Model GQR112 Series Sprinklers

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

Availability: APAC Bulletin 081 February 2024

Model GQR112 Series Sprinklers


Storage and Non-Storage Sprinklers
K11.2 (160 metric)

Product Description
Reliable Model GQR112 upright and pendent sprinklers are
standard coverage quick-response sprinklers that utilize a
sensitive 3mm glass bulb thermal element. These sprinklers
are intended for use in hydraulically calculated control mode
density area (CMDA) storage and non-storage occupancies in
accordance with the requirements of NFPA 13 or other applicable
standards.

The Model GQR112 sprinkler is FM Approved as a quick-


response storage and non-storage sprinkler when used in
accordance with FM Global Property Loss Prevention Data
Sheets.

The Model GQR112 is rated for a maximum working pressure Upright Pendent
of 175 psi (12 bar) and is available with either 3/4” NPT or ISO
Model GQR112 Series Sprinklers
7-R3/4 threads. Sprinklers without guards are installed using the
Reliable Model H wrench.

For use as an intermediate level sprinkler, the Model GQR112


upright sprinkler is available with a factory installed water shield.
Various other water shields, guards, or guard/shield options are
also available for both upright and pendent models (please refer
to Technical Specifications on following pages). Sprinkler guards
or guard/shields may be installed in the field or factory installed.
Use of the Reliable Model W15 sprinkler wrench is required
for installation where a guard is added to the sprinkler prior to
threading the assembly into a fitting.

Table A below provides a summary of the key data and approvals


for the Model GQR112 sprinkler. Additional technical information
is found on the following pages.
Upright with Factory Installed Shield
(Intermediate Upright)

Model GQR112 Sprinkler Summary Table A

Sprinkler Identification Listings and


Style Sensitivity K-Factor
Number (SIN) Approvals

Upright
R606
Upright Intermediate 11.2
FM Quick Reponse
(160 metric)
Pendent R605

www.reliablesprinkler.com
Model GQR112 Upright Sprinkler SIN R606
Technical Specifications Sensitivity
Style: Upright, Intermediate Upright Quick Response
Threads: 3/4” NPT or ISO 7-1R3/4
Nominal K-Factor: 11.2 (160 metric) Temperature Ratings
Max. Working Pressure: 175 psi (12 bar) 155°F (68°C)
200°F (93°C)
Material Specifications 286°F (141°C)
Thermal Sensor: 3mm Glass Bulb
Sprinkler Frame: Brass Alloy Guards & Shields
Button/Cup: Bronze Alloy D-7 Guard & Water Shield
Sealing Assembly: Brass with PTFE D-8 Guard
Load Screw: Brass Alloy Water Shield (factory installed)
Deflector: Bronze Alloy
Kick Spring: Stainless Steel Sprinkler Wrenches
Model H (without guard)
Sprinkler Finishes Model W15 (with guard)
Bronze
Chrome Listings and Approvals
Electroless Nickel PTFE(1) FM Approved

Notes:
1. FM Approved as corrosion resistant.

Model GQR112 Upright Components and Dimensions Figure 1

Bulletin 081 Page 2 of 5


February 2024 www.reliablesprinkler.com
Model GQR112 Pendent Sprinkler SIN R605
Sensitivity
Technical Specifications
Quick Response
Style: Pendent
Threads: 3/4” NPT or ISO 7-1R3/4
Temperature Ratings
Nominal K-Factor: 11.2 (160 metric)
155°F (68°C)
Max. Working Pressure: 175 psi (12 bar)
200°F (93°C)
286°F (141°C)
Material Specifications
Thermal Sensor: 3mm Glass Bulb
Guards & Shields
Sprinkler Frame: Brass Alloy
D-8 Guard
Button/Cup: Bronze Alloy
D-9 Guard & Water Shield
Sealing Assembly: Brass with PTFE
Load Screw: Brass Alloy S-2 Water Shield
Deflector: Bronze Alloy
Sprinkler Wrenches
Kick Spring: Stainless Steel
Model H (without guard)
Model W15 (with guard)
Sprinkler Finishes
Bronze
Listings and Approvals
Chrome
FM Approved
Electroless Nickel PTFE(1)

Notes:
1. FM Approved as corrosion resistant.

Model GQR112 Pendent Components and Dimensions Figure 2

Bulletin 081 Page 3 of 5


February 2024 www.reliablesprinkler.com
Model GQR112 Commodity Selection and Design Criteria Overview Table B

Storage Type NFPA FM GLOBAL

Sprinkler Type CMDA Storage


Response Type QR QR
Pendent - Wet Pendent - Wet
System Type
Upright - Wet, Dry, Preaction Upright - Wet, Dry, Preaction
Temperature Rating °F (°C) 155, 200, 286 (68, 93, 141) 155, 200, 286 (68, 93, 141)
Roof Construction See NFPA 13 See FM Global 2-0
Ceiling Slope See NFPA 13 See FM Global 2-0
Maximum Coverage Area See NFPA 13 See FM Global 2-0
Minimum Coverage Area See NFPA 13 See FM Global 2-0
Maximum Spacing See NFPA 13 See FM Global 2-0
Minimum Spacing See NFPA 13 See FM Global 2-0
Minimum Clearance to Commodity See NFPA 13 See FM Global 2-0
Sprinkler Distance to Ceiling See NFPA 13 See FM Global 2-0
Open Frame, Single, Double, Multiple
Row, or Portable Rack Storage of Class See NFPA 13 See FM 2-0 & 8-9
I - IV Commodity and Group A Plastic
Solid Pile or Palletized Storage of Class
See NFPA 13 See FM 2-0 & 8-9
I - IV Commodity and Group A Plastic
Idle Pallet Storage See NFPA 13 See FM 2-0, 8-9 & 8-24
Rubber Tire Storage See NFPA 13 See FM 8-3
See FM 8-21
Rolled Paper Storage See NFPA 13
Pendent Only
Flammable Liquid Storage See NFPA 30 See FM 7-29 and 8-9
Aerosol Storage See NFPA 13 See FM 7-31
Auto Components in Portable Racks See NFPA 13 See FM 2-0 and 8-9

Bulletin 081 Page 4 of 5


February 2024 www.reliablesprinkler.com
Installation Guarantee
Model GQR112 sprinklers must be installed according to For the Reliable Automatic Sprinkler Co., Inc. guarantee, terms, and
appropriate NFPA Standards, FM Global Loss Prevention conditions, visit www.reliablesprinkler.com.
Data Sheets, and/or the requirements of the authority having
jurisdiction using the Reliable installation wrench identified in this
bulletin. Any other type of wrench may damage the sprinkler. Ordering Information
Damaged sprinklers must be replaced immediately.
Specify the following when ordering.
A leak tight joint should be obtained with a torque of 14 to 20 lb-ft
Model GQR112 Sprinkler
(19 to 27 N.m) for 3/4 inch NPT and ISO 7-R3/4 thread sprinklers
• Upright
after applying an appropriate thread sealant. Exceeding
• Intermediate Upright
the maximum recommended torque may cause leakage or
• Pendent
impairment of the sprinklers.
Threads
Wrenches Figure 3 • 3/4” NPT
• ISO 7-R3/4

Temperature Rating
• 155°F (68°C)
• 200°F (93°C)
Model H Wrench (sprinkler) • 286°F (141°C)

Finish
• Bronze
• Chrome
• Electroless Nickel PTFE

Wrench
Model W15 Wrench (with guard installed) • Model H (without guard)
• Model W15 (with guard installed)

Maintenance
Reliable Model GQR112 sprinklers should be inspected and the
sprinkler system maintained in accordance with NFPA
25, as well as the requirements of any Authorities Having
Jurisdiction.

Prior to installation, sprinklers should remain in the original


cartons and packaging until used. This will minimize the potential
for damage to sprinklers that could cause improper operation or
non-operation.

Do not clean sprinklers with soap and water, ammonia liquid or


any other cleaning fluids. Remove dust by gentle vacuuming
without touching the sprinkler.

Replace any sprinkler which has been painted (other than factory
applied). A stock of spare sprinklers should be maintained to
allow quick replacement of damaged or operated sprinklers.

Failure to properly maintain sprinklers may result in inadvertent


operation or non-operation during a fire event.
P/N 99999XXXXX

Bulletin 081 Page 5 of 5


February 2024 www.reliablesprinkler.com