Reliable Sprinkler Product Services Bulletin 71
Reliable Sprinkler Product Services Bulletin 71
Reliable Sprinkler Product Services Bulletin 71
F1FR80-300 Series
Quick Response Sprinklers
K-factor 8.0 (115)
Features
• Standard coverage quick-response sprinklers
• 300 psi (20.7 bar) rated
• Upright and pendent deflectors
• Low profile, compact design
• Available in a wide variety of finishes
Product Description
Reliable Model F1FR80-300 series sprinklers are 300 psi
(20.7 bar) rated, quick-response standard spray automatic fire
sprinklers utilizing a sensitive 3.0 mm glass bulb thermal element. Model F1FR80-300 Upright
Upright RA7822
F1FR80-300 8.0 (115) cULus 300 (20.7)
Pendent RA7812
www.reliablesprinkler.com
Model F1FR80-300 Upright Sprinkler SIN RA7822
Sensitivity
Quick response
Deflector
Glass Bulb
(3 mm)
F1FR_THREE QTR_UPR
Technical Specifications
Temperature Ratings(1)
Style:
135°F (57°C)
Pendent
155°F (68°C)
Recessed Pendent
175°F (79°C)
Threads: 3/4” NPT or ISO 7-R3/4
200°F (93°C)
Nominal K-Factor: 8.0 (115)
286°F (141°C)
Max. Working Pressure: 300 psi (20.7 bar)
Notes:
1. 286°F (141°C) temperature rated sprinkler not listed for recessed use.
2. Not suitable for recessed pendent installations.
3 1/4" [83mm]
Threads
Wrench Flat
F1FR_THREE QTR_PEND_INT
2 3/8" [61mm]
Cap/Seal
Assembly
Glass Bulb
(3 mm)
Deflector
Load Screw
1 1/4" [30mm]
2-1/4" 2-1/4"
(57 mm) Dia. (57 mm) Dia.
Hole in Ceiling Hole in Ceiling
1-15/16" 1-15/16"
(49 mm) Dia. Reducing (49 mm) Dia. Reducing
Fitting Fitting
1-3/4" 1-3/4"
(44 mm) 1" (44 mm) 1-1/4"
(25 mm) (32 mm)
Models F1 & F1FR Pendent Sprinkler Models F1 & F1FR Pendent Sprinkler
with Model F1 Recessed Escutcheon with Model F2 Recessed Escutcheon
3/4" (19mm) Nominal Adjustment 1/2" (13mm) Nominal Adjustment
F1_REC_PEND_NO FP
F1 Recessed Escutcheon
(F2 similar)
Finishes(1) Table B
Standard Finishes Special Application Finishes
Sprinkler F1 Escutcheon Sprinkler F1 Escutcheons
Bronze Brass Electroless Nickel PTFE(2) Bright Brass
Chrome Plated Chrome Plated Bright Brass(3) Satin Chrome
White Polyester(2) White Polyester Satin Chrome Custom Color Polyester
Custom Color Polyester(2)
Notes:
1. Paint or any other coating applied over the factory finish will void all approvals and warranties.
2. cULus Listed as corrosion resistant.
3. For 200°F (93°C) maximum temperature rated sprinklers only.
Installation Maintenance
Model F1FR Series sprinklers must be installed in accordance Reliable Model F1FR80-300 series sprinklers should be
with NFPA13 and the requirements of all applicable authorities inspected and the sprinkler system maintained in accordance
having jurisdiction. Model F1FR80-300 Series sprinklers must be with NFPA 25, as well as the requirements of any Authorities
installed with the Reliable sprinkler installation wrench identified Having Jurisdiction.
in this bulletin. Any other wrench may damage the sprinkler. The
Models W2 and W4 wrenches have two sets of jaws. Use the Prior to installation, sprinklers should remain in the original
smallest set of jaws that fit on the wrench flats of the sprinkler. cartons and packaging until used. This will minimize the potential
A leak tight sprinkler joint can be obtained with a torque of 8 for damage to sprinklers that could cause improper operation or
to 18 lb-ft (11 to 24 N.m). Do not tighten sprinklers over the non-operation.
maximum recommended installation torque. Exceeding the
maximum recommended installation torque may cause leakage Do not clean sprinklers with soap and water, ammonia liquid or
or impairment of the sprinkler. any other cleaning fluids. Remove dust by gentle vacuuming
without touching the sprinkler.
Glass bulb sprinklers have orange bulb protectors or protective
caps to minimize bulb damage during shipping, handling and Replace any sprinkler which has been painted (other than factory
installation. Reliable sprinkler installation wrenches are designed applied). A stock of spare sprinklers should be maintained to
to install sprinklers with bulb protectors in place. Remove the allow quick replacement of damaged or operated sprinklers.
bulb protector at the time when the sprinkler system is placed in Failure to properly maintain sprinklers may result in inadvertent
service for fire protection. Removal of the bulb protector before operation or non-operation during a fire event.
this time may leave the bulb vulnerable to damage. Remove bulb
protectors by undoing the clasp by hand. Do not use tools to
remove bulb protectors.
Ordering Information
Specify the following when ordering:
Model
• F1FR80-300
Deflector/Orientation
• Upright
• Pendent
Temperature Rating
• See sprinkler technical specifications
Sprinkler Finish
• See Table B
Recessed Escutcheon*
• F1
• F2
Escutcheon Finish
• See Table B
Sprinkler Wrench
• Model W2 (upright, non-recessed pendent)
• Model W4 (recessed pendent)
• Model J (with guard installed)
P/N 9999970627