Model GQR112 Series Sprinklers
Model GQR112 Series Sprinklers
Model GQR112 Series Sprinklers
Product Description
Reliable Model GQR112 upright and pendent sprinklers are
standard coverage quick-response sprinklers that utilize a
sensitive 3mm glass bulb thermal element. These sprinklers
are intended for use in hydraulically calculated control mode
density area (CMDA) storage and non-storage occupancies in
accordance with the requirements of NFPA 13 or other applicable
standards.
The Model GQR112 is rated for a maximum working pressure Upright Pendent
of 175 psi (12 bar) and is available with either 3/4” NPT or ISO
Model GQR112 Series Sprinklers
7-R3/4 threads. Sprinklers without guards are installed using the
Reliable Model H wrench.
Upright
R606
Upright Intermediate 11.2
FM Quick Reponse
(160 metric)
Pendent R605
www.reliablesprinkler.com
Model GQR112 Upright Sprinkler SIN R606
Technical Specifications Sensitivity
Style: Upright, Intermediate Upright Quick Response
Threads: 3/4” NPT or ISO 7-1R3/4
Nominal K-Factor: 11.2 (160 metric) Temperature Ratings
Max. Working Pressure: 175 psi (12 bar) 155°F (68°C)
200°F (93°C)
Material Specifications 286°F (141°C)
Thermal Sensor: 3mm Glass Bulb
Sprinkler Frame: Brass Alloy Guards & Shields
Button/Cup: Bronze Alloy D-7 Guard & Water Shield
Sealing Assembly: Brass with PTFE D-8 Guard
Load Screw: Brass Alloy Water Shield (factory installed)
Deflector: Bronze Alloy
Kick Spring: Stainless Steel Sprinkler Wrenches
Model H (without guard)
Sprinkler Finishes Model W15 (with guard)
Bronze
Chrome Listings and Approvals
Electroless Nickel PTFE(1) FM Approved
Notes:
1. FM Approved as corrosion resistant.
Notes:
1. FM Approved as corrosion resistant.
Temperature Rating
• 155°F (68°C)
• 200°F (93°C)
Model H Wrench (sprinkler) • 286°F (141°C)
Finish
• Bronze
• Chrome
• Electroless Nickel PTFE
Wrench
Model W15 Wrench (with guard installed) • Model H (without guard)
• Model W15 (with guard installed)
Maintenance
Reliable Model GQR112 sprinklers should be inspected and the
sprinkler system maintained in accordance with NFPA
25, as well as the requirements of any Authorities Having
Jurisdiction.
Replace any sprinkler which has been painted (other than factory
applied). A stock of spare sprinklers should be maintained to
allow quick replacement of damaged or operated sprinklers.