02 MGS2000HV 50Hz 3
02 MGS2000HV 50Hz 3
02 MGS2000HV 50Hz 3
MGS2000HV
50Hz/3.3kV
POWER RATING (0.8 P.F.) MODEL CODE
53S-T83M 53CP-T82M
Prime: Code: CP
Applicable for supplying power with varying load instead of the utility for an unlimited time. Prime power in accordance with ISO 8528.
Conditions:
Engine ratings are based on SAE J1349 standard conditions and also apply at ISO3046/1, DIN6271 & BS5514 standard conditions. Fuel rates: based on ASTM D975, BS2869 and on fuel oil of 35 API (16C or 60 F) gravity having a LHV of 42,780 kJ/kg (18,390 Btu/lb.) when used at 29C (85 F) and weighing 838.9 g/liter (7.001 lbs./U.S. gal.).
Overall dimensions
mm mm mm kg kg
Gross Engine Power* Brake mean effective pressure Regenerative absorption Noise Level at 1 m (excluding: intake, exhaust & fan) Fuel consumption load 100%* Fuel consumption load 75%* Combustion air inlet flow rate Exhaust gas flow rate Exhaust gas temperature Heat rejection to coolant Heat rejection to exhaust Heat rejection to atmosphere from engine Heat rejection to atmosphere from generator * WITH FAN basis. Deration for engine
Mode selection & start engine button with interlock key switch system Menu navigation button LCD display for: AC amperage-each phase and earth current, AC voltage-each phase and neutral, Frequency Hz, Operation hours run, Lub. Oil pressure, Cooling water temperature, Generator Load kW/kVA/kVar, Generator Load kWh/kVAh/kVarh Operation status LED indicators CB control buttons Mute/Lamp test button Voltage adjuster Speed adjuster Emergency stop pushbutton Provided 5 outputs for status as standard equipment (Programmable 8 outputs available as option)
Mounting
Fabricated cubicle mounted on individual bracket with anti-vibration isolator
Electrical Design
In accordance with BS EN 60950 Low Voltage Directive, BS EN 61006-2 and 61006-4 EMC Directive. The optional interface can provide real time diagnostic facilities.
Engine cooling water temperature (C & F) Battery volts Engine hours run Generator Load kW, kVA, kVar Generator Load kWh, kVAh, kVarh Power Factor
Generator high current Over voltage (AC) Under voltage (AC) Over voltage (DC) Under voltage (DC) Auxiliary indication Auxiliary alarm (warning or shutdown) Common alarm Over frequency Under frequency
Visual indication alarm and automatically shutdown High engine temperature Over frequency Low oil pressure Under frequency Fail to start Oil pressure sender open circuit Over-speed Loss of speed signal High voltage High Crankcase internal pressure (MGS-C Continuous only) Low voltage Emergency Stop Operation status indicated by LED Remote start present Generator ready Lubrication oil filter clogged Electrical trip
Pre-Programmed Starting Unit Automatic start/stop sequence timing and delay systems configured via MS-Windows based software.
Winding System
Standard 6 wire winding is provided. All windings are formed wound and impregnated in vacuum pressure with a special epoxy resin. Overspeed capability: 125% for 2 minutes Insulation: Class 'H' of IEC Temperature rise: 150CStand-by Temperature rise: 125CPrime
Voltage Regulator
Fully sealed, 3 phase RMS sensing AVR with built-in protection against sustained over-excitation. This de-excites the generator after a minimum of 5 seconds. Voltage regulation: Less than +/- 0.5% from no load to full load at any power factor between 0.8 lagging and 1.0 allowing for a 4% engine speed variation Voltage adjustment: +/- 6% Wave form: Less than 5% deviation
Sensors
Temperature sensors are provided as follows. Stator winding, 2 per each phase, PT100 Bearing, PT100
Electrical Design
In accordance with BS5000 Part 3, VDE0530, UTE51100, NEMA MG1-22, CEMA, IEC34-1, CSA22.2, AS1359 and JEC2100. Telephone Influence Factor (TIF): Less than 50 Telephone Harmonic factor (THF): Less than 2.5% Radio interference: Suppression is in line with the provision of VDE Class G and N
Power Systems Engine Section, Engine Sales Department 16-5, KONAN 2-CHOME, MINATO-KU, TOKYO 108-8215 JAPAN TEL: 81-3-6716-4771 FAX: 81-3-6716-5854
Mitsubishi Heavy Industries, Ltd. serves for the customers with improved products continually. Therefore specification and some materials will be changed without notice. The International System of units (SI) is used in this publication.