Chapter Sixteen: Testing and Maintenance of Relays
Chapter Sixteen: Testing and Maintenance of Relays
Chapter Sixteen: Testing and Maintenance of Relays
Introduction:
The complexity of the present day systems and the ever increasing
technological improvements, where products have greater number of
functions to perform, warrants a high reliability in such affairs.
In general terms "Quality Control" is defined as An effective system for
coordinating quality maintenance and quality improvement efforts of
the various groups in an organization so as to enable production at the
most economical levels which allows for all customer satisfaction".
The reliability of a product may be defined as "a mathematical
probability that will operate in a specified manner for a specific period
of time".
2.0
TESTS ON RELAYS
Basically the tests conducted on relays are classified as:
1) Type tests
2) Routine tests
The above are the tests conducted in a factory at the manufacturing
stage. Subsequently when the relays are received at site the following
tests are conducted:
3) Acceptance tests
4) Installation tests
5) Maintenance or Functional tests
107
6) Repair tests.
3.0
Type Tests
3.1
4
3.2
Thermal Requirements
the relay shall comply with all other specification requirements. The
relay shall also withstand a single application of the limiting short time
thermal withstand value stated by the manufacturer for the following
times:
Current relays
1 sec
Voltage relays
10 secs
108
3.2.3 The relay shall also withstand a single application of the dynamic value
of the energising quantity. The duration of the test should be half a
cycle of the
sinusoidal waveform at rated frequency. The test may be made with
either symmetrical waveform or with asymmetrical waveform.
3.3
Accuracy
The accuracy of the dependent time relay is primarily associated with
the specified time, but may also be concerned with the accuracy
associated with the basic value of the characteristic quantity.
3.4
Mechanical Endurance
The mechanical endurance for relay is conducted under the following
conditions:
a) Mounted as for normal service
b) At rated value of the auxiliary energising quantity
c) At values of the characteristic or input energising quantity.
d) At specified rate
e) For relays with adjustable time setting; at the time setting values
which gives the most severe conditions for
mechanical durability.
After the tests, the relay shall be substantially in good condition and
should be capable of fulfilling its designed functions throughout its
setting range at least once at the minimum and once at the maximum
values of the operative range of the auxiliary energising quantities.
109
Shock Vibration
The relay shall be subjected to shock and vibration tests and the test
value is to be decided mutually between the manufacturer and the
purchaser.
3.6
Contact Performance
The contact performance of the relay contacts to be verified with
respect to the guaranteed values.
3.7
3.8
Insulation Requirements
input
transformer,
relay
contacts
and
auxiliary
energising
terminals must withstand 2KV insulation level for one minute between
ground and between each other.
3.8.2 Impulse Test
An impulse voltage withstand test is performed to determine whether
the relay and its individual components will withstand, without
damage, high voltage surges for short durations.
110
It is recommended in order to
111
a) Accuracy
b) Operating time
c) Resetting performance
d) Any other characteristics
The relay shall not change its output state in a faulty manner when the
auxiliary energising quantity is switched on or off.
3.10 Operating Value Test
112
ROUTINE TESTS
4.1
113
5) Dielectric test
4.2
The check list on Visual Inspection of all types of relays is listed below:
114
c) That the heads of the wire straps are turned towards the interior of the
relay to facilitate easy entry
d) That the earth wire is connected and fixation is alright
e) That the wiring does not come between the frameworks obstructing
the easy
entry and withdrawal of the relay either from the case or from the rack.
4.2.5 Varnishing:
Verify:
a) Whether all parts are varnished as per drawing particularly windings
and relays coils
b) Whether from appearance the terminal settings/terminals are free from
varnish
4.2.6 Winding:
Verify:
a) Whether the identification stamp, number or catalogue code is fixed
b) If the protection tape is properly wound and the winding is not exposed
4.2.7 Indication/Name Plate:
a) Verify the inscription details
b) Ensure that they are legible and can be easily read
c)
115
excess length
of loose and sagging wires, excess varnish, stained varnish on
undesirable terminals.
c) Ensure that the components are painted for locking to facilitate
removal of damaged component and re-assembly.
d) Endorse for approval.
4.3
116
117
b) Operating Time:
The operating time for definite time over voltage relays shall be
verified by suddenly applying 1.1 times the set voltage.
The time
118
ii.
iii.
119
i.
ii.
iii.
5.0
ACCEPTANCE TESTS
5.1
120
a) New products supplied for the first time: - Such products having not
been used previously in the system are subject to extensive tests on a
sample to gain experience and knowledge and/or additional technical
information. Sometimes they are installed in the field in parallel with
an existing similar relay to study the performance as above.
b) Tests on each product received: - Every product received from the
manufacturer is subject to a minimum of practical checks to ensure:
i.
ii.
To ensure that the relay can be safely accepted into the store inventory
and dispatched to site for subsequent
installation.
6.0
INSTALLATION TESTS
6.1
Staged Fault tests are actual faults applied to the power system to
verify the relay operations.
internal and external are applied. While this is the best method, the
121
cost and potential hazards are high. Therefore staged faults tests are
limited to very important and/or new relay installations to the power
system.
6.3
a) Checking the circuit and wiring diagrams, studying the relay and
equipment catalogues.
b) General inspection of equipment, checking all the connections, wires
on relays and terminals.
c) Checking the insulation resistance of all circuits to ground.
d) Checking the insulation resistance of control cables to ground and
between different cores of a control cable and between different
control cables.
e) Checking the insulation resistance between current, voltage secondary
circuits and auxiliary A.C. and D.C. supplies.
f) C.Ts tested for insulation, polarity, ratio and excitation characteristics.
g) V.Ts tested for insulation, polarity and ratio.
h) Relays tested independently by secondary simulated tests.
i) Relays tested by injection of current in primary of C.T. and secondary
circuits of V.T., Burden on C.Ts and P.Ts checked.
j) Operation of relays checked with 80% of D.C. voltage supply.
k) Relay flag indicator and alarm circuits checked
l) Tripping of circuit breaker checked by relay operation at 100% of D.C.
voltage and at 80% of D.C voltage.
122
7.1
maximum performance.
Besides
123
7.2
REPAIR TESTS
Repair tests as the name implies, involves re-calibration after major
repairs have been made. Such tests are usually made in a laboratory
attached to a relay repair shop.
carried out during maintenance tests and need not involve complete
re-calibration tests.
124
9.0
i.
Test switches are normally supplied with relays and are installed in the
control panels in the case of non-draw out type relays. But in the case
of draw-out type relays this is not the case as relay test jacks (plug)
are provided. Sometimes relay test terminal blocks are installed where
test switches are not installed.
short out and isolate the current circuits from the relay panel for
separate source testing.
iii.
When testing on line it is important to take out only one relay or relay
system at a time leaving the other back-up relay or relay system intact
in the event of a fault.
125
iv.
v.
vi.
vii.
viii.
ix.
126
127
xi.
128