Consultants/Contractors Confirmation Check List

Project:
PlotNo:Area:
Owner:
No wet area like toilet/bath room/kitchen/Pantry/Laundry/Swimming pool etc. Above electrical
1 room. Yes NA
2 NoMDBs/SMDBs/DBsareinstalledunderwetarea orinwetwall Yes NA
All electrical rooms are designed with adequate maintenance/operational access for the switch
3 gears/equipment/KWhmeters/capbanksetcasperDEWArules. Yes NA
4 Allelectricalroomsareprovidedwithunhinderedaccessfromthecommoncorridor/servicearea. Yes NA
5 Doorsofallelectricalroomsarenotopeningtothedriveway /staircase/ramp/ outside plot Yes NA
AllDBs/SMDBs/forthetenantsarelocated/installedin therespectivetenantareaneartothefront
6 entrance. Yes NA
Segregated wiring for each tenant area/metered area with physical separation provided with
7 separateaccesstoeachtenantpremise. Yes NA
8 Allcablesareroutedthroughcommonservicecorridor/area Yes NA
9 Airconditioningducts,chilledwaterlinesarenotpassingthroughtheelectricalroom. Yes NA
Voltagedropwithintheconsumerinstallationisverifiedandfoundwithinthepermissiblelimit(4%)
10 fromDEWAsupplypointtothefinaldistributionpoint. Yes NA
Harmonic study has been carried out and necessary active/passive filter are incorporated to
11 compensatetheeffectofnonlinearload. Yes NA
Number of light points, switched socket out lets and commercial load of equipments fittings
12 etc...Specifiedintheloaddistributionschedulesarecorrectaspertheprojectsummaryschedule. Yes NA
Circuit breakers/contactors are associated with Under Voltage (UV) Relays, having 'Auto Closing'
13 facility to restore supply for Chillers/Air Conditioning Units, after normalization of supply voltage, Yes NA
whentherelayresetautomatically.
All electrical installation shall comply with adequate earth leakage/over current/under voltage
14 protectionasperDEWAtechnicalspecification/regulation. Yes NA
AllAirconditioningunitsproposedfortheprojectaredesignedasperDMapprovedthermalload
15 calculationandiswithintheapprovedlimit. Yes NA
16 AllequipmentsandinstallationsarecomplyingwithGreenBuildingRegulation Yes NA
All provisional/proposed future loads where spares/space/standby are included in the total
17 connectedload/Installedload. Yes NA

Remarks:

Consultant/Contractorundertaking

I/We the under signed hereby agree to complete the LV installation as per DEWA rules & regulations. Any discrepancies/deviations
noticedduringsitetechnicalinspectionbyDEWAwillberectifiedbyusandwewillberesponsibleforanydelayforgettingelectricity
connectiontotheprojectduetononcomplianceofthisundertaking.

Signature&CompanyStamp:________________

Name:__________________________________

Designation:_____________________________