01 MGS2500C 50Hz KT83 PDF
01 MGS2500C 50Hz KT83 PDF
01 MGS2500C 50Hz KT83 PDF
MGS2500C
POWER RATING (0.8 P.F.) MODEL CODE
PRIME 2000 kVA 5CP-KT83
Conditions:
Engine ratings are based on SAE J1349 standard conditions. These ratings also apply at ISO3046/1, DIN6271 and
BS5514 standard conditions.
Fuel rates are based on fuel oil of 35° API (16°C or 60° F) gravity having a LHV of 42,780 kJ/kg (18,390 Btu/lb.)
when used at 29°C (85° F) and weighing 838.9 g/liter (7.001lbs./U.S. gal.).
Note: * Please consult with your nearest Mitsubishi MGS dealer for overload and additional rating requirements.
PRIME
2000 kVA
Overall dimensions L : Length mm 6040
W : Width mm 2395
H : Height mm 3460
Total Weight (Dry) kg 15100
Total Weight (Wet) kg 15800
MGS2500C (1/4)
MITSUBISHI MGS SERIES
DIESEL GENERATOR SET
MGS2500C
Bore mm 170
Stroke mm 180
Displacement L 65.4
Piston speed m/sec. 9.0
Compression ratio 13.5
Lubricating oil capacity L 230
Coolant capacity without radiator L 170
Coolant pump external resistance m water 5.0
Coolant pump flow rate L/min 1650
Cooling fan airflow rate m3/min 2500
Cooling fan air flow restriction kPa 0.1
Ambient air temperature ℃ 40
Allowable exhaust back pressure kPa 6.0
Exhaust flange size (internal diameter) mm 350
PRIME
2000 kVA
Gross Engine Power* kWm 1684
Brake mean effective pressure MPa 2.1
Regenerative absorption kW 140
Noise Level at 1 m dB(A) 111
(excluding: intake, exhaust & fan)
Fuel consumption load 100%* L/hr. 408
Fuel consumption load 75%* L/hr. 310
Combustion air inlet flow rate m3/min 140
Exhaust gas flow rate m3/min 369
Exhaust gas temperature ℃ 550
Heat rejection to coolant kW 528
Heat rejection to exhaust kW 1273
Heat rejection to atmosphere from engine kW 122
Heat rejection to atmosphere from generator kW 54
* WITH FAN basis.
MGS2500C (2/4)
MITSUBISHI MGS SERIES
DIESEL GENERATOR SET
MGS2500C
Mounting
Fabricated cubicle mounted on individual bracket with anti-vibration isolator
Electrical Design
In accordance with BS EN 60950 Low Voltage Directive, BS EN 61006-2 and 61006-4 EMC Directive. The optional
interface can provide real time diagnostic facilities.
MGS2500C (3/4)
MITSUBISHI MGS SERIES
DIESEL GENERATOR SET
MGS2500C
Winding System
Standard 6 wire winding provides 3 phase voltage. All windings are impregnated in vacuum pressure impregnated with a
special polyester resin.
Overspeed capability: 125% for 2 minutes
Insulation: Class 'H' of IEC
Temperature rise: Class 'F'
Voltage Regulator
Fully sealed, 3 phase RMS sensing AVR with built-in protection against sustained over-excitation. This de-excites the
generator after a minimum of 5 seconds.
Voltage regulation: Less than +/- 0.5% from no load to full load at any power factor between 0.8 lagging and 1.0
allowing for a 4% engine speed variation
Voltage adjustment: +/- 6%
Wave form: Less than 5% deviation
Electrical Design
In accordance with BS5000 Part 3, VDE0530, UTE51100, NEMA MG1-22, CEMA, IEC34-1, CSA22.2, AS1359 and
JEC2100.
Telephone Influence Factor (TIF): Less than 50
Telephone Harmonic factor (THF): Less than 2.5%
Radio interference: Suppression is in line with the provision of BS800 and VDE Class G and N
MGS2500C (4/4)