Tek 17-01B PDF
Tek 17-01B PDF
Tek 17-01B PDF
TEK 17-1B 2001 National Concrete Masonry Association (replaces TEK 17-1A)
Lintel Loading
The loads supported by a lintel depend on whether arch- 4 x wall thickness + width of bearing area of beam
ing action can occur or not. If arching occurs, only the self Beam
weight of the lintel, the weight of the wall below the arched
portion, and concentrated loads are considered. Otherwise, the
self weight, the weight of the wall above the lintel, roof and floor
loads, and concentrated loads are considered. Self weight is
a uniform load based on lintel weight (see Table 2).
When arching occurs, the wall weight supported by the 30 30
lintel is taken as the wall weight within the triangular area below
the apex (see Table 3). This triangular load has a base equal to the
effective span length of the lintel and a height of half the effective
span. Any superimposed roof and floor live and dead loads are Lintel
neglected, since they are assumed to be distributed to the Clear span
masonry on either side of the lintel. When arching is not present, Effective span
the full weight of the wall section above the lintel is considered, (see Figure 1)
as are superimposed loads. Figure 3Distribution of Concentrated Load
Concentrated loads are assumed to be distributed as For Running Bond Construction
illustrated in Figure 3. The load is then resolved onto the lintel as
a uniform load, with a magnitude determined by dividing the
concentrated load by this length. In most cases, this results in a DESIGN EXAMPLE
uniform load acting over a portion of the lintel span.
When a lintel or other beam supports unreinforced masonry, Design a lintel for a 12 in. (305 mm) normal weight concrete
Building Code Requirements for Masonry Structures (ref. 1) masonry wall laid in running bond with vertical reinforcement
limits lintel deflection to the clear lintel span divided by 600 or to at 48 in. (1.2 m) o.c. The wall configuration is shown in Figure 4.
0.3 in. (7.6 mm) to limit damage to the supported masonry. Check for Arching Action. Determine the height of ma-
sonry required for arching action. Assuming the lintel has at
Table 2Lintel Weights, lb/ft (kN/m)a least 4 in. (102 mm) bearing on each end, the effective span is:
L = 5.33 + 0.33 = 5.67 ft (1.7 m).
Nominal lintel Nominal wall thickness, in. (mm) The height of masonry above the lintel necessary for
height, in. 8 (203) 10 (254) 12 (305) arching to occur in the wall (from Figure 2) is h + 8 in. (203 mm)
(mm) LIGHTWEIGHT CMU = L/2 + 8 in. = 3.5 ft (1.1 m).
8 (203) 51(0.75) 65 (0.95) 79 (1.2) Because there is 18.0 - 7.33 = 10.67 ft (3.3 m) of masonry
16 (406) 103 (1.5) 130 (1.9) 158 (2.3) above the lintel, arching is assumed and the superimposed
24 (610) 154 (2.3) 195 (2.9) 237 (3.5) uniform load is neglected.
Design Loads. Because arching occurs, only the lintel and
NORMAL WEIGHT CMU wall dead weights are considered. Lintel weight, from Table 2, for
8 (203) 58(0.84) 73 (1.1) 88 (1.3) 12 in. (305 mm) normal weight concrete masonry units assuming
16 (406) 116 (1.7) 146 (2.1) 176 (2.6) an 8 in. (203 mm) height is,
24 (610) 174 (2.5) 219 (3.2) 264 (3.9) Dlintel = 88 lb/ft (1.3 kN/m)
a
Face shell mortar bedding. Unit weights: grout = 140 pcf For wall weight, only the triangular portion with a height
3
(2,242 kg/m ); lightweight masonry units = 100 pcf (1602 of 3.5 ft (1.1 m) is considered. From Table 3 wall dead load is,
3
kg/m ); normal weight units = 135 pcf (2,162 kg/m ). 3 D wall
= 68 lb/ft2 (3.5 ft ) = 238 lb/ft (3.5 kN/m) at the apex.
Maximum moment and shear are deter-
mined using simply supported beam relation-
Superimposed wall load
ships. The lintel dead weight is considered a
8 in. (203 mm) minimum
uniform load, so the moment and shear are,
Mlintel = wL2/8 = (88)(5.7)2/8 = 357 ft-lb
h = Effective span (0.48 kN-m)
45 2 Vlintel = wL/2 = (88)(5.7)/2 = 251 lb (1.1 kN)
Wall For triangular wall load, moment and
Lintel height shear are,
End bearing
Mwall = wL2/12 = (238)(5.7)2/12 = 644 ft-lb
4 in. (102 mm) (0.87 kN-m)
minimum (typ) Vwall = wL/4 = (238)(5.7)/4 = 339 lb (1.5 kN)
Since the maximum moments and shears
for the two loading conditions occur in the
Clear opening
same locations on the lintel, the moments
Effective span (see Figure 1)
and shears are superimposed by simple
Figure 2Arching Action addition:
1,000 lb/ft (14.6 kN/m) superimposed uniform load Case 2, No Arching Action. Using the same example,
recalculate assuming a 2 ft (0.6 m) height from the bottom of the
12 in. (305 mm) CMU lintel to the top of the wall. For ease of construction, the entire
fm = 1500 psi (10.3 MPa) 2 ft (0.6 m) would be grouted solid, producing a 24 in. (610 mm)
deep lintel.
Since the height of masonry above the lintel is less than
5 ft 4 in. (1.6 m) 18 ft 3.5 ft (1.1 m), arching cannot be assumed, and the superimposed
(5.5 m)
load must be accounted for.
Window 4 ft (1.2 m) Dlintel = 264 lb/ft (3.9 kN/m), from Table 2. Because the lintel is
24 in. (610 mm) deep, there is no additional dead load due to
3 ft 4 in. (1.0 m) masonry above the lintel.
Dtotal = 264 lb/ft + 1,000 lb/ft = 1,264 lb/ft (18.4 kN/m)
Figure 4Wall Configuration for Design Example Mmax = wL2/8 = (1,264)(5.7)2/8 x 12 in./ft = 61,601 in.-lb (7.0 kN-m)
Vmax = wL/2 = (1,264)(5.7)/2 = 3,602 lb (16.0 kN)
Mmax = 357 + 644 = 1,001 ft-lb = 12,012 in-lb (1.4 kN-m) From Table 4, a 12 x 24 lintel with one No. 4 (M 13)
Vmax = 251 + 339 = 590 lb (2.6 kN) reinforcing bar and 3 in. (76 mm) or less bottom cover is
Lintel Design. From Table 4, a 12 x 8 lintel with one No. 4 adequate.
(M 13) bar and 3 in. (76 mm) or less bottom cover has adequate
strength. In this example, shear was conservatively computed REFERENCES
at the end of the lintel. However, Building Code Requirements 1. Building Code Requirements for Masonry Structures, ACI
for Masonry Structures (ref. 1) allows maximum shear to be 530-99/ASCE 5-99/TMS 402-99. Reported by the Masonry
calculated using a distance d/2 from the face of the support. Standards Joint Committee, 1999.
Provided by:
Cinder & Concrete Block Corporation
NCMA and the companies disseminating this technical information disclaim any and all responsibility and
liability for the accuracy and the application of the information contained in this publication.
NATIONAL CONCRETE MASONRY ASSOCIATION To order a complete TEK Manual or TEK Index,
2302 Horse Pen Road, Herndon, Virginia 20171-3499 contact NCMA Publications (703) 713-1900
www.ncma.org