This is a general specification leaflet; for specific applications not covered herein, contact Suntec.
The SUNTEC AP oil pump has a built-in solenoid which provides a two-mode pressure operation. APPLICATIONS - Light oil. - 2 firing rates (with a sole nozzle line). - Two-pipe or one-pipe system. - Requires a separate cut-off valve. PUMP OPERATING PRINCIPLE The gear-set draws oil from the tank through the built-in filter and transfers it to the pressure regulating valve. The high pressure mode is obtained with the solenoid valve activated (ie. closed); activating this solenoid valve closes the by-pass channel to the return. Oil is then transferred to the nozzle line at the pressure given by the high pressure regulating valve. The low pressure mode is obtained with the solenoid valve open (ie. non activated); the by-pass channel is open, the oil is supplied to the nozzle line via the by-pass hole and the low pressure adjustment is made by the screw on the solenoid tube. It is preferable to set the high pressure given by the pump valve (with solenoid activated) before the low pressure, with solenoid non activated. Care should be taken not to overtighten the low pressure adjusting screw of the solenoid tube, as this may eliminate the low pressure range. For two pipe installation, the by-pass plug fitted in the return port allows any oil not required at the nozzle to be dumped back to the tank. For one pipe installation, the by-pass plug must be removed and the return port plugged, oil which is not required at the nozzle is then returned back to the suction port in the gear set . Bleed : Bleeding is assured by the by-pass hole of the nozzle plug. For the first start up, bleeding can be accelerated by loosening the plug of a pressure port . Note : Owing to the presence of the nozzle by-pass hole, the pump has no cut-off function; cut-off must be provided by an external solenoid valve.
Solenoid valve open ( low pressure mode ) Low pressure adjustment By-pass channel High pressure adjustment
AP
AP - 11 - Ed 6 - June 2001
PUMP IDENTIFICATION
( Not all model combinations are available. Consult your Suntec representative)
AP : two step model (one nozzle line and two pressure modes) without cut-off Gear set capacity (see pump capacity curves) Shaft rotation and nozzle location (seen from shaft end) A : clockwise rotation / right hand nozzle. B : clockwise rotation / left hand nozzle. C : anti clockwise rotation / left hand nozzle. D : anti clockwise rotation / right hand nozzle. Pump series 1000 : standard 7000 : with side pressure ports 4 : hub 54 mm 5 : hub 32 mm model number
AP
47 C 1 5 xx
P 05 00
Revision number Installation P : by-pass plug installed in return port for two-pipe operation Solenoid coil voltage 01 : 110 - 120 V ; 50/60 Hz 02 : 24 V ; 50/60 Hz 05 : 220 - 240 V ; 50/60 Hz Connector cable length 00 : no cable 35 : 35 cm 45 : 45 cm 60 : 60 cm 10 : 1 m
To nozzle By-pass hole Shaft seal Pressure gauge port Gear set
Back to suction Oil under suction Oil under pressure By-passed oil returned to tank or to suction By-pass plug removed ONE PIPE INSTALLATION By-pass plug inserted TWO PIPE INSTALLATION
Return Suction SUNTEC INDUSTRIES FRANCE - 1, rue Lavoisier - BP 102 - 21603 LONGVIC Cedex - Tel. 33 3 80 70 60 70 - Fax 33 3 80 70 61 11 - http://www.suntec.fr
Return plugged
AP 67
AP 57 AP 47
Weight
Hydraulic Data
Gear size 47/57
Low mode : High mode : 67 Low mode : High mode : * Other ranges available on request, fuel unit. Operating viscosity 2-12 cSt Oil temperature 0 - 60C max. in the pump Inlet pressure 2 bars max. Return pressure 2 bars max. Suction height 0,45 bars max. vacuum to prevent air separation from oil Rated speed 3600 rpm max. Torque (@ 45 rpm) 0,10 N.m (AP 47/57) - 0,12 N.m (AP 67)
Power consumption
Power (W) 200
150
100
AP 67
50
Connector characteristics
Material Cable type Cross section area Wire end terminals Polyamide H03 VV-F 0,5 mm per conductor in accordance with DIN 46228 D1-7Ms PUMP (Example shows "C" rotation and nozzle outlet)
42
AP 57 AP 47
10
15
20
DIMENSIONS
47
\ Z [
51 41 39
88
705
21 32 54 10,5 74
Inlet and Return with direct sealing for revision 5 models (sealing with washers can also be used)
118
35
]
13 25 21 7 8 13,5 13,5 63 92
Suction Return and internal by-pass plug Nozzle outlet Pressure gauge port
[ adjustment \
15
G1/4