A Method of Seamless Transitions Between Grid-Tied and Stand-Alone Modes of Operation For Utility-Interactive Three-Phase Inverters
A Method of Seamless Transitions Between Grid-Tied and Stand-Alone Modes of Operation For Utility-Interactive Three-Phase Inverters
A Method of Seamless Transitions Between Grid-Tied and Stand-Alone Modes of Operation For Utility-Interactive Three-Phase Inverters
3, MAY/JUNE 2014
Abstract—A method for the seamless transition of three-phase inverters. During this transition, the magnitude and frequency
inverters switched between grid-tied and stand-alone modes of of the voltage across the local loads may experience large
operation is presented in this paper. In this method, only the transients. Thus, the inverter control system needs to implement
inverter current and voltage sensors are utilized, and no con-
trol over the grid-side static transfer switch is needed. The pre- a mechanism to provide seamless transitions between the two
sented method contains two strategies for grid-tied-to-stand-alone modes of operation, namely, grid-tied and stand-alone (island-
and stand-alone-to-grid-tied transitions. In the stand-alone-to- ing) modes. In other words, grid-tied inverters should be able to
grid-tied transition strategy, a novel algorithm is presented for secure power delivery with minimal disturbance to their local
estimating the grid angle nearly instantaneously, which allows loads. Seamless transition is one of the technical challenges in
the three-phase inverter to respond very quickly if the grid and
point-of-common-coupling voltages are out of phase. This fast the renewable energy system technology, and therefore, many
response allows the inverter to effectively eliminate the transient industrial and academic investigations have been performed
overcurrent that would normally occur if it was connected to the in recent years. A majority of reported work on seamless
grid without first being synchronized. The fast response also allows transitions has made use of a controllable static transfer switch
the inverter to return to normal operation very quickly after such (STS) [2]–[8], while two sets of voltage and current sensors
an event. The strategy for the seamless transition from grid-tied
to stand-alone mode is also presented. These strategies have been are utilized in both sides of the STS [see Fig. 1(a)]. In [2],
verified through experiments, and the results are presented in this a virtually seamless transition to and from islanded operation
paper. is demonstrated using a controllable STS with sensors on both
Index Terms—Grid-tied and stand-alone modes, seamless tran- sides. Many other investigators have expanded on this concept
sition, utility-interactive inverters. in various ways, all using a controllable STS. In [3], the voltage
magnitudes and phase angles of both sides of the STS are mea-
I. I NTRODUCTION sured, and their differences are fed back into the inverter control
system to become resynchronized for the inverter reconnection
0093-9994 © 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
Seeuse
Authorized licensed http://www.ieee.org/publications_standards/publications/rights/index.html for more
limited to: KIIT University. Downloaded on May 17,2024 at 14:37:13 UTC from IEEE information.
Xplore. Restrictions apply.
OCHS et al.: METHOD OF SEAMLESS TRANSITIONS BETWEEN GRID-TIED AND STAND-ALONE MODES 1935
Fig. 4. Mode transition conceptual block diagram; mode = 0, −1, and +1 stand for coast (inverter turn-off), stand-alone (voltage control in Fig. 2), and grid-tied
(power control in Fig. 3) modes of operation, respectively.
can see how the proposed technique determines the inverter’s connected to the grid, ω0 and θ0 will be initialized to 120π and
mode of operation. In stand-alone mode, the inverter regulates zero, respectively.
the voltage at the PCC because the grid is disconnected (see As shown in Fig. 4, in stand-alone mode, the inverter intro-
Fig. 2). In grid-tied mode, the inverter operates as a power duces a dither signal, i.e., ωr = ω̃g + Δω, into the reference
source to inject certain amounts of active and reactive powers frequency of the voltage at the PCC. The magnitude of the
to the grid (see Fig. 3). In coast mode, all of the IGBTs are dither is ±0.08 Hz and the frequency of the dither signal is
turned off, which is necessary for proper transitions between 0.4 Hz; however, the magnitude of the dither must not adversely
stand-alone and grid-tied modes of operation. The direct path affect any load that is connected at the PCC. This dither signal
between coast and grid-tied modes is shown by a dashed line in is used in the transition from stand-alone mode to grid-tied
gray color, shown in Fig. 4. mode. As previously mentioned, the inverter captures the grid
The transition from grid-tied mode to stand-alone mode is the frequency and angle when a transition is made from grid-
simplest to execute. According to IEEE 1547-2003, the service tied mode to stand-alone mode. Therefore, in the event of a
voltage of a system should always remain between 0.918 and short disconnection, the grid and PCC voltages may still be
1.057 p.u., i.e., 191 < V < 220 for a 208-VLL system, and synchronized when the inverter is reconnected to the grid. For
the frequency should stay between 59.3 and 60.5 Hz [1]. If a longer disconnection time interval, the PCC and grid voltages
the inverter senses that either the voltage or the frequency has may or may not be synchronized. If the two are synchronized
surpassed the aforementioned ranges while it is in grid-tied prior to reconnection, there will not be an obvious transient
mode, the inverter controller switches to stand-alone mode, as when reconnection occurs. Rather, the frequency at the PCC
shown in Fig. 4. In stand-alone mode, the inverter still must will no longer follow the dither signal because it will be set by
have a reference angle for the control scheme. This angle can the grid. In other words, if the frequency error, defined as eω =
be interpolated from the grid conditions before the inverter is |ωr − ω̃g |, is greater than the threshold for mode transition
disconnected as follows: Δωth , the inverter shifts to grid-tied mode. Also, the PCC
voltage magnitude may change from its value in stand-alone
θr = ωr dt + θ0 (9) mode upon reconnection if the stand-alone voltage set point and
the grid voltage differ. Also, if the voltage strays too far from
its reference value while the inverter is operating in stand-alone
where ωr = ω̃g (tgrid−off ) is the grid angular frequency and mode, the inverter controller shifts to grid-tied mode, as shown
θ0 = θg (tgrid−off ) is the grid angle at the instant that the inverter in Fig. 4.
switched to stand-alone mode tgrid−off . Because the grid fre- If the PCC voltage and the grid voltage are not synchronized
quency may not be stable during a grid interruption, the inverter upon connection, this voltage difference will cause a large
stores the value of ω̃g in the microcontroller memory from transient current to flow unless an immediate action is taken to
several cycles. Thus, the inverter can use a reliable ω̃g value in prevent it. The basis of this action in the proposed technique
the event of a grid failure or disconnection. When the inverter is a voltage angle estimation technique in addition to the
senses a sudden change in voltage or frequency, it stores the
√ estimator. Assuming that the line–line voltage vab (t) =
PLL
present grid angle θ0 in memory and begins integrating ωr 2VLL cos(θg ) is the reference voltage, a first estimation for
according to (9). If the inverter controller switches to stand- the voltage angle θg can be obtained from
alone mode, θr is then considered to be the reference angle for √
use in the control system. If the inverter is started without being θ̃g1 = cos−1 (vab / 2VLL ) (10)
Authorized licensed use limited to: KIIT University. Downloaded on May 17,2024 at 14:37:13 UTC from IEEE Xplore. Restrictions apply.
1938 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 50, NO. 3, MAY/JUNE 2014
Thus, using the measured voltages, the sign of sin(θg ) can be IV. E XPERIMENTAL S ETUP
identified as sgn(sin(θg )) = sgn(vab + 2vbc ), i.e.,
The proposed techniques were tested on a laboratory-scale
√ 1.2-kVA 208-V 60-Hz three-phase system. The experimental
θ̃g = sgn(vab + 2vbc ) · cos−1 (vab / 2VLL ). (13)
test setup is shown in Fig. 5. A dSPACE CLP1103 system
In both stand-alone and grid-tied modes, the inverter refer- hosted the controllers and feedback signals from the sensors.
ence angle θr (for the control system) is approximately equal The inverter controllers were run from a Simulink model linked
to θ̃g , i.e., θ̃g ∼
= θr , considering the inherent phase shift caused to the dSPACE system. The local load was purely resistive, fed
by the voltage sensors and feedback path delays. However, the through an LCL filter, and the inverter pulsewidth-modulation
only situation in which θr can differ from θg by a significant (PWM) frequency was 5 kHz. The inductance and capacitance
margin is the instant that the inverter is connected to the grid. values of the LCL filter in Fig. 1, i.e., Lf 1 , Lf 2 , and Cf , were
In this case, the error between θr and θg , defined as eθ , will be 10 mH, 5 mH, and 10 μF, respectively. It should be noted that
greater than the threshold set for mode transition Δθth . When the LCL filter resonance frequency, i.e., fr = 1/2π Lf Cf ,
the inverter senses this condition, it immediately enters coast where Lf = Lf 1 Lf 2 , should be much smaller than the PWM
mode in order to minimize transient overcurrent, as shown in frequency [19]. The capacitance value of Cf is limited by the
Fig. 4. This strategy would not be possible if a PLL scheme reactive power absorbed by the circuit inductances at rated
were used instead of θ̃g because even a well-tuned PLL scheme conditions. This means that, for a Y-connected capacitor bank,
2 2
needs time to converge to the correct grid angle [16]–[18]. approximately Cf Vph,rated < (Lf 1 + Lf 2 + Lg )Irated , where
In this technique, a time series of estimated angles, e.g., Lg is the grid inductance value. Meanwhile, the grid was
θ̃g (tk−1 ), θ̃g (tk ), and θ̃g (tk+1 ), can be scanned to minimize connected to the load through an isolated 1:1 transformer, as
the impact of measurement noises and voltage disturbances shown in Fig. 5. The inverter control system had no feedback
on the process of the grid angle estimation. Using the set of signals from the grid while it was in stand-alone mode. During
estimations, as θg is a linear function over each (0 2π)-radian transitions, it only had the information gleaned from the two
interval, any sudden change (except at zero and 2π) between PTs and two CTs at the PCC.
the estimated angles is considered outlier data. Furthermore, The experimental results were acquired with a LeCroy
in the proposed method, (13) is used only for several cycles Waverunner 64XI oscilloscope equipped with ADP305 differ-
until the PLL scheme is converged. ential high-voltage probes (100-MHz bandwidth) and CP031
Notice that a small mismatch between the frequencies of the high-current probes (50-MHz bandwidth), while the control
inverter reference signal and the grid during stand-alone mode low-voltage signals were collected with a LeCroy WaveAce 214
could make the inverter reference and the grid angles out of oscilloscope.
phase. The inverter also switches to coast mode if it senses
a certain level of current flowing at the PCC. Both possible
V. E XPERIMENTAL R ESULTS
transition paths to coast mode are shown in Fig. 4. Because θ̃g
provides a nearly instantaneous estimate of the grid angle, coast In these experiments, a signal called “Mode” indicates the
mode need only be used for a short duration. In experimental inverter operating mode. The values of the Mode signal are
results, the inverter was programmed to stay in coast mode for −1, 0, and +1 for stand-alone, coast, and grid-tied modes
half a cycle, i.e., 8.33 ms. This predetermined time margin can of operation, respectively. The results of five different mode
be identified based on the rated voltage and power values of the transition tests are shown in Figs. 6–10.
system. Upon leaving coast mode, θ̃g can be used in the grid- The results in Fig. 6 demonstrate the transition from grid-
tied mode controller for several cycles while the PLL scheme tied mode to stand-alone mode. As can be seen, the inverter
converges to the actual grid angle. is disconnected from the grid at approximately t = 0.025 s by
Authorized licensed use limited to: KIIT University. Downloaded on May 17,2024 at 14:37:13 UTC from IEEE Xplore. Restrictions apply.
OCHS et al.: METHOD OF SEAMLESS TRANSITIONS BETWEEN GRID-TIED AND STAND-ALONE MODES 1939
Fig. 7. Measured voltage and current waveforms in transition from stand- Fig. 9. Measured voltage and current waveforms in transition from stand-
alone to grid-tied mode. alone to grid-tied mode, while the inverter and grid are 180◦ out of phase;
coast mode is activated by exceeding the current threshold, but θ̃g is used while
waiting on the PLL scheme to converge.
small distortions in the measured voltage and current wave-
forms. At that point, the voltage increases until it reaches
1.057 p.u., the upper threshold of acceptable voltage, at t = tied mode when the PCC and the grid are 180◦ out of phase
0.05 s. At t = 0.05, the inverter switches to stand-alone mode prior to the inverter’s connection to the grid (the worst case
and begins controlling the voltage at the PCC. scenario). In Fig. 8, the inverter is only allowed to switch to
In Fig. 7, the voltage and current waveforms are shown over coast mode when the PCC current exceeds its threshold value
the transition from stand-alone mode to grid-tied mode, when of 5.5 p.u. in this experimental setup. It should be emphasized
the inverter and the grid have been in phase accidentally prior to that the threshold value is practically set to a lower level, e.g.,
connection. In this test, at t = 0.05, the frequency error exceeds 2 p.u., to prevent any damage to the inverter. Regardless of the
the threshold as the inverter can no longer inject the dither threshold value, the peak current exceeds the acceptable level
signal because the PCC frequency is held steady by the grid. At during the transition. Then, only the PLL is used to provide
that point, the inverter switches to grid-tied mode and begins a reference angle for the inverter control system. This case is
injecting a set amount of real and reactive power, which, in this most comparable to the systems reported in the literature [9],
case, happens to be greater than that consumed power by the [10]. Because the controllers cannot function properly without
local load. an accurate estimate of the grid angle, the inverter is forced to
The next test, with results given in Fig. 8, is the first of stay in coast mode for two cycles while the PLL converges. This
three tests for the transition from stand-alone mode to grid- time may not still be enough as a significant transient (with a
Authorized licensed use limited to: KIIT University. Downloaded on May 17,2024 at 14:37:13 UTC from IEEE Xplore. Restrictions apply.
1940 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 50, NO. 3, MAY/JUNE 2014
Fig. 10. Measured voltage and current waveforms in transition from stand-
alone to grid-tied mode, while the inverter and grid are 180◦ out of phase; coast
mode is activated by exceeding the |θ̃g − θr | threshold, as presented in Fig. 4.
overcurrent reduces to one-third of the overcurrent observed [18] P. Rodriguez, A. Luna, I. Candela, R. Mujal, R. Teodorescu, and
when previously published methods (without a controllable F. Blaabjerg, “Multiresonant frequency-locked loop for grid synchroniza-
tion of power converters under distorted grid conditions,” IEEE Trans.
STS) are used. Furthermore, the time interval for which the Ind. Electron., vol. 58, no. 1, pp. 127–138, Jan. 2011.
current is greater than 2 p.u. is reduced by more than a factor [19] M. Lesseri, F. Blaabjerg, and S. Hansen, “Design and control of an LCL-
of 12 compared to those of the same methods. These seamless filter-based three-phase active rectifier,” IEEE Trans. Ind. Appl., vol. 41,
no. 5, pp. 1281–1291, Sep./Oct. 2005.
transition results, along with the fact that only one set of sensors
is needed, make the grid-tied inverter with no controllable STS
an attractive configuration for inexpensive small systems.
David S. Ochs (S’09) received the B.Sc. and M.Sc.
R EFERENCES degrees in electrical engineering from Kansas State
University, Manhattan, KS, USA, in 2010 and 2012,
[1] IEEE Standard for Interconnecting Distributed Resources With Electric respectively.
Power Systems, IEEE Std. 1547, 2003. Since 2013, he has been an Electric Motor Con-
[2] R. Tirumala, N. Mohan, and C. Henze, “Seamless transfer of trol Design Engineer with the Advanced Technology
grid-connected PWM inverters between utility-interactive and stand- Center, General Motors Powertrain, General Motors
alone modes,” in Proc. IEEE Appl. Power Electron. Conf., Mar. 2002, Corporation, Torrance, CA, USA, where he works on
pp. 1081–1086. developing control algorithms for hybrid and electric
[3] Y. Li, D. Vilathgamuwa, and C. Poh, “Design, analysis, and real-time powertrains. His current research interests include
testing of a controller for multibus microgrid system,” IEEE Trans. Power motor control and thermal management in power
Electron., vol. 19, no. 5, pp. 1195–1204, Sep. 2004. electronic converters.
[4] C. Chen, Y. Wang, J. Lai, Y. Lee, and D. Martin, “Design of parallel
inverters for smooth mode transfer microgrid applications,” IEEE Trans.
Power Electron., vol. 25, no. 1, pp. 6–15, Jan. 2010.
[5] S. Jung, Y. Bae, S. Choi, and H. Kim, “A low cost utility interactive
inverter for residential fuel cell generation,” IEEE Trans. Power Electron., Behrooz Mirafzal (S’01–M’05–SM’07) received
vol. 22, no. 6, pp. 2293–2298, Nov. 2007. the B.Sc. degree in electrical engineering from
[6] Z. Yao, L. Xiao, and Y. Yan, “Seamless transfer of single-phase grid- Isfahan University of Technology, Isfahan, Iran, in
interactive inverters between grid-connected and stand-alone modes,” 1994, the M.Sc. degree (with first-class honors) in
IEEE Trans. Power Electron., vol. 25, no. 6, pp. 1597–1603, Jun. 2010. electrical engineering from the University of Mazan-
[7] D. Dong, T. Thacker, I. Cvetkovic, R. Burgos, F. D.Boroyevich, and daran, Babolsar, Iran, in 1997, and the Ph.D. degree
G. Wang, “Modes of operation and system-level control of single-phase in electrical engineering from Marquette University,
bidirectional PWM converter for microgrid systems,” IEEE Trans. Smart Milwaukee, WI, USA, in 2005.
Grid, vol. 3, no. 1, pp. 93–104, Mar. 2012. From 1997 to 2000, he was a Research Engineer,
[8] I. Balaguer, Q. Lei, S. Yang, U. Supatti, and F. Peng, “Control for as well as a Lecturer, with several academic insti-
grid-connected and intentional islanding operations of distributed power tutions in Isfahan. From 2005 to 2008, he was a
generation,” IEEE Trans. Ind. Electron., vol. 58, no. 1, pp. 147–157, Senior Development/Project Engineer with Allen-Bradley, Rockwell Automa-
Jan. 2011. tion, Mequon, WI, USA, where he was involved in research and development
[9] R. Teodorescu and F. Blaabjerg, “Flexible control of small wind turbines related to motor-drive systems. From 2008 to 2011, he was an Assistant
with grid failure detection operating in stand-alone and grid-connected Professor with Florida International University, Miami, FL, USA. Since 2011,
modes,” IEEE Trans. Power Electron., vol. 19, no. 5, pp. 1323–1332, he has been an Assistant Professor with Kansas State University, Manhattan,
Sep. 2004. KS, USA. He has published over 50 articles in professional journals and
[10] S. Hu, C. Kuo, T. Lee, and J. Guerrero, “Droop-controlled inverters with conference proceedings and is the holder of three U.S. patents. His current
seamless transition between islanding and grid-connected operations,” in research interests include applications of power electronics in modern energy
Proc. IEEE Energy Convers. Congr. Expo., 2011, pp. 2196–2201. conversion systems and motor drives.
[11] J. Vasquez, J. Guerrero, A. Luna, P. Rodriguez, and R. Teodorescu, Dr. Mirafzal was the recipient of the 2008 second best IEEE Industry
“Adaptive droop control applied to voltage-source inverters operating in Applications Society Transactions Prize Paper Award published in 2007, the
grid-connected and islanded modes,” IEEE Trans. Ind. Electron., vol. 56, best 2012 IEEE Power and Energy Society Transactions Prize Paper Award
no. 10, pp. 4088–4096, Oct. 2009. published in 2011, and a 2014 U.S. National Science Foundation (NSF)
[12] J. Kwon, S. Yoon, and S. Choi, “Indirect current control for seamless CAREER Award. He served as the Technical Co-Chair of the IEEE Interna-
transfer of three-phase utility interactive inverters,” IEEE Trans. Power tional Electric Machines and Drives Conference in 2009, and is currently an
Electron., vol. 27, no. 2, pp. 773–781, Feb. 2012. Associate Editor of the IEEE T RANSACTIONS ON I NDUSTRY A PPLICATIONS.
[13] S. Yoon, H. Oh, and S. Choi, “Controller design and implementation of
indirect current control based utility-interactive inverter system,” IEEE
Trans. Power Electron., vol. 28, no. 1, pp. 26–30, Jan. 2013.
[14] D. Holmes and T. Lipo, Pulse Width Modulation for Power
Converters: Principles and Practice. Hoboken, NJ, USA: Wiley, 2003, Pedram Sotoodeh (S’10) was born in Isfahan, Iran.
pp. 32, 259-333. He received the B.S. degree in electrical engineering
[15] P. Krause, O. Wasynczuk, and S. Sudhoff, Analysis of Electric Machinery from Shahrekord University, Shahrekord, Iran, in
and Drive Systems, 2nd ed. Piscataway, NJ, USA: IEEE Press, 2002, 2008, and the M.Sc. degree from Sharif University
pp. 506–510. of Technology, Tehran, Iran, in 2010. He is currently
[16] C-C. Hsieh and C. Hung, “Phase-locked loop techniques—A survey,” working toward the Ph.D. degree in the field of
IEEE Trans. Ind. Electron., vol. 43, no. 6, pp. 609–615, Dec. 1996. power electronics and renewable energy systems at
[17] F. Gonzalez-Espin, E. Figueres, and G. Garcera, “An adaptive Kansas State University, Manhattan, KS, USA.
synchronous-reference-frame phase-locked loop for power quality im- His areas of interest include utility application of
provement in a polluted utility grid,” IEEE Trans. Ind. Electron., vol. 59, power electronics, electrical drives, renewable en-
no. 6, pp. 2718–2731, Jun. 2012. ergy systems, and machine design.
Authorized licensed use limited to: KIIT University. Downloaded on May 17,2024 at 14:37:13 UTC from IEEE Xplore. Restrictions apply.