12-Relay Remote Control Panel Interior
12-Relay Remote Control Panel Interior
12-Relay Remote Control Panel Interior
DESCRIPTION
The RINTER0012RC is the interior for a 12-relay TLC Remote Control Panel. The interior provides isolation between the line- and low-voltage sections of the panel, as well as the mounting frame for relays, the power supply and control devices. A complete assembly will include the following: 1. Tub (RTUB12) 2. Interior (RINTER0012RC) 3. Power Supply (RPWRxxx) 4. Cover (RCOV12xxx) 5. Relays (RR7P or RR9P) The tub/interior configuration simplifies installation. The tub can be mounted first, to allow easy access for pulling wires. The interior, with power supply and relays, then simply slides into the tub.
FEATURES
Up to twelve RR7P or RR9P plug-in relays. Two color-coded, numbered switch or sensor terminations per relay. Mounting holes for one or two RMS8, RMS16 or RPCON, or one RMS32 control devices. Accessory power for up to twelve occupancy sensors.
Before starting, read the installation instructions inside. If you have questions, call GE TLC Service at: 1-877-LTG-CNTL (584-2685) in the United States or 1-800-661-6619 in Canada.
INSTALLATION Environment
32-131F (0-50 C) 95% relative humidity 15 volts/meter, 10 KHz maximum RFI
Mounting
Mount the interior in the tub and secure it to the studs with the hardware supplied. Make sure that all line- and low-voltage wiring is confined to the appropriate areas.
Low-Voltage Wiring
Wire switches, sensors and other low-voltage control devices as shown in the Typical Wiring diagrams on the next two pages, using the 3/16" female push-on connectors installed on all leads.
Line-Voltage Wiring
Wire the relay SPST output terminals to the loads. Before making connections to the relay, however, make sure that none of the load circuits are shorted or miswired. Wire the power supply.
POWER SUPPLY CONNECTOR AND J1 TERMINAL TERMINALS FOR SWITCHES, SENSORS AND OTHER LOW-VOLTAGE CONTROL DEVICES
Relay Test
WHITE JUMPER PROBE TOUCH ON ALL RED (ON)
RED
1 2 3 11 12
Document Wiring
Record the circuits controlled by each relay on the enclosed Wiring Schedule and then place in the plastic envelope attached to the inside of the panel cover.
CONTINUE TO ALL RELAYS REPEAT FOR BLACK (OFF)
RED BLACK YELLOW WHITE
RED
RED
RED
INSTALLATION
STANDARD SWITCH
#20/3 AWG 1600 FEET MAXIMUM DISTANCE RSWIRE-3 (standard class) RSWIRE-3P (plenum applications)
RED
1 2
RED
LOCATION SWITCH
#20/4 AWG 1600 FEET MAXIMUM DISTANCE ROSWIRE-4 (standard class) ROSWIRE-4P (plenum applications)
(BLUE)
RED BLACK YELLOW WHITE
1 2
RED RED
#20/4 AWG 1600 FEET MAXIMUM DISTANCE RSWIRE-4 (standard class) RSWIRE-4P (plenum applications)
RED
1 2
RED
#20/4 AWG 1600 FEET MAXIMUM DISTANCE RSWIRE-4 (standard class) RSWIRE-4P (plenum applications)
RED
1 2
RED
#20/4 AWG MAXIMUM DISTANCE (See below) NUMBER MAXIMUM MAXIMUM RELAYS DISTANCE DISTANCE PARALLEL WITH #20/4 WITH #16/4 2 750 FEET 1900 FEET 4 325 FEET 825 FEET 6 180 FEET 450 FEET 8 110 FEET 275 FEET 10 65 FEET 160 FEET
RED
1 2 3
RED
RED
Note: Relays 1, 2 and 3 are now permanently wired as a group. You cant control them individually. If the pilot contacts are wired in parallel as above, turning ON any relay in the group will cause the pilot to light.
INSTALLATION
(BLUE)
1 2
RED RED
RED
1 2 3
24V
RED
(BLUE)
ACCESSORY POWER SUPPLY
24V RECT WHITE
RED
COM
B COM
DELAY ENABLE
LINE
RED BLACK YELLOW WHITE
HIGH
LOW
OFF-BLK
COMMON
PHOTOCELL
BLACK
WHITE
RED
BLUE
DRAIN
SENSOR ENABLE
ON
COM
TO PHOTODIODE SENSOR