Rooftop Package Technical Sales Guide

Model GK-C13TC1AF GK-C15TC1AF GK-C15TC1AF GK-C20TC1AF GK-C25TC1AF


kW 44 50 50 70 87.5
Total Capacity Cooling
ton 13 15 15 20 25
EER/C.O.P. Btu/W 8 8 8 8 8
Power supply V-Hz-Ph 220V-60Hz-3Ph
Rated Power
Electrical Cooling kW 32 32 29 34 54
input2
Data 2
Rated current Cooling A 88 88 88 120 190
Min/Max Voltage V 198/242 198/242 198/242 198/242 198/242
Sound Pressure Level (H/M/L)* dB (A) 75 75 75 78 81
Type - R22
Refrigerant
Throttling Method - Thermal Expansion Valve Capilary Thermal Expansion Valve
CFM 5900 5900 5900 8260 10324
Air Flow Volume
m3/h 10000 10000 10000 14000 17500
Pa 200 200 200 200 250
External Static Pressure Rated
InWg 0.8 0.8 0.8 0.8 1
Dehumidifying Volume l/h 15.6 15.6 15.6 15.6 26
Drive Type - Belt
Fan motor
Power Output Hp 7 7 7 7 10
Type - Centrifugal fan
Fan
Quantity - 1 1 1 1 1
Evaporator Material - Aluminum fin-copper tube
Side sq.ft 13.45 13.45 13.45 20.5 20.5
Face Area
Evaporator m2 1.25 1.25 1.25 1.9 1.9
Fins per
- 14 14 14 14 14
Inch(FPI)
Drain Connection Size Inch 3/4 3/4 3/4 1 1
Trademark - Danfoss Copeland Danfoss
Compressor Type - Scroll
Quantity - 2 2 2 2 2
Drive Type - Direct
Fan motor
Power Output Hp 1 1 1 2.4 2.4
Condenser Type - Axial fan
Fan
Side Quantity - 2 2 2 2 2
Material - Aluminum fin-copper tube
sq.ft 26.16 26.16 26.16 34.11 34.11
Face Area
Condenser m2 2.43 2.43 2.43 3.17 3.17
Fins per
- 16 16 16 14 14
Inch(FPI)
Permissible Excessive Operating
Mpa 3 3 3 3 3
Pressure for the Discharge Side
Permissible Excessive Operating
Mpa 0.9 0.9 0.9 0.9 0.9
Pressure for the Suction Side
Operation temp Cooling ℃ 21~52 21~52 21~52 21~52 21~52
Filter Size/NO. Used mm 455X1000/2 455X1000/2 455X1000/2 840X582/4 840X582/4
Isolation - Ⅰ Ⅰ Ⅰ Ⅰ Ⅰ
Moisture Protection - IP24 IP24 IP24 IP24 IP24
Outline dimension (WXDXH) mm 2205X1610X1190 2870X2120X1375
Dimension Package dimension
mm 2245X1640X1225 2950X2198X1555
(WXDXH)
Net weight Kg 640 640 640 1005 1049
Weight
Gross weight Kg 679 679 679 1170 1214
20'GP 3 3 3 1 1
Loading quantity 40'GP 7 7 7 4 4
40'HQ 14 14 14 4 4

9
Rooftop Package Technical Sales Guide

5.2 Electrical Data


Condenser
Unit main power Applicable  Compressor motor Evaporator fan Auxiliary
Model fan
VOL  Hz  Ph  Max. Min. STC RNC IPT RNC IPT RNC IPT IPT

GK-C03TC1AD 220 60 1 242 198 136 18 3.6 2.0 0.19 2.1 0.245 5/10*

GK-C04TC1AF 220 60 3 242 198 115 14.1 4.45 3.4 515 2.1 0.245 5/10*

GK-C05TC1AF 220 60 3 242 198 134 17.5 5.55 3.4 515 2.1 0.245 5/10*

GK-C08TC1AF 220 60 3 242 198 134 16.4 5.1 8.98 2.2 2.1 0.245 10/15/20*

GK-C10TC1AF 220 60 3 242 198 134 20.5 5.55 8.98 2.2 2.1 0.245 10/15/20*

GK-C13TC1AF 220 60 3 242 198 195 27.1 7.689 20.38 5.5 3.8 0.65 10/15/20*

GK-C15TC1AF 220 60 3 242 198 195 27.1 8.393 20.38 5.5 3.8 0.65 20/25/30*

GK-C20TC1AF 220 60 3 242 198 267 36.4 10.597 20.38 5.5 8.4 1.8 20/25/30*

GK-C25TC1AF 220 60 3 242 198 255 45.7 14.065 20.38 5.5 8.4 1.8 20/25/30*

GK-C03TC1AK 220 50 1 242 198 116 17 3.7 3.7 0.36 1.9 0.3 5/10*

GK-C04TC1AM 380-415 50 3 456 342 73 8.06 4.3 3.7 0.36 1.9 0.3 5/10*
63- 9.4-
GK-C05TC1AM 380-415 50 3 456 342 5.45 4.6 0.735 1.9 0.3 5/10*
69 9.7
GK-C08TC1AM 380-415 50 3 456 342 73 8.9 4.9 5.16 2.2 1.9 0.3 10/15/20*
63- 9.4-
GK-C10TC1AM 380-415 50 3 456 342 5.45 5.16 2.2 1.9 0.3 10/15/20*
69 9.7
GK-C15TC1AM 380-415 50 3 456 342 142 17.9 8.752 11.8 5.5 1.6 0.55 20/25/30*

GK-C20TC1AM 380-415 50 3 456 342 147 19.3 10.081 11.8 5.5 5.0 1.8 20/25/30*

GK-C25TC1AM 380-415 50 3 456 342 175 35 13.624 15.6 7.5 5.0 1.8 20/25/30*

GK-C30TC1AM 380 50 3 412 342 175 35 13.624 15.6 7.5 5.0 1.8 20/25/30*

GK-H05TC1AM 380-415 50 3 456 342 73 9.4 5.35 3.26 0.33 1.9 0.3 /

GK-H08TC1AM 380-415 50 3 456 342 73 8.9 4.9 5.16 2.2 1.9 0.3 /

GK-H15TC1AM 380-415 50 3 456 342 142 17.9 8.013 11.2 5.5 2.1 0.75 /

Note:
VOL:Unit Power Supply Rated(plated) Voltage(V)
Hz:Frequency(Hz)
STC:Staring Current(A)
RNC:Running Current(A)
IPT:Input(kW)
These data are based on the following conditions:Evaporator Air Input Temperature 85F DB,66F WB.
Condenser Air Input Temperature 115F DB.
The starting current is indicated for each compressor motor.
The maximum currents of the compressor can be estimated as follows.
One compressor unit Two compressor unit
Max.current RNC×Max.IPT/IPT RNC×Max.IPT/IPT
Max.instantaneous current STC STC+RNC×0.5×Max.IPT/IPT
Max.IPT:Compressor power input from the performance table at the expected maximum condition.
STC,IPT,RNC:Compressor data from the above table.
The data in the compressor motor column shall indicate the respective values of the refrigeration cycle.

11
GK-C20TC1AF,GK-C20TC1AM
Evaporator Airflow
Condenser Entering Air 12500m3/h 13500m3/h 14500m3/h
Temp. (℃ ) Evaporator Entering Air, WBE(℃ )
16 19 22 16 19 22 16 19 22
TC(kW) 58.00 66.66 68.99 65.16 74.90 77.52 69.07 79.39 82.17
29 SC(kW) 42.34 48.66 50.37 47.57 54.68 56.59 50.42 57.96 59.99
kW 23.51 24.49 25.23 24.36 25.38 26.14 26.07 27.16 27.97
TC(kW) 54.20 62.30 64.48 60.90 70.00 72.45 64.55 74.20 76.80
35 SC(kW) 40.38 46.41 48.04 45.37 52.15 53.98 48.09 55.28 57.21
kW 25.01 26.06 26.84 25.92 27.00 27.81 27.73 28.89 29.76
TC(kW) 50.14 57.63 59.64 56.33 64.75 67.02 59.71 68.64 71.04
40 SC(kW) 37.60 43.22 44.73 42.25 48.56 50.26 44.78 51.48 53.28
kW 26.51 27.62 28.45 27.48 28.62 29.48 29.40 30.62 31.54
TC(kW) 46.13 53.02 54.87 51.83 59.57 61.65 54.94 63.14 65.35
46 SC(kW) 35.06 40.29 41.70 39.39 45.27 46.86 41.75 47.99 49.67
kW 28.50 29.69 30.58 29.54 30.77 31.69 31.60 32.92 33.91
TC(kW) 41.97 48.25 49.93 47.16 54.21 56.11 49.99 57.46 59.47
52 SC(kW) 32.11 36.91 38.20 36.08 41.47 42.92 38.24 43.96 45.50
kW 31.07 32.36 33.33 32.19 33.54 34.54 34.45 35.88 36.96

Evaporator Airflow
Condenser Entering Air 7361CFM 7950CFM 8539CFM
Temp. ( ℉ ) Evaporator Entering Air, WBE( ℉ )
61 67 72 62 67 72 62 67 72
TC(MBH) 198.84 228.55 236.55 223.42 256.80 265.79 236.82 272.21 281.74
85 SC(MBH) 145.15 166.84 172.68 163.09 187.46 194.03 172.88 198.71 205.67
kW 23.51 24.49 25.23 24.36 25.38 26.14 26.07 27.16 27.97
TC(MBH) 185.83 213.60 221.08 208.80 240.00 248.40 221.33 254.40 263.30
95 SC(MBH) 138.44 159.13 164.70 155.56 178.80 185.06 164.89 189.53 196.16
kW 25.01 26.06 26.84 25.92 27.00 27.81 27.73 28.89 29.76
TC(MBH) 171.89 197.58 204.50 193.14 222.00 229.77 204.73 235.32 243.56
105 SC(MBH) 128.92 148.19 153.37 144.86 166.50 172.33 153.55 176.49 182.67
kW 26.51 27.62 28.45 27.48 28.62 29.48 29.40 30.62 31.54
TC(MBH) 158.14 181.77 188.14 177.69 204.24 211.39 188.35 216.49 224.07
115 SC(MBH) 120.19 138.15 142.98 135.04 155.22 160.66 143.15 164.54 170.29
kW 28.50 29.69 30.58 29.54 30.77 31.69 31.60 32.92 33.91
TC(MBH) 143.91 165.41 171.20 161.70 185.86 192.36 171.40 197.01 203.91
125 SC(MBH) 110.09 126.54 130.97 123.70 142.18 147.16 131.12 150.71 155.99
kW 31.07 32.36 33.33 32.19 33.54 34.54 34.45 35.88 36.96

Note:
TC-Total Capacity
SC-Sensible Heat Capacity
kW-Total unit power input
DBE-Dry Bulb Temp. of Air Entering Coil
WBE-Wet Bulb Temp. of Air Entering Coil
DR-Wet Bulb depression ratio(0.25~0.3)
Capacities above are based on DBE=81 ℉ (27℃ ). For higher or lower DBE, add following
Correction Factor to Sensible Capacity=1.08×CFM(1-DR)(DBE-81)

18
Model:13&15Ton
Parameter table for indoor unit air volume
External static pressure(Pa) 0 50 100 150 200 250 300
Air volume(m3/h) 10801 10557 10312 10058 9802 9540 9285
Cure diagram of static pressure, air flow volume

10800

10600

10400
Air volume(m3/h)

10200

10000

9800

9600

9400

9200
0 50 100 150 200 250 300
External static pressure(Pa)

Model:20Ton
Parameter table for indoor unit air volume
External static pressure(Pa) 0 50 100 150 200 250 300
Air volume(m3/h) 14370 14121 13886 13610 13388 13050 12753
Cure diagram of static pressure, air flow volume

14500
14300

14100
13900
Air volume(m3/h)

13700

13500

13300

13100

12900

12700

12500
0 50 100 150 200 250 300
External static pressure(Pa)

26
8 DIMENSION
Physical Dimension

B C B C

A
A

D
3~5Ton 8~15Ton 20~30Ton

Dimension(mm) 3 Ton,4 Ton 5 Ton 8 Ton,10 Ton 13 Ton,15 Ton 20 Ton,25 Ton,30on
A 640 790 1117 1190 1357
B 1055 1055 2006 2205 2870
C 1345 1345 1436 1610 2120
D 75 75 90 88 95

Horizonta l Sid e
OP Q R O P Q R
Horizonta l
Side

Retur n

U
Return
U

S
S

Suppl y
Supply
T

V
V

3~15Ton 20~30Ton

Dimension(mm) 3 Ton,4 Ton 5 Ton 8 Ton,10 Ton 13 Ton,15 Ton 20 Ton,25 Ton,30on
O 73 73 203 208 1083
P 400 400 460 460 765
Q 260 260 275 360 525
R 75 75 122 120 92
S 300 300 443 443 660
T 105 105 165 165 150
U 475 475 815 900 1130
V 104 104 175 170 150
Note: Above diagrams may be different from actual model.

32
Rooftop Package Technical Sales Guide

Bottom Botto m E F

G
Supply Suppl y

H
Y
Return

I
N Retur n

J
K L M
X W
3~5Ton 8~15Ton

Bottom
E F J K
G

L
Supply
H

Retur n
Y

X W
20~30Ton

Dimension(mm) 3 Ton,4 Ton 5 Ton 8 Ton,10 Ton 13 Ton,15 Ton 20 Ton,25 Ton,30on
E 400 400 443 443 1143
F 87 87 110 117 660
G 130 130 219 230 150
H 300 300 430 430 765
I 260 260 275 360 73
J 82 82 98 127 525
K 48 48 95 150 100
L 475 475 815 900 290
M 87 87 113 87 1500
N 50 50 50 50 55
W 312 312 215 152 1300
X 720 720 1570 1900 970
Y 1010 1010 1394 1564 2068
Z 16 16 14 14 14
Note: Above diagrams may be different from actual model.

33
9 WIRED CONTROLLER

9.1 Standard unit with Gree’s wired controlled:(Model WK010WA1)

Wiring terminal of the wired controller


THERMOSTAT TERMINALS (HEAT PUMP)
SYSTEM Heat Pump 1 Heat Pump 2
L Malfunction
C 24 Volt(Common)
R 24 Volt Emergency (hot)
E/W1 Emergency Mode 1st stage
W2 HP 1 and Emergency 2nd stage
Y1 Heat and Cool mode 1st stage (compressor)
Y2 No output 2nd stage compressor
G Blower/Fan Energized on call for Heat and Cool
O Energized in Cool Mode

Wiring diagram of the wired controller

o
THERMOSTAT
Y1 Y2 G W1 W2 C R SYSTEM

Reversing Compressor
Valve Contactor Heat Relay
Energized in Stage2 Stage1
Cool Mode
Hot

24 VAC 120 VAC


Compressor
Contactor Fan Relay Heat Relay
Stage1 Stage2
TRANSFORMER
(Class Current Limited)

34
Rooftop Package Technical Sales Guide

9.2 Digital Thermostat Owners Manual


1

4
5

6
7

No. Key Description


1 Enter It is intended to save the set parameter value and back to the home page.
2 Fan It is intended to control and select the running mode of the fan.
It is intended to access to the setting page of temperature, time, timer, memory function,
3 Set
unit, compressor delay protection function, default setting, etc.
4 Cancel It is intended to quit the current page and back to the home page.
It is intended to prevent the set temperature changing as the change of the timed
5 Hold
period.
6 Arrow Up & Down It is intended to set the parameter value.
It is intended to set the running mode of the unit. For the cooling only unit, there are
three modes, OFF , AS-HEAT, and COOL,For the cooling and heating unit, there are four
7 System
modes, OFF, AS-HEAT, HEAT, and COOL, which can be selected by pressing the “System”
button.

10 GUIDE SPECIFICATIONS
General Description
Units shall be factory-assembled, single packaged, Electric Cooling units, designed for outdoor mounted
installation.
The units shall be factory wired, piped, charged with R22 refrigerant and factory tested prior to shipment. All
unit wiring shall be both numbered and color-coded. All units shall be manufactured in a facility certified to
ISO 9001 standards, and the cooling performance shall be tested in accordance with SASO 2682-2007 test
procedures.
Unit Cabinet
Unit cabinet shall be constructed of galvanized steel, with exterior surfaces coated with a non-chalking,
powder paint finish
Unit shall have a rigidly mounted condenser coil guard to provide protection from objects and personnel
after installation.
Cabinet panels shall be “large” size, easily removable for servicing and maintenance, with built-in lift
handles.
Filters shall be furnished and be accessible through a removable access panel, sealed.