Nothing Special   »   [go: up one dir, main page]

X1 Line: Heat / Cool Temperature Controller / DIN - 48 X 96

Download as pdf or txt
Download as pdf or txt
You are on page 1of 61

X1 UK-ed6 19-02-2009 11:50 Pagina 1

Heat / Cool
temperature controller
1/ DIN - 48 x 96
8

X1 line c
ISO 9001 User Manual • 09/ 02 • Cod e: ISTR_M_X1_E_07_--

C e r t i f i e d

Ascon Tecnologic srl


viale Indipendenza 56, 27029 Vigevano (PV)
Tel.: +39-0381 69 871 - Fax: +39-0381 69 8730
Sito internet: www.ascontecnologic.com
Indirizzo E-Mail: sales@ascontecnologic.com
X1 UK-ed6 19-02-2009 11:50 Pagina 1

Heat / Cool
temperature controller
1/ DIN - 48 x 96
8

X1 line c
X1

45.80
45.80
X1 UK-ed6 19-02-2009 11:50 Pagina 2

Information

c Please, read carefully these instructions before proceeding with the installation of
the controller.
NOTES Class II instrument, rearl panel mounting.

ON ELECTRIC This controller has been designed with compliance to:


SAFETY AND Regulations on electrical apparatus (appliance, systems and installations) according to
the European Community directive 73/23/EEC amended by the European Comunity direc-
ELECTROMAGNETIC tive 93/68/EEC and the Regulations on the essential protection requirements in electrical
COMPATIBILITY apparatus EN61010-1 : 93 + A2:95.

Regulations on Electromagnetic Compatibility according to the European Community


directive n089/336/EEC, amended by the European Community directive No. 92/31/EEC,
93/68/EEC, 98/13/EEC and the following regulations:
Regulations on RF emissions
EN61000-6-3 : 2001 residential environments
EN61000-6-4 : 2001 industrial environments
Regulation on RF immunity
EN61000-6-2 : 2001 industrial equipment and system

It is important to understand that it’s responsibility of the installer to ensure the compliance
of the regulations on safety requirements and EMC.
The device has no user serviceable parts and requires special equipment and specialised
engineers. Therefore, a repair can be hardly carried on directly by the user. For this purpose,
the manufacturer provides technical assistance and the repair service for its Customers.
Please, contact your nearest Agent for further information.
All the information and warnings about safety and electromagnetic compatibility are
marked with the B sign, at the side of the note.
2
X1 UK-ed6 19-02-2009 11:50 Pagina 3

Table of contents

TABLE OF CONTENTS

Resources Operating mode 1 INSTALLATION ...................................................Page 4


Control Alarms Retransmission 2 ELECTRICAL CONNECTIONS .............Page 8
3 PRODUCT CODING ......................................Page 16
Main universal input PV / SP
4 OPERATIONS ......................................................Page 21
12 PV OP1 5 DISPLAYS ...............................................................Page 47
1 OP1 OP2 OP3 OP5 6 COMMANDS ........................................................Page 48
OP2 Single
Auxiliary input
action 7 TECHNICAL SPECIFICATIONS ...........Page 52
AUX 2 OP4 OP1 OP2 OP3 OP5
OP3

(option) OP4 3 OP1 OP2 OP3 OP5

Double
OP5 4 action OP1 OP4 OP2 OP3 OP5
(option)
5 OP4 OP2 OP1 OP3 OP5

X1

Setpoint Fuzzy tuning with automatic selection


Modbus RS485
Parameterisation One shot One shot
Auto tuning Natural Frequency
Supervision
Special functions (option) (option)

3
X1 UK-ed6 19-02-2009 11:50 Pagina 4

1 - Installation

1 INSTALLATION 1.1 GENERAL DESCRIPTION

IP 20 Terminal block
Installation must only be carried out by EN61010 - 1 (IEC1010 - 1)
qualified personnel.
Panel
surface
Before proceeding with the installation of
this controller, follow the instructions illus-
trated in this manual and, particularly the
installation precautions marked with the
B symbol, related to the European
Community directive on electrical protection
and electromagnetic compatibility.

B Product code label


To prevent hands or metal touching parts
that may be electrically live, the controllers
must be installed in an enclosure and/or
Mounting clamps
in a cubicle.

Sealing front panel gasket

Front panel
IP65 protection
EN 650529 (IEC 529)

4
X1 UK-ed6 19-02-2009 11:50 Pagina 5

1 - Installation

1.2 DIMENTIONAL DETAILS 1.3 PANEL CUT-OUT

48 mm 65 mm min
1.89 in 2.56 in min

96 mm
3.78 in

113 mm min
4.45 in min
10 mm max 10 mm max
0.39 in max 0.39 in max

3.62+0.031 in
92+0.8 mm
110 mm
4.33 in

45+0.6 mm
1.78+0.023 in

5
X1 UK-ed6 19-02-2009 11:50 Pagina 6

1 - Installation

1.4 ENVIRONMENTAL RATINGS B

Operating conditions

M Altitude up to 2000 m

T Temperature 0…50°C [1]

%Rh Relative humidity 5…95 % non-condensing

Special conditions Suggestions

M Altitude > 2000 m Use 24Vac supply version

T Temperature >50°C Use forced air ventilation

%Rh Humidity > 95 % Warm up

P Conducting atmosphere Use filter

Forbidden Conditions D
UL notes
C Corrosive atmosphere

[1] Operating surrounding temperature


0…50°C
E Explosive atmosphere

6
X1 UK-ed6 19-02-2009 11:50 Pagina 7

1 - Installation

1.5 PANEL MOUNTING [1]

1.5.1 INSERT 1.5.2 INSTALLATION 1.5.3 CLAMPS 1.5.4 INSTRUMENT


THE INSTRUMENT SECURING REMOVING UNPLUGGING B
1 Prepare panel cut-out 1 Fit the mounting clamps 1 Insert the screwdriver in the 1 Push and
2 Check front panel gasket 2 Push the mounting clamps clips of the clamps 2 pull to remove the instrument
position towards the panel surface to 2 Rotate the screwdriver
3 Insert the instrument through secure the instrument Electrostatic discharges can
the cut-out damage the instrument
1
1MΩ
1
Before removing the instrument
the operator must discharge
himself to ground
1

2
3
2
1
2
1
UL note
2
[1] For Use on a Flat Surface of a Type 2 and Type 3 ‘raintight’
Enclosure. 1

7
X1 UK-ed6 19-02-2009 11:50 Pagina 8

2 - Electrical connections

2 ELECTRICAL 2.1 TERMINATION UNIT [1] B


CONNECTIONS Rear
terminal
5.7 mm
1 25 0.22 in
cover
Wire size 1 mm2
1 13 N/C 25 L 2 26 [2]
RS485

2 14 N/C 26 N
3 0,5 27
C 3 15 N/C 27 Nm
4 N/C 16 N/C 28 NC
5 N/C 17 N/C 29 C OP3 28 24 screw terminals M3
6 N/C 18 N/C 30 NO
Option terminals
7 N/C 19 31 NO 29
OP5 OP1
8 20 32 C Tightening torque 0.5 Nm
TA OP2
9 21 N/C 33 NO 30
A
10 22 N/C 34 NO Phillips screw-driver PH1
b OP4
11 RTD 23 35 C 19 31
mV TC B REM Flat blade screw-driver
12 24 36 24V— 0.8 x 4 mm
OUT
8 20 32
Terminals
9 33
Pin connector
q 1.4 mm 0.055 in max.
10 34
Fork-shape AMP 165004
11 23 35 Ø Ø 5.5 mm - 0.21 in
UL notes
12 24 36 Stripped wire
[1] Use 60/70 °C copper (Cu) conductor only. L L 5.5 mm - 0.21 in
[2] Wire size 1mm2 (18 AWG Solid/Stranded)
8
X1 UK-ed6 19-02-2009 11:50 Pagina 9

2 - Electrical connections

PRECAUTIONS B 2.2 SUGGESTED WIRES ROUTING B


Despite the fact that the instru-
ment has been designed to work Conduit for supply and output cables
in an harsh and noisy environ-
mental (level IV of the industrial A B A B
standard IEC 801-4), it is recom-
mended to follow the following
suggestions. 1 25 1 25

A 2 26 2 26

All the wiring must comply with 3 27 3 27

the local regulations. 28 28

The supply wiring should be rout- 29 29

ed away from the power cables. 30 30


Avoid to use electromagnetic 19 19
31 31
contactors, power Relays and
8 20 32 8 20 32
high power motors nearby.
Avoid power units nearby, espe- 9 33 9 33

cially if controlled in phase angle 10 34 10 34 A= Power Supply


11 23 35 11 23 35 B= Outputs
Keep the low level sensor input 12 24 36 12 24 36
C= Analogue inputs
wires away from the power lines D= Analogue output
and the output cables. E= Digital I/O and
If this is not achievable, use Serial Comm.s
shielded cables on the sensor E C D E E C D E
input, with the shield connected
to earth. Conduit for low level sensor cables

9
X1 UK-ed6 19-02-2009 11:50 Pagina 10

2 - Electrical connections

2.3 EXAMPLE OF WIRING DIAGRAM (HEAT / COOL CONTROL) B


Commands Retransmission V~
Notes:
Power 1] Make sure that the power supply voltage is
supply [3] the same indicated on the instrument.
switch
2] Switch on the power supply only after that
PTC all the electrical connections have been
1 25
RS485 completed.
2 26 3] In accordance with the safety regulations,
3 C 27 the power supply switch shall bring the
OP3 Alarm identification of the relevant instrument. The
28 power supply switch shall be easily acces-
29 sible from the operator.
[6] [5]
30 4] The instrument is is PTC protected. In case
OP1 [5] of failure it is suggested to return the instru-
V~
Heating
19 31 ment to the manufacturer for repair.
OP5 [6]
8 20 32 5] To protect the instrument internal circuits
[6] V~ use:
9 33
OP2 [5] - 2 AT fuse for Relay outputs (220 Vac);
10 34 - 4 AT fuse for Relay outputs (110 Vac);
11 23 35 - 1 AacT fuse for Triac outputs.
Cooling
6] Relay contacts are already protected with
12 24 36
varistors.
Only in case of 24 Vac inductive loads,
use model A51-065-30D7 varistors (on
request)
CT Current transformer 50 mA ~

10
X1 UK-ed6 19-02-2009 11:50 Pagina 11

2 - Electrical connections

2.3.1 POWER SUPPLY B 2.3.2 PV CONTROL INPUT B


Switching power supply with A L-J-K-S-R-T-B-N-E-W thermocouple type
multiple isolation and internal • Connect the wires with the polarity as shown
PTC • Use always compensation cable of the correct type
11
• Standard version: for the thermocouple used
nominal voltage: • The shield, if present, must be connected to a prop-
100...240Vac (-15...+10%) er earth. 12
Frequency 50/60Hz Wire resistance
• Low Voltage version: 150Ω max.
Nominal voltage: B For Pt100 resistance thermometer
24Vac (-25...+12%) • If a 3 wires system is used, use always cables of the
10
Frequency 50/60Hz same section (1mm2 min.) (line 20 Ω/lead maximum A
or 24Vdc (-15...+25%) resistance) For 3 wires only
Power consumption 4W max. • When using a 2 wires system, use always cables of the b
11 Maximum line
Included PTC same diameter (1,5mm2 min.) and put a jumper between resistance: 20Ω/line
25 L terminals 11 and 12 12
B
Supply
C For ∆T (2x RTD Pt100) Special
26 N
A When the distance between the controller and the
sensor is 15 m using a cable of 1.5 mm2 section, A
10
27 produces an error on the measure of 1°C. R1 Use wires of the same
11 length and 1.5 mm2
B
For better protection against R1 + R2 must be <320Ω size.
R2
noise, it is recommended not to Maximum line
12
connect the earth clamp provid- A resistance: 20Ω/line
ed for civilian installations.
11
X1 UK-ed6 19-02-2009 11:50 Pagina 12

2 - Electrical connections

2.3.2 PV CONTROL INPUT B 2.3.3 AUXILIARY INPUT B

D For mA, mV D2 With 3 wires transmitter A - From Remote Setpoint 5 watt burden resistor
0.5Ω for 1A secondary
(option) transformer coil
mV mA
Transmitter Current 0/4…20mA 0.1Ω for 5A secondary
11
36 24V–
Input resistance = 30Ω transformer coil
PV [1]
mA
load CT
12
11 Voltage 8
External
shunt 2.5Ω
4…20mA 1…5V, 0…5V, 0…10V ~
12 Input resistance = 300kΩ 9
External 10…100A 50/100mA
Rj >10MΩ shunt 2.5Ω
23
Rj
D1 With 2 wires transmitter [1] Auxiliary power supply for external
transmitter 24Vdc ±20%/30mA 24
Transmitter mV-V mA
max. with no short-circuit protec-
36 24V–
PV 4…20mA [1] tion
mA
B- For Current Transformer
11
External CT not isolated
shunt 2.5Ω For the measure of the load cur-
12 rent (see page 45)

• Primary coil10A…100A S3
• Secondary coil 50mA default
100mA S3 internal jumper selec-
table Jumper for 100 mA secondary
transformer coil
12
X1 UK-ed6 19-02-2009 11:50 Pagina 13

2 - Electrical connections

2.3.5 OP1 - OP2 - OP3 - OP4 - OP5 OUTPUTS (OPTION) B


The functionality associated to Control outputs Alarms Retransmission
each of the OP1, OP2 and OP3 Heat Cool AL1 AL2 AL3 PV / SP
output is defined during the con-
figuration of the instrument index A OP1 OP2 OP3 OP5
n(see page 19). Single
The suggested combinations action
are:
B OP4 OP1 OP2 OP3 OP5

C OP1 OP2 OP3 OP5


Double
D OP1 OP4 OP2 OP3 OP5
action
E OP4 OP2 OP1 OP3 OP5

where:

OP1 - OP2 Relay or Triac output


OP3 Relay output (for AL3 only)
OP4 SSR drive control or Relay output
OP5 Retransmission analogue output
13
X1 UK-ed6 19-02-2009 11:50 Pagina 14

2 - Electrical connections

2.3.5-A SINGLE ACTION RELAY 2.3.5-C SINGLE ACTION


(TRIAC) CONTROL OUTPUT B ANALOGUE OUTPUT B
Fuse Fuse Fuse
31 31 32
OP1 [1] OP1 [1] OP2 [1]
32 32 33
Coil of the heat Coil of the heat Coil of the cool
load contactor load contactor load contactor

2.3.5-B SINGLE ACTION SSR DRIVE 2.3.5-D DOUBLE ACTION


CONTROL OUTPUT B RELAY (TRIAC)/RELAY (TRIAC) CONTROL OUTPUT B
Static Fuse Static
Relay 31 Relay
34 34
OP1 [1]
OP4 Load OP4
32 35
35 Cool
Coil of the heat load
load contactor

Relay output 2.3.5-E DOUBLE ACTION


• SPST Relay N.O., 2A/250 Vac RELAY (TRIAC)/SSR DRIVE CONTROL OUTPUT B
(4A/120Vac) for resistive load;
• Fuse 2AT at 250Vac, 4AT at 110Vac. Static Fuse
Logic output not isolated relay 32
34
• 0…5Vdc, ±20%, 30 mA max. OP2 [1]
OP4
33
35 Heat Coil of the cool
load load contactor

14
X1 UK-ed6 19-02-2009 11:50 Pagina 15

2 - Electrical connections

2.3.6 ALARM OUTPUTS B 2.3.7 OP5 ANALOGUE RETRANSMISSION 2.3.8 SERIAL COMMUNICATIONS
OUTPUT (OPTION) B (OPTION) B
A The relay/triac output OP1, OP2 and OP3,
can be used as alarm outputs only if they 19 1
are not used as control outputs. mA OP5 Load
20 2
Fuse
31
OP1 [1] AL1 load 3 C
32 V~
For PV/SP retransmission only: • Galvanic isolation 500Vdc/1 min
OP2 [1] AL2 load • Galvanic isolation 500Vac/1 min Compliance to the EIA RS485 standard
33 • 0/4…20mA, (750Ω or 15Vdc max.) for Modbus/Jbus
Fuse • Setting dip switches

Fuse O
NC N 1 2 3 4
28
[1] AL3 load
OP3
29 V~ ON OFF
C
[1] AL3 load
A Please, read:
30 gammadue® and deltadue® controller Position On Off
NO Fuse 5 VDC Polarization
series serial communication and con- 1
polarization excluded
figuration 2
Termination Termination
inserted excluded
[1] Varistor for inductive load 24Vdc only
0 VDC Polarization
3
polarization excluded
4 - -

15
X1 UK-ed6 19-02-2009 11:50 Pagina 16

3 - Product coding

3 PRODUCT CODING
Configuration code (software)
O P Q R
The complete code is shown on the instru- L M N
ment label. The informations about product
coding are accessible from the front panel Basic product code (hardware)
B C D
by mean of a particular procedure described
at section 5.2 page 47

X1

Instrument label 3150


Hard
P/N : X1-3150-0000
CONF : 0320-2301
S/N : A0A-9909/0013
V~(L-N) : 100÷240V 50/60 Hz - 4W

16
X1 UK-ed6 19-02-2009 11:50 Pagina 17

3 - Product coding

3.1 MODEL CODE

The product code indicates the specific hardware configuration of the instrument, that can be modified by specialized engineers only.
Configuration
Line Basic Accessories
1st part 2nd part
Mod.:
X 1 A B C D - E F G 0 / I L M N - O P Q R

Line X 1

Power supply A Special function E


100...240Vac (-15...+10%) 3 Not fitted 0
24Vac (-25...+12%) or 24Vdc (-15...+25%) 5 Start-up + Timer 2

Outputs OP1 - OP2- OP4 B User manual F


Relay - Relay - SSR Drive 1 Italian/English (std) 0
Triac - Triac - SSR Drive 5 French/English 1
Relay - Relay - Relay 9 German/English 2
Spanish/English 3
Serial Communications C
None 0 Front panel colour G
RS485 Modbus/Jbus SLAVE 5 Dark (std) 0
Beige 1
Options D
None 0
Retransmission output + Remote Set point input 5
17
X1 UK-ed6 19-02-2009 11:50 Pagina 18

3 - Product coding

3.2 CONFIGURATION CODING Input type and range I L


TR Pt100 IEC751 -99.9…300.0 °C -99.9…572.0 °F 0 0
Index I L M N
A 4+4 index code follows the TR Pt100 IEC751 -200…600 °C -328…1112 °F 0 1
1st part of TC L Fe-Const DIN43710 0…600 °C 32…1112 °F 0 2
model of the controller.
The code has to be set to con- configuration 0320 TC J Fe-Cu45% Ni IEC584 0…600 °C 32…1112 °F 0 3
mode Con.1 TC T Cu-CuNi -200 …400 °C -328…752 °F
figure the controller (see chap- 0 4
ter 3.1 page 17) TC K Chromel-Alumel IEC584 0…1200 °C 32…2192 °F 0 5
E.g. Enter the code 0320 to choose: TC S Pt10%Rh-Pt IEC584 0…1600 °C 32…2912 °F 0 6
- T/C type J input with range TC R Pt13%Rh-Pt IEC584 0…1600 °C 32…2912 °F 0 7
0...600°C TC B Pt30%Rh 0…1800 °C 32…3272 °F 0 8
- Single P.I.D. control algorithm, Pt6%Rh IEC584
reverse action TC N Nichrosil-Nisil IEC584 0…1200 °C 32…2192 °F 0 9
- Relay output TC E Ni10%Cr-CuNi IEC584 0…600 °C 32…1112 °F 1 0
TC NI-NiMo18% 0…1100 °C 32…2012 °F 1 1
Index O P Q R TC W3%Re-W25%Re 0…2000 °C 32…3632 °F 1 2
TC W5%Re-W26%Re 0…2000 °C 32…3632 °F 1 3
2nd part of Dc input 0…50mV linear Engineering and units
configuration 2301 Dc input 10…50mV linear Engineering and units
1
1
4
5
mode Con.2 Custom input and range [1] 1 6
[1] For instance, other thermocouples types, ∆T (with 2 PT 100), custom lin-
E.g. Enter the code 2301 to choose: earisation etc.
- AL1 absolute, active high
- AL2 absolute, active low
- AL3 Used by Timer
- Local + 2 Stored Setpoints with
tracking function

18
X1 UK-ed6 19-02-2009 11:50 Pagina 19

3 - Product coding

Engineering and units M Alarm 1 type and function O


ON-OFF reverse action 0 Disabled 0
ON-OFF direct action 1 Sensor break/Loop break alarm (LBA) 1
P.I.D. single reverse action 2 active high 2
P.I.D. single direct action 3 Absolute
active low 3
Linear cool output 4 active high 4
ON-OFF cool output 5 Deviation
P.I.D. double action active low 5
Water cool output [2] 6
Oil cool output [2] active out 6
7 Band
active in 7
Heater break active during ON output state 8
Output configuration by CT [3]
N active during OFF output state 9
Single action Double action
Relay (OP1) Heat OP1, Cool OP2 0
SSR drive or relay (OP4) Heat OP1, Cool OP4 1 Alarm 2 type and function P
- Heat OP4, Cool OP2 2 Disabled 0
Sensor break/Loop break alarm (LBA) 1
active high 2
Absolute
active low 3
[2] In consideration of the thermal characteristics of the different cooling liquids, active high 4
2 different correcting methods of the control output are available. One for water Deviation
active low 5
and the other for oil
active out 6
Band
OP water = 100•(OP2/100)2 OP oil = 100•(OP2/100)1,5 active in 7
[3] Only possible whether "Output configuration" n= 0 or 1) and HT.FS
. . para- Heater break active during ON output state 8
meter is different to OFF, see page 29) by CT [3] active during OFF output state 9

19
X1 UK-ed6 19-02-2009 11:50 Pagina 20

3 - Product coding

Alarm 3 type and function Q


Disabled or used by Timer 0
Sensor break/Loop break alarm (LBA) 1
active high 2
Absolute
active low 3
active high 4
Deviation
active low 5
active low 6
Band
active in 7
Heater break active during ON output state 8
by CT [3] active during OFF output state 9

Setpoint type R
Local only 0
Local and 2 tracking stored Setpoints 1
Local and 2 Stand-by stored Setpoints 2
Local and Remote 3
Local with trim 4
Remote with trim 5

20
X1 UK-ed6 19-02-2009 11:50 Pagina 21

4 - Operations

4 OPERATIONS 4.1.1 KEYS FUNCTIONS AND DISPLAY IN OPERATOR MODE

PV control input Over range Under range


X1 in engineering
units
____ 8888
8888 ----
8 Status LEDs (greens)
} Communications running
Ä Tuning running
45.80
Ö Timer running
Ü Remote Setpoint active
ú First stored Setpoint active
45.80 SP operating Setpoint
(Local/Remote or Stored)
ù Second stored Setpoint active
Control output LEDs (red)
å OP1/OP4 ON - ç OP2/OP4 OFF

Alarm status LEDs (reds)


Å AL1 ON
Ç AL2 ON Entry key for selection and value setting confirmation
É AL3 ON

Setpoint setting

Menu access

21
X1 UK-ed6 19-02-2009 11:50 Pagina 22

4 - Operations

4.1.2 KEYS FUNCTIONS AND DISPLAY IN PROGRAMMING MODE

A X1
The parameter setting procedure
has a timeout. If no keys are

35.0
Parameter value
pressed for, at least, 30 seconds,
the controller switches back,
automatically, to the operator
mode.
P.b. Parameter mnemonic

After having selected the para-


meter or the code, press $
and % to display or modify the
value (see page 23)
The value is entered when the
next parameter is selected, by
pressing the è key.

Until the $ or % are Entry key for selection


pressed or if you wait for 30 sec- and value setting confirmation
onds the parameter value is not
inserted Value modification

Pressing the í key, the next


group of parameters is present- Access to the menu for:
ed on the display. Parameter setting
Configuration

22
X1 UK-ed6 19-02-2009 11:50 Pagina 23

4 - Operations

4.2 PARAMETER SETTING

4.2.1 NUMERIC ENTRY


(i.e. the modification of the Setpoint
274.8 Operator
mode
4.2.2 MNEMONIC CODES SETTING
(e.g. configuration see page 28)
value from 275.0 to 240.0 ) 275.0 working Setpoint
displayed Press the $ or % to display the next or previous mnemonic for
the selected parameter.
Press $ or % momentari- Continued pressing of $ o r% will display further mnemonics
ly to change the value of 1 unit
every push 274.8 Local
Setpoint display
at a rate of one mnemonic every 0.5 s. The mnemonic displayed
at the time the next parameter is selected, is the one stored in the
Continued pressing of $ or 275.0 parameter.
% changes the value, at rate
that doubles every second. ————Decrease Engineering Degree
Releasing the button the rate of °C Units °f Fahrenheit
change decreases.
In any case the change of the
274.8 Setpoint
modification
Unit
Degree
Centigrade Unit
value stops when it has reached
230.0
the max./min limit set for the Degree no units
parameter. ————Increase
°f Fahrenheit none defined

In case of Setpoint modification:


274.8 Unit Unit
press $ or %once to dis- 240.0
play the local Setpoint instead after 2 s Degree
of working Setpoint. °C Centigrade
Ph
To evidence this change the dis-
°C Setpoint entry. Unit ph
play flashes once. Then the
Setpoint can be modified 240.0
The operation is
acknowledged by Unit
one flash of the
display.
23
X1 UK-ed6 19-02-2009 11:50 Pagina 24

4 - Operations

4.3 PARAMETERISATION - MAIN MENU


Back to the Operator mode
Operator
274.8 mode

275..0 Setpoint Menu


(see page 25)
Control Menu
(see page 26)
Aux. parameters
Menu (see page 27)
Configuration Menu
(see page 28 and 29)

s.p. Cont Ru.pa Conf


COMMANDS
Menu Menu Menu Menu
(if configured) Direct access
to the parameter
Timer (only if Code <5000)
t.run run/stop
(see page 49)
Password Entry

Only if Code value


OPTION
≥5000 (if installed)
Setpoint selection
l=r local/remote
(see page 50) Must be equal to the
value of the parameter
Code
Stored
s.sel Setpoint selection
(see page 50 ) 5033 Timer/Start-up Menu
tM.s.U
(see page 27)
pass YES Menu
OK
NO
Back to the Operator mode
24
X1 UK-ed6 19-02-2009 11:50 Pagina 25

4 - Operations

4.3.1 PARAMETERISATION - SETPOINT MENU


Menu Setpoint
éL.réange
s.p. Setpoint low limit low
s.p. l range…S.P. H Note
Menu [1] It is not presented if the controller
éH.réange has been configured with alarm
é 0 no. 2 not active or of sensor
AL1 alarm threshold s.p. H Setpoint high limit
S.P. L…High range break type. Digit O/P of the con-
AIs.p [1]
(see page 30 )
figuration code is assigned to 0
or 1.
é 0
AL2 alarm threshold
A2s.p [1]
(see page 30)
LOCAL, REMOTE, PROGRAMM.
configuration index r= O, 3, 6
é 0
LOCAL, + 2 STORED. LOCAL OR REMOTE WITH TRIM.
A3s.p AL3
[1]
alarm threshold

(see page 30)


configuration index r= 1, 2 configuration index r= 4, 5

é ::::::: é 1.00
é Off 1st stored Ratio
Setpoint ramp s.p. I Setpoint rtio Setpoint
sl. u up0ff/0.1…999.9
digit/min é ::::::: é 0
é Off 1nd stored Remote
Setpoint ramp down s.p. 2 Setpoint bias Setpoint bias
sl. d OFF/0.1…999.9
digit/min

25
X1 UK-ed6 19-02-2009 11:50 Pagina 26

4 - Operations

4.3.2 PARAMETERISATION - CONTROL MENU

Cont Control
Menu
é 1:00
é 0
Output safety value
Menu Derivative time S.Out 0.0…100.0%
t.d. 0ff / 0.01…10.00 (-100.0…100.0%
for Heat / Cool)
min

é 1:00 Heat / Cool


P.I.D. On-Off Algorithm
Algorithm Algorithm
O.C. Overshoot control
0.01…1.00
é 0:5
Dead band
Control output
é 0:5 é 50
Manual reset d.bnd -10.0…10.0%
hysteresis
0.1...10.0% sc.
hy. M.res (only with integral time
= 0ff)
0.0...100.0% output é 1:0
é Off Cool relative gain
Tune run/stop r.C.G.a 0.1…10.0
tune strt / StoP d.Err Error dead band
0ff/0.1... 10.0%
of the input span
é 5:0 é 20 é 20
Proportional band Cool cycle time
p.b. 0.5...999.9 of span t.c. Cycle time
(Time proportioning only) Cool
é 0:5
t.c. C (heat/cool time proportion-
1…200 seconds output
hysteresis
hy. C ing only)
1…200 seconds
é 5:0 é100:0 (On-Off only) é100:0
Integral time 0.1...10.0% sc Cool control output
t.i. 0ff / 0.1…100.0 min Op. H Control output
high limit Op.HC high limit
(P.I.D. only)
10.0…100.0%
Back to the tune parameter 10.0…100.0%
26
X1 UK-ed6 19-02-2009 11:50 Pagina 27

4 - Operations

4.3.3 PARAMETERISATION - AUXILIARY PARAMETERS MENU 4.3.4 PARAMETERISATION - TIMER AND START-UP MENU
If options installed
Au.pa Auxiliary é 1 Soft-start

Menu
parameters
Menu st.tM
activation time
(only if st.Op differ-
ent than 0ff)
tM.s.U Timer and
Start-up Menu
Menu Timer/Start-up
é 0:5 é Off
1…9999 s
t.Mod operating mode
(see table 1 page 41)
AL1 hysteresis Filter time constant
A1hy 0.1…10.0% of span t.fil OFF/1...30 s
énone é Off TIMER FUNCTION START-UP FUNCTION
Alarm latching Input shift (only if t.Mod = 1)
A1L.b and blocking
functions
In.sh 0ff/-60…60 digit (only with AL3 enabled)

none / Ltch é Off é 1


bloc / Lt.bL é 1 Timer Action Hold time
Communication t.Act (only if t.Mod not t.h.s.U 0…500 min
AL2 and AL3 parameters Addr address
(if option installed)
equal to Offor to 1)
(see table page 41)
é OFF 0ff / 1…247 é 0:5 é 0
LBA delay Timer setting Start-up Setpoint
éL. réange
t.Lba (see page 38)
0ff= sensor break Retransmission tiMe 1…9999 s or min s.p.s.U S.P. L…S.P. H
1…9999 s LBA rt.lo. low range
(only if installed)
é 0:5 whole range é 0 Stand-by Setpoint é100:0
Soft-start (only if t.Mod = 7) Output high limit
éH. réange
St.OP output value Retransmission s.p.sb S.P. L…S.P. H Op.Hs during
( t.Mod =0ff only)
0ff/0.1…100.0%
rt.hi high range
(only if installed)
Start-up
5.0…100.0%
whole range
Back to the A1hy parameter Back to the t.Mod parameter
27
X1 UK-ed6 19-02-2009 11:50 Pagina 28

4 - Operations

4.3.5 CONFIGURATION MENU

Enter the password before


accessing to the configuration
Index

1st part of
I L M N
Conf Password Entry

menu. configuration 0320 Menu Only if Code value


mode Con.1 <5000
If a not configured controller is (33 default from factory)
supplied, when powered up for E.g. Enter the code 0320 to
the first time, the display shows: choose:
- T/C type J input with range
33 Must be equal to the value
of the parameter Code
0...600°C
pass
9999 - Single P.I.D. control algorithm ,
Con.1 reverse action NO YES
- Relay output Back to
OK
Until the configuration code is Index O P Q R Operator mode
set correctly, the controller é Off
remains in stand-by with input 2nd part of
and output deactivated. configuration 2301 Con.1 Iof- the
Entry of digits
L-M-N
mode Con.2 configuration code
(chapter 3.2 pages 18, 19)
A 4+4 index code follows the é Off
model of the controller. E.g. Enter the code 2301 to Entry of digits
It has to be set to configure choose: Con.2 Oof-theP -configuration
Q-R
code
the controller. - AL1 absolute, active high (chapter 3.2 pages 19, 20)
(see chapter 3.1 page 17) - AL2 absolute, active low énone
- AL3 Used by Timer IL1 digital input
- Local + 2 Stored Setpoints with Unit function
(see table 1)
Tracking function

28
X1 UK-ed6 19-02-2009 11:50 Pagina 29

4 - Operations

LINEAR SCALE Table 1 Engineering


ONLY SERIAL COM. OPTION
(if installed) units
éM:bus
éunit
sc.dd No.
0…3
of decimals
prot Communication
protocol Value Description
M.buS / jbuS °C degree centigrade
°f degree Fahrenheit
é9600
none none
sc.lo Low range
-999…9999 baud Baud rate
1200/2400 mU mV
(min. 100 digit) 4800/9600 U Volt
mA mA
A Ampere
sc.Hi High range
-999…9999 ANALOGUE OUTPUT bar Bar
OPTION OP5 PSI
(min. 100 digit)
é4=20 (if installed) psI
rh Rh
REMOTE SETPOINT
(if configured)
retr Analogue control
output range ph pH
é4=20 0=20 / 4=20 mA
Table 2 Remote Setpoint
rs.in Remote
input
Setpoint
ép:U: input type
(see table 2)
rtH Control output
selection
Value
érs:In
Description
P.U. / S.P.
CT (only on proportional 0=5 0…5 Volt
output other than the
é 33 1=5 1…5 Volt
servomotor) Password
0=10 0…10 Volt
Ht.f.s CTrangeprimary high 0…9999
33 default from factory Code 0=20 0…20 mA
Off/1…200 A 4=20 4…20 mA
Back to the Con.1 parameter
29
X1 UK-ed6 19-02-2009 11:50 Pagina 30

4 - Operations

4.4 PARAMETERS 4.4.1 SETPOINT MENU

For a simpler use of the con- The OP1, OP2 or OP3 outputs, can A ALARM TYPE AND OPERATION CONDITIONS
troller, its parameters have been be used for alarms if they are not Absolute alarm (full scale)
organised in groups (menu),
according to their functionality
used as control outputs
It is possible to configure up to 4
On Active
Off high #A1s.P AL1 alarm
threshold
area. alarms: AL1, AL2, AL3, AL4 (see On AL2 alarm
page 19 and 20), selecting, for each
Off
hy
Active
low #A2s.P threshold
of them: AL3 alarm
A the type and the operating condi- low range
Alarm threshold
high range #A3s.P threshold
tion of the alarm Alarm occurrences of OP1,OP2
B the functionality of the alarm Deviation alarm and OP3 outputs, respectively
acknowledge (latching) # l tch SP On Active linked to AL1, AL2 and AL3.
(see page 37) Off high

C the start-up disabling (blocking) On Active The range of the alarm thresh-
#bloc (see page 37) Off low old correspond to the whole
D Loop break or sensor break hy
span and it is not limited by the
(see page 38) - low range + high range SP Setpoint span.
Alarm threshold
When the event occures, the
Band alarm
SP On Active
display will shows the red
Off out ledsÅ,Ç or É, respec-
On tively on.
Off Active
in
hy hy

full scale full scale


alarm threshold

30
X1 UK-ed6 19-02-2009 11:50 Pagina 31

4 - Operations

When Remote Setpoint is con- If index r= 1 (tracking),


#sl. u Setpoint
ramp up figured, we suggest to disable #S.P. L Setpoint
low limit the previous Local Setpoint
#sl. u and #sl. d parameters value will be lost, when the
#sl. d Setpoint
ramp down Off. #S.P. H Setpoint
high limit stored Setpoint is selected.
This parameter specifies the Low / high limit of the Setpoint
max.imum rate of change of the Example Target Setpoint value. If index r= 2 (Stand-by),
= 350°C
Setpoint in digit/min. the Local Setpoint value will not
Setpoint be lost, when the Stand-by
When the parameter is OFF, change
#sL. u = 10
#S.P. 1 1st stored
Setpoint Setpoint is selected. It will oper-
Initial digit/minutes ate again when back to Local.
this function is disabled and
the new Setpoint is reached Setpoint
= 250°C
#S.P. 2 2nd stored
Setpoint
immediately after being t t = 10 Preset Set values can be set See stored Setpoint selection
entered. from the keyboard and serial procedure at page 50
communication. The Setpoint
Otherwise, the Setpoint value is active is indicated by the ú or
reached according to the con- ù green led.
figured rate of change.

The new Setpoint value is called


"Target Setpoint". It can be dis-
played by means the parameter
#t.S.P.
(see procedure at page 47).

31
X1 UK-ed6 19-02-2009 11:50 Pagina 32

4 - Operations

4.4.1 SETPOINT MENU

Remote Setpoint Bias and Ratio If SR starting point is lower


#rtio Remote
Setpoint Ratio Remote then the ending point, both
Ratio is the coeff. which defines signal expressed in engineering
the remote Setpoint span with 10V ab units:
respect to the input span. bias = 20
ratio = 0.1
biaS= starting point = a
a´ b´
#bias Remote
Setpoint bias = 100
ratio = –0.1
rtio=
b-a
HR - LR
Bias defines the starting point of
analogue Remote Setpoint in Example:
Range
eng. units corresponding to the -200 0 20 100 600 °C
biaS= 20
low limit (current or voltage) of LR a (b´ ) b (a´ ) HR rtio=
the remote signal. Remote 100 - 20 80
= = 0.1
Setpoint span 600 - (-200) 800

PV = process variable
LR = PV low limit
HR = PV high limit
SR = Remote Setpoint
a (a´) = SR starting point
b (b´) = SR ending point

32
X1 UK-ed6 19-02-2009 11:50 Pagina 33

4 - Operations

If SR starting point is higher Working Setpoint (SP) as com- Examples:


then the ending point, both bination of Local Setpoint (SL) Local Setpoint (SL) with an
expressed in engineering units and remote signal external Trim with multiplying
coefficient of 1/10:
biaS= starting point = a´ Setpoint type Loc.t Setpoint type = Loc.t
(configuration index r= 4 ) rtio= 0.1
b´ - a´
rtio= SP = SL + (rtio • REM) biaS= 0
HR - LR + biaS
Example: Remote Setpoint (SR) with an
biaS= 100 Setpoint type reM.t internal Trim with multiplying
rtio= (configuration index r= 5 ) coefficient of 1/5:
20 - 100 - 80 SP = REM + (rtio • SL) Setpoint type = reM.t
= = - 0.1
600 - (-200) 800 + biaS rtio= 0.2
biaS= 0
SIGN = Remote signal
percentage Remote Setpoint range equal to
SPAN = HR-LR the Input range:
Setpoint type = Loc.t
SIGN * SPAN
REM = rtio = 1
100
biaS= LR
SL = 0

33
X1 UK-ed6 19-02-2009 11:50 Pagina 34

4 - Operations

4.4.2 CONTROL MENU

the start of the autotune oper-


#tune Run
Tune ation, the PV is far from the
The Fuzzy Tuning determines
automatically the best method
274.8 Operator
mode
Setpoint of more than 5% of the to use to calculate the P.I.D. 275..0
4.4.2.1 AUTOMATIC TUNE span. This method has the big term, according the process
advantage of fast calculation, conditions.
The Fuzzy-Tuning determines with a reasonable accuracy in press until
automatically the best P.I.D. the term calculation. FUZZY-TUNING START/STOP
term with respect to the process
behaviour. Natural frequency
PROCEDURE
Cont Control
menu
tuning start Start/stop of the Fuzzy Tuning Menu
The controller provides 2 types of The Tuning operation can be
“one shot” tuning algorithm, that PV variable started or stopped any time.
are selected automatically accord- End of the tuning
ing to the process condition when operating and setting
of the new calculated The green led Ä is ON when
the operation is started.
This type is selected when, at
terms. the Fuzzy Tuning is in progress.
At the end of this operation, the
stop To start
select
STEP response
Control output
calculated P.I.D. terms parame- tune strt
ter are stored and used by the
SP
This type is selected when the PV control algorithm and the con-
End of the tuning
Setpoint change
operating and setting of is close to the SP Setpoint. troller goes back to the operator
the new calculated This method has the advantage mode. The green led Ä
terms.
PV variable
Start of autotune
of a better accuracy in the term
calculation with a reasonable
becomes off. strt To stop
select
operation
speed calculation. tune stop
Control output

34
X1 UK-ed6 19-02-2009 11:50 Pagina 35

4 - Operations

#P.b. Proportional
band #O.C. Overshoot
control #t.c. Control output
cycle time #hy. Control output
hysteresis
This parameter specifies the pro- This parameter specifies the span Cool Cool output
portional band coefficient that of action of the overshoot control. #t.c. C cycle time #hy. C hysteresis
multiplies the error (SP - PV) Setting lower values (1.00 —> 0.01) It’s the cycle time of the SSR SP
the overshoot generated by a drive control output. The P.I.D. On
Setpoint change is reduced. The control output is provided by the
#t.i. Integral time
overshoot control doesn’t affect the pulse width modulation of the
Off
hy
It is the integral time value, that effectiveness of the P.I.D. algorithm. waveform.
specifies the time required by the Setting 1, the overshoot control is Control or alarm output hystere-
integral term to generate an out- disabled. sis span, set in % of the full scale.
put equivalent to the proportional #Op. H Control output
high limit
term. When Off the integral
term is not included in the con- #M.res Manual
Reset #Op.C.H Cool output
high limit
trol algorithm. This specifies the control output It specifies the maximum value
value when PV = SP, in a PD only the control output can be set.
algorithm (lack of the integral It is applied in manual mode,
#t.d. Derivative
time term). too.
It is the time required by the pro-
portional term P to repeat the
output provided by the deriva- #d.err Error
Dead Band #S.Out Output
Safety Value
tive term D. When Off the Inside this band for Output Value in case of input
derivative term is not included (PV - SP), the control output does not anomaly
in the control algorithm. change to protect the actuator (out-
put Stand-by)

35
X1 UK-ed6 19-02-2009 11:50 Pagina 36

4 - Operations

4.4.2 CONTROL MENU

4.4.2.2 HEAT/COOL CONTROL A Heat /Cool actions separated C Cool action adjusting
Insert positive d . nd value (0…10%)
# b Example with different relative cool gains
By a sole P.I.D. control algorithm, the con- =2.0 #r.C.Ga 0.1…10.0
troller handles two different outputs, one 100% -100% 100% =1.0 -100%
of these performs the Heat action, the other #Op. H #Op.HC =0.5
one the Cool action.
It is possible to overlap the outputs.
#d.bnd #d.bnd
The dead band parameter d # b
. nd, is the zone Heat Cool
output output Heat Cool
where it is possible to separate or overlap 0% 0% output output
the Heat and Cool actions. 100% 50% 0% 100% 50% 0%
PID output PID output
The Cool action can be adjusted using the B Heat /Cool actions overlapped D On-Off Cool action
relative cool gain parameter #r.C.Ga. Insert negative d . nd value (-10…0%)
# b
#hy. C
To limit the Heat and Cool outputs the para- 100% -100% 100% On
meters #0p. H and #0p.HC can be used. #Op. H #Op.HC

#d.bnd
When there is an overlap, the displayed out-
put # OUt shows the algebric sum of the #d.bnd
Heat Cool
Heat and Cool outputs. cool output Heat Cool
0% 0% output output Off
100% 50% 0% 100% 50% 0%
PID output PID output

36
X1 UK-ed6 19-02-2009 11:50 Pagina 37

4 - Operations

4.4.3 AUXILIARY PARAMETERS MENU

#Ltch ALARM #bloc START-UP DISABLING


#AIhy AL1
alarm hysteresis ACKNOWLEDGE FUNCTION
AL2 The alarm, once occurred, is presented on
#A2hy alarm hysteresis the display until to the time of acknowledge.
Ramp down
Disable
AL3 The acknowledge operation consists in ∆SP
#A3hy alarm hysteresis pressing any key.
SP
On
Hysteresis of the threshold of both the After this operation, the alarm leaves the Off
alarms, that activate OP1 and OP2 control alarm state only when the alarm condition Start-up
output. It is specified as a % of the full scale. is no longer present. Ramp up
SP
#AIL.b AL1, AL2, AL3
latching
∆SP
On
Disable

#A2L.b and
blocking
Off
Start-up

#A3L.b functions ∆SP Threshold = SP ± range

For each alarm it is possible to select the fol-


lowing functions
none none
Ltch latching
bloc blocking
Lt.bL both latching
and blocking

37
X1 UK-ed6 19-02-2009 11:50 Pagina 38

4 - Operations

4.4.3 AUXILIARY PARAMETERS MENU

ALARMS WITH LBA (LOOP BREAK ALARM)


AND SENSOR BREAK OPERATION #st.Op Soft-start
control output #t.fil Input filter
time constant
Select the code 1 on o, p or q configuration indexes (see value Time constant, in seconds, of the
pages 21 or 22). The following parameter is then available: Value of the control output dur- RC input filter applied to the PV
ing the Soft-start activation time. input.
When this parameter is set to
#t.lba LBA delay
Off the filter is bypassed.
Setting a value between 1 and Setting OFF the alarm works #st.tM Soft-start
activation time
9999 s the alarm works as as Sensor break with immedi- Time duration (starting from the Filter response
LBA+Sensor break with delay ate action. power on) of the Soft-start func- 100%
[1] This condition is shown by tion. 63,2% PV
This condition is shown by means the red led of the select-
means a red led as well as the ed alarm as well as:
OP
blinking PV display. 100%
0 t.Fil Time

274.8 ____
8888 ----
8888
275.0 1 2
275.0
3
or
1 2
275.0
3 #St.OP
#In.sh Input shift

1 2 3 OP1 This value is added to the mea-


Soft-start sured PV input value. Its effect is
Note [1] In case of sensor break,
to shift the whole PV scale of up
#St.tM
condition, the alarm action is imme-
Time to ± 60 digits.
mA Power on
°C
diate.

When the cause of the alarm disappears, the alarm status stops.
38
X1 UK-ed6 19-02-2009 11:50 Pagina 39

4 - Operations

4.4.4 TIMER AND START-UP 4.4.4.1 START-UP FUNCTION (OPTION)


MENU (OPTION)
To improve the instrument per- By means of this function it is
#Addr Controller
address formances and to reduce the possible to manipulate the con- #Op.Hs Control output
high limit
the address range is from 1 to 247 wiring and installation costs, trol output when the controller 5.0%…100.0%
and must be unique for each con- two special functions are avail- is switched on.
troller on the communication bus to able: The Start-up function includes
the supervisor. 4.4.4.1 Start-up To config- three phases:
When set to Off the controller is
not communicating
4.4.4.2 Timer 1 ure Start-
up func-
1st “Limy” - The control output
is limited to the #Op.Hs
In order to have the above func- t.Mod tion the
2nd “Hold” - The process variable
tions the product code digit parameter
#rt.lo Retransmission
low range emust be 2 (see page 19) is maintained to the Start-up
Setpoint for the time fixed by
Retransmission “Timer/Start-up operating mode”
#rt.Hi high range For example: X3 3100-2000 must be set to # 1. the parameter t # h
. s
. U
.
To select these functions use the (see page 41) 3rd “Off” - When the t
# h
. s
. U
. time
parameter: (see page 41). Three parameters are associat- is elapsed the process vari-
ed to the Start-up function. able is maintained to the
#t.Mod Timer/Start-up
operator mode working Setpoint.

A Selecting Timer or Start- #t.h.s.U Start-up


hold time
Whether the process variable,
for any reason (e.g. load
up, the Soft-start function 0…500 min change), decreases at a value
is disabled, therefore the lower than ( #s.p.sU - 40 digits),
parameters # s t. O p and
#st.tM will not be shown. #S.P.s.U Start-up
Setpoint
the Start-up function starts
again from the “Limy” phase.
(see page 29) (S.P. L…S.P. H)

39
X1 UK-ed6 19-02-2009 11:50 Pagina 40

4 - Operations

4.4.4.1 START-UP FUNCTION (OPTION)

When the Start-up is in Hold If, at the controller power-on, the A #s.P.sU < local Setpoint SP
phase, if the local Setpoint process variable PV is greater than power-on noise
becomes lower than the Start- the lowest between the s # p.sU Setpoint SP
up Setpoint or if the operating and the working Setpoint , the
mode changes to manual, the next phase (“Hold” or “Off”) will PV
Start-up function passes to the be executed instead of the “Limy”
“Off” phase. phase. #t.h.S.U 1 digit #t.h.S.U
#S.P.S.U
There are two possibilities:
A Start-up Setpoint #sp.sU
lower than the local
1285 OP=OP.H5
40 digit

Setpoint.
RUN
420 with TC = 25%
1sec min.
The “Hold” phase starts 1a “Limy” 2a “Hold” 3a “Off” 1a “Limy” 2a “Hold” 3a “Off”
when the process variable
Start-up
PV achieves the # s p. s U Setpoint
(with a tolerance of 1 digit). B #s.P.sU ≥ Setpoint locale SP
B Start-up Setpoint #sp.sU During the “Limy” and power-on #s.p.s.U
greater than or equal to “Hold” phases the Ö led is
1 digit noise
the local Setpoint. on. PV
Setpoint SP
When the process variable PV
achieves the local Setpoint (with a 40 digit
tolerance of 1 digit), the Start-up
OP=OP.H5
function passes directly to the “Off” with TC =
phase. 25%
1a “Limy” 3a “Off” 1a “Limy” 3a “Off”

40
X1 UK-ed6 19-02-2009 11:50 Pagina 41

4 - Operations

4.4.4.2 TIMER FUNCTION (OPTION)

A The Timer can’t be


enabled with Heat / Cool #t.Mod Timer/Start-up
operating mode #t.Act Timer
Action #tiMe Timer
setting
control. By this parameter can be defined: By this parameter can be (1…9999 s/min)
(see table 1) defined:(see table 2)
To enable this function do the fol- - the counting start time - the time units
lowing: - the control output status at the - the starting mode #S.P.sb Stand-by
Setpoint
1 In order to use this AL3 func- end of the counting - the OP3 status when the timer (only for t.Mod = 7)
tion, index qmust be set to is running. (S.P. L…S.P. H)
0 in configuration (see p. 20). When the timer is not running, the
2 To select one of the 6 possi- table 1 OP3 takes the opposite status.
ble functioning modes of the Timer/Start-up counting mode Value
Timer, set the value of the 2 Disabled OFF
following parameters in para- Start-up function 1 table 2
meterisation (see p. 27). Counting [1]
End mode Time Starting
start time OP3 Value
When inside the Control mode 2 units mode
status
band Output to 0 3 Manual by On 0
Control mode 4 keypad Off 1
When launched
Output to 0 Seconds
5 Auto at the On 2
When launched. Control mod power on [2] Off 3
Control disabled 6 Manual by On 4
keypad Off 5
When launched Control mod Minutes
stand-by Setpoint 7 Auto at the On 6
power on [2] Off 7
Now the other parameter values [1] If used by Timer
can be entered: [2] Using this selection, manual
starting mode is possible too.
41
X1 UK-ed6 19-02-2009 11:50 Pagina 42

4 - Operations

4.4.4.2 TIMER FUNCTION (OPTION)

TIMER COUNTING MODES

A - Counting start time inside the band, B - Counting start time inside the band, C - Counting start time = timer launch
end in control mode. end with control output forced to zero. time, end in control mode.

The time counting starts only when the error The time counting starts only when the error The time counting starts when the timer is
is inside a ± 1 digit band. The control action is inside a ± 1 digit band. At the end, the con- launched. The control action is not affected
is not affected by the Timer function. trol output is forced to zero. [1] by the Timer function.

Timer launch
#tiMe #t.Mod = 2 Timer launch
#tiMe #t.Mod =3 Timer launch
#tiMe #t.Mod = 4
Setpoint Setpoint Setpoint
±1 digit ±1digit
Process band Process band Process
variable PV variable PV variable PV

Output OP Output OP Output OP

OP3 OP3 OP3

[1] When the Timer is not running the con-


trol output is forced to zero, also before the
Timer launch
42
X1 UK-ed6 19-02-2009 11:50 Pagina 43

4 - Operations

TIMER COUNTING MODES

D - Counting start time = timer launch time, E - No control action during F - Control action with stand-by
end with control output forced to zero. the counting time. Setpoint during the counting time

The time counting starts when the timer is The time counting starts when the timer is The time counting starts when the timer is
launched. At the end, the control output is launched and the control output is forced to launched and the control action use the
forced to zero [1]. zero. At the end, the control action starts. Stand-by Setpoint. At the end, the control
action use the working Setpoint.

Timer launch
#tiMe #t.Mod = 5 Timer launch
#tiMe
#t.Mod = 6 Timer launch
#tiMe #t.Mod =7
Setpoint Setpoint Setpoint
Process Process
Process variable PV variable PV
variable PV
#s.p. 2

Output OP Output OP Output OP

OP3 OP3 OP3

[1] When the Timer is not running the con-


trol output is forced to zero, also before the
Timer launch
43
X1 UK-ed6 19-02-2009 11:50 Pagina 44

4 - Operations

4.4.4.2 TIMER FUNCTION (OPTION)

Operator mode
POWER FAILURE DISPLAY
850 and Timer running
If there is a power failure dur- TIMER STARTING 850 RUN

850
ing the Timer execution, the RUN
850
value of the elapsed time is See the Timer starting procedure
lost. at page 49. Press until
When the Timer is running, the
Remaining time
Depending on Timer action led Ö is on.
# t . a ct selection, when the 234
controller restarts you can have 850 RUN

tM.r.
two different situations: End
• with automatic mode Counting stop
( # t . a ct = 2 , 3 , 6 , 7 ), the
Timer function starts again When the Timer ends, the Remaining time
and the counting time is Setpoint display shows alterna-
234 value
reinitialised. tively the message E
# nd and
RUN
tM.r.
• with manual mode the Setpoint value until a key is
(t# a. ct = 0,1,4,5), the con- pressed. Value change
trol output is forced to zero, if
#tMod = 3 e 5; otherwise TIMER REMAINING TIME
60 If set to # 0
the control action restarts the timer ends
using the working Setpoint When the timer is running it is
RUN
tM.r.
always possible to see the
remaining time and to modify it.

44
X1 UK-ed6 19-02-2009 11:50 Pagina 45

4 - Operations

4.4.5 CONFIGURATION MENU

RETRANSMISSION Example: CURRENT TRANSFORMER INPUT


When OP5 output is present, it • T/C S,
retransmits linearised PV or SP. range 0…1600°C With CT option, it is possible to The alarm condition must be
On configuration (see page 29) • Output range, 4…20 mA display the load current and set longer than 120 ms to set the
it is possible to set • Retransmitted signal PV on an alarm threshold. alarm.
800…1200°C range By the parameter
#retr Output
The setting can be done by
range
0=20 / 4=20 mA means the 8 or 9 configuration #Ht.f.S CT primary
high range
index of the codes O, P or Q OFF/ 1…200A
20
#retr = 4=20 (see pages 19 and 20). the load current display can be
#rtH Retransmitted
signal #rt.H = P.U. It is possible to set one of the adapted to the transformer
none P.U. / S.P. #rt.Lo = 800 alarms (see pages 19 and 20) to characteristics. (OFF means dis-
The following parameters define #rt.Hi =1200 have an alarm when, during the abled)
the low and high range of the ON time of the time proportion-
OP5 retransmission output cor- al output, the load current is less During the OFF time the para-
responding to 0…4mA or 20mA then the specified threshold meter t
# C
. ur latches the last on
(see page 27): (index 8), or during the OFF time current value
4 time there is a value > 3% of full
°C
scale load current.
#rt.lo Retransmission
low range
800 1200 1600

Retransmission
#rt.Hi high range With rt.lo greater than
rt.hi it is possible to obtain
a reverse scale.

45
X1 UK-ed6 19-02-2009 11:50 Pagina 46

4 - Operations

4.4.5 CONFIGURATION MENU

CURRENT TRANSFORMER INPUT SERIAL COMMUNICATIONS

Example:
CT input on OP1, alarm on AL2 during on time (configuration digit
p = 8, , see page 19) #prot Communication
protocol
M.bus/ j.bus
120 ms 120 ms

OP1 ON OFF ON
#baud Baud rate
1200/ 2400
4800/ 9600
t.Cur

A2s.p
Load current

3%

AL2 OFF ON OFF ON OFF

46
X1 UK-ed6 19-02-2009 11:51 Pagina 47

5 - Displays

5 DISPLAYS
5.1 OF THE PROCESS VARIABLES 5.2 OF THE CONFIGURATION CODES

Operator Operator
274.8 mode
274.8 Engineering
units
274.8 mode
274.8
Engineering
units
275..0 °C (see Table 2 page 29) 275..0 °C
(see table 2 page 29)

Manual AUTO

Local
Setpoint 275.0 63.4 OP1
output 3150 Basic
product code
modifiable S.P. Out P.I.D. only Hard (Hardware page 17)
value

1st part of the


380.0 Target Setpoint value
local mode only
2002 configuration code
t.S.P. (not displayed if the Con.1 (see pages 18 and 19)
Slopes are disabled)
Software
release
2nd part of the
33 Timer remaining
time 47 Load current
in Ampere 00A 2321 configuration code
tM.r. modifiable value t.Cur (CT option only,
see page 45)
reL. Con.2 (see pages 18 and 19)
(if option installed,
see page 44)

47
X1 UK-ed6 19-02-2009 11:51 Pagina 48

6 - Commands

6 COMMANDS COMMANDS TO THE CONTROLLER AND OPERATING PHASES

The commands can be


entered in 2 ways:

6.1 KEYPAD 6.2 SERIAL


see page 49 COMMUNICATIONS
see the manual on this topic
• Setpoint modification
• Timer start
• Local/remote selection
• Stored Setpoint display
• Keypad lock
• Outputs lock

48
X1 UK-ed6 19-02-2009 11:51 Pagina 49

6 - Commands

6.1 KEYPAD COMMANDS

6.1.1 SETPOINT MODIFICATION 6.1.2 TIMER STARTING (option)

Operator
The Setpoint is directly modified Depending on the Timer action
with the $%keys. 274.8 Operator
mode #t.act selection, there can be 350 mode

Once entered, the new value is 275.0 two different starting ways: 350
checked and becomes operating Example of Setpoint - Automatic at the power on
after 2 seconds.. The end of this modification from - Manual by keypad, digital
phase is flagged by flashing 275 to 350 inputs or serial communica- Press until
momentarily the display with SP. tions.
274.8
350.0
Modified
Setpoint value
To start/stop the Timer:
stop To start
select strt
t.run
after 2 seconds

274.8 Flash momentarily


the SP value to con- strt To stop
select stop
350.0 firm that it has t.run
become operating.
back to the operator
mode
Press the key è to confirm

49
X1 UK-ed6 19-02-2009 11:51 Pagina 50

6 - Commands

6.1 KEYPAD COMMANDS

6.1.3 LOC/ REM SELECTION 6.1.4 STORED SETPOINTS SELECTION


configuration index r = 4 or 5) (configuration index r = 1 or 2)

Operator 274.8
mode 274.8 275.0
Press until
275.0
Press until

Tracking Stand-by
Select reM Index r = 1 Index r = 2
Loc to enable
L=r Remote Setpoint
none Select S.P.1 Loc The selected Setpoint
S.Sel to force S.Sel becomes operating
the first Setpoint pressing the
Select Loc è key.
reM to enable Select S.P.2
L=r Local Setpoint S.P. 1 to force the S.P. 1 The corrispondig
green led
S.Sel second Setpoint S.Sel (ú or ù) is on

Select none to free the


Setpoint modification, then S.P. 2 S.P. 2 Select Loc
The selected Setpoint becomes operating Press $% S.Sel S.Sel to come back to the previ-
pressing the è to change the local Setpoint ous local Setpoint value
When in Remote, the green led Ü is on

50
X1 UK-ed6 19-02-2009 11:51 Pagina 51

6 - Commands

6.1.5 KEYPAD LOCK 6.1.6 OUTPUTS LOCK


operator mode operator mode
To lock/unlock the keypad press X1 The outputs are switched to the X1
the keys í and è simulta- OFF status by pressing the keys
neously for 2 seconds. í and %together.
To confirm the keypad
lock/unlock the display flashes
45.80 When the outputs are locked ,
the message # Off is dis-
45.80
once. played instead of the Setpoint

The keypad lock/unlock can be


45.80 value.
To unlock the outputs press
Off
achieved by serial communica- again the keys simultaneously
tions too. (the Soft-start will be enabled).

The outputs lock/unlock can


A The keypad lock is main- be achieved by serial com-
tained in case of power munications too
failure.

AThe outputs lock/unlock


is maintained in case of
power failure.

Press simultaneously Press simultaneously


for 2 seconds for 2 seconds

51
X1 UK-ed6 19-02-2009 11:51 Pagina 52

7 - Technical specifications

7 TECHNICAL SPECIFICATIONS
Features
Description
(at 25°C environmental temp.)
From keypad or serial communication the user selects:
Total configurability - the type of input - the type and functionality of the alarms
(see chapter 3.2 page 18 - the type of control algorithm - the type of Setpoint
chapter 4.3.5 page 28)
- the type of output - control parameter values

A/D converter with resolution of 50000 points


Common Update measurement time: 0.2 seconds
Sampling time: 0.5 seconds
characteristics Input bias: - 60…+ 60 digit
Input filter with enable/disable: 1…30 seconds
0.25% ±1 digits for temperature sensors Between 100…240Vac the error
Accuracy 0.1% ±1 digits (for mV and mA) is minimal
Resistance 2 or 3 wires
Pt100Ω at 0°C Max. wire Res: 20Ω max. (3 wires)
thermometer connection Input drift: 0.35°C/10° Env. Temp.
PV Input (IEC 751)
(for ∆T: R1+R2 Burnout <0.35°C/10Ω Wire Res.
(see pages 11,12 and °C/°F selectable
must be <320Ω) (with any combination)
page 18)
L, J, T, K, S, R, B, N, E, W3, W5 Internal cold junction Line 150Ω
(IEC 584) compensation con NTC
Thermocouple Input drift: <2µV/°C Env. Temp.
Rj >10MΩ Error 1°C/20°C ±0.5°C
°C/°F selectable Burnout <5µV/10Ω Wire Res.
4…20mA,0...20mA Burnout. Engineering units
DC input (current) with external shunt 2.5Ω Conf. decimal point position
Rj >10MΩ Init. Scale -999…9999 Input drift: <0.1%/20°C Env. Temp.
10…50mV, 0...50mV Full Scale -999…9999
DC input (voltage) (min. range of 100 digits)
Rj >10MΩ
52
X1 UK-ed6 19-02-2009 11:51 Pagina 53

7 - Technical specifications
Features
(at 25°C environmental temp.) Description
Current
0/4…20mA
Remote Setpoint (option) Rj = 30Ω Bias in engineering units and ±range
Not isolated Ratio from -9.99…+99.99
accuracy 0.1% Voltage Local + Remote Setpoint
Auxiliary inputs 1...5/0...5/0...10V
Rj = 300kΩ
50 or 100 mA Current visualisation 1...200A
CT current transformer input hardware With 1A resolution
(see pages12 and 45) selectable and Heater Break Alarm

Control output AL1 alarm AL2 alarm AL3 alarm Retransmiss.

Single OP1-Relay/Triac OP2-Relay/Triac OP3-Relay OP5-Analogue


action

1 single or OP4- OP1-Relay/Triac OP2-Relay/Triac OP3-Relay OP5-Analogue


double action SSR drive-Relay
Operating mode
P.I.D. loop or
and Outputs On/Off with
1, 2 or 3 alarms OP1-Relay/Triac OP2-Relay/Triac OP3-Relay OP5-Analogue

Double action
Heat / Cool OP1-Relay/Triac OP4- OP2-Relay/Triac OP3-Relay OP5-Analogue
SSR drive-Relay

OP4-
SSR drive-Relay OP2-Relay/Triac OP1-Relay/Triac OP3-Relay OP5-Analogue

53
X1 UK-ed6 19-02-2009 11:51 Pagina 54

7 - Technical specifications
Features
(at 25°C environmental temp.) Description
- P.I.D. with overshoot control or ON-OFF
Algorithm
- P.I.D. with valve drive algorithm, for motorised actuators control
Proportional band (P) 0.5…999.9%
Integral time (I) 0.1…100.0 min
Derivative time (D) 0.01…10.00 min OFF = O
Error dead band 0.1…10.0 digit
Single action
Overshoot control 0.01…1.00 P.I.D. algorithm
Manual reset 0.0…100.0%
Cycle time (Time proportional only) 1…200 s
Control mode
Control output high limit 10.0…100.0%
Soft-start output value 0.1…100.0% OFF = O
Output safety value 0.0…100.0% (-100.0…100.0% for Heat / Cool)
Control output hysteresis 0.1…10.0% On-Off algorithm
Dead band -10.0…10.0%
Relative cool gain 0.1…10.0 Double action
P.I.D. algorithm
Cycle time (Time proportional only) 1…200 s (Heat / Cool)
Control output high limit 10.0…100.0% with overlap

Cool output hysteresis 0.1…10.0%


54
X1 UK-ed6 19-02-2009 11:51 Pagina 55

7 - Technical specifications
Features
(at 25°C environmental temp.) Description
SPST Relay N.O., 2A/250Vac (4A/120Vac) for resistive load
OP1-OP2 outputs
Triac, 1A/250Vac for resistive load
OP3 output SPDT relay N.O., 2A/250Vac (4A/120Vac) for resistive load
OP4 output SSR drive not isolated: 0/5Vdc, ±10% 30mA max. - SPST Relay N.O., 2A/250Vac (4A/120Vac) for resistive load
Galvanic isolation: 500 Vac/1 min.
OP5 analogue output Control or PV/SP
Resolution 12bit (0.025%) In current: 0/4…20mA, 750Ω / 15V max.
(option) retransmission
Accuracy: 0.1 %
Hysteresis 0.1…10.0% c.s.
Active high Deviation threshold ±range
Action type Band threshold 0…range
AL1 - AL2 - AL3 Active low Absolute threshold whole range
alarms Action
Sensor break, heater break alarm
Special functions Acknowledge (latching), activation inhibit (blocking)
Connected to Timer or program (if options installed)
Local
Local
Up and down ramps 0.1…999.9 digit/min. (OFF=0)
Setpoint Local and Remote Low limit: from low range to high limit
High limit: from low limit to high range
Local with trim If option installed
Remote with trim

55
X1 UK-ed6 19-02-2009 11:51 Pagina 56

7 - Technical specifications
Features
(at 25°C environmental temp.) Description
Automatic start at the power on, manual start by keypad, Digital inputs or serial comm.s
Timer (see page 41) Setting time: 1…9999 s/min
Special functions Stand-by Setpoint: from Setpoint low limit to Setpoint high limit
(option) Start-up Setpoint: from Setpoint low limit to Setpoint high limit
Start-up Hold time: 0…500min
(see page 39)
Control output high limit: 5.0…100.0%
The controller selects automatically the best Step response
Fuzzy-Tuning one shoot
method according to the process conditions Natural frequency
Serial comm. (option) RS485 isolated, Modbus/Jbus protocol, 1200, 2400, 4800, 9600 bit/s, 3 wires
Auxiliary Supply +24Vdc ±20% 30mA max. - for external transmitter supply
Detection of out of range, short circuit or sensor break with automatic activation of the safety
Measure input
strategies and alerts on display
Operational safety
Control output Safety value: -100…+100%
Parameters Parameter and configuration data are stored in a non volatile memory for an unlimited time
Access protection Password to access the configuration and parameters data, keypad lock, outputs lock
Power supply 100/240Vac (-15...+10%) 50/60Hz or
Power consumption 4W max.
(fuse protected) 24Vac (-15...+25%) 50/60Hz and 24Vdc (-15...+25%)
General Safety Compliance to EN61010-1 (IEC 1010 – 1), installation class 2 (2.5kV) pollution class 2, instrument class II
characteristics Electromagnetic compatibility Compliance to the CE standards (see page 2)
UL and cUL approval File 176452
Protection EN60529 (IEC529): IP65 front panel
Dimensions 1/ DIN - 48 x 96, depth 110 mm, weight 250 g approx.
8

56
X1 UK-ed6 19-02-2009 11:51 Pagina 57

Warranty

1 WARRANTY

We warrant that the products will


be free from defects in material and
workmanship for 18 months from
the date of delivery.
The warranty above shall not apply
for any failure caused by the use of
the product not in line with the
instructions reported on this manual.

57
X1 UK-ed6 19-02-2009 11:51 Pagina 58

Icons table

ICONS TABLE Digital input


connected functions
Main universal input Digital input

Thermocouple Isolated contact Auto/Manual

Run, Hold, Reset and


RTD (Pt100) NPN open collector
program selection

Delta Temp (2x RTD) TTL open collector PV hold

Setpoint slopes
mA and mV
inhibition
Setpoint

Custom Local
Output

Frequency Stand-by SPST Relay

Keypad lock Triac


Auxiliary input

Current transformer Outputs lock SPDT Relay

mA Remote setpoint Start-up function mA

Volt Remote setpoint Timer function mA mV

Feedback
Memorized SSR Drive
potentiometer

Remote

Setpoint programmer

58
X1 UK-ed6 19-02-2009 11:51 Pagina 59

59
X1 UK-ed6 19-02-2009 11:51 Pagina 60

60

You might also like