The construction of this component and any acceptable variation thereto is specified in the schedule to this type examination certificate. The Physikalisch Technische Bundesanstalt, notified body No. 0102 in accordance with Article 9 of the Council Directive 94/9/EC of 23 March 1994, certifies that this component has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of equipment and protective systems intended for use in potentially explosive atmospheres, given in Annex II to the Directive. The results of the test are recorded in the confidential report No. PTB Ex 00-30039.
(9)
The Essential Health and Safety Requirements are met by compliance with EN 50 014:1997 EN 50 020:1994 EN 50 018:1994 EN 50 028:1987 EN 50 019:1994
(10) If the sign X is placed after the certificate number, it indicates special conditions for safe use of the equipment specified in the schedule to this certificate. (11) This EC Type Examination Certificate relates only to the design and construction of the specified component in accordance with Directive 94/9/EC. Further requirements of this directive apply to the manufacture and supply of this equipment. (12) The marking of the component shall include the following:
Page 1/3
Uncertified Translation
Physikalisch-Technische Bundesanstalt
Braunschweig und Berlin
(13) (14)
Schedule
EC-Type Examination Certificate PTB 00 ATEX 3116
(15) Description of the component Terminal boxes, series 8125/1... and 8125/2..., made of sheet steel or stainless sheet steel, for fixed installation, with - separately certified - line-up terminals for non-intrinsically safe or separately certified - intrinsically safe circuits. The empty enclosures used are tested as components and specified in EC Type Examination Certificate PTB 00 ATEX 3111 U Type 8125/1... can additionally be equipped with - separately certified - isolating terminals and/or fuses. The marking with the identification symbol of the types of explosion protection is to be adapted to the components used. For intrinsically safe circuits, the box or area around the box is marked, e.g. with light blue colour. Technical data Rated voltage: max. 1100 V (depending on the operating voltage range of the terminals used) -50 C Tamb +55 C -50 C Tamb +75 C min. IP 54 to EN 60 529: 1991
Ambient temperature range, max. for type 8125/1...: Ambient temperature range, max. for type 8125/2...: Contact, foreign particles and ingress of water protection:
Rated current, number of conductors and conductor cross section are stipulated in the ascertained supplementary sheets. Note The terminal boxes are suitable for an ambient temperature range of -20 C to +40 C. The suitability for deviating ambient temperature ranges is visible by special marking. Only such separately certified - gaskets and - separately certified - built-in and built-on parts, suitable for these temperatures, are used. Additional instructions of the manufacturer have to be followed. Terminal boxes containing fuses and/or, beside the usual non-intrinsically safe circuits, intrinsically safe circuits, are provided with an additional marking. (16) Test report PTB Ex 00-30039 (17) Special conditions not applicable Page 2/3
Uncertified Translation
Physikalisch-Technische Bundesanstalt
Braunschweig und Berlin Schedule to EC-Type Examination Certificate PTB 00 ATEX 3116
(18) Essential Health and Safety Requirements The ingress protection - minimum IP 54 - is achieved only when using the tested gaskets, cable glands and stopping plugs properly.
Page 3/3
SUPPLEMENTARY SHEET 1
to EC Type Examination Certificate PTB 00 ATEX 3116
Fitting of terminal boxes Type 8125/1041 Max number of conductors
1)
current / A 1,5
3 6 10 16 20 25 35 50 63 80 100 125 45 45 15 6 30 17 8
2,5
25
116 33 19 5 36 14 2 35 11 4
2)
29 13 5
48 15 6 7
4) 3)
45
30
19
11
max. number of terminals depending on the above mentioned enclosure size and the cross section resp. max permissible conductor cross section of the builtin terminals
Notes 1) Each incoming conductor and each internal connection wire is counted as a conductor. Bridges and earthing conductors are not counted. 2) additional conductors optional 3) to be specified by the manufacturer (including temperature rise test) 4) When applying the values of this table simultaneous factors or load factors to IEC 439 may be considered. Mixed equipment with circuits of different cross sections and currents is possible if the various values of the table are applied proportionally: Example: (general) cross section / mm 2,5 16 25 current / A 16 50 63 number of conductors 10 (of 30) 12 (of 48) 36 (of 90) total utilization = 33 % = 25 % = 40 % = 98 % < 100 %
\\SGTSRV05\D0\ABTL\SGZ\UEBERSET\8125\8125kl_2_Beibl_e.doc
SUPPLEMENTARY SHEET 2
to EC Type Examination Certificate PTB 00 ATEX 3116
Fitting of terminal boxes Type 8125/1051 Max number of conductors
1)
current / A 1,5
3 6 10 16 20 25 35 50 63 80 100 125 75 51 17 7 34 19 9
2,5
25
132 38 21 6 41 16 2 40 13 4
2)
33 15 6
55 17 7 12
4) 3)
75
50
19
18
15
max. number of terminals depending on the above mentioned enclosure size and the cross section resp. max permissible conductor cross section of the builtin terminals
Notes 1) Each incoming conductor and each internal connection wire is counted as a conductor. Bridges and earthing conductors are not counted. 2) additional conductors optional 3) to be specified by the manufacturer (including temperature rise test) 4) When applying the values of this table simultaneous factors or load factors to IEC 439 may be considered. Mixed equipment with circuits of different cross sections and currents is possible if the various values of the table are applied proportionally: Example: (general) cross section / mm 2,5 16 25 current / A 16 50 63 number of conductors 10 (of 30) 12 (of 48) 36 (of 90) total utilization = 33 % = 25 % = 40 % = 98 % < 100 %
\\SGTSRV05\D0\ABTL\SGZ\UEBERSET\8125\8125kl_2_Beibl_e.doc
SUPPLEMENTARY SHEET 3
to EC Type Examination Certificate PTB 00 ATEX 3116
Fitting of terminal boxes Type 8125/1061 Max number of conductors
1)
current / A 1,5
3 6 10 16 20 25 35 50 63 80 100 125 160 105 54 18 7 36 21 10
2,5
25
35
140 40 23 6 44 17 2 43 14 4
2)
35 16 6
58 18 7
65 17 7 10
4) 3)
105
75
38
26
21
17
max. number of terminals depending on the above mentioned enclosure size and the cross section resp. max permissible conductor cross section of the builtin terminals
Notes 1) Each incoming conductor and each internal connection wire is counted as a conductor. Bridges and earthing conductors are not counted. 2) additional conductors optional 3) to be specified by the manufacturer (including temperature rise test) 4) When applying the values of this table simultaneous factors or load factors to IEC 439 may be considered. Mixed equipment with circuits of different cross sections and currents is possible if the various values of the table are applied proportionally: Example: (general) cross section / mm 2,5 16 25 current / A 16 50 63 number of conductors 10 (of 30) 12 (of 48) 36 (of 90) total utilization = 33 % = 25 % = 40 % = 98 % < 100 %
\\SGTSRV05\D0\ABTL\SGZ\UEBERSET\8125\8125kl_2_Beibl_e.doc
SUPPLEMENTARY SHEET 4
to EC Type Examination Certificate PTB 00 ATEX 3116
Fitting of terminal boxes Type 8125/1063 Max number of conductors
1)
current / A 1,5
3 6 10 16 20 25 35 50 63 80 100 125 160 105 71 24 10 47 27 13
2,5
25
35
183 53 30 8 58 22 3 56 18 6
2)
46 21 8
76 24 10
86 22 9 10
4) 3)
105
75
38
26
21
17
max. number of terminals depending on the above mentioned enclosure size and the cross section resp. max permissible conductor cross section of the builtin terminals
Notes 1) Each incoming conductor and each internal connection wire is counted as a conductor. Bridges and earthing conductors are not counted. 2) additional conductors optional 3) to be specified by the manufacturer (including temperature rise test) 4) When applying the values of this table simultaneous factors or load factors to IEC 439 may be considered. Mixed equipment with circuits of different cross sections and currents is possible if the various values of the table are applied proportionally: Example: (general) cross section / mm 2,5 16 25 current / A 16 50 63 number of conductors 10 (of 30) 12 (of 48) 36 (of 90) total utilization = 33 % = 25 % = 40 % = 98 % < 100 %
\\SGTSRV05\D0\ABTL\SGZ\UEBERSET\8125\8125kl_2_Beibl_e.doc
SUPPLEMENTARY SHEET 5
to EC Type Examination Certificate PTB 00 ATEX 3116
Fitting of terminal boxes Type 8125/1071 Max number of conductors
1)
current / A 1,5
3 6 10 16 20 25 35 50 63 80 100 125 160 175 56 19 8 37 22 10
2,5
25
35
146 42 24 7 46 18 2 45 14 5
2)
37 17 6
61 19 8
68 18 7 10
4) 3)
175
112
57
41
33
27
max. Klemmenanzahl in Abhngigkeit von oben genannter Gehusegre und dem Querschnitt bzw. dem max. zul. Leiterquerschnitt der eingebauten Klemmen
Notes 1) Each incoming conductor and each internal connection wire is counted as a conductor. Bridges and earthing conductors are not counted. 2) additional conductors optional 3) to be specified by the manufacturer (including temperature rise test) 4) When applying the values of this table simultaneous factors or load factors to IEC 439 may be considered. Mixed equipment with circuits of different cross sections and currents is possible if the various values of the table are applied proportionally: Example: (general) cross section / mm 2,5 16 25 current / A 16 50 63 number of conductors 10 (of 30) 12 (of 48) 36 (of 90) total utilization = 33 % = 25 % = 40 % = 98 % < 100 %
\\SGTSRV05\D0\ABTL\SGZ\UEBERSET\8125\8125kl_2_Beibl_e.doc
SUPPLEMENTARY SHEET 6
to EC Type Examination Certificate PTB 00 ATEX 3116
Fitting of terminal boxes Type 8125/1073 Max number of conductors
1)
current / A 1,5
3 6 10 16 20 25 35 50 63 80 100 125 160 200 225 250 175 175 112 72 24 10 48 28 13 187 54 30 9
2,5
35
50
70
59 23 3
2) 57 18 6 47 22 8
78 24 10
88 23 9
23 8
20 7 2 7
4) 3)
57
41
33
27
10
max. number of terminals depending on the above mentioned enclosure size and the cross section resp. max permissible conductor cross section of the built-in terminals
Notes 1) Each incoming conductor and each internal connection wire is counted as a conductor. Bridges and earthing conductors are not counted. 2) additional conductors optional 3) to be specified by the manufacturer (including temperature rise test) 4) When applying the values of this table simultaneous factors or load factors to IEC 439 may be considered. Mixed equipment with circuits of different cross sections and currents is possible if the various values of the table are applied proportionally: Example: (general) cross section / mm 2,5 16 25 current / A 16 50 63 number of conductors 10 (of 30) 12 (of 48) 36 (of 90) total utilization = 33 % = 25 % = 40 % = 98 % < 100 %
\\SGTSRV05\D0\ABTL\SGZ\UEBERSET\8125\8125kl_2_Beibl_e.doc
SUPPLEMENTARY SHEET 7
to EC Type Examination Certificate PTB 00 ATEX 3116
Fitting of terminal boxes Type 8125/1075 Max number of conductors
1)
current / A 1,5
3 6 10 16 20 25 35 50 63 80 100 125 160 200 225 250 175 175 112 83 28 11 55 32 15 215 62 35 10
2,5
35
50
70
68 26 4
66 21 7
2) 54 25 9 90 28 12
101 26 10
27 9
23 8 3 7
4) 3)
57
41
33
27
10
max. number of terminals depending on the above mentioned enclosure size and the cross section resp. max permissible conductor cross section of the built-in terminals
Notes 1) Each incoming conductor and each internal connection wire is counted as a conductor. Bridges and earthing conductors are not counted. 2) additional conductors optional 3) to be specified by the manufacturer (including temperature rise test) 4) When applying the values of this table simultaneous factors or load factors to IEC 439 may be considered. Mixed equipment with circuits of different cross sections and currents is possible if the various values of the table are applied proportionally: Example: (general) cross section / mm 2,5 16 25 current / A 16 50 63 number of conductors 10 (of 30) 12 (of 48) 36 (of 90) total utilization = 33 % = 25 % = 40 % = 98 % < 100 %
\\SGTSRV05\D0\ABTL\SGZ\UEBERSET\8125\8125kl_2_Beibl_e.doc
SUPPLEMENTARY SHEET 8
to EC Type Examination Certificate PTB 00 ATEX 3116
Fitting of terminal boxes Type 8125/1081 and Type 8125/1201 Max number of conductors
1)
current / A 1,5
3 6 10 16 20 25 35 50 63 80 100 125 160 392 77 26 11 51 30 14
2,5
25
35
199 58 32 9 63 24 3 61 20 6
2)
50 23 9
83 26 11
93 24 10 22
4) 3)
392
224
126
82
66
54
max. number of terminals depending on the above mentioned enclosure size and the cross section resp. max permissible conductor cross section of the builtin terminals
Notes 1) Each incoming conductor and each internal connection wire is counted as a conductor. Bridges and earthing conductors are not counted. 2) additional conductors optional 3) to be specified by the manufacturer (including temperature rise test) 4) When applying the values of this table simultaneous factors or load factors to IEC 439 may be considered. Mixed equipment with circuits of different cross sections and currents is possible if the various values of the table are applied proportionally: Example: (general) cross section / mm 2,5 16 25 current / A 16 50 63 number of conductors 10 (of 30) 12 (of 48) 36 (of 90) total utilization = 33 % = 25 % = 40 % = 98 % < 100 %
\\SGTSRV05\D0\ABTL\SGZ\UEBERSET\8125\8125kl_2_Beibl_e.doc
SUPPLEMENTARY SHEET 9
to EC Type Examination Certificate PTB 00 ATEX 3116
Fitting of terminal boxes Type 8125/1083 and Type 8125/1203 Max number of conductors
1)
current / A 1,5
3 6 10 16 20 25 35 50 63 80 100 125 160 200 225 250 392 392 224 94 32 13 62 36 17 243 70 40 11
2,5
35
50
70
77 30 4
2) 74 24 8 62 28 11
102 32 13
114 30 12
30 10
27 9 3 15
4) 3)
126
82
66
54
22
15
max. number of terminals depending on the above mentioned enclosure size and the cross section resp. max permissible conductor cross section of the built-in terminals
Notes 1) Each incoming conductor and each internal connection wire is counted as a conductor. Bridges and earthing conductors are not counted. 2) additional conductors optional 3) to be specified by the manufacturer (including temperature rise test) 4) When applying the values of this table simultaneous factors or load factors to IEC 439 may be considered. Mixed equipment with circuits of different cross sections and currents is possible if the various values of the table are applied proportionally: Example: (general) cross section / mm 2,5 16 25 current / A 16 50 63 number of conductors 10 (of 30) 12 (of 48) 36 (of 90) total utilization = 33 % = 25 % = 40 % = 98 % < 100 %
\\SGTSRV05\D0\ABTL\SGZ\UEBERSET\8125\8125kl_2_Beibl_e.doc
S U P P L E M E N T A R Y S H E E T 10
to EC Type Examination Certificate PTB 00 ATEX 3116
Fitting of terminal boxes Type 8125/1085 and Type 8125/1205 Max number of conductors
1)
current / A 1,5
3 6 10 16 20 25 35 50 63 80 100 125 160 200 225 250 392 392 224 105 36 15 70 41 19 272 79 45 13
2,5
35
50
70
86 33 5
2) 84 27 9 69 32 12
114 36 15
128 33 13
34 11
30 10 4 15
4) 3)
126
82
66
54
22
15
max. number of terminals depending on the above mentioned enclosure size and the cross section resp. max permissible conductor cross section of the built-in terminals
Notes 1) Each incoming conductor and each internal connection wire is counted as a conductor. Bridges and earthing conductors are not counted. 2) additional conductors optional 3) to be specified by the manufacturer (including temperature rise test) 4) When applying the values of this table simultaneous factors or load factors to IEC 439 may be considered. Mixed equipment with circuits of different cross sections and currents is possible if the various values of the table are applied proportionally: Example: (general) cross section / mm 2,5 16 25 current / A 16 50 63 number of conductors 10 (of 30) 12 (of 48) 36 (of 90) total utilization = 33 % = 25 % = 40 % = 98 % < 100 %
\\SGTSRV05\D0\ABTL\SGZ\UEBERSET\8125\8125kl_2_Beibl_e.doc
S U P P L E M E N T A R Y S H E E T 11
to EC Type Examination Certificate PTB 00 ATEX 3116
Fitting of terminal boxes Type 8125/1091 Max number of conductors
1)
current / A 1,5
3 6 10 16 20 25 35 50 63 80 100 125 160 819 89 30 12 59 34 16
2,5
25
35
231 67 38 11 73 28 4 71 23 7
2)
59 27 10
97 30 13
108 28 11 66
4) 3)
819
560
294
205
138
114
max. number of terminals depending on the above mentioned enclosure size and the cross section resp. max permissible conductor cross section of the builtin terminals
Notes 1) Each incoming conductor and each internal connection wire is counted as a conductor. Bridges and earthing conductors are not counted. 2) additional conductors optional 3) to be specified by the manufacturer (including temperature rise test) 4) When applying the values of this table simultaneous factors or load factors to IEC 439 may be considered. Mixed equipment with circuits of different cross sections and currents is possible if the various values of the table are applied proportionally: Example: (general) cross section / mm 2,5 16 25 current / A 16 50 63 number of conductors 10 (of 30) 12 (of 48) 36 (of 90) total utilization = 33 % = 25 % = 40 % = 98 % < 100 %
\\SGTSRV05\D0\ABTL\SGZ\UEBERSET\8125\8125kl_2_Beibl_e.doc
S U P P L E M E N T A R Y S H E E T 12
to EC Type Examination Certificate PTB 00 ATEX 3116
Fitting of terminal boxes Type Typ 8125/1093 Max number of conductors
1)
current
A
3 6 10 16 20 25 35 50 63 80 100 125 160 200 225 250 315 400 500
105 36 15
70 41 19
272 79 45 13 86 33 5 84 27 9
69 32 12
2) 114 36 15 128 34 13
34 11
30 10 4
26 15 8
80 31 19 4 40 11 24 5
16 2 7
48 9 7
4) 3)
819
819
560
294
205
138
114
66
32
32
max. number of terminals depending on the above mentioned enclosure size and the cross section resp. max permissible conductor cross section of the built-in terminals
Notes 1) Each incoming conductor and each internal connection wire is counted as a conductor. Bridges and earthing conductors are not counted. 2) additional conductors optional 3) to be specified by the manufacturer (including temperature rise test) 4) When applying the values of this table simultaneous factors or load factors to IEC 439 may be considered. Mixed equipment with circuits of different cross sections and currents is possible if the various values of the table are applied proportionally: Example: (general) cross section / mm 2,5 16 25 current / A 16 50 63 number of conductors 10 (of 30) 12 (of 48) 36 (of 90) total
\\SGTSRV05\D0\ABTL\SGZ\UEBERSET\8125\8125kl_2_Beibl_e.doc
S U P P L E M E N T A R Y S H E E T 13
to EC Type Examination Certificate PTB 00 ATEX 3116
Fitting of terminal boxes Type 8125/1095 Max number of conductors
1)
current
A
3 6 10 16 20 25 35 50 63 80 100 125 160 200 225 250 315 400 500
116 40 16
77 45 21
300 87 49 14 95 37 5 92 30 10
76 35 13
2) 126 39 17 141 37 15
37 13
33 12 4
29 16 8
89 35 21 4 44 12 26 5
18 2 7
53 10 7
4) 3)
819
819
560
294
205
138
114
66
32
32
max. number of terminals depending on the above mentioned enclosure size and the cross section resp. max permissible conductor cross section of the built-in terminals
Notes 1) Each incoming conductor and each internal connection wire is counted as a conductor. Bridges and earthing conductors are not counted. 2) additional conductors optional 3) to be specified by the manufacturer (including temperature rise test) 4) When applying the values of this table simultaneous factors or load factors to IEC 439 may be considered. Mixed equipment with circuits of different cross sections and currents is possible if the various values of the table are applied proportionally: Example: (general) cross section / mm 2,5 16 25 current / A 16 50 63 number of conductors 10 (of 30) 12 (of 48) 36 (of 90) total
\\SGTSRV05\D0\ABTL\SGZ\UEBERSET\8125\8125kl_2_Beibl_e.doc
S U P P L E M E N T A R Y S H E E T 14
to EC Type Examination Certificate PTB 00 ATEX 3116
Fitting of terminal boxes Type 8125/1076 Max number of conductors
1)
current / A 1,5
3 6 10 16 20 25 35 50 63 80 100 125 160 200 225 250 175 175 112 94 32 13 62 36 17 242 70 40 11
2,5
35
50
70
77 30 4
2) 74 24 8 62 28 11
102 32 13
114 30 12
30 10
27 9 3 7
4) 3)
57
41
33
27
10
max. number of terminals depending on the above mentioned enclosure size and the cross section resp. max permissible conductor cross section of the built-in terminals
Notes 1) Each incoming conductor and each internal connection wire is counted as a conductor. Bridges and earthing conductors are not counted. 2) additional conductors optional 3) to be specified by the manufacturer (including temperature rise test) 4) When applying the values of this table simultaneous factors or load factors to IEC 439 may be considered. Mixed equipment with circuits of different cross sections and currents is possible if the various values of the table are applied proportionally: Example: (general) cross section / mm 2,5 16 25 current / A 16 50 63 number of conductors 10 (of 30) 12 (of 48) 36 (of 90) total utilization = 33 % = 25 % = 40 % = 98 % < 100 %
\\SGTSRV05\D0\ABTL\SGZ\UEBERSET\8125\8125kl_2_Beibl_e.doc
S U P P L E M E N T A R Y S H E E T 15
to EC Type Examination Certificate PTB 00 ATEX 3116
Fitting of terminal boxes Type 8125/1106 and Type 8125/1107 Max number of conductors
1)
current / A 1,5
3 6 10 16 20 25 35 50 63 80 100 125 160 200 225 250 245 245 168 104 35 14 69 40 19 268 78 44 13
2,5
35
50
70
85 33 4
2) 82 27 9 68 31 12
112 35 15
126 33 13
33 11
29 10 4 9
4) 3)
84
52
40
34
22
max. number of terminals depending on the above mentioned enclosure size and the cross section resp. max permissible conductor cross section of the built-in terminals
Notes 1) Each incoming conductor and each internal connection wire is counted as a conductor. Bridges and earthing conductors are not counted. 2) additional conductors optional 3) to be specified by the manufacturer (including temperature rise test) 4) When applying the values of this table simultaneous factors or load factors to IEC 439 may be considered. Mixed equipment with circuits of different cross sections and currents is possible if the various values of the table are applied proportionally: Example: (general) cross section / mm 2,5 16 25 current / A 16 50 63 number of conductors 10 (of 30) 12 (of 48) 36 (of 90) total utilization = 33 % = 25 % = 40 % = 98 % < 100 %
\\SGTSRV05\D0\ABTL\SGZ\UEBERSET\8125\8125kl_2_Beibl_e.doc
S U P P L E M E N T A R Y S H E E T 16
to EC Type Examination Certificate PTB 00 ATEX 3116
Fitting of terminal boxes Type 8125/1086, Type 8125/1206, Type 8125/1087 and Type 8125/1207 Max number of conductors
1)
current / A 1,5
3 6 10 16 20 25 35 50 63 80 100 125 160 200 225 250 392 392 224 117 40 16 77 45 21 302 87 49 14
2,5
35
50
70
95 37 5
2) 93 30 10 77 35 13
126 39 17
142 37 15
38 13
33 12 4 15
4) 3)
126
82
66
54
22
15
max. number of terminals depending on the above mentioned enclosure size and the cross section resp. max permissible conductor cross section of the built-in terminals
Notes 1) Each incoming conductor and each internal connection wire is counted as a conductor. Bridges and earthing conductors are not counted. 2) additional conductors optional 3) to be specified by the manufacturer (including temperature rise test) 4) When applying the values of this table simultaneous factors or load factors to IEC 439 may be considered. Mixed equipment with circuits of different cross sections and currents is possible if the various values of the table are applied proportionally: Example: (general) cross section / mm 2,5 16 25 current / A 16 50 63 number of conductors 10 (of 30) 12 (of 48) 36 (of 90) total utilization = 33 % = 25 % = 40 % = 98 % < 100 %
\\SGTSRV05\D0\ABTL\SGZ\UEBERSET\8125\8125kl_2_Beibl_e.doc
S U P P L E M E N T A R Y S H E E T 17
to EC Type Examination Certificate PTB 00 ATEX 3116
Fitting of terminal boxes Type 8125/1256 and Type 8125/1257 Max number of conductors
1)
current / A 1,5
3 6 10 16 20 25 35 50 63 80 100 125 160 200 225 250 322 322 224 112 38 16 74 43 20 288 83 47 14
2,5
35
50
70
91 36 5
2) 89 29 9 73 34 13
121 38 16
135 36 14
36 12
32 11 4 12
4) 3)
126
82
66
44
22
15
max. number of terminals depending on the above mentioned enclosure size and the cross section resp. max permissible conductor cross section of the built-in terminals
Notes 1) Each incoming conductor and each internal connection wire is counted as a conductor. Bridges and earthing conductors are not counted. 2) additional conductors optional 3) to be specified by the manufacturer (including temperature rise test) 4) When applying the values of this table simultaneous factors or load factors to IEC 439 may be considered. Mixed equipment with circuits of different cross sections and currents is possible if the various values of the table are applied proportionally: Example: (general) cross section / mm 2,5 16 25 current / A 16 50 63 number of conductors 10 (of 30) 12 (of 48) 36 (of 90) total utilization = 33 % = 25 % = 40 % = 98 % < 100 %
\\SGTSRV05\D0\ABTL\SGZ\UEBERSET\8125\8125kl_2_Beibl_e.doc
S U P P L E M E N T A R Y S H E E T 18
to EC Type Examination Certificate PTB 00 ATEX 3116
Fitting of terminal boxes Type 8125/1356 and Type 8125/1357 Max number of conductors
1)
current
A
3 6 10 16 20 25 35 50 63 80 100 125 160 200 225 250 315 400 500
115 39 16
76 44 21
297 86 49 14 94 37 5 91 30 10
76 35 13
2) 125 39 16 140 37 15
37 13
33 11 4
28 16 8
88 34 21 4 43 12 26 5
18 2 6
52 10 6
4) 3)
414
414
304
171
110
88
44
36
20
12
max. number of terminals depending on the above mentioned enclosure size and the cross section resp. max permissible conductor cross section of the built-in terminals
Notes 1) Each incoming conductor and each internal connection wire is counted as a conductor. Bridges and earthing conductors are not counted. 2) additional conductors optional 3) to be specified by the manufacturer (including temperature rise test) 4) When applying the values of this table simultaneous factors or load factors to IEC 439 may be considered. Mixed equipment with circuits of different cross sections and currents is possible if the various values of the table are applied proportionally: Example: (general) cross section / mm 2,5 16 25 current / A 16 50 63 number of conductors 10 (of 30) 12 (of 48) 36 (of 90) total
\\SGTSRV05\D0\ABTL\SGZ\UEBERSET\8125\8125kl_2_Beibl_e.doc
S U P P L E M E N T A R Y S H E E T 19
to EC Type Examination Certificate PTB 00 ATEX 3116
Fitting of terminal boxes Type 8125/1306 and Type 8125/1307 Max number of conductors
1)
current
A
3 6 10 16 20 25 35 50 63 80 100 125 160 200 225 250 315 400 500
123 42 17
82 48 22
317 92 52 15 100 39 5 97 32 10
81 37 14
2) 133 41 18 149 39 16
40 13
35 12 4
30 17 9
94 37 22 4 46 13 28 6
19 2 7
56 11 7
4) 3)
532
532
336
210
123
99
74
44
20
20
max. number of terminals depending on the above mentioned enclosure size and the cross section resp. max permissible conductor cross section of the built-in terminals
Notes 1) Each incoming conductor and each internal connection wire is counted as a conductor. Bridges and earthing conductors are not counted. 2) additional conductors optional 3) to be specified by the manufacturer (including temperature rise test) 4) When applying the values of this table simultaneous factors or load factors to IEC 439 may be considered. Mixed equipment with circuits of different cross sections and currents is possible if the various values of the table are applied proportionally: Example: (general) cross section / mm 2,5 16 25 current / A 16 50 63 number of conductors 10 (of 30) 12 (of 48) 36 (of 90) total
\\SGTSRV05\D0\ABTL\SGZ\UEBERSET\8125\8125kl_2_Beibl_e.doc
S U P P L E M E N T A R Y S H E E T 20
to EC Type Examination Certificate PTB 00 ATEX 3116
Fitting of terminal boxes Type 8125/1585 Max number of conductors
1)
current
A
3 6 10 16 20 25 35 50 63 80 100 125 160 200 225 250 315 400 500
131 45 18
87 51 24
86 40 15
2) 142 44 19 2 160 42 17
42 14
37 13 5
32 18 10
100 39 24 5 50 14 30 6
20 3 11
60 12 11
4) 3)
957
957
609
325
252
153
126
68
23
23
14
14
11
11
max. number of terminals depending on the above mentioned enclosure size and the cross section resp. max permissible conductor cross section of the built-in terminals
Notes 1) Each incoming conductor and each internal connection wire is counted as a conductor. Bridges and earthing conductors are not counted. 2) additional conductors optional 3) to be specified by the manufacturer (including temperature rise test) 4) When applying the values of this table simultaneous factors or load factors to IEC 439 may be considered. Mixed equipment with circuits of different cross sections and currents is possible if the various values of the table are applied proportionally: Example: (general) cross section / mm 2,5 16 25 current / A 16 50 63 number of conductors 10 (of 30) 12 (of 48) 36 (of 90) total
\\SGTSRV05\D0\ABTL\SGZ\UEBERSET\8125\8125kl_2_Beibl_e.doc
S U P P L E M E N T A R Y S H E E T 21
to EC Type Examination Certificate PTB 00 ATEX 3116
Fitting of terminal boxes Type 8125/1586 Max number of conductors
1)
current
A
3 6 10 16 20 25 35 50 63 80 100 125 160 200 225 250 315 400 500
143 49 20
95 55 26
94 44 16
2) 155 48 21 2 173 46 18
46 16
41 14 5
35 20 10
109 43 26 5 54 15 32 7
22 3 11
65 13 11
4) 3)
957
957
609
325
252
153
126
68
23
23
14
14
11
11
max. number of terminals depending on the above mentioned enclosure size and the cross section resp. max permissible conductor cross section of the built-in terminals
Notes 1) Each incoming conductor and each internal connection wire is counted as a conductor. Bridges and earthing conductors are not counted. 2) additional conductors optional 3) to be specified by the manufacturer (including temperature rise test) 4) When applying the values of this table simultaneous factors or load factors to IEC 439 may be considered. Mixed equipment with circuits of different cross sections and currents is possible if the various values of the table are applied proportionally: Example: (general) cross section / mm 2,5 16 25 current / A 16 50 63 number of conductors 10 (of 30) 12 (of 48) 36 (of 90) total
\\SGTSRV05\D0\ABTL\SGZ\UEBERSET\8125\8125kl_2_Beibl_e.doc
S U P P L E M E N T A R Y S H E E T 22
to EC Type Examination Certificate PTB 00 ATEX 3116
Fitting of terminal boxes Type 8125/1096, Type 8125/1906, Type 8125/1097 and Type 8125/1907 Max number of conductors
1)
current
A
3 6 10 16 20 25 35 50 63 80 100 125 160 200 225 250 315 400 500
127 43 18
84 49 23
83 39 15
2) 138 43 18 2 154 40 16
41 14
36 13 5
31 18 9
97 38 23 5 48 14 29 6
20 2 7
57 11 7
4) 3)
819
819
560
294
205
138
114
66
32
32
max. number of terminals depending on the above mentioned enclosure size and the cross section resp. max permissible conductor cross section of the built-in terminals
Notes 1) Each incoming conductor and each internal connection wire is counted as a conductor. Bridges and earthing conductors are not counted. 2) additional conductors optional 3) to be specified by the manufacturer (including temperature rise test) 4) When applying the values of this table simultaneous factors or load factors to IEC 439 may be considered. Mixed equipment with circuits of different cross sections and currents is possible if the various values of the table are applied proportionally: Example: (general) cross section / mm 2,5 16 25 current / A 16 50 63 number of conductors 10 (of 30) 12 (of 48) 36 (of 90) total
\\SGTSRV05\D0\ABTL\SGZ\UEBERSET\8125\8125kl_2_Beibl_e.doc
S U P P L E M E N T A R Y S H E E T 23
to EC Type Examination Certificate PTB 00 ATEX 3116
Fitting of terminal boxes Type 8125/1916 and Type 8125/1917 Max number of conductors
1)
current
A
3 6 10 16 20 25 35 50 63 80 100 125 160 200 225 250 315 400 500
170 58 24
113 66 31
111 52 20
2) 184 57 24 2 206 54 22
55 19
48 17 6
52 24 13
129 51 31 6 64 18 38 8
26 3 15
77 15 15
4) 3)
1770
1180 616
430
276
232
138
64
64
20
20
15
15
max. number of terminals depending on the above mentioned enclosure size and the cross section resp. max permissible conductor cross section of the built-in terminals
Notes 1) Each incoming conductor and each internal connection wire is counted as a conductor. Bridges and earthing conductors are not counted. 2) additional conductors optional 3) to be specified by the manufacturer (including temperature rise test) 4) When applying the values of this table simultaneous factors or load factors to IEC 439 may be considered. Mixed equipment with circuits of different cross sections and currents is possible if the various values of the table are applied proportionally: Example: (general) cross section / mm 2,5 16 25 current / A 16 50 63 number of conductors 10 (of 30) 12 (of 48) 36 (of 90) total
\\SGTSRV05\D0\ABTL\SGZ\UEBERSET\8125\8125kl_2_Beibl_e.doc
S U P P L E M E N T A R Y S H E E T 24
to EC Type Examination Certificate PTB 00 ATEX 3116
Fitting of terminal boxes Type 8125/1913 Maximale Anzahl der Leiter 1) in Abhngigkeit vom Querschnitt und dem zulssigen Dauerstrom:
current
A
3 6 10 16 20 25 35 50 63 80 100 125 160 200 225 250 315 400 500
147 50 21
97 57 27
379 110 62 18
120 47 116 7 38 13
96 45 17
2) 159 50 178 21 47 2 19
47 16
42 15 5
36 21 11
112 44 27 5
56 16
33 7
23 3 15
66 13 15
4) 3)
1770
64
64
20
20
15
15
max. number of terminals depending on the above mentioned enclosure size and the cross section resp. max permissible conductor cross section of the built-in terminals
Notes 1) Each incoming conductor and each internal connection wire is counted as a conductor. Bridges and earthing conductors are not counted. 2) additional conductors optional 3) to be specified by the manufacturer (including temperature rise test) 4) When applying the values of this table simultaneous factors or load factors to IEC 439 may be considered. Mixed equipment with circuits of different cross sections and currents is possible if the various values of the table are applied proportionally: Example: (general) cross section / mm 2,5 16 25 current / A 16 50 63 number of conductors 10 (of 30) 12 (of 48) 36 (of 90) total utilization = 33 % = 25 % = 40 % = 98 % < 100 %
K:\sg\sgz\sgz_zert\Uebersetzungen\8125\8125kl_2_Beibl_en.doc