Acwc 150 e DR
Acwc 150 e DR
Acwc 150 e DR
Description:
Two stage air-cooled portable water chiller system. System capacity indicated on table is the approximate BTU/hr
based on a leaving fluid temperature of 50°F with an ambient air temperature of 95°F.
STANDARD FEATURES:
• Controls: Electronic programmed temperature controller with constant (set point & process) temperature
readout.
• Refrigeration Components: Efficient scroll compressors, sight glass/moisture indicators, balanced port
expansion valves, filter drier, pump down valves, fan cycling head pressure controls.
• Process Fluid Components: Bronze “Y” strainer with 20 mesh stainless steel screen. Pumps are stainless steel
centrifugal. Tanks are insulated with shoe box lid, fill port, and level sight glass. Portable systems will include a
bypass flow valve.
• Safety Controls: High and low refrigerant pressure, high and low fluid temperature, freeze, low water flow,
overloads for compressor and fan motors, safety fuses or overloads for pump.
• Construction: Welded steel powder coated frame and full metal cabinet, copper piping connections.
• Warranty: One year parts / five year compressor.
1
Flow Design (_=Portable, ST=Stationary, RF=Reverse Flow, EXCH=Extra Heat Exchanger, DP=Dual Pump, DR=Dual Return)
2
Leaving Fluid Temperature (_=Standard, LT=Low Temperature-specify lowest temperature in °F)
3
Ambient Temperature Conditions (see above)
4
Electrical Power Code (see above)
TechSpec_ACWC-150-E-_-_-_-_(0620).docx
Performance Curve and Data Sheet
PUOD-180-002-0-0
2Hp/3Ø Motor ODP/ Pump with 5.0”Impeller and 0.240”Vane at 3500rpm
&2/'6+27&+,//(560DUURQH &R,QF
0D[LPLOLDQ'ULYH+RXVWRQ7H[DV3KRQH
)D[ ZZZZDWHUFKLOOHUVFRP
DATA_PUOD-180-002-0-0 (0414) .doc
FRONT RIGHT SIDE
Temperature Controller
Control Panel
PUMP OFF COOL
Power Switch
High Pressure
Reset
"Y" Strainer
(INSIDE)
"Y" Strainer
(INSIDE)
Primary Inlet
(MNPT) Capped
Secondary Inlet (MNPT)
Coating
Optional
to tank 18.75in.
Outlet
NPT-MALE
14.00in.
3.25 3.25
Chiller Pump
(INSIDE)
70.0in.
Tank Level
Insulated Stainless
Sightglass
Steel Tank
73.5in.
Condenser Fans
TOP
39.5in.
NOTES
- Unit should be installed with at least 4' clearance on all sides and a
minimum of 8' clear air space above the unit
- Dimensions are approximate. (inches)
- Casters (Optional)
- All specifications subject to change without notice.
Refrigerant
STRAINER
Fluid
MANUAL
BYPASS
TANK
EVAPORATOR
PROCESS
Line Guide
STRAINER CHILLER/PROCESS
TEMPERATURE
CONTROLLER SENSOR PUMP
COLD CHILLED FLUID
HOT FLUID
COLD FLUID
WARM FLUID
NOTES
DRAWN ENGINEERING
A -See uppercomponents
Additional Note list may be included.
- Evaporator may be located in tank.
Typical FLOW OPTIONS for Chiller Circuits 1