Preface
Manual Configuration
This manual describes the working environment of the CENTUM-XL engineering
function used in connecting an existing system to the CENTUM-CS system. For the
description of the XL-builder operation, refer to the related operation manual.
This manual is composed of three chapters and appendixes:
Chapter 1 introduces how the function is used.
Chapter 2 describes the environment required to use the function.
Chapter 3 describes the procedure for using the function.
Appendixes list available XL engineering packages and differences between XL and CS
engineering functions.
Applicable Readers
This manual has been written for instrumentation and control engineers who plan to
connect an existing system to the CENTUM-CS system and have primary knowledge of
the CENTUM-XL engineering function as well as the CENTUM-CS builder operation.
Trademarks
UNIX is a registered trademark in the United States and other countries and
licensed exclusively through X/Open Company Limited.
Motif and OSF/Motif are trademarks of Open Software Foundation, Inc.
X-Window and X Window System are trademarks of the Massachusetts
Institute of Technology.
Ethernet is a registered trademark of XEROX Corporation.
HP and HP9000 are registered trademark of Hewlett Packard Company.
IBM is a registered trademark of International Business Machine Corporation.
SUN is a registered trademark of Sun Microsystems, Inc.
Other brand and product names are registered trademarks of their respective holders.
FD No. IM 33G4Q10-11E
4th Edition: Apr. 2003 (YG)
All Rights Reserved, Copyright 1996, Yokogawa Electric Corporation
IM 33G4Q10-11E
Document Map
System
Overview (TI)
ICS Operation
and Monitoring
Function Manual
FCS Control
Function Manual
ICS Management
Information
Function Manual
Advanced
Control Function
Manual
User Program
Function Manual
Other Software
Operation
Manuals of ICS
Subsystem
Communication
Function Manual
Communication
Unit Function
Manual
ICS
Startup Operation
Manual
Other Software
Operation
Manual of FCS
Other Function
Manuals
System
Configuration
Manual
Builder Common
Operation Manual
FCS Builder
Operation Manual
Builder Operation
Manuals of Other
Units and Functions
Engineering Manuals
ICS Builder
Operation Manual
Recipe Management
/ Batch Control
Function Manual
Graphic Builder
Operation Manual
Test Function
Manual
Installation and
Maintenance Manuals
Self
Documentation
Manual
Installation
Guidance (TI)
Operation Manuals
ICS Operation
Manual
ICS Hardware
Manual
FCS Hardware
Manual
Message Manual
Peripherals
Manual
Node Device
Manual
ii
Communication and
Network Device
Hardware Manual
Related Device
Manual
IM 33G4Q10-11E
Notice
ATTENTION
Ce symbole marqu sur le produit indique que loprateur doit se reporter au
manuel dinstruction pour viter tout accident corporel ou tout dgt matriel.
Le manuel dinstruction indique que loprateur doit faire particulirement
attention pour viter tout choc lectrique ou autre accident pouvant entrainer
un accident ou la mort.
IM 33G4Q10-11E
iii
iv
IM 33G4Q10-11E
IMPORTANT
Indicates that operating the hardware or software in this manner may damage
it or lead to system failure.
IMPORTANT
Indique que manipuler le matriel ou le logiciel de cette manire peut
lendommager ou provoquer larrt du systme.
NOTE
Draws attention to information essential for understanding the operation and
features.
NOTE
Attire lattention sur une information essentielle pour la comprehension des
oprations effectuer ou des caractristiques.
3. If protection / safety circuits are to be used for the product or the system controlled
by it, they should be installed outside of the product.
4. When you replace parts or consumables of the product, use those specified by our
company.
5. Do not modify the product.
Regarding Force Majeure
1. Yokogawa Electric Corporation does not make any warranties regarding the product
except those mentioned in the WARRANTY that is provided separately.
2. Yokogawa Electric Corporation assumes no liability to any party for any loss or
damage, direct or indirect, caused by the use or any unpredictable defect of the
product.
Regarding Software Supplied by YOKOGAWA
1. Yokogawa makes no other warranties expressed or implied except as provided in its
warranty clause for software supplied Yokogawa.
2. Use this software with one specified computer only.
You must purchase another copy of the software for use with each additional
computer.
3. Copying this software for purposes other than backup is strictly prohibited.
4. Store the streamer or tape (original medium) in a secure place.
5. Reverse engineering such as the disassembly of software is strictly prohibited.
6. No portion of the software supplied by Yokogawa may be transferred, exchanged, or
sublet or leased for use by any third party without prior permission by Yokogawa.
IM 33G4Q10-11E
Documentation Conventions
Throughout this manual, the following conventions of notation clarify the input device
(keyboard, touch panel, or mouse) used.
Characters or symbols enclosed in [ ] denote keys on the ICS operation keyboard.
Example:To change to the next page, press the [ ] key.
Characters enclosed in < > represent keys on the engineering keyboard.
Example:To enter %, press the <%> key while pressing the <SHIFT> key.
Characters enclosed in [ ] indicate an ICS softkey, command for a window or menu,
or an item on worksheets of various types.
Example:Press on the [START] softkey to save the data.
An underlined boldface font denotes the format of data you enter on a panel.
Example:The cursor appears, prompting input.
FIC100.SV=50.0
This manual uses the following conventional symbols.
TIP
Gives information that complements the present topic.
See Also
Gives the reference locations for further information on the topic.
vi
IM 33G4Q10-11E
Contents
Contents
Preface ............................................................................................................................. i
Document Map .............................................................................................................. ii
Notice ............................................................................................................................. iii
Documentation Conventions ........................................................................................ vi
Chapter 1 Overview
1.1
1.2
Appendixes
Appendix 1 XL Engineering Function Packages ..................................... Appendix-3
Appendix 2 Differences in Engineering Functions .................................. Appendix-4
Appendix 3 Transfer of Files from ENGS ............................................... Appendix-7
Appendix 4 Restrictions on Use ............................................................. Appendix-10
Appendix 4.1 Precautions on Operation ........................................... Appendix-13
Appendix 5 Operation for Registering Options ..................................... Appendix-16
Appendix 5.1 Use of the Sequence-logic Function ......................... Appendix-16
Appendix 5.2 Use of the Self-Tuning Control Function ................. Appendix-18
Appendix 6 Precautions In Loading Data of EWS to EOPS ................. Appendix-19
Appendix 7 Precautions In Correcting a Tag-List .................................. Appendix-20
Appendix 8 Configuration of Printer into the XL-builder Functions .... Appendix-21
IM 33G4Q10-11E
vii
1. Overview
Chapter 1
Overview
The CENTUM-XL engineering function is used to connect an existing system to the
CENTUM-CS system. This chapter introduces how the function is used.
Contents
1.1
1.2
IM 33G4Q10-11E
1-3
1-5
1-6
1-7
1-7
1-7
1-8
1-8
1-9
1-9
1-9
1-1
1. Overview
1.1
IM 33G4Q10-11E
1-3
1-4
IM 33G4Q10-11E
1. Overview
1.2
IM 33G4Q10-11E
1-5
1.2.1
CS XL-Builder Function
The CS XL-builder function is contained in the XL engineering function this manual
describes. The builder function permits to create, compile, and load XL-station source
files at the ICS of the CS system. It calls the tag-list conversion tool when a tag list is
loaded on the ICS, automatically converting the tag list for the EOPS to that for the ICS.
Generation
Source file
Load
Object file
Load
EOPS
Conversion
(taglist conversion
tool used)
Tag list and
Message file
for ICS
EFCS, etc.
FCS
Option pkg.
required at EOPS
Load
ICS
Bus
converter
1-6
IM 33G4Q10-11E
1. Overview
1.2.2
1.2.3
1.2.4
Engineering function
[WS, ICS]
Definition
panel
Tag-list message
file for ICS
Tag-list
generation tool
Load
ICS
Engineering function
[WS, ICS]
Modification
panel
Tag-list
modification tool
Tag-list message
file for ICS
Tag-list message
file for EOPS
Load
Tag-list
conversion tool
Copy
ENGS
(CENTUM-XL)
IM 33G4Q10-11E
1-7
1.3
1.3.1
XL builder
Operator utility
XL builder
Test function
XL test function
XL self-document function
XL tag-list generation utility
XL tuning parameter printout
XL sensor parameter utility
1-8
IM 33G4Q10-11E
1. Overview
1.4
1.4.1
Engineering Methods
An existing system can be engineered in the following methods:
(1) Using the CS XL-builder.
(2) Using the ENGS builder and the CS EOPS tag-list conversion tool.
(3) Using the existing-system builder, the ENGS tag-list generation utility or the XL
builders XL tag-list generation utility, and the CS EOPS tag-list conversion tool.
(4) Using the MOPS builder, the ENGS MOPS tag-list conversion tool, and the CS
EOPS tag-list conversion tool.
(5) Using the existing-system builder and the CS tag-list generation tool.
For the description of methods 2 to 5, refer to the operation manual IM33G4P10-11E,
Tag-list Generation Utility Package.
1.4.2
IM 33G4Q10-11E
1-9
The CS XL-builder builds the XL system in the CS system using source files. The
EOPS tag list is converted to an ICS tag list automatically by the tag-list generation
utility function of the XL builder. To load the tag list in the EOPS automatically,
however, it is necessary to install an optional package (EP370) at the EOPS.
ICS
WS
ACG10S-E
V net
ABC11D-H
EOPS
HF bus
EFCS
1-10
IM 33G4Q10-11E
Chapter 2
Function Operating
Environment
This chapter describes the hardware and software required to use the XL engineering
function and how XL jobs are managed in the CS system.
Contents
2.1
2.2
2.3
IM 33G4Q10-11E
2-3
2-4
2-5
2-1
2.1
Hardware Required
The hardware listed in Table 2.1 is required to run the XL builder:
Table 2.1 Hardware Required
Computer
Computer main storage
Computer auxiliary storage
Peripheral equipment
IM 33G4Q10-11E
2-3
2.2
Software Required
The software and CS engineering packages listed in Tables 2.2 and 2.3 are required to
run the XL builder:
Table 2.2 Software Required
OS
HP-UX 9.0 (9.01, 9.03, 9.05, 9.07) or HP-UX10.20 or later (See note)
GUI
Note: To be able to operate an EWS using HP-UX10.20 software, the following bundle of patches must be
installed.
XSW700GR1020 (General-release), Version 10.20.35 or later
XSW700CR1020 (Critical), Version 10.20.35 or later
XSW700HW1020 (Hardware-Enablement), Version 10.20.35 or later
The following failures may occur if the aforementioned patches are not installed.
(1) The "Load complete" message is not received from the bus converter, even if loading
is carried out using the XL builder.
(2) The grids are not visible when working with the XL graphic builder.
Table 2.3 CS Engineering Packages Required
Package Code
Package Name
SHW5100
SHW5101
SHW5102
System utility
SHW5103
Operational utility
SHW5110
ICS Builder
SHW5210
SHW5240
SHW5310
SHW5490
Self-document
TIP
Automatic loading of a tag-list and other programs onto EOPS requires pre-installation
of the EP370 CENTUM CS file transfer functions package.
XL engineering packages are interdependent and the use of every package requires other
packages as listed in Table 2.4:
2-4
IM 33G4Q10-11E
Code
Required Packages
SEE301W
XL-sensor parameter
setting function
SEE303W
Test function
SEE401W
Self-document
SEE002W, SEE601W
SEE601W
XL-system definition/
EOPS builder
SEE002W, SEE601W
SEE603W
SEE604W
SEE611W
SEE631W
SEE681W
SEE682W
2.3
Host computer
Builder
CS project A
XL job A
XL job B
CS project B
IM 33G4Q10-11E
2-5
Chapter 3
Function Operating Procedure
This chapter describes the operating procedure for the XL engineering function.
Contents
3.1
IM 33G4Q10-11E
3-3
3-3
3-3
3-4
3-7
3-8
3-9
3-1
3.1
XL-builder Operation
The operation of the XL builder and related procedures are described.
3.1.1
Creating a Project
A CS project in which the database of an XL job must be created to manage the job
under the project.
The project maintenance utility of the system utility is used to create a CS project.
Refer to the operation manual IM33G4H10-11E, Builder Common Operation, for the
procedure.
3.1.2
IM 33G4Q10-11E
3-3
3.1.3
System Builder
BCV
ICS Builder
Operator Utility
FCS
FCS
OFF
ON
FCS Builder
ECS
ECS System
ECS
CGW
Communication Gateway
ECS
ECS Builder
Grp
*
Model Builder
Option Builder
C
O
I
W
Test Function
Operational Utility
1
XL Builder
3-4
IM 33G4Q10-11E
2
XL Builder
XL Test Function
XL Self-Document
XL Sensor Utility
IM 33G4Q10-11E
3-5
emgbuild_s
* CENTUM BUILDER *
0. New job
1. YOKOGAWA
2. XLjob
3.
4.
5.
6.
7.
99. Exit
8.
9.
10.
3-6
IM 33G4Q10-11E
3.1.4
emgbuild_s
* CENTUM BUILDER *
0. New job
1. YOKOGAWA
2. XLjob
3.
4.
5.
6.
7.
8.
99. Exit
9.
10.
Graphic
Common Pattern Codes
System Configuration
System Constants
Load-Save Utility
On-Off Scan
IM 33G4Q10-11E
3-7
3.1.5
3-8
IM 33G4Q10-11E
3.1.6
System Builder
BCV
ICS Builder
Operator Utility
FCS
FCS
OFF
ON
FCS Builder
ECS
ECS System
ECS
CGW
Communication Gateway
ECS
ECS Builder
Grp
*
Model Builder
Option Builder
C
O
I
W
Test Function
Operational Utility
1
XL Builder
IM 33G4Q10-11E
3-9
2
XL Builder
XL Test Function
XL Self-Document
XL Sensor Utility
3-10
IM 33G4Q10-11E
Self Document
Output printer
lp
Completed document
Feedback Control Loop Chart
SAMA Control Loop Chart
Sequential Instrument Loop Chart
Sequential Logic Chart
Graphic Panel
Graphic Common Segments
OK
CANCEL
IM 33G4Q10-11E
Entry Item
Job name.
Example: XLjob
Job name, station number, DDC***
Example: XLjob 01 DDC002
Job name, station number, DDC***
Example: XLjob 01 DDC002
Job name, station number, SQI***
Example: XLjob 02 SQI002
Job name, station number, IBD***
Example: XLjob 01 IBD002
Job name, graphic, source-file name
Example: XLjob graphic gr0001.so
Job name, graphic, common segment filename
Example: XLjob graphic gr0020.sg
3-11
Appendixes
Appendixes
Contents
Appendix 1
Appendix 2
Appendix 3
Appendix 4
Appendix
Appendix 5
Appendix
Appendix
Appendix 6
Appendix 7
Appendix 8
IM 33G4Q10-11E
Appendix-3
Appendix-4
Appendix-7
Appendix-10
Appendix-13
Appendix-16
Appendix-16
Appendix-18
Appendix-19
Appendix-20
Appendix-21
Appendix-1
Appendixes
Appendix 1
Name
SEE002W
SEE301W
SEE303W
Test function
SEE401W
SEE601W
SEE603W
SEE604W
SEE611W
Operator utility
SEE631W
SEE681W
SEE682W
SEE691W
Remarks
IM 33G4Q10-11E
Name
SEF001W
SEF002W
SEF011W
SEF021W
SEF031W
SEF071W
SEF092W
SEF301W
Remarks
Appendix-3
Appendix 2
CS Engineering Function
No blinking. Instead, handle is displayed.
Language
Plural number of XL system constants
Automatic update of source files
Character input
Character input
Mouse operation
Mouse operation
Japanese language input
Function keys
File dates can be displayed for stations where engineering files are
stored and managed. File dates cannot be displayed at other
engineering workstations.
No menu is available to call the generation function from the sequence
table. The system generation function must be called using the FCS
builder menu already displayed.
There is no command for version upgrading. If you are using an earlier
version of the ENGS source file, upgrade it to the latest version at the
ENGS and then move it to the CSs CENTUM-XL builder.
Generation screen (window) is displayed even after invoking another
screen.
Generation results can be confirmed only after closing this Generation
screen.
Appendix-4
CS Engineering Function
UNIX is not supported.
CS tag-lists are automatically equalized for the ICS. Tag lists are
automatically loaded to the EOPS if the optional CS/XL file transfer
function (EP870) is installed at the EOPS.
IM 33G4Q10-11E
Appendixes
XL Self-document
CS Engineering function
Item
Printer type
The data held by the engineering function are printed at all times and
EOPS data are not printed. Therefore printer specification is not
applicable.
This command cancels any new output request and does not cancel the
output of data already spooled the CANCEL command must be used
to cancel their output.
Fat bitmaps are used.
Calling up Self-document
If any part of a primitive lies on the outer frame, the primitive cannot be
printed. In some cases a printer can not identify the deleted image. For
this reason, the original image is printed as well.
Operators can operate engineering functions on the EWS which stores
and controls engineering files (on a remote EWS, these functions
cannot be performed).
Remote printers connected to other EWS can be used for output (a Selfdocument cannot be output to a printer connected to the ICS or PICS).
Prints single-byte yen symbols after converting them into backslashes.
Set the following call-up conditions on the Self-document (top level)
window.
Printer to output the called-up document
Calling the complete document
Calling the feedback control loop chart
Calling the SAMA control loop chart
Calling the sequential instrument loop chart
Calling the sequential logic chart
Calling the graphic panel
Calling the graphic common segments
CS Engineering function
Output to the LBP printer only. English printout use the same printer as
in the Self-document. Use A4-size paper only. 60 lines per page are
printed on the HP Laserjet 4.
(1) Click on [XL Tuning Parameter Printout] in the XL builder menu.
(2) hpterm is invoked so that the program of the tuning parameter
function is executed.
(3) Enter the call-up conditions in the dialog box.
IM 33G4Q10-11E
CS Engineering Function
The same name as used in the CS system configuration definition must
be specified using up to eight alphanumeric characters (uppercase
alphabetic characters only). Kanji characters cannot be used.
All engineering stations must be specified as ENGS and not as
*ENGS.
A menu to display builders at the on-line maintenance mode.
This builder is displayed even when another builder is called up. While
other builders are being displayed, operation on this builder is disabled
(in order to disable the operations on the stations being called up).
This system definition builder cannot be called up from multiple
stations at a time.
Appendix-5
Graphic Builder
Item
CS Engineering Function
Can be moved with the mouse. (The cursor keys on the keyboard
cannot be moved.)
Moving cursor
Operator Utility
Date comparison
Item
CS Engineering Function
The date comparison function is not available.
EOPS reading
Test Function
Item
CS Engineering Function
Message display
EFCS Builder
Item
CS Engineering function
Generation screen
Generation message
CS Engineering function
This function is not supported. Use the vi editor commands. Use the
standard size (80 columns x 24 lines) of the terminal emulator in the vi
editor.
The generated utility tag-list is copied to the working directory for ICS
tag-list conversion.
These messages are displayed in either the error dialog box or the
message server.
Enter these names from the dedicated Motif window.
Appendix-6
CS Engineering function
This operates on one hpterm. Use the window size in which it was
initially invoked.
Previously it was possible to display PV values of the tag data on the
EOPS in bars. This function is not provided.
IM 33G4Q10-11E
Appendixes
Appendix 3
See Also
Subsection 3.1.3, "Starting the XL Builder," for how to open the XL-builder menu.
emgbuild_s
* CENTUM BUILDER *
IM 33G4Q10-11E
Appendix-7
NOTE
Do not begin the file name with a slash (/). Always save the files under a relative
pathname. Do not save the files using an engineering tool, as this saves the files under
their absolute pathname.
builder
Connect a streamer to the ICS, and then execute the following command.
$ remshICS<host name>-lroot"/usr/lbin/sctermoff"
Install the tape on which you saved the files in step 5, in the streamer. Then, execute
the following command.
$ remshICS<host name>-lroot"ddif=/dev/rmt/.
ctape0"|cpio-icBvdum
$ remshICS<host name>-lroot"/usr/lbin/sctermon"
Appendix-8
IM 33G4Q10-11E
Appendixes
NOTE
Files under directories set to "read only" in the ENGS are given the error code "errno
13" and not copied. This does not affect the operation of the XL builder in the EWS. If
such a directory contains a file or files that must be copied for some particular reason,
create a new directory manually and transfer the file or files to the new directory.
IM 33G4Q10-11E
Appendix-9
Appendix 4
Restrictions on Use
The restrictions on use of the XL builder are summarized in the following table. Exercise care when using any of the functions listed in the table.
Restrictions
Item
Multi-user, multi-host
Redisplay
Invalid display
Operation
Cross-hair cursor
Test function
Test function
DDC loop chart status
Test function
Sequential logic chart status display
Sequential logic chart builder
Builder operation for an identical
source file
Tool for registering options
Loading
Appendix-10
Description
The engineering function cannot be used in a multi-user, multihost environment.
This function, when used with a builder window, displays all the
visible elements again. This is also true in the case of an
automatic redisplay applied when elements hidden by another
window show up or in the case of a redisplay applied when a
window is moved.
Some operations, such as clicking the Maximize button, may
cause garbage to appear on the panel. Garbage for menu
selection or data entry may also appear when pictures are
redrawn. An invalid indication of selection may occur with the
red borders of a menu.
Continued use of a builder window will result in a decreased
amount of available memory. Close the window as often as
possible.
For more information, refer to Appendix 4-1 Precautions on
Operation.
In a builder where the entry field is provided at the lower part of
the screen, cursor control keys cannot be used. As the cursor is
displayed at the end of a character string, move the cursor
forward with the backspace key.
For the Japanese-language input mode, an NLIO entry window
opens below the builder window. To confirm the entry, press
the down arrow key ( ) instead of the return key.
When a window is moved with the cross-hair cursor displayed
on the screen, a trace of the cursor may sometimes remain on the
screen.
There is no definite position where a test-function window
appears.
The size of Japanese contained in the Detailed Specification
Description Column does not fit the column width. Even if the
window size is changed, the size of characters contained in the
loop pattern does not match the pattern size.
There is no definite position where a test-function window
appears.
Character size has been reduced.
Character size has been reduced.
Only output elements cannot be moved, when the selectable area
of these output elements is quite limited, or characters such as a
comment overlap the selectable area.
Do not edit or refer to an indenical source file in any methods
including the multi-user method (e.g. in activating multiple
builder screens).
A tool for registering options is not supported. When using the
sequence a logic function, the set up the appropriate
environment using the procedure shown in Appendix 5.
The results of a tag-list conversion or modification that is carried
out when tag-lists are loaded to a BCV or ICS are not shown on
the panel. They are stored in the syslog file only. The data of a
loading panel are not updated while a tag-list convestion or
modification is in progress.
If this builder is initiated in a language environment other than
japanese.euc, C, the job selection dialog box malfunctions.
IM 33G4Q10-11E
Appendixes
Restrictions (continued)
Item
Graphic builder
Graphic builder
Lock file
Loading
Graphic builder
Operator utility
IM 33G4Q10-11E
Description
Do not define any batch function. Otherwise, compilation will
not be performed correctly.
The file-lock function does not work. Consequently, the same
modified file will be created in two or more windows.
There is a restriction for a case where more than one window of
the Sequence Table builder is open. When using the previous or
next page operation, do not call a sequence table that is already
displayed in another window. Otherwise, a lock file will remain
in the builder window, resulting in a failure to call that sequence
table thereafter.
The file control status is updated just after the list screen is
called up. If you write in a sheet newly called up, the status of
the list screen which has already been called up is not updated.
There is a restriction for a case where more than one window of
the Computational. Expression builder is open. When using the
previous or next page operation, do not call a computational
expression that is already displayed in another window.
Otherwise, a lock file will remain in the builder window,
resulting in a failure to call that computational expression
thereafter.
The file control status is updated just after the list screen is
called up. If you write in a sheet newly called up, the status of
the list screen which has already been called up is not updated.
The file control status is updated just after the list screen is
called up. If you write in a sheet newly called up, the status of
the list screen which has already been called up is not updated.
When using software with versions earlier than R2.07, delete
lock file according to the procedure below. When using R2.07
or greater software, the lock file is deleted at the startup of the
engineering function.
How to delete lock file
Delete lock file with the rm command, and restart the
engineering function. The lock file is in <project top
direcory>/real/etc/users1/ctmsrc/<job name>/<station>/<builder
classification>/i.XXXXX.XX. The suffix begins with i. The file
name differs depending on the type of builder.
During loading, do not use any of the following operations:
Generation, saving and on/off scanning relating to the station
being loaded, or concurrent loading to the station currently being
loaded.
Since an EWS lacks proper fonts, the size of a character on an
EOPS screen differs from that on a builder panel.
One file is shared by three builders. Therefore, the file cannot
be editted when calling up the three builders of trend pen
assignment, overview panel assignment, and control group
assignment at the same time.
Self-documentation function
If you print the report form for a large-scale job continuously, the
self-documentation function will output data alternating between
this job and another on a form-by-form basis. When printing
such a job, make sure the first cycle of printing is complete before
you proceed to the next cycle.
Appendix-11
Restrictions (continued)
Item
Description
XL graphic builder
-YEWCOM modification function
XL graphic builder
-change in attributes of
pattern blocks
Appendix-12
XL self-documentation
-handling of single-byte yen sign
XL self-documentation
-startup of selfdocumentation menu
When using the XL builder, make sure the project name and the
name of the projects top directory are the same. If not, match
them using the Project Maintenance Utility.
IM 33G4Q10-11E
Appendixes
Appendix 4.1
Precautions on Operation
This section describes precautions on the operations described in Appendeix 4
Restrictions on Use.
If you perform too many operations in one builder, the builder may end abnormally due
to memory shortage. The operational amount depends on memory capacity installed in a
machine. When using a machine with more than 80 Mbytes of memory, close the
builder window in the following cases 1 to 6. With less than 80 Mbytes of memory,
minimize operations of each builder, and carry out the following builder operations for
efficient use of memory. If it takes more time than usual when updating display, the
machine may be short of memory. In this case, close the window once then call it up
again.
Memory shortage is caused by entering many character strings, displaying many
characters and turning many pages. On a screen where many data can be defined,
reduce the number of turning pages as much as possible. If you continue builder
operations without closing windows which are called up, memory used increases.
However, when redisplaying a window with a window redisplay command, memory
used does not increase.
For efficient use of memory, follow the instructions bellow:
1. Graphic builder
After correcting one page, close the window (and return to the file list screen).
2. Common pattern definition builder
After correcting 96 patterns, close the window.
3. FCS builder
FCS common item, I/O card, and resource control element:
No restrictions when used normally.
Sequential instrument and feedback instrument:
Assume that the max. number of instruments is defined in a new sheet and each instrument specification is displayed in one page.
When performing the above operations up to 15 pages while turning pages, close the
window.
When performing many operations per page, close the window after completing 2 to 3
pages.
(It is no use to return to the file list screen.)
Valve output monitor, timer/counter/code I/O, internal switch, contact I/O, and
sequential message printout:
Close the window after changing 5 pages of elements.
IM 33G4Q10-11E
Appendix-13
Sequence table:
When performing a large number of operations, close the window after changing about 5
pages.
Relational expression:
Close the window after changing 11 pages of relational expressions.
Computational expression:
Close the window after changing 20 pages of computational expressions.
Printout of message with data; operator guide message:
Close the window after changing 20 pages of data.
Annunciator message (EFCS, etc.):
Close the window after changing 5 pages of data.
Sequential logic chart:
Assuming that the operation of defining 16 input elements and 16 output elements in a
new sheet is counted as one page, close the window after changing 30 pages of data (It
is no use to simply return to the file list screen.).
4. EOPS Builder
Operator station configuration, operation group, trend recording:
No restriction when used normally.
Panel name and comment:
Overview panel, control group panel, trend group panel, graphic panel:
Close the window after changing 30 pages of data respectively.
Scheduler:
Close the window after changing 30 pages of data.
Sequential message request:
Close the window after changing 8 pages of data.
Panel set:
Close the window after changing 10 pages of data.
Window
Process window:
Avoid turning pages of the list screen as much as possible. Close the list screen after
changing 35 windows of data.
Trend window:
Close the window after changing one page of data.
Voice output message:
Close the window after changing one page of data.
Appendix-14
IM 33G4Q10-11E
Appendixes
5. Operator Utility
Function keys definition, control group assignment:
Close the window after changing 15 pages of data.
Trend pen assignment:
Close the window after changing 15 pages of data.
External recorder assignment, operation sequence:
No restriction when used normally.
Overview panel assignment:
Close the window after changing 20 pages of data.
Operation mark definition:
No restriction when used normally.
Help message:
Avoid turning pages of the list screen as much as possible. If pages are turned without
closing the input window, close the window after changing 60 pages of data.
6. System Variable
Switch position label, engineering unit: No restriction when used normally.
IM 33G4Q10-11E
Appendix-15
Appendix 5
Appendix 5.1
Appendix-16
IM 33G4Q10-11E
Appendixes
The information contained in the file is classified according to the type number of the
FCS. Also classify the added information according to the type number of the FCS.
Figure A5.1 Example of Added Information
000102
000103
000201
000103
000201
012102
012201
012301
012201
013102
013203
013201
013301
013201
013203
014102
014201
014301
014201
015101
015201
015301
050101
IM 33G4Q10-11E
EFCS/D Program L
/usr/lib/ctm/data/efcsprg.sv
EFCS/D_logic
L
/usr/lib/ctm/data/efcslogic.sv Addition
EFCS/DData
Lsls SFS${STC}B.ud
EFCS/Dstc
L
/usr/lib/ctm/data/efcsstc.sv
Addition
EFCS/D Program1 L
/usr/lib/ctm/data/efcsprg1.sv
EFCS-H4/D-H4Program L /usr/lib/ctm/data/efcsh4prg.sv
EFCS-H4/D-H4Data LSls SF${STC}B.ud
EFCS-H4/D-H4Data
LSls
SF${STC}C.ud
EFCS-H4/D-H4SubSystm
L
subsdrv.sv
EFCS-H2/D-H2Program L /usr/lib/ctm/data/efcsh2prg.sv
EFCS-H2/D-H2stc L
/usr/lib/ctm/data/efcsh2stc.sv Addition
EFCS-H2/D-H2Data
LSls
SF${STC}B.ud
EFCS-H2/D-H2Data
LSls
SF${STC}C.ud
EFCS-H2/D-H2SubSystm
L
subsdrv.sv
EFCS/D-H2_logic L /usr/lib/ctm/data/efcsh2logic.sv Addition
EFCE-H2 Program L
/usr/lib/ctm/data/efcsh2prg.sv
EFCE-H2Data LSls SF${STC}B.ud
EFCE-H2Data LSls SF${STC}C.ud
EFCE-H2SubSystmL subsdrv.sv
EMCS/D-H4Program L /usr/lib/ctm/data/emcsh4prg.sv
EMCS/D-H4Data LSls SF${STC}B.ud
EMCS/D-H4Data LSls SF${STC}C.ud
ECGW2Program
L SF${STC}A.ud
Appendix-17
Appendix 5.2
Information contained in the file is classified according to the models of the FCS. Also,
classify added information according to the models of the FCS. For more information,
refer to Figure 5.1 Example of Added Information.
Appendix-18
IM 33G4Q10-11E
Appendixes
Appendix 6
(4) Identify the STN name of EOPS described in the system configuration definition of the XL builder with
that in the system configuration definition of the CS
If you specify load to EOPS on the XL builder, the STN network information will
refer to the STN name in the system configuration definition of the CS. If the STN name
is incorrect, an error will result.
IM 33G4Q10-11E
Appendix-19
Appendix 7
If inconsistency arises, after loading with the XL builder, always re-define the existing
tag name by running the tag-list correction builder, and then execute Load.
Appendix-20
IM 33G4Q10-11E
Appendixes
Appendix 8
TIP
You cannot output data from an EWS installed with the XL-builder functions, to a
printer connected to a PICS, nor can you output data to a printer connected to an ICS.
1. XL-builder Packages Offering Printouts
The following table lists the XL-builder packages that enable printouts.
Package
Printout
Parameter printout
Printout of ID definitions table
IM 33G4Q10-11E
Appendix-21
TIP
The following explains how to configure a remote printer under the Japanese-version
operating system.
The names of files listing the printer models that can be selected for use with the XLbuilder functions are LIPS3 and lbpb406s. The following explains how to configure the
local printer. The configuration procedure varies depending on whether the EWS'
operating system is HP-UX9.xx or HP-UX10.20 or later version, and also on whether
the name of a file listing printer models is LIPS3 or lbpb406s.
When the EWS' Operating System Is HP-UX9.xx:
No extra work is involved if you select lbpb406s as the name of the printer model
file. If you selected LIPS3 however, follow the procedure given below:
(1) Log on with the account "builder" to open the hpterm directory.
(2) Make sure you are currently at the home directory.
Type:
$ cd
and press the return key. This will move you to the home directory.
(3) Type the following command to open a new file. (A triangle () in keyed-in
statements of commands, etc. indicates a space hereinafter.)
$ vi.lpr_option
After this, type the following to configure the file so that it contains a statement in
the first line only.
lp-ojapanese.euc
(4) Save the file and quit the vi command.
(5) Terminate the engineering function once and then restart it.
The printer named LIPS3 should print correctly now.
When the EWS' Operating System Is HP-UX10.20 or later version:
No extra work is involved.
Appendix-22
IM 33G4Q10-11E
Appendixes
TIP
The following explains how to configure a remote printer under the Japanese-version
operating system.
When the Operating System of an EWS Installed With the XL Builder and the
Operating System of an EWS Connected to a Remote Printer, are both HP-UX9.xx:
No new files need to be made. Using such commands as sam, configure a remote
printer connected to an EWS installed with the XL builder. Data for printouts are output
to the remote printer.
When the Operating System of an EWS Installed With the XL Builder is HP-UX9.xx
and the Operating System of an EWS Connected to a Remote Printer is HP-UX10.20
or later version:
A new file must be made in the home directory of the account "builder" and the engineering function must be restarted. The following explains the procedure.
(1) Log on with the account "builder" to open the hpterm directory.
(2) Make sure you are currently at the home directory.
Type:
$ cd
and press the return key. This will move you to the home directory.
(3) Type the following command to open a new file. (A triangle () in keyed-in
statements of commands, etc. indicates a space hereinafter.)
$ vi.lpr_option
After this, type the following to configure the file so that it contains a statement in
the first line only.
lp-oja_JP.eucJP
(4) Save the file and quit the vi command.
(5) Terminate the engineering function once and then restart it.
(6) Using such commands as sam, configure a remote printer by specifying the default
printer of an EWS installed with the XL builder, as the remote printer. Data for
printouts are output to the remote printer.
When the Operating System of an EWS Installed With the XL Builder and the
Operating System of an EWS Connected to a Remote Printer, are both HP-UX10.20
or later version:
No new files need to be made. Using such commands as sam, configure a remote
printer connected to an EWS installed with the XL builder. Data for printouts are output
to the remote printer.
IM 33G4Q10-11E
Appendix-23
When the Operating System of an EWS Installed With the XL Builder is HPUX10.20 or later version and the Operating System of an EWS Connected to a
Remote Printer is HP-UX9.xx:
A new file must be made in the home directory of the account "builder" and the engineering function must be restarted. The following explains the procedure.
(1) Log on with the account "builder" to open the hpterm directory.
(2) Make sure you are currently at the home directory.
Type:
$ cd
and press the return key. This will move you to the home directory.
(3) Type the following command to open a new file. (A triangle () in keyed-in
statements of commands, etc. indicates a space hereinafter.)
$ vi.lpr_option
After this, type the following to configure the file so that it contains a statement in
the first line only.
If the name of the printer model file specified in the EWS to which the remote
printer should be connected is lbpb406s:
lp-oeuc
If the name of the printer model file specified in the EWS to which the remote
printer should be connected is LIPS3:
lp-ojapanese.euc
(4) Save the file and quit the vi command.
(5) Terminate the engineering function once and then restart it.
(6) Using such commands as sam, configure a remote printer by specifying the default
printer of an EWS installed with the XL builder as the remote printer. Data for
printouts are output to the remote printer.
Appendix-24
IM 33G4Q10-11E
Attention
Name
Date
Company
Div. & Sect.
Address
Phone No.
Ext.
Fax. No.
Manual No.
Title
Pages
.........................................................................................................................................................................................................................................
.........................................................................................................................................................................................................................................
.........................................................................................................................................................................................................................................
.........................................................................................................................................................................................................................................
.........................................................................................................................................................................................................................................
.........................................................................................................................................................................................................................................
.........................................................................................................................................................................................................................................
.........................................................................................................................................................................................................................................
.........................................................................................................................................................................................................................................
.........................................................................................................................................................................................................................................
Revision Record
Manual No. : IM 33G4Q10-11E (4th Edition)
Title
Edition
Date
Revised Item
1st
Oct. 1995
Newly published
2nd
Aug. 1996
R2.06 or later
3rd
Mar. 1998
R2.08 or later
4th
Apr. 2003
R2.13 or later
* : Denotes the release number of the software corresponding to the contents of this users manual.
The revised contents are valid until the next edition is issued.
Rev. No. *
R2.03