Conventional Detector: Optical Smoke
Conventional Detector: Optical Smoke
Conventional Detector: Optical Smoke
C-9102
548d(cl5) 0832CPD0524
Description
With the technique of scattering, the detector's reliability, stability and consistency are improved. The special chamber design ensures the insert-defend, dirt-defend and anti-light disturbance. The conventional type can be used directly with our conventional fire alarm panels. Using an interface (I-9319), it can be connected to our intelligent panels.
Technical Specifications
Standard: EN54:7 Approval: LPCB, CE-CPD Operating Voltage: 24VDC (12VDC~28VDC) Standby Current: 60A Alarm Current: 10mA I 30mA Indicators: Red. Quiet in normal condition. Illuminates steadily in alarm. Remote Indicator Output: Directly connecting with LED (built-in 2k resistor in series). Quiet in normal condition. Illuminates steadily in alarm. Maximum Ripple Voltage: 4V (peak-to-peak) Alarm Clear: Instantaneous Power-off (5s Max., 2.5VDC Max.) Power-up Time: 10s Max. Wind Speed: 7.6m/s (1500fpm) Wiring: Polarized 2-core for detection zone Cable. Ambient temperature: -10+50 Relative Humidity: 95%, non condensing Ingress Protection Rate: IP23 Material and Color of Enclosure: ABS, white (RAL 9016) Dimensions: Diameter: 100mm Height: 56mm (with base) Mounting Hole Distance: 45mm75mm Weight: About 120g
Wiring and Connection
1.When the detector is connected with conventional fire alarm control panel or I-9319 addressable zone monitor unit in series, if a P-9907 AEOL is connected to the end of output loop, a 1N5819 Diode should be connected to the detector base. Used as the detector base, the AEOL is to install a conventional detector on it. The system connection is shown below:
I-9319 Addressable Zone Monitor Unit
Diode
Diode
Output+
+
Output-
Conventional MCP
P-9907 AEOL
When the AEOL is not used as the detector base, a cover should be added, the system connection is shown below:
I-9319 Addressable Zone Monitor Unit
Diode
Output-
Conventional MCP
P-9907 AEOL
2. When the detector is connected with conventional fire alarm control panel (those within the dotted line are equivalent to a conventional fire alarm control panel) or I-9319 Addressable zone monitor unit in series, if an end of line resistor is connected to the end of output loop, then no diode is connected to the detector base. The system connection is shown below:
I-9319 Addressable Zone Monitor Unit Fire Alarm Control Panel
Output+
+
Output-
Remote Indicator Remote Indicator Conventional MCP Conventional Detector Conventional Detector
Maximum 15 detectors can be connected in one zone. Cooperating with end of line device, the compatible panel can monitor the cable for open circuit and short circuit. Panel will report if any detector is removed. With the AEOL, the functioning of other device will not be affected by the detector removal.
Accessories
Part Number: DZ-03 Description: Detector Base - EOLR Weight / Kg.: 0.05 Pack Qty. per Box: 300 Part Number: DZ-03D Description: Base with Diode AOL Weight / Kg.: 0.05 Pack Qty. per Box: 300
Ordering Information
Part Number:C-9102 Description: Conventional Optical Smoke Detector Weight / Kg.: 0.123 Pack Qty. per Box: 100
4.7k Resistor
MANUFACTUREDINACCORDANCEWITH