (50) UVB Pa 85 130 130 115 115 115 44 100 100 100 100 100 90 140
F6 (100) UVB Pa / / / / / / / / / 25 25 25 25 35
F7a (50) UVB Pa 90 190 190 180 180 180 99 140 140 140 140 140 130 200
F7b UVB Pa / / / 170 170 170 206 239 239 193 193 193 193 245
F9 UVB Pa / / / 210 210 210 241 295 295 235 235 235 235 290
Soundprof. baffle
U Pa 12 17 17 18 18 18 10 15 15 55 55 55 55 73
discharge
Soundprof. baffle
V Pa 12 17 17 18 18 18 10 15 15 55 55 55 55 73
discharge
Soundprof. baffle
B Pa 12 17 17 18 18 18 10 15 15 55 55 55 55 73
discharge
Soundprof. baffle
V Pa 23 35 35 30 30 30 16 23 23 34 34 34 34 46
suction
Soundprof. baffle
B Pa 7 8 8 12 12 12 7 8 8 10 10 10 10 13
suction
MODELS ED A/W/M 341 321 361 451 351 431 531 471 521 601 581 651 721 821
Pressure drop BC UVB Pa 14 13 13 13 22 22 22 15 15 15 17 17 18 18
F5 (50) UVB Pa 40 45 45 45 32 32 32 40 40 40 40 40 50 50
F5 (100) UVB Pa 2 10 10 10 0 0 0 2 2 2 0 0 0 0
F6 (50) UVB Pa 140 135 135 135 135 135 135 130 130 130 150 150 165 165
F6 (100) UVB Pa 35 30 30 30 20 20 20 30 30 30 25 25 35 35
F7a (50) UVB Pa 200 200 200 200 195 195 195 180 180 180 325 325 375 375
F7a (100) UVB Pa 90 100 100 100 95 95 95 90 90 90 195 195 225 225
F7b UVB Pa 245 350 350 350 185 185 185 150 150 150 200 200 210 210
F9 UVB Pa 290 395 395 395 220 220 220 185 185 185 242 242 253 253
Soundprof. baffle
U Pa 73 118 118 118 36 36 36 28 28 28 42 42 47 47
discharge
Soundprof. baffle
V Pa 73 118 118 118 36 36 36 28 28 28 42 42 47 47
discharge
Soundprof. baffle
B Pa 73 118 118 118 36 36 36 28 28 28 42 42 47 47
discharge
Soundprof. baffle
V Pa 46 46 46 46 49 49 49 23 23 23 29 29 32 32
suction
Soundprof. baffle
B Pa 13 13 13 13 15 15 15 13 13 13 25 25 28 28
suction
Notes
The F5,F6,F7a filters are to replacing the standard filters F4
Selecting a different filter from the STD one and/or the optional BG, RE, AM..,AR.., it is necessary to check and, eventually, to select, a higher pressure to the fans
MILLENNIUM E 07/02
PRESSURE DROP
FOR MODELS ED A/W/M - ONE CIRCUIT VERSION D
MODELS ED A/W/M 61 81 91 101 121 141 151 171 201 221 241 251 291 301
Pressure drop BC D Pa 11 13 13 10 10 10 8 9 9 12 12 12 12 14
Pressure drop BG D Pa 21 23 23 18 18 18 14 15 15 21 21 21 21 23
F5 (50) D Pa 30 45 46 56 56 56 35 50 50 / / / / /
F5 (100) D Pa / / / / / / / / / 65 65 65 65 115
F6 (50) D Pa 115 155 156 171 172 172 115 155 155 / / / / /
F7a (50) D Pa 247 235 236 246 246 246 190 220 220 / / / / /
F7b D Pa / / / 194 194 194 195 274 274 268 268 268 268 330
F9 D Pa / / / 234 234 234 260 320 320 310 310 310 310 375
Soundprof. baffle
D Pa 23 35 35 30 30 30 16 23 23 34 34 34 34 46
discharge
Soundprof. baffle
D Pa 12 17 17 18 18 18 10 15 15 55 55 55 55 73
suction
MODELS ED A/W/M 341 321 361 451 351 431 531 471 521 601 581 651 721 821
Pressure drop BC D Pa 14 13 13 13 22 22 22 15 15 15 17 17 18 18
Pressure drop BG D Pa 23 18 18 18 31 31 31 26 26 26 24 24 25 25
F6 (100) D Pa 235 / / / 130 130 130 100 100 100 145 145 170 170
F7a (100) D Pa / / / / 310 310 310 255 255 255 305 305 345 345
F7b D Pa 330 / / / 195 195 195 175 175 175 220 220 230 230
F9 D Pa 375 / / / 230 230 230 210 210 210 262 262 273 273
Soundprof. baffle
D Pa 46 46 46 46 49 49 49 23 23 23 29 29 32 32
discharge
Soundprof. baffle
D Pa 73 118 118 118 36 36 36 28 28 28 42 42 47 47
suction
Notes
The F5,F6,F7a filters are to replacing the standard filters F4
Selecting a different filter from the STD one and/or the optional BG, RE, AM..,AR.., it is necessary to check and, eventually, to select, a higher pressure to the fans
MILLENNIUM E 07/02
PRESSURE DROP
FOR MODELS ED A/W/M - TWO CIRCUITS VERSIONS U - V - B
MODELS ED A/W/M 172 192 202 232 272 342 302 362 442 412 452 492
F5 (50) UVB Pa 25 25 25 25 25 40 45 45 45 32 32 32
F5 (100) UVB Pa / / 0 0 0 2 10 10 10 0 0 0
F6 (50) UVB Pa 100 100 100 100 100 140 135 135 135 135 135 135
F6 (100) UVB Pa / / 25 25 25 35 30 30 30 20 20 20
F7a (50) UVB Pa 140 140 140 140 140 200 200 200 200 195 195 195
F7b UVB Pa 239 239 193 193 193 245 350 350 350 185 185 185
F9 UVB Pa 285 285 235 235 235 290 395 395 415 220 220 220
Soundprof. baffle
U Pa 15 15 55 55 55 73 118 118 118 36 36 36
discharge
Soundprof. baffle
V Pa 15 15 55 55 55 73 118 118 118 36 36 36
discharge
Soundprof. baffle
B Pa 15 15 55 55 55 73 118 118 118 36 36 36
discharge
Soundprof. baffle
V Pa 23 23 34 34 34 46 46 46 46 49 49 49
suction
Soundprof. baffle
B Pa 8 8 10 10 10 13 13 13 13 15 15 15
suction
MODELS ED A/W/M 482 532 572 602 542 622 682 842 762 892 1002 1102
Pressure drop BC UVB Pa 15 15 15 15 17 17 18 18 19 19 19 22
F5 (100) UVB Pa 2 2 2 2 0 0 0 0 0 0 0 10
F6 (50) UVB Pa 130 130 130 130 150 150 165 165 178 178 178 275
F6 (100) UVB Pa 30 30 30 30 35 35 35 35 48 48 48 80
F7a (50) UVB Pa 180 180 180 180 325 325 375 375 258 258 258 370
F7a (100) UVB Pa 90 90 90 90 190 190 225 225 143 143 143 230
F7b UVB Pa 150 150 150 150 200 200 210 210 208 208 208 287
F9 UVB Pa 185 185 185 185 242 242 253 253 252 252 252 335
Soundprof. baffle
U Pa 28 28 28 28 42 42 47 47 46 46 46 76
discharge
Soundprof. baffle
V Pa 28 28 28 28 42 42 47 47 46 46 46 76
discharge
Soundprof. baffle
B Pa 28 28 28 28 42 42 47 47 46 46 46 76
discharge
Soundprof. baffle
V Pa 23 23 23 23 29 29 32 32 32 32 32 52
suction
Soundprof. baffle
B Pa 13 13 13 13 25 25 28 28 25 25 25 40
suction
Notes
The F5,F6,F7a filters are to replacing the standard filters F4
Selecting a different filter from the STD one and/or the optional BG, RE, AM..,AR.., it is necessary to check and, eventually, to select, a higher pressure to the fans
MILLENNIUM E 07/02
PRESSURE DROP
FOR MODELS ED A/W/M - TWO CIRCUITS VERSION D
MODELS ED A/W/M 172 192 202 232 272 342 302 362 442 412 452 492
Pressure drop BC D Pa 9 9 12 12 12 14 13 13 13 22 22 22
Pressure drop BG D Pa 15 15 21 21 21 23 18 18 18 31 31 31
F5 (50) D Pa 50 50 / / / / / / / / / /
F7b D Pa 274 274 268 268 268 330 / / / 195 195 195
Soundprof. baffle
D Pa 23 23 34 34 34 46 46 46 46 49 49 49
discharge
Soundprof. baffle
D Pa 15 15 55 55 55 73 118 118 118 36 36 36
suction
MODELS ED A/W/M 482 532 572 602 542 622 682 842 762 892 1002 1102
Pressure drop BC D Pa 15 15 15 15 17 17 18 18 19 19 19 22
Pressure drop BG D Pa 26 26 26 26 24 24 25 25 11 11 11 14
F5 (100) D Pa 25 25 25 25 45 45 60 60 55 55 55 10
F6 (100) D Pa 100 100 100 100 145 145 170 170 135 135 135 195
F7a (100) D Pa 255 255 255 255 305 305 345 345 / / / /
F7b D Pa 175 175 175 175 220 220 230 230 241 241 241 /
F9 D Pa 210 210 210 210 262 262 273 273 285 285 285 /
Soundprof. baffle
D Pa 23 23 23 23 29 29 32 32 32 32 32 52
discharge
Soundprof. baffle
D Pa 28 28 28 28 42 42 47 47 46 46 46 76
suction
Notes
The F5,F6,F7a filters are to replacing the standard filters F4
Selecting a different filter from the STD one and/or the optional BG, RE, AM..,AR.., it is necessary to check and, eventually, to select, a higher pressure to the fans
MILLENNIUM E 07/02
PRESSURE DROP
FOR MODELS UV - VERSIONS U - V - B
F5 (50) UVB Pa 2 20 75 12 5 22 25 24
F5 (100) UVB Pa / / / / 0 0 0 0
F6 (100) UVB Pa / / / / 25 25 25 25
F7a (50) UVB Pa 45 130 265 154 190 145 145 180
Soundprof. baffle
U Pa 8 17 28 18 73 61 56 105
discharge
Soundprof. baffle
V Pa 8 17 28 18 73 61 56 105
discharge
Soundprof. baffle
B Pa 8 17 28 18 73 61 56 105
discharge
Soundprof. baffle
V Pa 20 35 48 28 45 38 35 40
suction
Soundprof. baffle
B Pa 5 7 18 10 13 10 10 12
suction
F5 (100) UVB Pa 0 2 10 0 0 0 0 25
F6 (50) UVB Pa 130 120 140 190 195 155 235 290
F6 (100) UVB Pa 25 35 40 55 50 40 70 95
F7a (50) UVB Pa 180 170 195 415 370 260 310 /
F7b UVB Pa 315 155 150 235 205 235 285 272
Soundprof. baffle
U Pa 105 36 30 33 52 58 80 75
discharge
Soundprof. baffle
V Pa 105 36 30 33 52 58 80 75
discharge
Soundprof. baffle
B Pa 105 36 30 33 52 58 80 75
discharge
Soundprof. baffle
V Pa 40 49 26 37 35 42 56 51
suction
Soundprof. baffle
B Pa 12 12 14 22 20 23 30 39
suction
Notes
The F5,F6,F7a filters are to replacing the standard filters F4
Selecting a different filter from the STD one and/or the optional BG, RE, AM..,AR.., it is necessary to check and, eventually,
to select, a higher pressure to the fans
MILLENNIUM E 07/02
PRESSURE DROP
FOR MODELS UV - VERSION D
F5 (50) D Pa 46 65 60 70 / / / /
Soundprof. baffle
D Pa 28 13 30 24 45 38 35 40
discharge
Soundprof. baffle
D Pa 13 23 18 15 73 61 56 105
suction
Soundprof. baffle
D Pa 40 49 26 20 35 42 56 51
discharge
Soundprof. baffle
D Pa 105 36 30 27 52 58 80 75
suction
Notes
The F5,F6,F7a filters are to replacing the standard filters F4
Selecting a different filter from the STD one and/or the optional BG, RE, AM..,AR.., it is necessary to check and,
eventually, to select, a higher pressure to the fans
MILLENNIUM E 07/02
EXAMPLE : Model ED.A 101 U
STD AVAILABLE PRESSURE CUSTOMER'S REQUEST
BG = 18 Pa
PROBLEM'S SOLUTION
F7b = 245 Pa
BC = 19 Pa
PROBLEM'S SOLUTION
MILLENNIUM E 07/02