• What is winter fuel
• Process description
• Plant description
• Operating instructions
WINTER FUEL BIODIESEL PLANT
PROCESS DESCRIPTION
WINTER FUEL BIODIESEL PLANT
Stage 2
Fractionation process Cooling and crystallization
according to a cooling curve
Water
Stage 1 return
Preheating of
the feedstock
to 40°C
Recirculation
Steam
Ester
feed
Recirculation
To filter press
Hot Chilled
water water
WINTER FUEL BIODIESEL PLANT
Core Blow
Recirculation
Stearin
Stage 3
Filtration to separate
liquid ester (olein) from
solid ester (stearin)
40°C
Temperature (°C)
Time (hour)
Water Ester
WINTER FUEL BIODIESEL PLANT
Olein
• Stearin is retained by the
filter cloth, forming a cake
which fills the filter
Stearin chamber
WINTER FUEL BIODIESEL PLANT
Olein for
squeezing
Filtration : Squeezing step
• Inflation of the flexible
membrane with olein
• The inflated membrane
presses on the stearin
cake thus forcing out
olein trapped in the cake
WINTER FUEL BIODIESEL PLANT
Drip Pan
WINTER FUEL BIODIESEL PLANT
PLANT DESCRIPTION
WINTER FUEL BIODIESEL PLANT
Plant 1 - Crystallizers
To
filter
press
WINTER FUEL BIODIESEL PLANT
Plant 1 - Filtration
Cold Room
WINTER FUEL BIODIESEL PLANT
Plant 2 - Crystallizers
To
filter
press
Plant 2 - Filtration
WINTER FUEL BIODIESEL PLANT
Utility Section
Glycol
Chiller
Hot Chilled
Water Water
Tank Tank
HOT CHILLED
WATER WATER
SYSTEM SYSTEM
WINTER FUEL BIODIESEL PLANT
Utility section
Additive tanks
WINTER FUEL BIODIESEL PLANT
Filter 1 Filter 2
Olein
dryer
Stearin
dryer
WINTER FUEL BIODIESEL PLANT
Step B Step C
Plant 1 Plant 2
35% 25% 20% 20%
Winter fuel
WINTER FUEL BIODIESEL PLANT
Step A’
Plant 1
35% 65%
Olein A’ Stearin A
Winter fuel
WINTER FUEL BIODIESEL PLANT
OPERATING INSTRUCTIONS
WINTER FUEL BIODIESEL PLANT
Recirculation Water
inlet return
• Agitator
• Frequency inverter
• Level transmitter c/w settings
Crystallizer
for HLA & LLA
• High level switch
• Inlet actuated valve
• Outlet actuated valve
• Water circulation pump
• Water circulation flowmeter
• Temperature of ester
• Temperature control for water
• Level control for water
Hot water
Chilled water
Ester
To filter
feed Recirculation press
outlet
WINTER FUEL BIODIESEL PLANT
Segment no. 0 1 2 3 4 5 6 7 8 … … … 19
Water temperature (°C) 35 25 20 18 18 - - - - - - - -
Segment time (min) 0 30 50 120 300 - - - - - - - -
35
Cooling curve
Temperature (°C)
25
20
18
30 50 120 300
Time (min)
WINTER FUEL BIODIESEL PLANT
Select the type of feed material – Methyl Ester (Step A) or Liquid Ester (Step B).
WINTER FUEL BIODIESEL PLANT
Select FILL – inlet valve V401-1 will open, the feed pump will start. When
LT401 reaches 50%, agitator AG401 will start.
WINTER FUEL BIODIESEL PLANT
At high level HLA or high high level LSH, the feed pump will stop. After a
preset delay timer, inlet valve V401-1 will close .
WINTER FUEL BIODIESEL PLANT
At the end of the preset homogenizing period, cooling will start automatically
– pump P301 will start, controllers LIC301 and TIC401 will run.
WINTER FUEL BIODIESEL PLANT
The cooling time varies from 20 hr to 50 hr. In the mean time, start feeding
ester into the next crystallizer.
WINTER FUEL BIODIESEL PLANT
Start the filtration process at the filter press PLC panel. Operation of the filter
press from closing to opening is fully automatic.
WINTER FUEL BIODIESEL PLANT
At low level LLA, agitator AG401 and pump P301 will stop. After a preset
delay timer, outlet valve V401-3 will close.
WINTER FUEL BIODIESEL PLANT
Batch Report
WINTER FUEL BIODIESEL PLANT