Service Manual Split Type: RAV-SM562MUT-E
Service Manual Split Type: RAV-SM562MUT-E
Service Manual Split Type: RAV-SM562MUT-E
A06-005
SERVICE MANUAL
SPLIT TYPE
<DIGITAL INVERTER>
INDOOR UNIT
RAV-SM562MUT-E
This Service Manual describes contents of the new indoor unit.
For the outdoor unit, refer to the Service Manual with FILE NO. A05-001.
R410A
PRINTED IN JAPAN, Aug.,2006 ToMo
WARNING
Cleaning of the air filter and other parts of the air filter involves dangerous work in high places, so be sure to
have a service person do it. Do not attempt it yourself. The cleaning diagram for the air filter is there for the
service person, and not for the customer.
CONTENTS
1. SPECIFICATIONS .......................................................................................................... 3
1-1. Indoor Unit .............................................................................................................................................. 3
1-2. Combination Specifications of Indoor Units with Outdoor Units ...................................................... 4
1-3. Operation Characteristic Curve ............................................................................................................ 5
4. WIRING DIAGRAM....................................................................................................... 10
4-1. Indoor Unit ............................................................................................................................................ 10
13
13
17
18
19
21
22
23
23
9. TROUBLESHOOTING.................................................................................................. 35
9-1.
9-2.
9-3.
9-4.
35
37
40
41
1. SPECIFICATIONS
1-1. Indoor Unit
1-1-1. Compact 4-way Cassette Type
DI
DI TWIN
SDI
SDI TWIN
SM562MUT-E
SM562MUT-E
SM562MUT-E
SM562MUT-E
RAV-
SM562MUT-E
SM562MUT-E
RAV-
SM562AT-E
SM1102AT-E
SP562AT-E
SP1102AT-E
Cooling capacity
(kW)
5.0
10.0
5.0
10.0
Heating capacity
(kW)
5.6
11.2
5.6
11.2
Indoor unit
Model
Outdoor unit
RAV-
Power supply
(A)
7.02 to 7.75
14.96 to 16.32
6.6 to 7.15
10.31 to 11.24
(kW)
1.61
3.52
1.53
2.4
Power factor
EER
(%)
95
98
97
97
(W/W)
3.11
2.84
3.27
4.17
4.0
4.5
(A)
7.04 to 7.72
13.35 to 14.56
6.62 to 7.21
10.95 to 11.95
Power consumption
(kW)
1.61
3.14
1.54
2.55
Power factor
(%)
95
98
97
97
(W/W)
3.48
3.57
3.64
4.39
4.5
4.5
Energy rating
Electrical
chracteristics
Running current
Heating
COP
Ceiling panel
Main unit
Outer
dimension
Model
Panel color
Height
(mm)
268
Width
(mm)
575
Depth
(mm)
575
Height
(mm)
27
(mm)
700
(mm)
700
(kg)
17
Ceiling panel
Width
(Sold separately)
Depth
Total weight
RBC-UM11PG (W)-E
Main unit
Ceiling panel (Sold separately)
Heat exchanger
Finned tube
Fan
Fan unit
Turbo fan
H/M/L
Motor
(m/min.)
(W)
60
Air filter
(Content)
(Content)
Remote controller
Connecting pipe
Gas side
(mm)
12.7
Liquid side
(mm)
6.4
Drain port
VP25
H/M/L
(dBA)
43 / 39 / 34
H/M/L
(dBA)
58 / 54 / 49
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8616 based
on the reference piping 7.5m.
Note 2 : The sound level is measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in
the actual operating environment become larger than the indicated values due to the effects of external sound.
Note 3 : Rated conditions
Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB
Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB
Note 4 : DI : Digital Inverter, SDI : Super Digital Inverter
RAV-SM562MUT-E
Outdoor Unit
RAV-SP562AT-E
Cooling
Heating
(kW)
5.30 (2.20-5.60)
5.60 (2.20-7.10)
(W/W)
3.46
4.67
Power supply
Running current
7.17-6.57
5.62-5.15
Power consumption
(kW)
1.53
1.20
Power factor
(%)
97
97
Electrical characteristics
Sound level
Indoor unit
High/Mid./Low
(Note 2)
(dBA)
32/29/27
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8616 based
on the reference piping 7.5m.
Note 2 : The sound level is measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in
the actual operating environment become larger than the indicated values due to the effects of external sound.
Note 3 : Rated conditions
Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB
Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB
10
10
Current (A)
Current (A)
<Cooling>
4
Conditions
Indoor : DB27C/WB19C
Outdoor : DB35C
Air flow : High
Pipe length : 7.5m
230V
4
Conditions
Indoor : DB20C
Outdoor : DB7C/WB6C
Air flow : High
Pipe length : 7.5m
230V
0
0
20
40
60 70 80
100
20
40
60
80 90 100
<Heating>
10
12
10
Current (A)
Current (A)
8
6
4
4
Conditions
Indoor : DB27C/WB19C
Outdoor : DB35C
Air flow : High
Pipe length : 7.5m
230V
Conditions
Indoor : DB20C
Outdoor : DB7C/WB6C
Air flow : High
Pipe length : 7.5m
230V
0
0
20
40 50 60 70 80
100
20
40
60 70 80 90 100
1000 or more
Check port
( 450)
Stand-up
850 or less
Indoor unit
Bottom face
of ceiling
Note)
As ABS is used for the drain discharge port of the main unit,
the vinyl chlor paste cannot be used.
Use the flexible hose (Band fix) included in the package.
4
207
175
149
200
2.7
Check port
( 450)
Stand-up
627.5
or less
1000 or more
120
Wired remote
controller
(RBC-AMT31E)
16
368.5
268
63
320.5
Wiring
connection
port
Refrigerant pipe
(Liquid) 6.4
For branch ductt
knockout square
hole 150
Refrigerant pipe
(Gas) 12.7
Bottom face
of ceiling
Ceiling panel
162
97.5
162
134
142
177
510 Hanging bolt pitch
595 to 660 Ceiling open dimension
700 Panel external dimension
235
105
235
70
105
145.5
120
21
256
145.5
93
27
220.5
105
148
Bottom face
of ceiling
64
158
64
29
120
142
214
42
15 or more
Obustacle
Check port
( 450)
200
1000 or more
15 or more
200
55
70
105
93
139.5
190.5
RAV-SM562MUT-E
Distributor
(Strainer
incorporated)
Indoor unit
TCJ sensor
Air heat
exchanger
TC sensor
Refrigerant pipe
at liquid side
Outer diameter 6.4
Refrigerant pipe
at gas side
Outer diameter 12.7
To outdoor unit
To outdoor unit
Twin type (Combination of two indoor units and one outdoor unit)
RAV-SM562MUT-E
Indoor A unit
Distributor
(Strainer
incorporated)
Heating time
Cooling time
RAV-SM562MUT-E
Distributor
(Strainer
incorporated)
TCJ sensor
Air heat
exchanger
TCJ sensor
Air heat
exchanger
TC sensor
Refrigerant pipe
at liquid side
Outer diameter 6.4
Indoor B unit
TC sensor
Refrigerant pipe
at gas side
Outer diameter 12.7
Refrigerant pipe
at liquid side
Outer diameter 6.4
Refrigerant pipe
at gas side
Outer diameter 12.7
Branch pipe
Branch pipe
Refrigerant pipeat liquid side
Outer diameter 9.5
To outdoor unit
To outdoor unit
RAV-SM562MUT-E / RAV-SP562AT-E
Indoor unit
TCJ
sensor
Air heat exchanger
TC sensor
Outer diameter of refrigerant pipe
Gas side A
Liquid side B
12.7mm
6.4mm
Refrigerant pipe
at gas side
Outer dia. A
Refrigerant pipe
at liquid side
Outer dia. B
Min. Max.
5m 50m
Pd
Packed valve
Outer dia. A
Outdoor unit
Ps
Modulating
(PMV)
(SKV-18D26)
Strainer
TS sensor
Packed valve
Outer dia. B
TO sensor
TD sensor
Strainer
TE
sensor
4-way valve
(STF-0213Z)
Muffler
Accumulator
(1500cc)
25 L210
25 L160
Heat exchanger8
1 row 30 stages
FP1.3 flat fin
Capillary
32
L530
Rotary compressor
(DA220A2F-20L)
R410A 1.5 kg
Cooling
Heating
Pipe surface temperature (C)
Pressure
(MPa)
Cooling
Heating
Discharge
Suction
Compressor
Indoor heat Outdoor heat revolutions per
exchanger
exchanger
second (rps)
Indoor
fan
Pd
Ps
(TD)
(TS)
(TC)
(TE)
Standard
2.71
1.03
75
15
10
38
43
HIGH
Indoor/Outdoor
temp. conditions
(DB/WB) (C)
Indoor
Outdoor
27/19
35/
Overload
3.48
1.16
81
20
16
51
44
HIGH
32/24
43/
Low load
1.92
0.74
34
11
24
LOW
18/15.5
5/
Standard
2.22
0.72
62
38
41
HIGH
20/
7/6
Overload
3.47
1.16
81
20
55
15
41
LOW
30/
24/18
Low load
1.79
0.25
71
16
30
18
70
HIGH
15/
20/(70%)
The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.
For the details of the outdoor units during twin combination of a digital inverter and a super digital inverter, refer to
page 34 (Digital Inverter) and also page 37 (Super Digital Inverter) of the Service Manual File No.A05-018.
RAV-SM562MUT-E / RAV-SM562AT-E
Indoor unit
TCJ
sensor
Air heat exchanger
TC sensor
Outer diameter of refrigerant pipe
Gas side A
Liquid side B
12.7mm
6.4mm
Refrigerant pipe
at gas side
12.7
Packet valve
Packed valve
Outer dia. A
Refrigerant pipe
at liquid side
6.4
Packet valve
Outdoor unit
PMV
(Pulse Motor Valve)
(CAM-B30YGTF-1)
TS sensor
TO sensor
2-step muffler
19 .05 200L
Min. Max.
5m 30m
Packed valve
Outer dia. B
TD sensor
Strainer
4-way valve
(STF-0108Z)
TE
sensor
Heat exchanger
8 ripple, 2 rows,
14 steps
FP1.3 flat fin
Muffler
19 L160
Rotary compressor
(DA150A1F-20F)
Distributor
R410A 1.0 kg
Cooling
Heating
Pressure
(MPa)
Pd
(kg/cmG)
Ps
Discharge
Suction
(TD)
(TS)
Indoor/Outdoor
Compressor
Indoor heat Outdoor heat revolutions per Indoor temp. conditions
(DB/WB) (C)
fan
exchanger
exchanger
second (rps)
(TC)
(TE)
Indoor Outdoor
Ps
Pd
Standard 3.50
0.97
35.7
9.9
85
14
12
48
70
HIGH
1.08
39.8
11.0
93
26
17
54
70
0.70
19.4
7.1
48
30
50
27/19
35/
HIGH
32/24
43/
LOW
18/15.5
5/
Standard 2.31
0.61
13.6
6.2
87
40
97
HIGH
20/
7/6
0.89
29.2
9.1
86
17
47
11
95
LOW
28/
24/18
0.25
19.0
2.6
69
14
31
15
98
HIGH
15/
10/(70%)
The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.
For the details of the outdoor units during twin combination of a digital inverter and a super digital inverter, refer to
page 34 (Digital Inverter) and also page 37 (Super Digital Inverter) of the Service Manual File No.A05-018.
4. WIRING DIAGRAM
4-1. Indoor Unit
4-1-1. Compact 4-way Cassette Type
TA
FS
CN34
(RED)
3 3
2 2
1 1
LM1
5
4
3
2
1
LM2
5
4
3
2
1
5
4
3
2
1
5
4
3
2
1
5
4
3
2
1
5
4
3
2
1
TC
Connection interface (option)
1 2
1 2
1 2
1 2
1 2
1 2
1 2 3
1 2
1 2
CN104
(YEL)
CN102
(RED)
CN101
(BLK)
CN80
(GRN)
CN73
(RED)
CN70
(WHI)
(EXCT)
MCC-1402
5
4
3
2
1
CN33
(WHI)
5
4
3
2
1
TCJ
FM
Motor
drive
circuit
CN68 1 2 3
(BLU) 1 2 3
RY
303
1 2 3
CN304
(GRY)
U3 U4
Terminal for
central remote
controller
2 2 CN001
1 1 (WHI)
3 3
2 2
WHI
1 1
Fuse
F301
250V~
T6.3A
Adapter for
Wireless Remote
Controller
3
2 CN309
(YEL)
1
BLK
RY
302
1 2 CN40
1 2 (BLU)
6
5
4 CN60
3 (WHI)
2
1
WHI
1
2
3
4
5
5
4
P.C.
3 Board
2
1
BLK
CN334
(WHI)
1
2
3
4
5
5
4
3
2
1
6
5
4 CN61
3 (YEL)
2
1
Fuse
F302
T3.15A
250V~
5
4
3
2
1
5
4
3
2
1
(FAN DRIVE)
Power
supply
circuit
5
4
3
2
1
5
4
3
2
1
CN51
(RED)
2 CN32
1 (WHI)
DC20V
DC15V
DC12V
DC7V
CN333
(WHI)
CN50
(WHI)
P301
CN67 1 2 3 4 5
(BLK) 1 2 3 4 5
BLK 1 2
CN66
(WHI)
CN41
(BLU)
B
A
BLK
B
A
WHI
Wired Renote
Controller
DP
1 2 3
Indoor unit
earth screw
NOTE
FM
TA
TC
TCJ
LM1,LM2
DP
FS
RY302
: Fan motor
: Indoor temp. sensor
: Temp. sensor
: Temp. sensor
: Louver motor
: Drain pump motor
: Float switch
: Drain control relay
1 2 3
Serial
signal
Single phase
220 to 240V
50Hz
L N
10
Outdoor unit
earth screw
Color
Identification
BLK
BLU
RED
GRY
PNK
GRN
WHI
BRN
ORN
YEL
:
:
:
:
:
:
:
:
:
:
BLACK
BLUE
RED
GRAY
PINK
GREEN
WHITE
BROWN
ORANGE
YELLOW
Single type
Power supply 220-240V
Single phase 50Hz
Outdoor unit
L
N
1 2 3
1 2 3
Indoor unit
Notes)
A B
A B
1.
: indicates a terminal block
2. Broken line and chain line indicate wiring at local site.
3. For the inner wiring diagram of the outdoor unit and the
indoor unit, refer to the wiring diagram of each model.
4. There is no polarity. It is no problem that the remote
controller is connected to the indoor unit terminal block
A and B reversely.
5. When using a wireless remote controller, connection of
the remote controller to A and B terminal blocks are
unnecessary.
Twin type
Power supply 220-240V
Single phase 50Hz
Outdoor unit
L
N
1 2 3
1 2 3
Indoor unit
No.1 (Master)
1 2 3
Earth
screw
A B
Indoor unit
No.2 (Sub)
A B
Notes)
A B
1.
: indicates a terminal block
2. Broken line and chain line indicate wiring at local site.
3. For the inner wiring diagram of the outdoor unit and the
indoor unit, refer to the wiring diagram of each model.
4. There is no polarity. It is no problem that the remote
controller is connected to the indoor unit terminal block
A and B reversely.
5. When using a wireless remote controller, connection of
the remote controller to A and B terminal blocks are
unnecessary. (Wire connection between indoor unit No.1
and No.2 is necessary.)
11
Parts name
Type
SWF-230-60-1R
Specifications
Output (Rated) 60 W, 220240 V
155 mm
10 k at 25C
6 mm, 1200 mm
10 k at 25C
6 mm, 1200 mm
10 k at 25C
Float switch
FS-0218-106
ADP-1406
12
6. REFRIGERANT R410A
This air conditioner adopts the new refrigerant HFC
(R410A) which does not damage the ozone layer.
The working pressure of the new refrigerant R410A
is 1.6 times higher than conventional refrigerant
(R22). The refrigerating oil is also changed in
accordance with change of refrigerant, so be careful
that water, dust, and existing refrigerant or refrigerating oil are not entered in the refrigerant cycle of the
air conditioner using the new refrigerant during
installation work or servicing time.
The next section describes the precautions for air
conditioner using the new refrigerant. Conforming to
contents of the next section together with the
general cautions included in this manual, perform
the correct and safe work.
13
R410A
R22
1/4
6.35
0.80
0.80
3/8
9.52
0.80
0.80
1/2
12.70
0.80
0.80
5/8
15.88
1.00
1.00
2) Joints
For copper pipes, flare joints or socket joints are used. Prior to use, be sure to remove all contaminants.
a) Flare Joints
Flare joints used to connect the copper pipes cannot be used for pipings whose outer diameter exceeds
20 mm. In such a case, socket joints can be used.
Sizes of flare pipe ends, flare joint ends and flare nuts are as shown in Tables 6-2-3 to 6-2-6 below.
b) Socket Joints
Socket joints are such that they are brazed for connections, and used mainly for thick pipings whose
diameter is larger than 20 mm.
Thicknesses of socket joints are as shown in Table 6-2-2.
Nominal diameter
1/4
6.35
0.50
3/8
9.52
0.60
1/2
12.70
0.70
5/8
15.88
0.80
14
Outer
diameter
(mm)
Thickness
(mm)
Clutch type
1/4
6.35
0.8
0 to 0.5
1.0 to 1.5
1.5 to 2.0
3/8
9.52
0.8
0 to 0.5
1.0 to 1.5
1.5 to 2.0
1/2
12.70
0.8
0 to 0.5
1.0 to 1.5
2.0 to 2.5
5/8
15.88
1.0
0 to 0.5
1.0 to 1.5
2.0 to 2.5
Outer
diameter
(mm)
Thickness
(mm)
Clutch type
1/4
6.35
0.8
0 to 0.5
0.5 to 1.0
1.0 to 1.5
3/8
9.52
0.8
0 to 0.5
0.5 to 1.0
1.0 to 1.5
1/2
12.70
0.8
0 to 0.5
0.5 to 1.0
1.5 to 2.0
5/8
15.88
1.0
0 to 0.5
0.5 to 1.0
1.5 to 2.0
Outer diameter
(mm)
Thickness
(mm)
1/4
6.35
3/8
Dimension (mm)
Flare nut
width (mm)
0.8
9.1
9.2
6.5
13
17
9.52
0.8
13.2
13.5
9.7
20
22
1/2
12.70
0.8
16.6
16.0
12.9
23
26
5/8
15.88
1.0
19.7
19.0
16.0
25
29
15
Nominal
diameter
Outer diameter
(mm)
Thickness
(mm)
1/4
6.35
3/8
Dimension (mm)
0.8
9.0
9.2
6.5
13
17
9.52
0.8
13.0
13.5
9.7
20
22
1/2
12.70
0.8
16.2
16.0
12.9
20
24
5/8
15.88
1.0
19.4
19.0
16.0
23
27
3/4
19.05
1.0
23.3
24.0
19.2
34
36
to 4
45
43
to 4
Fig. 6-2-2 Relations between flare nut and flare seal surface
Note)
When applying oil to the flare surface, be sure to use oil designated by the manufacturer.
If any other oil is used, the lubricating oils may deteriorate and cause the compressor to burn out.
Nominal
diameter
Outer diameter
(mm)
Tightening torque
Nm (kgfcm)
1/4
6.35
14 to 18 (140 to 180)
16 (160), 18 (180)
3/8
9.52
33 to 42 (330 to 420)
42 (420)
1/2
12.70
50 to 62 (500 to 620)
55 (550)
5/8
15.88
63 to 77 (630 to 770)
65 (650)
16
6-3. Tools
6-3-1. Required Tools
The service port diameter of packed valve of the outdoor unit in the air conditioner using R410A is changed to
prevent mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing dimensions and
opposite side dimension of flare nut (For 12.7 copper pipe) of the refrigerant piping are lengthened.
The used refrigerating oil is changed, and mixing of oil may cause a trouble such as generation of sludge,
clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types.
1) Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22))
2) Tools exclusive for R410A, but can be also used for conventional refrigerant (R22)
3) Tools commonly used for R410A and for conventional refrigerant (R22)
The table below shows the tools exclusive for R410A and their interchangeability.
Tools exclusive for R410A (The following tools for R410A are required.)
Tools whose specifications are changed for R410A and their interchangeability
R410A
air conditioner installation
No.
Used tool
Usage
Existence of
new equipment
for R410A
Conventional air
conditioner installation
Whether new equipment
can be used with
conventional refrigerant
Flare tool
Pipe flaring
Yes
*(Note 1)
Flaring by conventional
flare tool
Yes
*(Note 1)
*(Note 1)
Torque wrench
Yes
Gauge manifold
Evacuating, refrigerant
charge, run check, etc.
Yes
Charge hose
Vacuum pump adapter
Vacuum evacuating
Yes
Refrigerant charge
Yes
Refrigerant cylinder
Refrigerant charge
Yes
Leakage detector
Yes
Charging cylinder
Refrigerant charge
(Note 2)
Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection
margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.
Note 2) Charging cylinder for R410A is being currently developed.
17
(INDOOR unit)
(Liquid side)
(OUTDOOR unit)
Opened
(Gas side)
Refrigerant cylinder
(With siphon pipe)
Check valve
Closed
Open/Close valve
for charging
Service port
Electronic balance for refrigerant charging
18
Gauge manifold
Gauge manifold
OUTDOOR unit
OUTDOOR unit
Refrigerant
cylinder
Refrigerant
cylinder
Electronic
balance
Electronic
balance
Siphon
6-5-2. Flux
1) Reason why flux is necessary
By removing the oxide film and any foreign
matter on the metal surface, it assists the flow
of brazing filler.
In the brazing process, it prevents the metal
surface from being oxidized.
By reducing the brazing filler's surface tension,
the brazing filler adheres better to the treated
metal.
19
Piping
material
Used brazing
filler
6-5-3. Brazing
As brazing work requires sophisticated techniques,
experiences based upon a theoretical knowledge, it
must be performed by a person qualified.
In order to prevent the oxide film from occurring in
the pipe interior during brazing, it is effective to
proceed with brazing while letting dry Nitrogen gas
(N2) flow.
Used
flux
Do not use
Copper - Iron
Silver
Paste flux
Iron - Iron
Silver
Vapor flux
M Flow meter
Stop valve
Nitrogen gas
cylinder
From Nitrogen cylinder
Pipe
Nitrogen
gas
Rubber plug
20
Pipe length
(One Direction)
Height
Difference
1102AT
Full length
L + a or L + b
Below 50m
(actual length)
Branch piping
a, b
Below 15m
(actual length)
Below 10m
Outdoor unit
Indoor unit
H
Below 30m
Below 15m
Below 0.5m
Less than 10 bends
Indoor unit A
Indoor unit B
Branch pipe
b
H
L
Outdoor unit
CAUTION
When planning a layout for Units A and B, comply with the following:
1. The lengths after branching (a and b) should be equal if feasible. Install Units A and B so that the
difference of the branching lengths becomes less than 10m if the lengths cannot be equal due to the
branch pipe position.
2. Install Units A and B on the same level. If Units A and B cannot be installed on the same level, the
difference in level should be limited to 0.5m or less.
3. Be certain to install Units A and B in the same room.
Units A and B cannot be operated independently each other.
21
: Additional refrigerant amount per meter of actual main piping length (kg)
: Additional refrigerant amount per meter of actual branch piping length (kg)
: Actual length of main piping (m)
: Actual length of branch piping (m)
Outdoor model
RAV-SM or RAV-SP
Main piping
Branch piping
1102AT-E
18 m
2m
0.040
0.020
Indoor unit A
Indoor unit B
Branch piping
Branch pipe
b
a
Branch piping
H
L
Main piping
Outdoor unit
CAUTION
1. Be certain to wire the additional refrigerant amount, pipe length (actual length), head and other
specification on the nameplate put on the outdoor unit for recording.
2. Seal the correct amount of additional refrigerant in the system.
22
15.9 (1.0)
Branch piping
12.7 (0.8)
Main piping
9.5 (0.8)
Branch piping
6.4 (0.8)
Gas side
Pipe side
Liquid side
OK
OK
500mm or
more
Horizontal
Horizontal
NO GOOG
Inclination
NO GOOG
Inclination
23
Display
LCD
Weekly timer
LCD
driver
Function setup
CPU
Function setup
CPU
Display
LED
Display
LCD
Key switch
Key switch
CN2
CN1
DC5V
DC5V
Remote controller
communication
circuit
Central control remote controller
(Option)
Power
circuit
*2
Option
Indoor
unit
#1
Secondary
battery
Power
circuit
Option
#2
Connection Interfase
(Option)
#3
TCC-LINK
communication
circuit
DC20V
Remote controller
communication
circuit
EEPROM
DC5V
TA sensor
DC12V
TC sensor
CPU
Louver
motor
TCJ sensor
Driver
Same as
the left
*1
Same as
the left
*1
1 2 3
1 2 3
Float input
Drain
pump
Outside output
Run
Warning Ready
Thermo. ON
Cool/Heat Fan
CPU
Fan motor
control
circuit
Indoor
fan
motor
DC280V
AC
synchronous
signal input circuit
Serial
send/receive
circuit
Power circuit
Outdoor
unit
1 2 3
1 2 3
Outdoor unit
Temporary
operation SW
Power
circuit
DC5V
CPU
Function
setup SW
Buzzer
Receive circuit
24
Display LED
Outdoor
unit
Item
When power
supply is reset
Operation mode
selection
Outline of specifications
1) Distinction of outdoor units
When the power supply is reset, the outdoors are
distinguished, and control is exchanged according to
the distinguished result.
2) Setting of speed of the indoor fan/setting whether to
adjust air direction or not.
Based on EEPROM data, speed of the indoor fan or
setting whether to adjust air direction or not is selected.
Remarks
Air speed/
Air direction adjustment
Outline of control
Air conditioner stops.
Fan operation
Cooling operation
DRY
Dry operation
HEAT
Heating operation
AUTO
Ta
(C)
COOL
+1.5
(COOL ON)
Tsc
or Tsh
(COOL OFF)
-1.5
HEAT
25
Ta : Room temperature
Ts : Setup temperature
Tsc : Setup temperature in
cooling operation
Tsh : Setup temperature
+ Room temperature
control temperature
compensation
No.
3
Item
Room
temperature
control
Outline of specifications
Remarks
Heating
operation
Auto
operation
Wired type
18 to 29
18 to 29
18 to 29
Wireless type
18 to 30
16 to 30
17 to 27
+0C
+2C
+4C
+6C
Setting at shipment
Setup data
Automatic
capacity control
(GA control)
Air speed
selection
<COOL>
Ta (C)
+3.0
+2.5
+2.0
+1.5
+1.0
+0.5
Tsc
-0.5
A
B
C
D
HH
(HH)
H (HH)
H (HH)
L(H)
L(H)
L(H)
L(L)
F
G
26
No.
Item
Air speed
selection
(Continued)
Remarks
Outline of specifications
<HEAT>
Ta (C)
L(L)
L(H)
H(H)
(-0.5) 1.0
(0)
Tsh
(+0.5) +1.0
(+1.0) +2.0
(+1.5) +3.0
H
(HH)
HH
(HH)
C
B
(+2.0) +4.0
HEAT
UL
High ceiling
COOL
HEAT
L
L+
M
M+
H
M
M+
Tap
UL
L
L+
UL
L
L+
M+,M
M+,M
FD
FD
FB
FA
F9
F8
F7
F6
F5
F4
F3
F2
F1
SM562
Revolutions per
minute (rpm)
320
320
330
350
360
370
400
410
420
440
480
530
580
27
[PRE-HEAT] display
Tc
(C)
47
F5
42
F5
F4
No.
6
Item
Cool air
discharge
preventive
control
Outline of specifications
Remarks
28
UL
D zone
26
20
16
OFF
C zone
B zone
A zone
K
2
J
High-temp
release control
56 (54)
52 (52)
Tc (C)
Tcj A
M
N
B
L
NOTE :
When the operation has started or when Tc or Tcj became
lower than 30C after start of the operation, temperature is
controlled between values in parentheses of A and B.
28
No.
Item
Outline of specifications
10 After-heat elimination
11
Flap control
In cooling/dry operation
Remarks
In heating/fan operation
29
Warning :
A check code is displayed
on the remote controller,
and the indoor unit stops.
(Excluding [F08] and
[L31])
No.
12
Item
Frequency fixed
operation
(Test run)
Outline of specifications
Remarks
13
30
No.
14
Item
Central control
mode selection
Outline of specifications
Remarks
(No display)
] goes on.
] goes on.
15
Energy-save
control
(By connected
outdoor unit)
16
Max. frequency
cut control
+3
Tsc
3) HEAT operation mode: the frequency
is controlled according to the right
figure if To > 15C.
Ta(C)
Tsh
3
4
17
DC motor
Normal control
31
Connection interface
DC fan output
Indoor/Outdoor
inter-unit cable
Optional
power supply
32
Remote controller
power supply LED
DC fan return
*1
Drain pump output
Float SW
Fan output
HA (T10)
TA sensor
Optional output
Louver
(Used only for 4-way Air Discharge Cassette Type, Under Ceiling type)
TCJ sensor
EXCT
DISP Used for
CHK servicing
EEPROM
<MCC-1402>
CAUTION
A sensor trouble may cause a liquid back-flow or abnormal overheat resulting in excessive shortening of the
compressor life. In a case of trouble on the compressor, be sure to check there is no error in the resistance
value an the refrigerating cycle of each sensor after repair and then start the operation.
SM562
117
112
108
105
98
TD [C]
Error stop ("P03" display with 4 times of error counts)
a
Frequency down
b
c
Frequency holding
d
Frequency slow-up
(Up to command)
e
As command is
[A]
Frequency down
I1
10.5
Hold
Hold
Normal operation
Objective
model
COOL
HEAT
I1 value [A]
9.22
11.93
33
Outside error
input
Filter option
error
Connector
No.
CN60
CN80
CN70
CHK
Operation check
CN71
DISP display
mode
CN72
EXCT demand
CN73
Pin
No.
Specifications
Remarks
DC12V (COM)
Defrost output
Thermo. ON output
Cooling output
Heating output
Fan output
DC12V (COM)
DC12V (COM)
Filter/Option/Humidifier
setup input
0V
0V
0V
Demand input
0V
Display mode enables indoor unit and remote controller to communicate. (When power is turned on)
Forced thermo-OFF operation in indoor unit
34
9. TROUBLESHOOTING
9-1. Summary of Troubleshooting
<Wired remote controller type>
1. Before troubleshooting
1) Required tools/instruments
+ and screwdrivers, spanners, radio cutting pliers, nippers, push pins for reset switch
Tester, thermometer, pressure gauge, etc.
2) Confirmation points before check
a) The following operations are normal.
1. Compressor does not operate.
Is not 3-minutes delay (3 minutes after compressor OFF)?
Does not thermostat turn off?
Does not timer operate during fan operation?
Is not outside high-temperature operation controlled in heating operation?
2. Indoor fan does not rotate.
Does not cool air discharge preventive control work in heating operation?
3.Outdoor fan does not rotate or air volume changes.
Does not high-temperature release operation control work in heating operation?
Does not outside low-temperature operation control work in cooling operation?
Is not defrost operation performed?
4. ON/OFF operation cannot be performed from remote controller.
Is not the control operation performed from outside/remote side?
Is not automatic address being set up?
(When the power is turned on at the first time or when indoor unit address setting is changed, the
operation cannot be performed for maximum approx. 5 minutes after power-ON.)
b) Did you return the cabling to the initial positions?
c) Are connecting cables of indoor unit and remote controller correct?
2. Troubleshooting procedure
When a trouble occurred, check the parts along with the following procedure.
Trouble
NOTE :
For cause of a trouble, power conditions or malfunction/erroneous diagnosis of microcomputer due to outer
noise is considered except the items to be checked. If there is any noise source, change the cables of the
remote controller to shield cables.
35
Trouble
Check defective
position and parts.
1) Outline of judgment
The primary judgment to check where a trouble occurred in indoor unit or outdoor unit is performed with
the following method.
Method to judge the erroneous position by flashing indication on the display part of indoor unit
(sensors of the receiving unit)
The indoor unit monitors operating status of the air conditioner, and the blocked contents of self-diagnosis
are displayed restricted to the following cases if a protective circuit works.
36
Diagnostic function
Wired remote
controller
Operation
Timer
Ready
Check code
E03
Cause of operation
No communication from remote controller (including wireless)
and communication adapters
The serial signal is not output from outdoor unit to indoor unit.
Miscabling of inter-unit cables
Defective serial sensing circuit on outdoor P.C. board
Defective serial receiving circuit on indoor P.C. board
Status of air
conditioner
Condition
Stop
Displayed when
(Automatic reset) error is detected
37
E04
E08
E10
E18
F01
Stop
Displayed when
(Automatic reset) error is detected
l
l
F02
Stop
Displayed when 1. Check indoor heat exchanger temperature sensor (TC).
(Automatic reset) error is detected 2. Check indoor P.C. board.
F04
Stop
F06
Stop
F08
Operation
continues.
F10
Stop
Displayed when 1. Check indoor heat exchanger temperature sensor (TA).
(Automatic reset) error is detected 2. Check indoor P.C. board.
l
l
F29
Stop
Displayed when 1. Check indoor EEPROM. (including socket insertion)
(Automatic reset) error is detected 2. Check indoor P.C. board.
H01
H02
Stop
H03
Stop
l
l
l
L03
L07
L08
S top
Displayed when
(Automatic reset) error is detected
Breakdown of compressor
Displayed when error is detected
Displayed when
error is detected
Stop
Displayed when
(Automatic reset) error is detected
Stop
Displayed when
(Automatic reset) error is detected
Stop
Stop
Stop
Stop
Displayed when 1. Check whether there is modification of remote controller connection (Group/Individual) or not
after power has been turned on (finish of group configuration/address check).
error is detected
* If group configuration and address are not normal when the power has been turned on, the
Displayed when
mode automatically shifts to address setup mode. (Resetting of address)
error is detected
Displayed when
error is detected
Diagnostic function
Wired remote
controller
Operation
Timer
Ready
Check code
L09
L29
L30
L31
Cause of operation
Unset indoor capacity
Outdoor unit and other errors
Communication error between CDB and IPDU
(Coming-off of connector)
Heat sink temperature error
(Detection of temperature over specified value)
Abnormal outside interlock input
Phase detection protective circuit operates. (Normal models)
Fan motor thermal protection
Status of air
conditioner
Condition
Stop
Stop
Displayed when
error is detected
Stop
Operation continues. Displayed when 1. Check power phase order (Reversed phase)/phase missing.
(Compressor stops.) error is detected 2. Check outdoor P.C. board.
Stop
38
P03
Stop
P04
Stop
P10
Stop
P12
Stop
P19
P22
l
l
l
P26
P29
P31
Stop
(Automatic reset)
Stop
Stop
Stop
Stop (Sub unit)
(Automatic reset)
For an error mode detected in outdoor unit, the fan operates because sub unit of a group operation does not communicate with the outdoor unit.
Diagnostic function
Wired remote
controller
Operation
Timer
Ready
Condition
Check code
No communication with master indoor unit
Remote controller cable is not correctly connected.
No check code is Power of indoor unit is not turned on.
displayed.
(Remote controller Automatic address cannot be completed.
does not operate.)
Stop
39
E01
E02
E09
L20
Stop
(Sub unit continues operation.)
Displayed when
error is detected
Stop
(Automatic restart)
Displayed when
error is detected
Diagnostic function
Wired remote
controller
Operation
Timer
Ready
Check code
C05
C06
P30
Continuation/Stop
(Based on a case)
Condition
Displayed when 1. Check communication line/miscabling/ Check power of indoor unit.
error is detected 2. Check communication. (U3, U4 terminals)
3. Check network adapter P.C. board.
Displayed when 4. Check central controller (such as central control remote controller, etc.).
error is detected
5. Terminal resistance check (connection interface SW01)
Displayed when Check the check code of corresponding unit by remote controller
error is detected
No.
Item
Check
code
Type A
CDB side
IPDU side
LED display
D800
(Red)
D801
(Yellow)
D802
(Yellow)
D803
(Yellow)
l
l
l
l
l
l
l
l
TE sensor error
F06
TD sensor error
F04
TS sensor error
F06
TO sensor error
F08
P03
P22
L29
P04
EEPROM error
10
11
P26
12
P29
13
H03
14
H02
15
Comp. breakdown
H01
: Go on l : Go off
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
: Flash (5Hz)
<<Check code>>
The check codes are classified into Type A and Type B according to the used remote controller.
Be sure to check the remote controller which you use.
Type A :
Neutral 2-cores type wired remote controller such as RBC-AMT31E, RBC-AS21E, and wireless
remote controller kit such as TCB-AX21U (W)-E2
40
NO
YES
NO
NO
Is group control operation?
YES
NO
NO
YES
YES
Are two remote controllers
set without master unit?
NO
[E09 error]
YES
NO
41
[E04 error]
NO
Does outdoor unit operate?
YES
NO
Is setup of group address correct?
YES
NO
Correct inter-unit cable.
NO
Correct connection of connector.
YES
Does voltage between
2 and 3 of inter-terminal blocks (1, 2, 3)
of indoor unit vary?*
YES
NO
S5277G
White
2
1
Inter-terminal block
YES
Does case thermo. operate?
NO
MCC-5009
RAV-SM562AT-E
RAV-SP562AT-E
42
Check/Correct charged
refrigerant amount.
[E10 error]
[E18 error]
NO
YES
NO
NO
YES
Is group control operation?
NO
If the above is detected when power has been turned on, the mode automatically enters in automatic address setup mode. (Check code is not displayed.)
However, if the above is detected during automatic address setup mode, the check code may be displayed.
[L09 error]
YES
43
[L20 error]
NO
NO
[L30 error]
NO
[P10 error]
Is connection of float switch connector
(Indoor control P.C. board CN34) normal?
NO
YES
NO
Is circuit
cabling normal?
NO
YES
YES
Is power of drain
pump turned on?
NO
YES
YES
[F10 error]
NO
YES
NO
Are characteristics of TA sensor resistance value normal?
YES
Replace TA sensor.
* Refer to Characteristics-1.
44
[P12 error]
<Only for 4-way air discharge cassette type models>
YES
NO
Remove connectors CN333 and
CN334 of indoor unit P.C. board
(MCC-1402).
NO
YES
Are resistance values between phases
at fan motor connector CN333 motor side of
indoor P.C. board (MCC-1402) correct? *1
YES
NO
*1
Are not coil windings between 1 (Red lead) and 3 (White lead),
between 3 (White lead) and 5 (Black lead), between
5 (Black lead) and 1 (Red lead) opened or shorted?
For resistance, see the following values.
RAV-SM562, SM802, SM1102, SP562, SP802, SP1102
Approx. 70 to 100W
RAV-SM1402, SP1402 Approx. 35 to 50W
Is not earthed between cabinet and 1, 3, 5 10MW or more
NO
*2
NO
*3
CN334
45
[P22 error]
CN301, * CN303
NO
YES
The status that the resistance values
between leads below are 50 to 80W
for 40W motor (ICF-140-40) and 25 to 55W
for 60W motor (ICF-140-60-1) is normal.
Between 1 (Red lead) and 2 (White lead)
Between 2 (White lead) and 3 (Black lead)
Between 3 (Black lead) and 1 (Red lead)
of motor winding of connector (CN301)
NO
CN300
YES
The status that there is
5k to 20kW resistance values between
1 (Yellow lead) and 4 (Pink lead)
of motor position detection of
connector (CN300) is normal.
YES
Single phase
RAV-SM562AT-E
RAV-SP562AT-E
CN300
CN301
CN301
CN300
46
[P19 error]
Is operation of
4-way valve normal?
NO
Is voltage applied
to 4-way valve coil terminal
in heating operation?
YES
NO
NO
YES
Is flow of refrigerant
by electron expansion
valve normal?
YES
NO
Is circuit cable normal?
YES
NO
Are characteristics
of TC sensor resistance
value normal?
Replace TC sensor.
YES
In cooling operation, if high pressure is abnormally raised, [P19 error]/[08 error] may be displayed. In this
case, remove cause of pressure up and then check again referring to the item [P04 error]/[21 error].
[F02 error]
NO
YES
Are characteristics of
TC sensor resistance value normal?
YES
NO
Replace TC sensor.
* Refer to Characteristics-2.
47
[F01 error]
NO
YES
Are characteristics of
TCJ sensor resistance value normal?
YES
NO
* Refer to Characteristics-2.
[P26 error]
NO
NO
YES
* For RAV-SM562AT-E,
check RY01 on the control P.C. board.
Does RY01 relay of
IPDU operate?
YES
NO
NO
YES
* Single-phase type is not
provided to RAV-SM562AT-E.
Replace IPDU.
YES
Is not AC fuse fused?
NO
Replace IPDU.
NO
Is compressor normal?
YES
Check IPDU.
Defect
Replace
48
[P29 error]
NO
Are connections of
cable/connector normal?
YES
NO
Is compressor normal?
YES
YES
Is not earthed?
NO
Is not winding shorted?
(Is resistance between windings 0.6 to 1.2W?)
YES
NO
YES
Is not winding opened?
NO
[H03 error]
NO
YES
Check IPDU.
Defect Replace
49
[F06 error]
Are connections of
TE/TS sensor connectors of
CDB CN604/CN605 normal?
YES
Are characteristics of TE/TS sensor
resistance values normal?
NO
YES
Check CDB.
Defect
Replace
* Refer to Characteristics-3.
[F04 error]
NO
Replace TD sensor.
YES
* Refer to Characteristics-4.
[F08 error]
NO
Replace TO sensor.
YES
Check CDB.
Defect
Replace
* Refer to Characteristics-5.
50
[L29 error]
In the case of SUPER DIGITAL INVERTER
Are connections of
CDB CN800 and CDB IPDU CN06
connectors normal?
NO
Correct connection of connector.
YES
Was the error just after
power ON determined?
YES
NO
Are cabling/connector normal?
YES
NO
NO
Correct mounting.
YES
YES
Fault of compressor.
Check rare short
Defect
Replace
NO
Is compressor normal?
YES
[H02 error]
NO
Is power voltage normal?
YES
Are connections of
cable/connector normal?
NO
YES
NO
Is compressor normal?
Is there no
slackened refrigerant?
YES
NO
Compressor lock
Replace
YES
Does electron expansion
valve normally operate?
NO
YES
51
[P03 error]
NO
Are connections of
cable/connector normal?
YES
NO
YES
Check parts. Defect
NO
Replace
NO
Replace TD sensor.
* Refer to Characteristics-4.
Check CDB.
Defect
Replace
* For RAV-SM562AT-E, replace control P.C. board.
[H01 error]
NO
YES
YES
NO
Check and correct circuit cables.
YES
Check IPDU.
Defect
Replace
* For RAV-SM562AT-E, replace control P.C. board.
52
[P04 error]
Is high-voltage
protective operation by
TE sensor normal?
NO
YES
NO
Is connection of cabling
connector normal?
Correct connection of
cabling connector.
YES
Check TE sensor.
Defect
Replace
NO
NO
Is connection of
connector normal?
Correct connection of
connector.
YES
NO
Is fan motor normal?
YES
NO
Does PMV normally operate?
YES
Do not TD and TO sensors
come off the detection part?
Correct coming-off.
YES
Are characteristics of
TD, TO, TC sensor resistance
values normal?
YES
Check charged refrigerant amount.
Check liquid/gas valves.
Check abnormal overload.
NO
NO
Check CDB.
Defect
Replace
* For RAV-SM562AT-E, replace control P.C. board.
53
YES
Are connections between connectors
CN51 of connection interface P.C. board
and connectors CN51 of indoor P.C. board
normal?
NO
YES
NO
Is A, B communication line normal?
YES
YES
Is there no connection error of power line?
NO
YES
Is not power of source power supply turned on?
NO
YES
Did a power failure occur?
NO
YES
Is there no noise source, etc.?
NO
Can central remote controller
control normally other indoor units?
Is handling of central remote controller reflected
on the operation status of indoor unit?
NO
(Same as others)
YES
Can handy remote controller control
normally other indoor units?
NO
YES
54
(Power ON)
(Approx. 3 minutes)
[SET] is displayed on
main remote controller.
(Approx. 1 minute)
[SET] goes off.
(Repetition)
LED (D02) on
indoor unit P.C. board flashes
with 1Hz for approx. 10 seconds.
Reboot
(Reset)
55
20
40
TA sensor
Caracteristics-2
Caracteristics-1
Resistance
(kW)
Resistance
(kW)
10
20
10
10
20
30
40
0
10
50
10
Temperature [C]
20
30
40
50
60
70
Temperature [C]
20
200
Caracteristics-3
Resistance
(kW)
(10C or higher)
Resistance
(kW)
(10C or lower)
10
100
0
-10
10
20
30
40
50
60
70
Temperature [C]
TD sensor
200
20
Caracteristics-4
Resistance
(kW)
(50C or higher)
Resistance
(kW)
(50C or lower)
10
100
0
50
100
Temperature [C]
56
<REPLACEMENT PROCEDURE>
CASE 1
Before replacement, power of the indoor unit can be turned on and the setup data can be readout
from the wired remote controller.
Read EEPROM data *1
Power reset (All indoor units in the group when group operation)
CASE 2
Before replacement the setup data can not be readout from the wired remote controller.
Replace service P.C. board & power ON *2
Write the data such as high ceiling setup to EEPROM (According to the customers information) *3
Power reset (All indoor units in the group when group operation)
57
10
Type
11
12
Line address
13
Indoor address
14
Group address
1) Type and capacity of the indoor unit is necessary to set the revolutions
frequency of the fan.
2) If Line/Indoor/Group addresses differ from those before replacement, the
mode enters in automatic address setup mode and a manual resetting
may be required.
Notes)
MCC-1402-07
When
replacement
CN34
Contents
DN
If short-circuit-plug is inserted in
CN34 of the P. C. board to replace,
re-use it in service P. C. board.
58
UNIT No.
R.C.
3
4
6
1
59
TIME
FILTER
RESET TEST
SET
CL
No.
SWING/FIX
UNIT
VENT
5
2
Item
Memo
01
According to type
02
0000: Standard
03
0099: Unfixed
06
0F
Cooling only
10
Type
11
12
Line address
0099: Unfixed
13
0099: Unfixed
14
Group address
0099: Unfixed
19
According to type
1E
28
0000: None
2A
Option
0002:
At shipment
2b
0000: Thermo ON
2E
Option
0000:
32
Sensor selection
5d
0000: Standard
60
0000: Available
8b
0000: None
Type
Item code [10]
Setup data
0014
Type
Abbreviated name
RAV-SM562MUT-E
Type
Abbreviated name
0009
RAV-SM562MUT-E
60
button.
Then push
TEST is displayed on LC display during operation of Test Run.
During Test Run, temperature cannot be adjusted but air volume can be selected.
In heating and cooling operation, a command to fix the Test Run frequency is output.
Detection of error is performed as usual. However, do not use this function except case of Test Run because it applies load on the unit.
2. Use either heating or cooling operation mode for [TEST].
NOTE : The outdoor unit does not operate after power has been turned on or for approx. 3 minutes after
operation has stopped.
TEST
3. After a Test Run has finished, push
button again and check that [TEST] on LC display has gone off.
(To prevent a continuous test run operation, 60-minutes timer release function is provided to this remote
controller.)
Receiver unit
Spacer
M4 25 screw
(2 pieces)
Notch
Nameplate
Small screw
61
Description
Turn on power of the air conditioner.
The operation is not accepted for 5 minutes when power has been turned on at first time after installation,
and 1 minute when power has been turned on at the next time and after. After the specified time has
passed, perform a test operation.
Push [Start/Stop] button and change the operation mode to [COOL] or [HEAT] with [Mode] button.
Then change the fan speed to [High] using [Fan] button.
Test cooling operation
4545.
After approx. 10 seconds, all the display lamps on the sensor part of wireless remote controller,
[Operation] (Green), [Timer] (Green), and [Ready] (Yellow) flash and the air conditioner starts operation.
If the lamps do not flash, repeat the procedure
2 and after.
After the test operation, push [Start/Stop] button to stop the operation.
3, 4, 5, 6
2, 7
62
Description
Item
At shipment
01
0000 : None
0002 : 2500H (4-Way/Duct/Ceiling Type)
02
0000 : Standard
0001 : High degree of dirt (Half of standard time)
0000 : Standard
03
06
0000 : No shift
0002 : +2C
to
0099 : Unfixed
to
0001 : +1C
0010 : -10C
(Up to recommendation + 6)
0002 : +2C
(Floor type 0000: 0C)
0F
Cooling only
10
Type
0014 : SM562MUT-E
11
0000 : Unfixed
0012 : 802 type
0017 : 1402 type
12
Line address
13
14
Group address
0000 : Individual
0002 : Sub of group
1E
Temp difference of
automatic cooling/heating
mode selection COOL
HEAT, HEAT COOL
0000 : 0 deg
to
0010 : 10 deg
(For setup temperature, reversal of
COOL/HEAT by (Data value)/2)
0003 : 3 deg
(Ts1.5)
28
0000 : None
0000 : None
2A
Option
2b
2E
Option
0000 : Default
30
Option
0000 : Default
31
Option
0000 : Default
32
Sensor selection
33
Temperature indication
0000 : C (celsius)
0001 : F (Fahrenheit)
0000 : C
40
Option
5d
0000 : Standard
60
Timer set
(Wired remote controller)
0000 : Available
8b
0000 : None
0000 : None
to
0099 : Unfixed
to
0099 : Unfixed
0099 : Unfixed
19
0001 : Restart
0002 : Default
0000 : Indoor thermo ON
0001 : Output of outdoor comp-ON receiving
0000: Thermo. ON
0003 : Default
0001 : Correction
63
Sold separately
A B
A B
Sub remote
controller
Master remote
controller
1 2
DIP switch
Remote controller
cables (Procured locally)
Terminal block for
remote controller cables
1 2
A B
Indoor unit
1 2 3
1 2 3
Outdoor unit
(Setup method)
One or multiple indoor units are controlled by two
remote controllers.
(Max. 2 remote controllers are connectable.)
64
1
2
CL
TEST
Push +
buttons simultaneously for 4 seconds or more to call the service monitor mode.
The service monitor goes on, the master indoor unit No. is displayed, and then temperature of the item
code 00 is displayed.
Push the temperature setup
/
buttons to select the sensor No. (Item code) of the sensor to be monitored.
The sensor numbers are described below:
SET DATA
UNIT No.
R.C.
No.
TEMP.
2
4
FILTER
RESET TEST
ON / OFF
TIMER SET
FAN
MODE
TIME
SWING/FIX
VENT
SET
CL
UNIT
1
<Operation procedure>
Item code
Indoor
unit data
Data name
Item code
00
01
02
03
04
Data name
60
61
Outside temp. TO
62
Discharge temp. TD
63
Suction temp. TS
64
65
3
4
The temperature of indoor units and outdoor unit in a group control can be monitored by
UNIT
button to select the indoor unit to be monitored.
pushing
Pushing
TEST
65
SET DATA
UNIT No.
CL
TEST
R.C.
Push +
buttons simultaneously for 4
seconds or more to call the service check
mode.
Service Check goes on, the item code 01 is
displayed, and then the content of the latest alarm is
displayed. The number and error contents of the
indoor unit in which an error occurred are displayed.
TEMP.
2
3
TEST
No.
ON / OFF
TIMER SET
FAN
MODE
TIME
SWING/FIX
VENT
FILTER
RESET TEST
SET
CL
UNIT
1
<Operation procedure>
<Requirement>
CL
Do not push
button, otherwise all the error histories of
the indoor unit are deleted.
<System example>
OUT
IN
OUT
1-1
IN
OUT
Master
2-1
IN
OUT
3-1
IN
OUT
4-1
IN
7-1
Max. 8 units
Remote controller
66
CN51
TCC-LINK
communication circuit
Central
controller
CN40
Terminal
resistance
SW01
MCC-1440
Terminal block
(A, B)
TCC-LINK
Communication units:
Total 64 units
Communication distance:
2km
Remote controller
3. Installation Procedure
1) Cut off the slit of bell mouth on the Air Conditioner unit (RAV-SMMUT-E) with nipper or a cutter for
attaching the Connection Interface Kit.
67
3) Install the spacers and P.C. board that are attached to TCB-PCNT30TLE2, on the Connection Interface
Kit.
Spacers
(Attached to the TCB-PCNT30TLE2)
P.C. board
(Attached to the TCB-PCNT30TLE2)
4) Remove the 2P terminal block for the communication cable of the electric parts box on the unit, and then
replace with the attached 4P terminal block for the communication wires.
a) Disconnect the lead wires on the 2P terminal block of the electric parts box from the Faston connector
on the unit.
b) Replace the 2P connector with 4P connector on the terminal block.
c) Connect the lead wires that are disconnected as shown above steps a), to the 4P terminal block.
(A), (B) terminals
(Connecting for the Remote Controller)
CN41
(BLUE)
CN41
(BLUE)
A B U3 U4
1
1
3
CN41
3
Main P.C. B
MCC-1402
1 2 3 4 5 CN50
1 2 3 4 5 (WHITE)
CN50
(WHITE)
CN51
1 2 3 4 5
CN51
1 2 3 4 5
Sub P.C. B
MCC-1440
CN41
(BLUE)
CN40
Connecting cable B
Connecting cable A
68
Wiring diagram
Screw (4 10)
Connection
Interface Kit cover
Hook of
Connection Interface Kit
Screw (4 10)
CAUTION
1)
2)
3)
4)
When controlling customized setup collectively, TCC-LINK adapter (This option) is required.
In case of group operation or twin/triple operation, the adapter is necessary to be connected to the main unit.
Connect the central control devices to the central control system wiring.
When controlling collectively customized setup only, turn on only Bit 1 of SW01 of the least line of the system
address No. (OFF when shipped from the factory)
In case of customized setup, the address is necessary to be set up again from the wired remote
controller after automatic addressing.
Central control device
U1 U2
U3 U4
U1 U2
U3 U4
Refrigerant line 1
Refrigerant line 2
Refrigerant line 3
Refrigerant line 4
1 2 3
1 2 3
1 2 3
Outdoor unit
1 2 3
Caution 3
Indoor unit
U3 U4
1 2 3
U3 U4
Maater
unit
1 2 3
A B
TCC-LINK adapter
This product
sold separately
Caution 1
Sub
unit
1 2 3
A B
A B
Sub unit
1 2 3
A B
U3 U4
Maater unit
1 2 3
A B
A B
Caution 2
Remote controller
wiring
Remote controller
Remote controller
Remote controller
Remote controller
Twin/Triple operation (Example of triple)
69
Sub unit
1 2 3
5. Wiring Specifications
Use 2-core with no polar wire.
Size
No. of wires
Match the length of wire to wire length of the central
Up to 1000m: twisted wire 1.25mm2
control system.
2
Up to 2000m: twisted wire 2.0mm2
If mixed in the system, the wire length is
lengthened with all indoor/outdoor inter-unit wire length at side.
To prevent noise trouble, use 2-core shield wire.
Connect the shield wire by closed-end connection and apply open process (insulating process) to the last terminal. Ground the earth wire to 1 point at indoor unit side. (In case of central controlling of digital inverter unit setup)
CAUTION
1) Closed-end connection of shield wire (Connect all the connecting parts of each indoor unit)
2) Apply open process to the last terminal (insulating process).
3) Ground earth wire to 1 point at indoor unit side.
Caution 2
Caution 1
Caution 3
Outdoor unit
Indoor unit
U3 U4
1 2 3
1 2 3
1 2 3
1 2 3
Master
unit
U3 U4 1 2 3
Sub unit
1 2 3
A B
A B
Remote controller
1 2 3
Sub unit
1 2 3
U3 U4
A B
Remote controller
: TCC-LINK adapter
(This option)
A B
Remote controller
Master unit
1 2 3
A B
A B
Earth terminal
Remote controller
(Group operation)
Sub unit
1 2 3
(Triple operation)
U1 U2
U3 U4
U1 U2
U3 U4
Refrigerant line 1
Refrigerant line 2
Refrigerant line 3
Refrigerant line 4
1 2 3
1 2 3
1 2 3
Outdoor unit
1 2 3
Indoor unit
U3 U4
1 2 3
U3 U4
A B
A B
TCC-LINK adapter
This product
sold separately
Sub
unit
1 2 3
Master
unit
1 2 3
Sub unit
1 2 3
A B
A B
Remote controller
Remote controller
Remote controller
Remote controller
1 2 3
A B
A B
1
ON
OFF
Turn SW01 Bit 1 to ON.
SW01
Bit 1
OFF
OFF
ON
ON
2
OF
OFF
As status shipped from factory
4
OF
(OFF at shipment from factory)
OFF
(OFF at shipment from factory)
As status shipped from factory
Terminator
None
100
75
43
Remote controller
Sub unit
1 2 3
Line address
SW01 Bit 1
SW01 Bit 2
Remarks
U3 U4
Master unit
Remarks
Mixed with multi (Link wiring) at shipment from factory
Central control by digital inverter only
Spare
Spare
70
52
85
8. Address Setup
In addition to set up the central control address, it is necessary to change the indoor unit number.
(Line/Indoor/Group address).
For details, refer to TCC-LINK Adapter Installation Manual.
TEST
VENT
Push +
buttons for 4 seconds or more.
When group control is executed, first the unit No. RLL is displayed and all the indoor units in the group
control are selected. In this time, fans of all the selected indoor units are turned on. (Fig. 1)
(Keep RLL displayed status without pushing
button.)
In case of individual remote controller which is not group-controlled, Line address and Indoor unit address
are displayed.
UNIT
2
3
4
SET
TIME
TEMP.
buttons, select the setup data. The setup data is shown in the right
Push
TEST
03.
(Fig.1)
2.
button.
SET DATA
UNIT No.
R.C.
(Table 1)
No.
TEMP.
Setup data
0001
0002
0003
:
0064
1
2
3
:
64
0099
2
1
5
71
FILTER
RESET TEST
ON / OFF
TIMER SET
FAN
MODE
TIME
SWING/FIX
VENT
SET
CL
UNIT
3
1
4
NO
NO
(MANUAL)
NO
Is group control performed?
YES
) (
Setup of automatic
address finishes within
4 to 5 minutes.
END
When the following addresses are not stored in the neutral memory (IC10) on the indoor P.C. board, a test run
operation cannot be performed. (Unfixed data at shipment from factory)
Item code
Data at shipment
Line
address
12
0099
Indoor unit
address
13
0099
Group
address
14
0099
72
1. Single
Outdoor
Indoor
1-1
Individual (Master/Sub)
2-1
Sub
1-1
Sub
4-1
Master
3-1
Sub
8-1
Sub
Remote
controller
1-1
Individual (Master/Sub)
2) Gr operation
(Multiple outdoor units = Miltiple indoor units only with serial
communication)
2-1
Sub
1-1
Sub
4-1
Master
8-1
Sub
Max. 8 units
73
1
2
3
4
5
6
7
8
9
10
11
SET
CL
OUT
IN
IN
TEST
Push
+
+
buttons simultaneously
for 4 seconds or more.
(
Line address)
Using the temperature setup
set 12 to the item code.
Using timer time
Push
SET
(
Indoor unit address)
Using the temperature setup
set 13 to the item code.
Using timer time
Push
SET
buttons,
buttons,
Line address
Indoor unit address
Group address
buttons,
2
1
2
(
Group address)
Using the temperature setup
set 14 to the item code.
Push
1
1
1
Group address
Individual : 0000
Master unit : 0001
Sub unit
: 0002
TEST
Push
button.
Setup completes. (The status returns to the usual stop status.)
SET DATA
UNIT No.
R.C.
No.
TEMP.
2, 5, 8
END 11
FILTER
RESET TEST
ON / OFF
TIMER SET
FAN
MODE
TIME
SWING/FIX
VENT
SET
CL
3, 6, 9
4, 7, 10
UNIT
1
<Operation procedure>
74
10
11
END
1
2
ON / OFF
Push
UNIT
Push
button.
Unit No. 1-1 is displayed on LCD.
(It disappears after several seconds.)
The displayed unit No. indicate line address and
indoor unit address.
(When other indoor units are connected to the
identical remote controller (Group control unit), other
UNIT
unit numbers are also displayed every pushing
button.
TEMP.
FILTER
RESET TEST
ON / OFF
TIMER SET
FAN
MODE
TIME
SWING/FIX
VENT
SET
CL
1
Operation
UNIT
2
<Operation procedure>
2 END
VENT
SET DATA
UNIT No.
R.C.
No.
TEST
Push
and
buttons simultaneously for
4 seconds or more.
Unit No. ALL is displayed.
Fans and flaps of all the indoor units in the group
control operate.
TEMP.
1
FILTER
RESET TEST
ON / OFF
TIMER SET
FAN
MODE
TIME
SWING/FIX
VENT
SET
CL
UNIT
UNIT
Every pushing
button, the unit numbers
in the group control are successively displayed.
The unit No. displayed at the first time indicates the
master unit address.
Fan and flap of the selected indoor unit only
operate.
TEST
Push
button to finish the procedure.
All the indoor units in the group control stop.
75
3
<Operation procedure>
3 END
13. DETACHMENTS
13-1. Indoor Unit
Ceiling panel: RBC-UM11PG(W)E
Preparing work:
1. Before work, be sure to stop the power supply of the air conditioner and turn off switch of the power supply
breaker. (Otherwise an electric shock may be caused.)
2. Be sure to put on the gloves when working; otherwise an injury may be caused with parts sharp edges etc.
No.
Part name
Suction grille
Procedure
Remarks
1. Detachment
1) Slide hooks (2 positions) of the suction grille
to inner side, and then hang down the
suction grille.
2) Take off the strap that connects the panel
and the suction grille, and then lift up shaft of
the suction grille to remove the suction grille.
Suction grille
Ceiling panel
2. Attachment
1) Hook shaft of the suction grille to the panel.
2) Hook strap of the suction grille to the original position of the panel.
3) Close the suction grille and slide the hooks outward to fix it.
2
Electric parts
cover
1. Detachment
1) Perform work of procedure 1 -1.
2) Take off screws (4 10, 3 pcs.) fixing the
electric parts cover.
3) Remove the electric parts cover from the
temporary hanging hook of the electric parts
cover, and then open the cover.
Screws
2. Attachment
1) Close the electric parts cover and hook the
cover hole to the temporary hanging hook.
2) Tighten the fixing screws. (4 10, 3 pcs.)
Screw
Unnecessary to remove this hook.
76
No.
Part name
Adjust
corner cover
Procedure
Remarks
1. Detachment
1) Perform work of procedure of 1 -1.
2) Turn clockwise screws (4 positions) at the
suction port corner until adjust corner
cover rises up.
NOTE)
2
Torque~12Nm
2. Attachment
1) Attach the strap of adjust corner cover to
the panel, hook claws of adjust corner
cover to the panel corner, and then push
the opposite side into the panel.
2) Turn screws (4 positions) of the suction
port corner counterclockwise until bump
between adjust corner cover and panel
disappears.
NOTE)
When you work, keep the torque at below 12Nm.
Do not use an electric screwdriver;
otherwise the mechanism of adjust corner cover
may be damaged and not be removed.
4
Ceiling
panel
Torque~12Nm
1. Detachment
1) Perform works of procedure 1 -1-, 2 -1,
and 3 -1.
2) Remove the flap connector (CN33, White,
5P) connected to the control P.C. board
and then take off the lead wire from the
clamp.
Hanging
section of tentative
hook of ceiling panel
Temporary
bracket
Push to remove
NOTE)
Drain piping
corner
2. Attachment
Temporary
bracket
NOTE)
The panel has directionality. Therefore mount the
panel according to the temporary bracket and the
bracket mounting position.
2) Tighten the fixing screws. (M5, 4 pcs.)
3) Connect flap connector of the ceiling
panel to the connector
(CN33, White, 5P) of the control
P.C. board.
Cable clamp
77
Washer
based screw
Hanging section
of temporary bracket
CN33
No.
Part name
Control P.C.
board
Procedure
Remarks
1. Detachment
1) Perform works of procedure 1 -1- and 2 -1.
2) Remove the connectors connected from the control P.C. board to other parts.
CN33 : Flap motor (5P, White)
CN34 : Float switch (3P, Red)
CN41 : Terminal block of remote controller (3P, Blue)
CN40 : Terminal block of crossover between inside and outside (5P, Black)
CN68 : Drain pump (3P, Blue)
CN67 : Terminal block of power supply (3P, Black)
CN101 : TC sensor (2P, Black)
CN102 : TCJ sensor (2P, Red)
CN104 : Room temp sensor (2P, Yellow)
CN333 : Fan motor power supply (5P, White)
CN334 : Fan motor position detection (5P, White)
NOTE)
Remove the connectors after
unlocking the lock of the housing.
2. Attachment
1) Fix the control P.C. board to the card edge spacer. (6 positions)
2) Connect the connectors as original before being removed in item 1.
NOTE)
For drawing of each wire and position of ferrite core, perform wiring same as those before removing. If there is incomplete drawing of wire, short or water leakage of the parts may be caused.
Fix the sensor lead wires with cord clamps (2 positions) so that
it does not slacken at P.C. board side and draw wires as shown in the figure.
Cord clamp
Adhere on the
transformer.
Arrow view E
Please note the
float SW lead wires are
set at inner side of the
fan motor lead wires.
Cord clamp
78
No.
6
Part name
Electric
parts box
Procedure
Remarks
1. Detachment
1) Perform works of procedure 1 -1-and 2 -1.
2) Remove connectors of the lead wire connected to the following connectors of the control
P.C. board.
CN33 : Flap motor (5P, White)
CN34 : Float switch (3P, Red)
CN68 : Drain pump (3P, Blue)
CN101 : TC2 sensor (2P, Black)
CN102 : TCJ sensor (2P, Red)
CN333 : Fan motor power supply (5P, White)
CN334 : Fan motor position detection (5P, White)
NOTE)
Remove the connectors after unlocking the lock of the housing.
3) Remove each lead wire
from cord clamps in the
electric parts box.
4) Remove the power supply
wiring, remote controller
wiring, and crossover wiring.
5) Take off screws
(4 10, 2 pcs.)
2. Attachment
1) Tighten screws (4 10, 2 pcs.) fixing the electric parts box.
2) Connect the connectors as original before being removed in item 1.
3) Perform power supply wiring, remote controller wiring, and crossover wiring between inside
and outside.
NOTE)
For drawing of each wire and position of ferrite core, perform wiring same as those before removing. If there is incomplete drawing of wire, short or water leakage of the parts may be caused.
Fix the sensor lead wires with cord clamps (2 positions) so that
it does not slacken at P.C. board side and draw wires as shown in the figure.
Cord clamp
Adhere on the
transformer.
Arrow view E
Please note the
float SW lead wires are
set at inner side of the
fan motor lead wires.
Cord clamp
79
No.
7
Part name
Bell mouth
Procedure
Remarks
1. Detachment
1) Perform work of procedure 1 -1.
2) Take off the lead wires of the drain pump, float
switch, and fan motor from the bell mouth.
3) Take off fixing screws of the bell mouth.
(4 10, 4 pcs.)
Fixing claws
for lead wires
Bell mouth
2. Attachment
1) Mount the bell mouth with screws.
(4 10, 4 pcs.)
2) Perform wiring as original before being
removed.
NOTE)
Pinch lead wire of the drain pump and float switch
with lead wire fixing claws of the bell mouth and
perform wiring along the guide.
Turbo fan
4 screws
Fixing claws
for lead wires
1. Detachment
1) Perform work of procedure 7 -1.
2) Take off the nut (M6 nut 1 pc.) of the turbo fan.
NOTE)
Use a box wrench for attachment and detachment of
the turbo fan. If using a monkey wrench etc, the
other parts may be damaged in work.
2. Attachment
1) Insert the turbo fan into the fan motor so that
boss of the turbo fan matches with cut surface
of the fan motor, and then tighten it with nut.
NOTE)
Tightening torque of turbo fan: 5.9 0.6N.m
Apply looseness-preventing agent to the nut after
tightening.
Turbo fan
80
Drawing-out port of
fan motor lead wire
No.
9
Part name
Fan motor
Procedure
Remarks
1. Detachment
1) Perform work of procedure 8 .
2) Take off screws fixed with lead holding bracket
of the fan motor. (4 10, 2 pcs.)
3) Open wiring holding part of the fan motor lead
holding bracket and then take off the fan motor
lead wire from the bracket.
4) Take off fixing nuts for the fan motor to remove
the fan motor.(M 3 pcs.)
Fan motor
NOTE)
Use a box wrench for attachment and detachment of
the fan motor fixing nuts; otherwise contact or
damage for other parts may be caused.
Fan motor
earth wire
Fixing screw
2. Attachment
1) Mount the fan motor with the fixing nuts.
NOTE)
Tightening torque of turbo fan: 5.9 0.6N.m
Apply looseness-preventing agent (as paints) to the
nut after tightening.
2) Attach the fan motor lead wire holder.
NOTE)
For the fan motor lead wire, fix the lead wire
holding bracket along concave part of the ceiling
panel. (There is no catch-in of lead wire and ceiling
panel.)
When fixing the lead wire bracket, tighten fan
motor earth together with the lead wire.
For this work, do not use an electric screwdriver.
Take note the damage of earth terminal.
3) Bend the lead wire holding part and fix the fan
motor lead wire.
NOTE)
Be sure that the lead wire does not come to contact
with the heat exchanger.
81
Concave part
of ceiling panel
No.
10
Part name
Drain pan
Procedure
Remarks
1. Detachment
2 screws
NOTE)
Soc
Socket
et of drain
drain pan
Drain
Drain pan
2. Attachment
1) Insert the drain cap into the drain pan.
NOTE)
Put a stick or others into hole at center of the drain
cap, and then insert the drain cap until it strikes on
the socket of the drain pan.
2 screws
NOTE)
Drain pump
assembly
Piping holder
Lead wire
1. Detachment
1) Perform work of procedure 10 -1.
2) Pick up the hose band and slide it from the
pump connecting part to remove the drain
hose.
3) Take off screws (4 10, 3 pcs.) fixing the
drain pump assembly, and then move hooking
claw (1 position) of the main body from the
drain pump assembly to remove the drain
pump assembly.
2. Attachment
White marked position
NOTE)
For fixing, use a hooking claw (1 position) and
screws (3 positions).
When screwing, be sure not to run on the hooking
claw at main body side.
2) Mount the drain hose and the hose band as
original.
NOTE)
Insert the drain hose up to the end of pump connecting part, and then put the band at white marked
position of the hose.
Fixing screw
for drain pump
82
Hooking claw
for drain pump
No.
12
Part name
Heat
exchanger
Procedure
Remarks
1. Detachment
1) Recover refrigerant gas.
2) Remove the refrigerant pipe at indoor unit
side.
3) Perform work of procedure 10 -1.
4) Take off screws (4 10, 3 pcs.) fixing the
piping cover to remove the piping cover.
5) While holding the heat exchanger, remove
fixing band and fixing screws (4 10, 3 pcs.)
and then remove the heat exchanger.
Piping cover
2. Attachment
1) Mount parts in order, heat exchanger
fixing band piping cover drain pan
bell mouth electric parts box as original.
3 screws
NOTE)
Arrange wires as original.
2) Attach the removed connectors and wires as
original.
3) Connect the refrigerant pipe as original, and
then perform vacuuming.
Fixing band
TCJ sensor
(Black)
TC sensor
(Red)
2 fixing screws for heat exchanger
83
308
302
307
315
316
309
314
311
304
312
310
313
305
303
306
301
Location
No.
Part No.
301
302
303
304
305
306
307
308
43109414
4302C059
43180332
43497012
43100322
43107259
43122089
43122090
Description
Location
No.
Part No.
309
310
311
312
313
314
315
316
43122091
43122092
43122093
43107261
43100369
43107262
43107263
43160580
84
Description
Joint, Kit (A)
Joint, Kit (B)
Louver
Outlet, Air Form
Panel
Fix, Motor
Fix, Motor
Lead, Motor
234
223
202
221
203
231
228
201
209
235
241
236
205
247
233
237
224
222
242
226
225
227
230
215
213
220
211
219 216 217
85
Location
No.
Part No.
Description
201
202
203
205
209
211
213
215
216
217
219
220
221
222
223
224
225
226
227
228
230
231
233
234
235
236
237
238
43120225
43122094
43172185
43121738
4314J329
4314Q034
43047685
43149351
43047688
43149353
43147195
43049697
43170244
43079249
43060029
43163052
43119482
43170248
43119483
43097212
43019904
43179135
43139137
43162056
43177001
43151289
43179126
43166002
239
43166004
240
43166005
241
43166006
242
247
4318T743
43197155
86
402
401
405
404
403
Location
No.
Part No.
401
43160565
402
43050425
403
404
43050426
43160568
405
4316V280
Description
Terminal Block, 3P,
AC250V, 20A,
Sensor Assy, Service
TC (F6)
Sensor, Service, TA
Terminal, 2P,
AC30V/DC42V, 1A
P.C. Board Assy,
MMC-1402 (220V 240V)
87
402
404
405
403
Location
No.
Part No.
Description
401
402
403
404
43160565
43050425
43050426
43160568
405
4316V280
88
401
NOTE 2 :
The standards for minimum room volume are as
follows.
(1) No partition (shaded portion)
Outdoor unit
e.g., charged
amount (10kg)
Outdoor unit
e.g.,
charged amount (15kg)
Very
small
room
Indoor unit
Small
room
Medium
room
Large room
NOTE 3 :
The minimum indoor floor area compared with the
amount of refrigerant is roughly as follows:
(When the ceiling is 2.7m high)
40
m 35
30
25
20
15
10
Range above
the density limit
of 0.3 kg/m
(countermeasures
needed)
5
0
10
20
30
Total amount of refrigerant
kg